Siemens AG    6RX1700-0AD76 
6-65 
SIMOREG DC-MASTER    Operating Instructions 
Pulse encoder input (see also Section 8, sheet G145) 
Module C98043-A7001  (CUD1) 
Function 
Terminal
X173 
Connection values/Remarks 
Supply  (+13,7V to+15,2V) 
26 
200mA; short-circuit-proof (electronic protection) 
Overload response:  Fault message F018  
Warning signal A018 
Ground pulse encoder M 
27 
Track 1 
Positive terminal 
Negative  terminal 
28 
29 
Load: 
5.25mA at 15V 
(w/o switching losses, see below for cable, cable length, 
shield connection) 
Track 2 
Positive terminal 
Negative terminal 
30 
31 
Switching hysteresis: See below 
Pulse/pause ratio:  1:1 
Zero marker  Positive terminal 
Negative terminal 
32 
33 
Level of input pulses: See below 
Track offset: 
Table 1 see below 
Pulse frequency: 
Table 2 see below 
Cable length: 
See below 
Characteristic data of pulse tacho evaluation electronics 
Level of input pulses: 
Encoder signals (symmetrical and asymmetrical) up to a max. 27V differential voltage can be processed by 
the evaluated electronics. 
Electronic adaptation of evaluation electronics to signal voltage of encoder: 
–  Rated input voltage range 5V P142=0: 
Low level: 
Differential voltage <0.8V 
High level: 
Differential voltage >2.0V 
Hysteresis: 
>0.2V 
Common-mode control range:  ±10V 
–  Rated input voltage range 15V P142=1: 
Low level: 
Differential voltage <5.0V 
High level: 
Differential voltage >8.0V Restriction: See switching frequency 
Hysteresis: 
>1V 
Common-mode control range:  ±10V 
If the pulse encoder does not supply symmetrical encoder signals, then its ground must be routed as a 
twisted-pair
lead with every signal cable and connected to the negative terminals of track 1, track 2 and the 
zero marker. 
Switching frequency: 
The maximum frequency of the encoder pulses is 300kHz. To ensure correct evaluation of the encoder 
pulses, the minimum distance T
min
between two encoder signal edges (tracks 1 and 2) specified in the table 
must be observed: 
Table 1: 
Rated input voltage 5V 
Rated input voltage 15V 
Differential voltage 1) 
2V 
>2.5V 
8V 
10V 
>14V 
T
min
2) 
630ns 
380ns 
630ns 
430ns 
380ns 
1)  Differential voltage at terminals of evaluation electronics 
2)  The phase error L
(deviating from 90°), which may occur as the result of encoder and cable, can be 
calculated from T
min 
L
G
= ± (90° – f
p
T
min
*
360°) 
L
G
= phase error 
f
p
= pulse frequency 
T
min
= minimum distance between edges 
This formula applies only if the encoder pulse ratio is 1:1. 
Add picture to pdf file - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
add picture to pdf in preview; add picture to pdf
Add picture to pdf file - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
add an image to a pdf acrobat; add an image to a pdf
6-66
Siemens AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
If the pulse encoder is incorrectly matched to the encoder cable, disturbing cable reflections will be produced 
at the receive end. These reflections must be damped so that the encoder pulses can be correctly evaluated. 
The limit values listed in the table below must be maintained to ensure that the resultant power loss in the 
adapting element of the evaluation electronics is not exceeded. 
Table 2: 
f
max
50kHz 
100kHz 
150kHz 
200kHz 
300kHz 
Differential voltage  3) 
Up to 27V 
Up to 22V 
Up to 18V 
Up to 16V  Up to 14V 
3
Differential voltage of encoder pulses at no load  
(approximate encoder power supply voltage) 
Cable, cable length, shield connection: 
The encoder cable capacitance must be recharged at each encoder edge change. The RMS value of this 
current is proportional to the cable length and the pulse frequency and must exceed the current specified by 
the encoder manufacturer. A suitable cable
as recommended by the encoder manufacturer must be used. 
The maximum cable length must not be exceeded. Generally, a twisted cable pair with common pair shield
is 
sufficient for each track. Crosstalk between the cables is thus reduced. The shielding of all pairs protects 
against noise pulses. The shield must be connected to the shield bar of the SIMOREG converter over the 
largest possible surface area.  
Temperature sensor inputs (motor interface 1) (see also Section 8, sheet G185) 
Module C98043-A7001  (CUD1) 
Function 
Terminal
X174 
Connection values/Remarks 
Motor temperature 
Connection of the temperature 
sensor 
22 
23 
Sensor acc. to P490 index 1 
The cable to the temperature sensor on the motor must 
be shielded and connected to ground at both ends.  
Ground analog M 
24 
Analog outputs (see also Section 8, sheet G115) 
Module C98043-A7001  (CUD1) 
Function 
Terminal
X175 
Connection values/Remarks 
Actual current 
Ground analog M 
12 
13 
0. . .±10V corresponds to 0. . .±200% 
Converter rated DC current (r072.002) 
Max. load 2mA, short-circuit-proof 
Select output 
analog 1 
Ground analog M 
14 
15 
Select output 
analog 2 
Ground analog M 
16 
17 
0. . . ±10V, max. 2mA 
short-circuit-proof 
Resolution ±11bits 
C# TIFF: How to Insert & Burn Picture/Image into TIFF Document
Support adding image or picture to an existing or new new REImage(@"c:\ logo.png"); // add the image powerful & profession imaging controls, PDF document, tiff
adding an image to a pdf in acrobat; adding an image to a pdf
VB.NET Image: Image Cropping SDK to Cut Out Image, Picture and
NET image cropper control SDK; VB.NET image cropping method to crop picture / photo; you can adjust the size of created cropped image file, add antique effect
add jpeg to pdf; add photo to pdf reader
Siemens AG    6RX1700-0AD76 
6-67 
SIMOREG DC-MASTER    Operating Instructions 
Binary control inputs (see also Section 8, sheet G110) 
Module C98043-A7001  (CUD1) 
Function 
Terminal
X171 
Connection values/Remarks 
Supply (output) 
34 
24V DC, short circuit proof 
max. load 200mA (terminals 34, 44, and 210 combined), 
internal supply with respect to internal ground 
Ground digital M 
35 
Overload response:  Error signal F018 
Warning signal A018 
Select input  
binary 1 
36 
Power On / Shutdown 
H signal:  Power ON 
Line contactor CLOSED + 
(with H signal at terminal 38), 
acceleration along ramp-
function generator ramp to 
operating speed. 
L signal:  Shutdown 
Deceleration along ramp-
function generator ramp to 
n < n
min
(P370) + , controller 
disable + line contactor OPEN. 
See Section 9.3 for exact 
function description. 
37 
Enable operation 
H signal:  Controller enabled 
L signal:  Controller disabled 
See Section 9.3.4 for exact 
function description 
38 
Select input 
binary 2 
39 
H signal: +13V to +33V 
L signal: – 33V to +3V or terminal open 
8.5mA at 24V 
Safety shutdown (E-STOP) (see also Section 9.8 and  Section 8, sheet G117) 
Module C98043-A7002 or A7003 power interface 
Function 
Terminal
XS 
Connection values/Remarks 
Supply for safety shutdown (output) 
106 
24V DC, max. load  50mA, short-circuit-proof 
Overload response:  Error signal F018 
Warning signal A018 
Safety shutdown   switch 
105 
I
= 20mA 
Safety shutdown   pushbutton 
107 
NC contact  I
= 30mA 
Safety shutdown   Reset 
108 
NO contact  I
= 10mA 
NOTICE 
Both 105 + 106 terminals or 106, 107 + 108 terminals can be used! Combined use of terminals 
105 – 108 will result in a malfunction. 
Terminal 105 is connected to terminal 106 in the state as delivered. 
VB.NET Image: Image Scaling SDK to Scale Picture / Photo
VB.NET method to scale image file in .NET Framework VB.NET sample code for how to scale image / picture; RasterEdge VB.NET image scaling control SDK add-on.
add jpg to pdf acrobat; how to add an image to a pdf in reader
C# Word - Paragraph Processing in C#.NET
Add references: C# users can set paragraph properties and create content such as run, footnote, endnote and picture in a paragraph.
how to add a picture to a pdf document; add a picture to a pdf file
6-68
Siemens AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Binary control outputs (see also Section 8, sheet G112) 
Module C98043-A7001  (CUD1) 
Function 
Terminal
X171 
Connection values/Remarks 
Select output 
binary 1 
Ground  M 
46 
47 
Select output 
binary 2 
Ground  M 
48 
54 
H signal:  +20V to +26V 
L signal:  0 to +2V 
Short-circuit-proof 100mA 
Internal snubber circuit (free-wheeling diode) 
Overload response:  Error signal F018 
Warning signal A018 
Binary control outputs (isolated relay outputs) 
Module C98043-A7002 or A7003 power interface 
Function 
Terminal
XR 
Connection values/Remarks 
Relay for line contactor 
109 
110 
Load capability: 
250V AC, 4A; cosΦ=1 
250V AC, 2A; cosΦ=0,4 
30V DC, 2A 
External fuse protection max. 4A, characteristic C 
recommended 
Serial interface 1  RS232  (9-pin SUBMIN D socket connector)  (G-SST1) 
X300 
Use a shielded connecting cable! Ground shield at both ends! 
Module C98043-A7005  PMU 
Con. pin  
X300 
Function 
Housing earth 
Receive cable to RS232 (V.24) standard 
Send and receive cables to RS485, two-wire, positive differential input/output 
Input: Reserved for later use 
Ground 
5 V voltage supply for OP1S 
Send cable to RS232 (V.24) standard 
Send and receive cables to RS485, two-wire, positive differential input/output 
Ground 
Cable length:  Up to 15m according to EIA Standard RS232C 
Up to 30 m capacitive load, max. 2.5nF (cable and receiver) 
A serial connection to a PLC or PC can be made using connector X300 on the PMU, allowing the converter 
to be controlled and operated from a central control center or room. 
VB.NET Image: Image Resizer Control SDK to Resize Picture & Photo
NET Method to Resize Image & Picture. Here we this VB.NET image resizer control add-on, can provide powerful & profession imaging controls, PDF document, image
how to add an image to a pdf file in acrobat; adding image to pdf form
VB.NET Image: Create Code 11 Barcode on Picture & Document Using
This PDF document editor add-on contains unique APIs for VB.NET developers to decode, encode and process PDF file independently.
add photo to pdf form; how to add a jpeg to a pdf file
Siemens AG    6RX1700-0AD76 
6-69 
SIMOREG DC-MASTER    Operating Instructions 
Serial interface 2  RS485  (G-SST2) 
Module C98043-A7001  (CUD1) 
Function 
Terminal 
X172 
Connection values/Remarks 
TX+ 
56 
RS485,  4-wire send cable, positive differential output 
TX- 
57 
RS485,  4-wire send cable, negative differential output 
RX+/TX+ 
58 
RS485,  4-wire receive cable, positive differential input,  
2-wire send/receive cable, positive differential input 
RX-/TX- 
59 
RS485,  4-wire receive cable, negative differential input,  
2-wire send/receive cable, negative differential input 
60 
Ground 
Cable length:  For transmission rate =187.5kBd  600m 
For transmission rate 93.75kBd  1200m 
The following must be observed: DIN 19245 Part 1 
The potential difference between the data reference potentials M of all interfaces must not 
exceed -7V / +12V. If this cannot be guaranteed, then equipotential bonding must be 
provided.  
Activation of interface 1 or 2: 
–  Set the baud rate in parameter P783 or P793. 
–  Set the protocol in parameter P780 or P790. 
VB.NET Image: VB.NET Codes to Add Antique Effect to Image with .
mature technology to replace a picture's original colors add the glow and noise, and add a little powerful & profession imaging controls, PDF document, image
add picture to pdf file; add image to pdf java
VB.NET TIFF: How to Draw Picture & Write Text on TIFF Document in
to drawing on TIFF file page. RaterEdgeDrawing = New RaterEdgeDrawing() drawing.Picture = "RasterEdge" drawing & profession imaging controls, PDF document, tiff
how to add image to pdf; add picture to pdf document
6-70
Siemens AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Options:
Terminal expansion CUD2
 
Terminal type
:
Plug-in terminal (screw-type) 
Max. connection cross-section 1.5mm
Motor interface (see also function diagrams, Section 8, sheets G185 and G186) 
Module C98043-A7006  CUD2 
Function 
Terminal
X164 
Connection values/Remarks 
Motor temperature 
(temperature sensor input) 
204 
205 
Sensor acc. to P490 index 2 
The cable to the temperature sensor on the motor must 
be shielded and connected to ground at both ends. 
Module C98043-A7006  CUD2 
Function 
Terminal
X161 
Connection values/Remarks 
Supply for digital inputs 
(output) 
210 
24V DC, short circuit proof with respect to internal 
ground 
max. load 200mA (terminals 34, 44, and 210 
combined), 
Overload response:  Error signal F018 
Warning signal A018 
Binary input 
Binary input 
Binary input 
Binary input 
211 
212 
213 
214 
H signal: +13V to +33V 
L signal: – 33V to +3V or terminal open 
Input resistance = 2.8k 
Ground for binary inputs 
Ground for binary inputs 
215 
216 
217 
can be isolated from internal ground 
(open wire jumper between terminals 
216 and 217) 
Analog inputs (see also Section 8, sheet G114) 
Module C98043-A7006  CUD2 
Function 
Terminal
X164 
Connection values/Remarks 
Select input 
analog 2 
Ground analog 
Select input 
analog 3 
Ground analog 
10 
11 
±10V, 52k 
Resolution: ±10bit 
Common mode suppression: ±15V 
Analog outputs (see also Section 8, sheet G116) 
Module C98043-A7006  CUD2 
Function 
Terminal
X164 
Connection values/Remarks 
Select output 
analog 3 
Ground analog  M 
18 
19 
Select output 
analog 4 
Ground analog  M 
20 
21 
0. . . ±10V, max. 2mA 
Short-circuit-proof 
Resolution ±11bit 
Siemens AG    6RX1700-0AD76 
6-71 
SIMOREG DC-MASTER    Operating Instructions 
Binary inputs (see also Section 8, sheet G111) 
Module C98043-A7006  CUD2 
Function 
Terminal
X163 
Connection values/Remarks 
Supply 
44 
24V DC, short circuit proof 
max. load 200mA (terminals 34, 44, and 210 combined), 
internal supply with respect to internal ground 
Ground digital M 
45 
Overload response:  Error signal F018 
Warning signal A018 
Select input 
binary 3 
40 
Select input 
binary 4 
41 
Select input 
binary 5 
42 
Select input 
binary 6 
43 
H signal: +13V to +33V 
L signal: – 33V to +3V or terminal open 
8.5mA at 24V 
Binary outputs (see also Section 8, sheet G112) 
Module C98043-A7006  CUD2 
Function 
Terminal
X163 
Connection values/Remarks 
Select output 
binary 3 
Ground  M 
50 
51 
Select output 
binary 4 
Ground  M 
52 
53 
H signal: +20V to +26V 
L signal: 0 to +2V 
Short-circuit-proof 100mA 
Overload response:  Error signal F018 
Warning signal A018 
Internal snubber circuit (free-wheeling diode) 
Serial interface 3  RS485  (G-SST3) 
Module C98043-A7006  CUD2 
Function 
Terminal 
X162 
Connection values/Remarks 
TX+ 
61 
RS485,  4-wire send cable, positive differential output 
TX- 
61 
RS485,  4-wire send cable, negative differential output 
RX+/TX+ 
63 
RS485,  4-wire receive cable, positive differential input,  
2-wire send/receive cable, positive differential input 
RX-/TX- 
64 
RS485,  4-wire receive cable, negative differential input,  
2-wire send/receive cable, negative differential input 
65 
Ground 
Cable length:  For transmission rate =187.5kBd  600m 
For transmission rate 93.75kBd  1200m 
The following must be observed: DIN 19245 Part 1 
The potential difference between the data reference potentials M of all interfaces must not 
exceed -7V / +12V. If this cannot be guaranteed, then equipotential bonding must be 
provided.  
Activate interface 3: 
–  Set the baud rate in parameter P803. 
–  Set the protocol in parameter P800. 
6-72
Siemens AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
SIEMENS AG    6RX1700-0AD76 
7-1 
SIMOREG DC-MASTER    Operating Instructions 
Start-Up 
7.1  General safety information for start-up 
DANGER
Before commencing with start-up on the converters (90A to 600A), make sure that the 
transparent terminal cover is mounted in the correct position (see Section 5.1). 
CAUTION 
Before handling any boards (in particular, the A7001 electronics board), please make sure that 
your body is electrostatically discharged to protect electronic components against high voltages 
caused by electrostatic charges. The simplest way of doing this is to touch a conductive, 
grounded object (e.g. bare metal cabinet component immediately beforehand). 
PCBs must not be allowed to come into contact with highly insulating materials (e.g. plastic foil, 
insulating table tops or clothing made of synthetic fibers). 
PCBs may only be set down on electrically conducting surfaces. 
7-2
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
WARNING
Hazardous voltages and rotating parts (fans) are present in this electrical equipment during 
operation. Non-observance of the safety instructions can result in death, severe personal injury 
or substantial property damage. 
Hazardous voltage may be present at the signaling relays in the customer’s installation. 
The converters must not be connected to a supply with earth-leakage circuit-breaker (VDE 
0160, Section 6.5) since, in the event of a fault to frame or ground, the fault current may 
contain a DC component that will either prevent or hinder a higher-level e.l.c.b. from tripping. In 
this case, all loads connected to this e.l.c.b. have no protection either. 
Only qualified personnel who are thoroughly familiar with all safety notices contained in the 
operating instructions as well as erection, installation, operating and maintenance instructions 
should be allowed to work on these devices. 
The successful and safe operation of this equipment is dependent on careful transportation, 
proper storage and installation as well as correct operation and maintenance.  
The converter is at a hazardous voltage level even when the line contactor is open. The gating 
board (board mounted directly to lower part of housing) has many circuits at hazardous voltage 
levels. Before carrying out any maintenance or repair work, all converter power sources must 
be disconnected and locked out. 
These instructions do not claim to list all of the measures required to ensure safe and reliable 
operation of the converter. For special applications, additional, supplementary information or 
instructions might be required. If problems do occur and you feel in any way uncertain, please 
contact your local Siemens office or representative. 
The use of unauthorized parts in the repair of this converter and handling of the equipment by 
unqualified personnel can give rise to hazardous conditions which may cause death, severe 
personal injury or substantial property damage. All safety notices contained in this instruction 
manual and attached to the converter itself must be carefully observed. 
Please read the safety information given in Section 1 of this instruction manual. 