SIEMENS AG    6RX1700-0AD76 
7-3 
SIMOREG DC-MASTER    Operating Instructions 
7.2  Operator control panels 
The basic converter is equipped with a simple operator panel (PMU) as standard. A user-friendly 
panel with plaintext display (OP1S) can be connected as an option. 
7.2.1  Simple operator control panel (PMU “P
aram
eterization U
nit“) 
The simple operator control panel is mounted in the converter door and consists of a 5-digit, 7-
segment display with three status display LEDs and three parameterization keys below. 
All adjustments and settings that need to be undertaken for the purpose of start-up can be made 
on the simple control panel. 
X300
Run Ready Fault
•  P key 
−  Switches over between parameter number (parameter mode), parameter value (value 
mode) and index number (index mode) on indexed parameters. 
−  Acknowledges active fault messages. 
−  P and RAISE keys to switch a fault message and alarm to the background (see Section 
10, Fault Messages and Alarms) 
−  P and LOWER key to switch a fault message and alarm from the background back to the 
foreground display on the PMU (see Section 10, Fault Messages and Alarms) 
•  UP key (▲) 
−   Selects a higher parameter number in parameter mode. When the highest number is 
displayed, the key can be pressed again to return to the other end of the number range 
(i.e. the highest number is thus adjacent to the lowest number). 
−   Increases the selected and displayed parameter value in value mode. 
−   Increases the index in index mode (for indexed parameters) 
−   Accelerates an adjustment process activated with the DOWN key (if both keys are 
pressed at the same time). 
•  DOWN key (▼) 
−   Selects a lower parameter number in parameter mode. When the lowest number is 
displayed, the key can be pressed again to return to the other end of the number range 
(i.e. the lowest number is thus adjacent to the highest number). 
−   Decreases the selected and displayed parameter value in value mode. 
−  Decreases the index in index mode (for indexed parameters) 
−  Accelerates an adjustment process activated with the UP key (if both keys are pressed at 
the same time). 
Add an image to a pdf form - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
adding images to pdf forms; add image to pdf form
Add an image to a pdf form - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
adding jpg to pdf; add picture to pdf reader
7-4
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
LED displays 
Run  green LED 
LED illuminated  ⇒  in “Torque direction active” state (MI, MII, M0). 
(see r000 in Section 11) 
Ready  yellow LED 
LED illuminated  ⇒  in “Ready” state (o1 .. o7). 
(see r000 in Section 11) 
Fault  red LED 
LED illuminated  ⇒  in “Fault signal present” state (o11) 
(see r000 in Section 11 and Faults and Alarms (Section 10)) 
LED flashing 
⇒  An alarm is active (see Faults and Alarms in Section 10). 
7.2.2  User-friendly operator control panel (OP1S) 
The optional, user-friendly, operator control panel with plaintext display (order no.: 6SE7090-
0XX84-2FK0) is mounted in the special location provided in the converter door. 
This location provides a connection to the serial basic converter interface SST1. 
Parameters can be selected directly through input of the parameter number via the keyboard of the 
OP1S. The following interrelationships apply: 
Displayed 
number 
Number to be keyed in 
on OP1S 
rxxx, Pxxx 
(0)xxx 
Basic converter 
parameter 
Uxxx, nxxx 
2xxx 
Hxxx, dxxx 
1xxx 
Technology board 
parameter 
Lxxx, cxxx 
3xxx 
If the RAISE or LOWER key on the OP1S is used to select adjacent parameter numbers, then any 
missing numbers in the range of basic converter parameters are skipped. 
This automatic skipping over missing numbers does not work for technology board parameters. In 
this case, the numbers of existing parameters must be entered directly. 
The OP1S switches to operational display a few 
seconds after initialization. 
By pressing the <P> key, you can switch from the 
operating display to the Basic Menu in which you can 
either select "Free access" to all parameters or a variety 
of functions. Details of these functions can be found in the 
function diagram "OP1S operational display" (Section 8, 
Sheet Z123) and the OP1S operating instructions. 
The converter parameters can be set in "Free access" 
status. 
You can return to the operating status display by pressing 
the <R> key (several times if necessary). 
Operating status
display
Basic menu
Free access
<P>
<P>
<R>
<R>
C# PDF Image Extract Library: Select, copy, paste PDF images in C#
Scan image to PDF, tiff and various image formats. Get image information, such as its location, zonal information Able to edit, add, delete, move, and output PDF
adding an image to a pdf file; how to add image to pdf acrobat
C# PDF Form Data Read Library: extract form data from PDF in C#.
featured PDF software, it should have functions for processing text, image as well can help you have a quick evaluation of our PDF SDK. Add necessary references
how to add image to pdf document; add image pdf
SIEMENS AG    6RX1700-0AD76 
7-5 
SIMOREG DC-MASTER    Operating Instructions 
Control bits from OP1S operator panel: 
(see also function diagram "OP1S operational display" (Section 8, Sheet Z123) and the OP1S 
operating instructions) 
Data are exchanged between the OP1S and SIMOREG 6RA70 converter via the G-SST1 interface 
(RS485) and USS protocol. 
The OP1S operator panel transfers the following control bits in process data word 1 in the USS 
message: 
Key on OP1S 
Function *) 
Bit in PZD word1 
(connector K2001) 
Binector 
ON key / OFF key (I / 0)  ON / OFF1 
Bit 0 
B2100 
Reset 
Acknowledge 
Bit 7 
B2107 
Jog 
Jog (inch) 
Bit 8 
B2108 
Reverse 
Enable positive direction of rotation 
Bit 11 
B2111 
Enable negative direction of rotation 
Bit 12 
B2112 
UP key 
Increase motorized potentiometer 
Bit 13 
B2113 
DOWN key 
Decrease motorized potentiometer 
Bit 14 
B2114 
*)  Suggested functions. Since binectors can be freely wired up to any selector switch, the control signals from the OP1S 
can be used for any type of control task in the SIMOREG 6RA70. 
Connection of control signals from the OP1S for the suggested functions:
Functions can be implemented via the OP1S only if the following conditions are fulfilled: 
1)  Bit-by-bit input of control bits in control word 1 (P648 = 9), see also Section 8, Function 
Diagrams, Sheet G180 
2)  OP1S in "Operational display" status 
ON / OFF1: 
Parameterization of switch-on/shutdown via OP1S by setting 
P654 = 2100 
Please also note AND operation with "Switch-on/Shutdown" from terminal 37 (see also Function 
Diagrams, Sheet G130 in Section 8 and Section "Switch-on/Shutdown (ON / OFF) terminal 37" in 
Section 9) 
Acknowledge: 
Parameterization of fault message acknowledgements via OP1S by setting 
P665, P666 or P667 = 2107 
Faults can always be acknowledged by pressing the <P> key on the PMU. 
Inching: 
Parameterization of inching via OP1S by setting 
P668 or P669 = 2108 
Selection of source of inching setpoint via the corresponding index of P436 (see "Inching setpoint" 
function diagram) 
Direction of rotation enable: 
Parameterization of direction of rotation enabling via OP1S by setting 
P671 = 2111 (positive direction of rotation) 
P672 = 2112 (negative direction of rotation) 
Motorized potentiometer: 
Parameterization of motorized potentiometer via OP1S by setting 
P673 = 2113 (higher) 
P674 = 2114 (lower) 
P644 = 240 (main setpoint from motorized potentiometer) 
VB.NET PDF Form Data Read library: extract form data from PDF in
featured PDF software, it should have functions for processing text, image as well can help you have a quick evaluation of our PDF SDK. Add necessary references
add image to pdf acrobat; add png to pdf acrobat
VB.NET PDF Image Extract Library: Select, copy, paste PDF images
multiple types of image from PDF file in VB.NET, like XObject Image, XObject Form, Inline Image DLLs for PDF Image Extraction in VB.NET. Add necessary references
add jpg to pdf preview; add picture pdf
7-6
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
7.3  Parameterization procedure 
Parameterization is the process of changing setting values (parameters) via the operator panel, 
activating converter functions or displaying measured values. 
Parameters for the basic converter are called P, r, U or n parameters. Parameters for an optional 
supplementary board are called H, d, L or c parameters. 
The basic unit parameters are displayed first on the PMU, followed by the technology board 
parameters (if such a board is installed). It is important not to confuse the parameters of the 
optional S00 technology software of the basic unit with the parameters of an optional 
supplementary board (T100, T300 or T400). 
Depending on how parameter P052 is set, only some parameter numbers (see Section 11, 
Parameter List) are displayed. 
7.3.1  Parameter types 
Display parameters are used to display current quantities such as the main setpoint, armature 
voltage, setpoint/actual value difference of speed controller, etc. The values of display parameters 
are read-only values and cannot be changed
Setting parameters are used to both display and change quantities such as the rated motor 
current, thermal motor time constant, speed controller P gain, etc. 
Indexed parameters are used to both display and change several parameter values which are all 
assigned to the same parameter number. 
7.3.2  Parameterization on simple operator control panel 
After the electronics supply voltage has been switched on, the PMU is either in the operational 
display state and indicating the current operating status of the SIMOREG 6RA70 (e.g. o7.0), or in 
the fault/alarm display state and indicating a fault or alarm (e.g. F021). 
Operational states are described under parameter r000 in Section 11 and the fault and alarm 
messages in Section 10. 
1.  To reach the parameter number level from the operational display state (e.g. o7.0), press the P 
key and then the <Up> or <Down> key to select individual parameter numbers. 
2.  To reach the parameter index level (for indexed parameters) from the parameter number level, 
press P and then the <Up> or <Down> key to select individual indices. 
If you press P when a non-indexed parameter is displayed, you go directly to the parameter 
value level. 
3.  To reach the parameter value level from the parameter index level (for indexed parameters), 
press P. 
4.  On the parameter value level, you can change the setting of a parameter value by pressing the 
<Up> or <Down> key. 
NOTE
Parameters can be altered only if the following conditions are fulfilled: 
The appropriate access authorization is set in key parameter P051, e.g. “40” (see Section 11, 
“Parameter List”). 
The converter is the correct operational state. Parameters with characteristic “offline” cannot 
be changed when the converter is in the “Run” (online) state. To change parameters with this 
characteristic, switch the converter to the ≥o1.0 status (“Ready”). 
The values of display parameters can never be changed (read only). 
VB.NET PDF Password Library: add, remove, edit PDF file password
passwordSetting.IsAnnot = True ' Allow to fill form. passwordSetting document. passwordSetting.IsAssemble = True ' Add password to PDF file. PDFDocument
adding an image to a pdf form; add picture to pdf preview
C# PDF Password Library: add, remove, edit PDF file password in C#
passwordSetting.IsAnnot = true; // Allow to fill form. passwordSetting document. passwordSetting.IsAssemble = true; // Add password to PDF file. PDFDocument
add picture to pdf form; add photo to pdf in preview
SIEMENS AG    6RX1700-0AD76 
7-7 
SIMOREG DC-MASTER    Operating Instructions 
5.  Manual shifting 
If the 5 existing digits on the 7-segment display are not sufficient to display a parameter value, the 
display first shows just 5 digits (see Fig. 7.1). To indicate that digits are concealed to the right or 
left of this “window”, the right-hand or left-hand digit flashes. By pressing the <P>+<Down> or 
<P>+<Up> key, you can shift the window over the remaining digits of the parameter value. 
As an orientation guide, the position of the right-hand digit within the overall parameter value is 
displayed briefly during manual shifting. 
Example: Parameter value “208.173“ 
"208.17" is displayed when the parameter is selected. When the 
P and LOWER keys are pressed, "1" appears briefly followed by 
“08.173“, i.e. the right-hand digit 3 is the 1
st
position in the 
parameter value. 
When the P and RAISE keys are pressed, "2" appears briefly 
followed by “208.17“, i.e. the right-hand digit 7 is the 2
nd
position 
in the parameter value. 
Fig. 7.1 
Shifting the PMU display for parameter values with more than 5 digits 
+
P
+
P
6      5       4       3      2      1
6       5      4       3      2      1
6.  Press the P key to return to the parameter number level from the parameter value level. 
Tables 7.1 and 7.2 below show an overview of displays which may appear on the PMU: 
Parameter number 
Index 
Parameter value
e. g. 
e. g. 
e. g. 
Display 
parameters 
Basic unit 
Technology 
or 
or 
Setting 
parameters 
Basic unit 
Technology 
or 
or 
Table7.1 
Display of visualization and setting parameters on the PMU 
Actual value 
Parameter value 
not (currently) 
possible
Alarm 
Fault 
Display
Table 7.2 
Status displays on the PMU 
NOTE
Parameters are described in the Parameter List in Section 11 and faults and alarms in Section 
10. 
C# Create PDF from images Library to convert Jpeg, png images to
List<Bitmap> images = new List<Bitmap>(); images.Add(new Bitmap(Program.RootPath + "\\" 1.gif")); / Build a PDF document with GIF image.
add picture to pdf online; acrobat insert image in pdf
C# PDF Sticky Note Library: add, delete, update PDF note in C#.net
C#.NET PDF SDK - Add Sticky Note to PDF Page in C#.NET. Able to add notes to PDF using C# source code in Visual Studio .NET framework.
add multiple jpg to pdf; add image pdf document
7-8
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
7.4  Reset to default value and adjust offset 
Restoring parameters values to defaults (works settings) and performing an internal converter 
offset adjustment. 
The "Restore factory setting" function must
be executed after every software update if the 
converter software has been updated from version 1.0 or 1.1. 
With converter SW version 1.2 and later, it is no longer necessary to execute "Restore factory 
settings" after a software update because the parameter settings prior to the update remain valid. 
The “Restore to default” function can
be executed if a defined basic setting is to be established, 
e.g. in order to carry out a complete new start-up operation. 
NOTICE 
When the “Restore to default” function is activated, all parameters set for a specific installation 
are overwritten (deleted). We therefore recommend that all old settings be read out beforehand 
with Drive Monitor and stored on a PC or programmer.  
“Restore to default” must be followed by a completely new start-up operation or else the 
converter will not be “ready” with respect to safety. 
Execution of function:
1.  Set parameter P051 = 21 
2.  Transfer parameter values to the non-volatile memory.  
The parameter values are stored in non-volatile storage (EEPROM) so that they will still be 
available when the converter is switched off. This operation takes at least 5 s (but may also last 
several minutes). The number of the parameter currently being processed is displayed on the 
PMU during the process. The electronics power supply must remain connected while this 
operation is in progress. 
3.  Offset adjustments 
Parameter P825.ii is set (takes approx. 10 s). 
The offset adjustment can also be activated as an individual function by means of parameter 
P051 = 22. 
SIEMENS AG    6RX1700-0AD76 
7-9 
SIMOREG DC-MASTER    Operating Instructions 
7.5  Start-up procedure 
WARNING
The converter is at a hazardous voltage level even when the line contactor is open. The gating 
board (board mounted directly to lower part of housing) has many circuits at hazardous voltage 
levels. 
Non-observance of the safety instructions given in this manual can result in death, severe 
personal injury or substantial property damage. 
1
Access authorization 
P051 . . . Key parameter 
 Parameter cannot be changed 
40  Parameter can be changed 
P052 . . . Selection of parameters to be displayed 
 Only parameters that are not set to default are visible 
 All parameters are visible 
P927 . . . Enter an odd number if parameters are to be entered via CB (PROFIBUS) 
Adjustment of converter rated currents
NOTICE 
On North American manufactured Base Drive assemblies (Type 6RA70xx-2xxxx) the US rating 
must be set in Parameter P067. 
The rated converter armature DC current must be adapted by the setting in parameter P076.001 
(in %) or parameter P067, if: 
0,5
current
 DC
armature
Rated
current
armature
Max.
<
The rated converter field DC current must be adjusted by the setting in parameter P076.002 (in %) 
if: 
0,5
current
 DC
 field
converter
Rated
current
 field
Max.
<
3
Adjustment to actual converter supply voltage 
P078.001 . . . Rated input voltage converter armature (in volts) 
P078.002 . . . Rated input voltage converter field (in volts) 
7-10
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
4
Input of motor data 
In the parameters below, the motor data must be entered as specified on the motor rating plate. 
P100 . . . Rated armature current (in amps) 
P101 . . . Rated armature voltage (in volts) 
P102 . . . Rated field current (in amps) 
P104 . . . Speed n
1
(in rpm) 
see also Section 9.16 
P105 . . . Armature current I
1
(in amperes) 
see also Section 9.16 
P106 . . . Speed n
2
(in rpm) 
see also Section 9.16 
P107 . . . Armature current I
2
(in amperes) 
see also Section 9.16 
P108 . . . Maximum operating speed n
3
(in rpm) 
see also Section 9.16 
P109 . . . 1 = speed-dependent current limitation active 
see also Section 9.16 
P114 . . . Thermal time constant of motor (in minutes) 
see also Section 9.14 
(if necessary: activate fault signal F037 with P820!) 
5
Actual speed sensing data 
5.1
Operation with analog tacho 
P083 = 1:  The actual speed is supplied from the “Main actual value” channel (K0013) 
(terminals XT.103, XT.104) 
P741 
Tacho voltage at maximum speed (– 270,00V to +270,00V) 
5.2
Operation with pulse encoder 
P083 = 2:  The actual speed is supplied by the pulse encoder (K0040) 
P140  Selecting a pulse encoder type (pulse encoder types see below) 
 No encoder/"Speed sensing with pulse encoder" function not selected 
 Pulse encoder type 1 
 Pulse encoder type 1a 
 Pulse encoder type 2 
 Pulse encoder type 3 
1.  Pulse encoder type
1
Encoder with two pulse tracks mutually displaced by 90° (with/without zero marker) 
Track 1
X173   28, 29
Track 2
X173   30, 31
Zero marker
X173   32, 33
Heidenhain ROD
Teldix Rotaswitch Serie 26
SIEMENS AG    6RX1700-0AD76 
7-11 
SIMOREG DC-MASTER    Operating Instructions 
2.  Pulse encoder type 1a
Encoder with two pulse tracks mutually displaced by 90° (with/without zero marker). 
The zero marker is converted internally to a signal in the same way as on encoder 
type 1. 
Track 1
X173   28, 29
Track
X173   30, 31
Zero marker
X173   32, 33
internal zero marker
Hübner OG9DN, POG9DN
Teldix Rotaswitch Serie 25
Honeywell HDM Series
≤360°
°
225 ± 60°
°
3.  Pulse encoder type 2
Encoder with one pulse track per direction of rotation (with/without zero marker). 
Track 1
X173   28, 29
Track 2
X173   30, 31
Zero marker
X173   32, 33
CCW rotation
CW rotation
4.  Pulse encoder type 3
Encoder with one pulse track and one output for direction of rotation (with/without 
zero marker). 
Track 1
X173   28, 29
Track 2
X173   30, 31
Zero marker
X173   32, 33
CCW rotation
CW rotation
Pulse output
Rot. direction
Zero marker
P141  Number of pulses of pulse encoder (in pulses/rev) 
P142  Matching to pulse encoder signal voltage 
 Pulse encoder outputs 5 V signals 
 Pulse encoder outputs 15V signals 
Matching of internal operating points to signal voltage of incoming pulse encoder 
signals. 
NOTICE 
Resetting parameter P142 to the alternative setting does not
switch over the supply 
voltage for the pulse encoder (terminals X173.26 and 27). 
Terminal X173.26 always supplies +15V. An external voltage supply must be 
provided for pulse encoders requiring a 5V supply. 
P143  Setting the maximum speed for pulse encoder operation (in pulses/rev) 
The speed set in this parameter corresponds to an actual speed (K0040) of 100%. 
7-12
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
5.3
Operation without tacho (EMF control) 
P083 = 3:  The actual speed is supplied from the “Actual EMF” channel (K0287), 
but weighted with P115. 
P115 
EMF at maximum speed 
(1.00 to 140.00% of rated converter supply voltage (r078.001)). 
5.4
Freely wired actual value 
P083 = 4:  The actual value input is defined with P609. 
P609 
Number of connector which is connected to controller actual value input. 
6
Field data 
6.1
Field control 
P082 = 0:  Internal field is not used  
(e.g. with permanent-field motors) 
P082 = 1:  The field is switched together with the line contactor 
(field pulses are enabled/disabled when line contactor closes/opens) 
P082 = 2:  Automatic connection of standstill field set via P257 after a delay parameterized via 
P258, after operating status o7 or higher has been reached 
P082 = 3:  Field current permanently connected 
6.2
Field weakening 
P081 = 0:  No field weakening as a function of speed or EMF 
P081 = 1:  Field weakening operation as a function of internal EMF control so that, in the field 
weakening range, i.e. at speeds above rated motor speed (= “threshold speed”), 
the motor EMF is maintained constantly at setpoint 
EMFset (K289) = P101 – P100 * P110. 
7
Selection of basic technological functions 
7.1
Current limits 
P171 
Motor current limit in torque direction I (in% of P100) 
P172 
Motor current limit in torque direction II (in% of P100) 
7.2
Torque limits 
P180 
Torque limit 1 in torque direction I 
(in % of rated motor torque) 
P181 
Torque limit 1 in torque direction II 
(in % of rated motor torque) 
Documents you may be interested
Documents you may be interested