SIEMENS AG    6RX1700-0AD76 
7-43 
SIMOREG DC-MASTER    Operating Instructions 
Apart from these data, a SIMOLINK master can also send special telegrams with application-
specific data (addresses 201 to 204 and channel number 0). An SLB as dispatcher does not 
support these special telegrams. 
If a transceiver stops receiving telegrams due to an interruption, it automatically transmits special 
telegram "Time Out“. 
The transmission rate is 11 Mbits/s. The data telegrams are transmitted in direct succession, 
followed by a SYNC telegram and a pause telegram, within one bus cycle. Transferring the data 
telegrams without pauses ensures a higher data throughput. At a data transmission rate of 11 
Mbit/s, the transmission time for one telegram is 6.36µs. 
. . .
Bus cycle 
Data telegrams 
Break
SYNC
The assignment of telegrams to nodes is determined by the type of SIMOLINK application, i.e. 
peer-to-peer functionality or master-slave functionality. 
When an SLB is configured as the dispatcher, only the peer-to-peer functionality is available. 
Peer-to-peer functionality 
In this mode, there is no defined logical master for distributing information. The drives have equal 
status in logical terms and exchange data with one another via the ring bus. One node (SLB) 
specifies the bus cycle in its dispatcher role to keep the transmission alive. All nodes receive 
and/or send user data. Dispatcher and transceivers can read any telegram, but may only write 
information in the telegrams specifically assigned to them (node address = address in telegram). 
Master-slave functionality 
A logical master (e.g. SIMATIC) supplies all nodes with information on the one hand and, on the 
other, specifies the bus clock cycle (dispatcher function). All other nodes behave as described 
above under peer-to-peer functionality, i.e. they receive and/or send user data, but are only 
permitted to read or write telegrams containing their address. 
In contrast to peer-to-peer functionality, the restrictions described above (no gaps in address 
sequence, uniform number of used channels, no special data) do not apply. The master has its 
own 8 channels for transferring data, but can also use telegrams with the address and channel 
numbers of the transceivers for its data transmissions. 
NOTE
An external 24V power supply to the SIMOLINK modules ensures that communication with the 
other bus nodes continues if a device fails. 
However, this power supply does not prevent the short interruption in communication when the 
device is switched on again when establishing communication is forced. 
Add image pdf acrobat - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
add signature image to pdf acrobat; how to add image to pdf file
Add image pdf acrobat - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
add an image to a pdf; add jpg signature to pdf
7-44
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
7.7.5  Procedure for starting up expansion boards (EB1 and EB2) 
Remove connector X480 from the EB1 board for safety reasons. A short circuit could 
otherwise occur should the signal direction of the bidirectional binary inputs/outputs be 
incorrectly parameterized (see also point 3). 
This risk of short circuits does not exist on EB2 boards. 
The analog inputs on the EB1 can be used either as current or voltage inputs, the mode 
being selected by setting jumpers (X486, X487, X488) appropriately (see Function 
Diagrams, Section 8). The same applies to EB2 (X498); on this board, the analog output can 
also be configured as a current or voltage source (X499). 
Parameterize the desired functions for the inputs and outputs (see Function Diagrams, 
Section 8). 
If you wish to operate a bidirectional binary input/output on an EB1 as an input, please note 
that the output circuit must be deactivated in the corresponding parameter (e.g. U769.01=0). 
A short circuit will otherwise occur if the signal levels of the external input and output signals 
are opposed. 
Switch off the device. 
With the power supply disconnected, insert the adapter board with expansion board in a 
location. Please remember to insert a board in location 2 before you use location 3.  
EB1 boards only: Plug connector X480 back into board. 
Expansion boards EB1 and EB2 expand the range of terminals on the basic converter. A total of 2 
EB1 boards and 2 EB2 boards may be installed in one SIMOREG DC-MASTER 6RA70. The EB1 
and/or EB2 are plugged into adapter (carrier) boards (ADB). 2 boards may be mounted on each 
ADB. 
The EB1 provides the following expansion terminals: 
3 binary inputs 
4 bidirectional binary inputs/outputs 
1 analog input for differential signal (current or voltage input) 
2 analog inputs (single ended), can also be used as binary inputs 
2 analog outputs 
1 connector for external 24 V voltage supply to binary outputs 
The EB2 provides the following expansion terminals: 
2 binary inputs 
1 connector for external 24 V voltage supply to binary outputs 
1 relay output with changeover contacts 
3 relay outputs with NO contacts 
1 analog input for differential signal (current or voltage input) 
1 analog output (current or voltage output) 
For further details, see Section 8, function diagrams for expansion boards EB1 and EB2. 
.NET PDF Document Viewing, Annotation, Conversion & Processing
Convert image files to PDF. File & Page Process. Annotate & Comment. Add, insert PDF native annotations to PDF file. Support for all the print modes in Acrobat PDF
how to add a jpg to a pdf; how to add a photo to a pdf document
C# PDF Converter Library SDK to convert PDF to other file formats
without using other external third-party dependencies like Adobe Acrobat. you can easily perform file conversion from PDF document to image or document
attach image to pdf form; add picture to pdf document
SIEMENS AG    6RX1700-0AD76 
7-45 
SIMOREG DC-MASTER    Operating Instructions 
7.7.6  Procedure for starting up the pulse encoder board (SBP) 
Set the switches (for encoder supply and bus terminating resistors) on the SBP board: 
If one
pulse encoder is connected to one
SBP board, then the three switches for bus 
terminating resistors must be switched to ON. 
If one
pulse encoder is connected to several
SBP boards, then the three switches for bus 
terminating resistors must be switched to ON only on the last SBP. 
The fourth switch connects and disconnects the supply voltage for the encoder. 
(Caution: Switch open means supply voltage connected) 
Disconnect power supply and insert adapter with board into location. Please remember to 
insert a board in location 2 before you use location 3.  
Connect the terminals on strips X400, X401 on the pulse encoder board to the appropriate 
terminals on the encoder (for circuit example, refer to operating instructions for pulse 
encoder board). If you connect unipolar signals, a ground connection for all signals to 
terminal 75 (CTRL-) is sufficient. For very long lines or high interference irradiation, we 
recommend jumpering terminals 69, 71, and 75 (A-, B-, and CTRL-) and connecting to 
encoder ground. The zero track of the pulse encoder is not evaluated by SIMOREG and 
need not therefore be connected. 
The terminals designated coarse pulse1, coarse pulse2 and fine pulse2 can be used as 
digital inputs for any function (see Function Diagrams in Section 8) 
Please make the following settings: 
- U790  Voltage level of inputs 
0: 
HTL unipolar 
1: 
TTL unipolar 
2: 
HTL differential input 
3: 
TTL/RS422 differential input 
- U791  Level of encoder supply 
0: 
5V   voltage supply 
1: 
15V voltage supply 
- U792   Pulse encoder resolution 
- U793   Type of pulse encoder 
0: 
Encoder with A/B track (two tracks displaced by 90 degrees) 
1: 
Encoder with separate forward and reverse track 
- U794  Reference speed 
(For further details, see Section 11, description of parameters U790- U794) 
The pulse encoder board SBP (Sensor Board Pulse) supports commercially available pulse 
encoders with pulse frequencies up to 410kHz. The voltage level of the encoder signals can be 
parameterized. TTL or HTL level pulses, bipolar or unipolar, can be used. 
A voltage supply for 5V and 15V encoders is provided on the board. 
Evaluation of a temperature sensor is not supported on SIMOREG DC-MASTER 6RA70 
converters. 
C# Windows Viewer - Image and Document Conversion & Rendering in
without using other external third-party dependencies like Adobe Acrobat. Image and Document Conversion Supported by Windows Viewer. Convert to PDF.
add png to pdf acrobat; how to add image to pdf document
C# powerpoint - PowerPoint Conversion & Rendering in C#.NET
using other external third-party dependencies like Adobe Acrobat. SDK to convert PowerPoint document to PDF document code for PowerPoint to TIFF image conversion
add an image to a pdf form; acrobat insert image into pdf
7-46
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
7.7.7  Sequence of operations for starting up DeviceNet boards (CBD): 
With the power supply switched off, insert the board or adapter board with board in the slot. 
Please note that slot 2 (on right) must always be occupied before slot 3 (in center) can be 
used.  
Wire up the DeviceNet using appropriate cabling (see below for details of cables).  
The following parameters are relevant with respect to communications. Index 1 of the 
relevant parameter applies to the 1
st
communication board (1
st
CBx) and index 2 to the 2
nd
communication board (2
nd
CBx):  
U711  CB parameter1 
Definition of number of words in the process data area that the SIMOREG sends as 
a response to a request by the master (produced data). The following options can be 
selected: 
U711 = 170 ... 4 PZD (status word and actual values) 
U711 = 171 ... 8 PZD (status word and actual values) 
U711 = 172 ... 16 PZD (status word and actual values) 
-U712 CB parameter2 
Definition of number of words in the process data area that SIMOREG expects to 
receive  after a request from the master (consumed data). The following options can 
be selected: 
U712 = 120 ... 4 PZD (control word and setpoints) 
U712 = 121 ... 8 PZD (control word and setpoints) 
U712 = 122 ... 16 PZD (control word and setpoints) 
U711 and U712 can be parameterized independently of one another. The first 4 PZD 
words (produced data) are always sent after a request from the master. 
-U720 CB parameter10 
Definition of the DeviceNet transmission rate. The following options can be selected: 
U720 = 0 ....... 125kbaud 
U720 = 1 ....... 250kbaud 
U720 = 2 ....... 500kbaud 
- U722 CB/TB telegram failure time 
Definition of the time period within which at least 1 telegram with PZDs must be 
exchanged before a fault message is generated. 
This parameter should be set to "0" first (monitoring function deactivated). Once the 
network is operating correctly, a time value can be set within which PZDs are 
normally exchanged. 
P918  Bus address 
Definition of DeviceNet MAC ID for the CBD in the 0 to 63 range. 
P927  Parameterizing enable (necessary only if parameter values need to be altered via 
DeviceNet) 
The process data of the 1
st
or 2
nd
communication board are wired up by means of the 
appropriate connectors or binectors (see Section 8, function diagrams Z110 and Z111). 
For meaning of the control and status word bits, see Section 8, Sheets G180 to G183. 
Switch the electronics power supply off and on again or set U710.001 or U710.002 to "0" to 
transfer the values of parameters U712, U720, U722 and P918 to the supplementary board. 
C# Word - Word Conversion in C#.NET
using other external third-party dependencies like Adobe Acrobat. Word SDK to convert Word document to PDF document. demo code for Word to TIFF image conversion
adding image to pdf in preview; add picture to pdf in preview
VB.NET PDF: How to Create Watermark on PDF Document within
Using this VB.NET Imaging PDF Watermark Add-on, you can a watermark that consists of text or image (such as And with our PDF Watermark Creator, users need no
how to add a jpeg to a pdf file; add image pdf
SIEMENS AG    6RX1700-0AD76 
7-47 
SIMOREG DC-MASTER    Operating Instructions 
WARNING
This initialization process will interrupt the communication of any supplementary 
board that has already been started up. 
The CBD board supports "DeviceNet Explicit Messages“ for the transfer of process data, as well as 
"DeviceNet I/O Messages“ for the transmission of parameter data. The meaning of the data within 
an I/O message is determined by the corresponding "Connection ID". 
The CBD supports the "Predefined Master/Slave Connection Set“ defined in the DeviceNet 
Specification. Both "poll" and "bit strobe I/O messages“ are supported. 
The CBD adheres to the "DeviceNet Device Profile for Communication Adapter“ (Device Type 12). 
This profile has been selected to allow the DeviceNetMaster to utilize all the options and extended 
functions provided by the SIMOREG.  
DeviceNet messages can be divided roughly into 3 groups: 
DeviceNet configuration data, e.g. channel assignment, timeouts and I/O messages, for 
which explicit messages are used 
Process data, e.g. control/status word and setpoints/actual values, for which I/O 
messages are used 
Parameter data, for which manufacturer-specific PKW objects and explicit messages are 
used, to read or modify drive parameter settings 
The drive is controlled by process data. The number of process data words is determined either by 
the value of particular CB parameters (U711 and U712) after booting, or dynamically by the 
DeviceNet. 
The master uses a manufacturer-specific PKW object to read or modify drive parameters via 
DeviceNet, utilizing the explicit messaging channel. The user thus has access via DeviceNet to all 
SIMOREG parameters and any installed technology board (e.g. detailed diagnostic information and 
fault messages). 
DeviceNet specifies a shielded cable with 2 individually screened two-wire conductors for signal 
transmission and power supply. 2 types of different cross-sections may be used, i.e. "Thin Cable“ 
and "Thick Cable“. 
Thick cables are used in networks of >100m in length and thin cables for spur lines and networks 
of <100m. 
The following cable types are recommended for use as DeviceNet bus cables: 
Thin cable: Belden 3084A 
Thick cable: Belden 3082A, 3083A or 3085A 
Pin assignment and color coding are defined as follows: 
Pin 
Function 
Color of wire in DeviceNet cable 
X438.1 
V- 
Black (power supply ground) 
X438.2 
CAN- 
Blue 
X438.3 
Shield 
X438.4 
CAN+ 
White 
X438.5 
V+ 
Red ( +24V supply +/- 1% ) 
Recommended bus connector: Phoenix Combicon MSTB 2.5/5-ST-5.08-AU 
BMP to PDF Converter | Convert Bitmap to PDF, Convert PDF to BMP
Also designed to be used add-on for .NET Image SDK, RasterEdge Bitmap to PDF Converter can Powerful image converter for Bitmap and PDF files; No need for
add image in pdf using java; add photo to pdf in preview
PDF to WORD Converter | Convert PDF to Word, Convert Word to PDF
out transformation between different kinds of image files and Word Converter has accurate output, and PDF to Word need the support of Adobe Acrobat & Microsoft
acrobat add image to pdf; add picture to pdf reader
7-48
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Transmission rates and bus cable lengths: 
Spur line length (thin cable) 
Transmission rate 
Max. cable length 
(thick cable) 
Maximum 
Cumulative 
125kbaud 
500m 
6m 
156m 
250kbaud 
250m 
6m 
78m 
500kbaud 
100m 
6m 
39m 
To ensure proper functioning, both ends of the bus cable must be terminated by a terminating 
resistor (121Ω metal film resistor, +/- 1%, 0.25W). 
The DeviceNet cable screen should be earthed at ONE point (e.g. at the power supply). Earthing 
the screen at several locations can produce ground loops and cause malfunctions. 
Telegrams transmitted via DeviceNet have the same useful data structure as those used in CAN 
Bus communication.  
A CAN telegram comprises the protocol header, CAN identifier, up to 8 bytes of useful data and the 
protocol trailer. 
The methods applied for DeviceNet transmissions allow useful data of any length to be transferred. 
Data which are longer than 8 bytes can be transmitted in fragmented form (in several consecutive 
telegrams). 
PZD object (process data) 
Both control words and setpoints as well as status words and actual values (process data) are 
transmitted by means of DeviceNet I/O message connections. The number of process data to be 
transferred (4, 8 or 16) depends on which DeviceNet I/O assembly instance has been selected. 
The quantity of process data transmitted by the drive can differ from the quantity received. 
Options for defining the number of PZD: 
"Consumed Connection Path“ with "Poll I/O" (direction: Master -> drive) 
U712 = 120 ... 4 PZD (control word and setpoints) 
U712 = 121 ... 8 PZD (control word and setpoints) 
U712 = 122 ... 16 PZD (control word and setpoints) 
"Produced Connection Path“ with "Poll I/O“ (direction: Drive -> master) 
U711 = 170 ... 4 PZD (status word and actual values) 
U711 = 171 ... 8 PZD (status word and actual values) 
U711 = 172 ... 16 PZD (status word and actual values) 
"Produced Connection Path“ with "Bit Strobe I/O“  
U711 = 170 ... 4 PZD (status word and actual values); cannot be changed 
The meaning of each process data word is determined by the assignment of connectors 
parameterized in the drive (see function diagrams in Section 8, particularly "Data exchange with 1
st
and 2
nd
CB"). Process data can be exchanged between the SIMOREG and CBD 6x per line period, 
i.e. every 3.3ms at 50Hz, but is dependent on the data exchange mode via DeviceNet. For further 
details, see also "Information about PZD transmission" in Section 7, "Sequence of operations for 
starting up CAN Bus boards“. 
Information about PZD transmission: 
The low-order byte or word is always transferred before the high-order byte or word. 
Control word 1 must always be sent as the first PZD word. If control word 2 is also used, this must 
always be sent as the 4
th
PZD word. 
Bit10 in control word 1 ("control requested“) must always be set or else no new setpoints will be 
accepted from the drive. 
The second PZD word should normally contain the main setpoint. 
VB.NET PowerPoint: VB Code to Draw and Create Annotation on PPT
as a kind of compensation for limitations (other documents are compatible, including PDF, TIFF, MS VB.NET PPT: VB Code to Add Embedded Image Object to
adding images to pdf; how to add an image to a pdf in preview
JPEG to PDF Converter | Convert JPEG to PDF, Convert PDF to JPEG
It can be used standalone. JPEG to PDF Converter is able to convert image files to PDF directly without the software Adobe Acrobat Reader for conversion.
add an image to a pdf; add picture to pdf reader
SIEMENS AG    6RX1700-0AD76 
7-49 
SIMOREG DC-MASTER    Operating Instructions 
The consistency of a block of data words is guaranteed within a DeviceNet I/O message 
connection even in cases where more than 4 PZD words are used and the transmission data is 
distributed among several telegrams. The data are not transferred from the CBD to the drive until 
all data words have been received. 
PKW object (parameter data) 
The manufacturer-specific PKW object (class 100) is used to read and modify parameters of the 
drive or a technology board by means of the DeviceNet master (PKW = parameter identifier value). 
Explicit messaging mode is used for this purpose.  
Only two instances are implemented for the PKW object: Instance 0 permits access to class 
attributes and instance 1 (always set to "1") access to all parameter numbers (see DeviceNet 
objects below).  
Apart from the protocol header and trailer specific to DeviceNet, the structure of a telegram is 
follows: 
Parameter identifier 
PKE 
Parameter index 
IND 
Parameter value1 
PWE1 
Parameter value2 
PWE2 
For details about this telegram area, see also Section 7.7.9, Structure of request/response 
telegrams. The useful data area of PROFIBUS, CAN Bus and DeviceNet telegrams is structured 
identically. 
DeviceNet GET Single 
This object is used to read parameter values and 9 bytes in length. 
Byte 
DeviceNet identification 
[FRAG] [XID] [SRC/DST MAC ID] 
[R/R] [Service] 
0x0E  [Get_Attribute_Single] 
Class 
100 
[PKW object] manufacturer-specific 
Instance 
[Instance number] always set to 1 
Attribute 
[Attribute number] always set to 1 
Parameter ID, L byte 
PKE 
Parameter ID, H byte 
Parameter index, L byte 
IND 
Parameter index, H byte 
DeviceNet SET Single 
This object is used to modify parameter values and 14 bytes in length 
Byte 
DeviceNet identification 
[FRAG] [XID] [SRC/DST MAC ID] 
[Fragmentation Protocol] 
[R/R] [Service] 
0x10  [Set_Attribute_Single] 
Class 
100 
[PKW object] manufacturer-specific 
Instance 
[Instance number] always set to 1 
Attribute 
[Attribute number] always set to 1 
Parameter ID, L byte 
PKE 
Parameter ID, H byte 
Parameter index, L byte 
10 
IND 
Parameter index, H byte 
11 
Parameter value, L word, L byte 
12 
PWE1 
Parameter value, L word, H byte 
13 
Parameter value, H word, L byte 
14 
PWE2 
Parameter value, H word, H byte 
7-50
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
DeviceNet Response 
This object is used to respond to requests of the above type and 8 bytes in length. 
Byte 
DeviceNet identification 
[FRAG] [XID] [SRC/DST MAC ID] 
[R/R] [Service] 
0x8E  [Get/Set_Attribute_Single] 
0x90   
Parameter ID, L byte 
PKE 
Parameter ID, H byte 
Parameter value, L word, L byte 
PWE1 
Parameter value, L word, H byte 
Parameter value, H word, L byte 
PWE2 
Parameter value, H word, H byte 
Examples 
Read parameter P101.004 using GET Single (for details in the shaded data area, see also Section 
7, Starting up PROFIBUS boards): 
Byte 
DeviceNet identification 
[FRAG] [XID] [SRC/DST MAC ID] 
[R/R] [Service] 
0x0E  [Get_Attribute_Single] 
Class 
100 
[PKW object] manufacturer-specific 
Instance 
[Instance number] always set to 1 
Attribute 
[Attribute number] always set to 1 
0x65  Parameter ID, L byte 
PKE 
0x60  Parameter ID, H byte 
Parameter index, L byte 
IND 
Parameter index, H byte 
Request identifier = 0x6065 (request parameter value (array) P101), Index = 0004h = 4d 
Response by SIMOREG: 
Byte 
DeviceNet identification 
[FRAG] [XID] [SRC/DST MAC ID] 
[R/R] [Service] 
0x8E  [Get_Attribute_Single] 
0x65  Parameter ID, L byte 
PKE 
0x40  Parameter ID, H byte 
0x90  Parameter value, L word, L byte 
PWE1 
0x01  Parameter value, L word, H byte 
0x00  Parameter value, H word, L byte 
PWE2 
0x00  Parameter value, H word, H byte 
Response identifier = 0x4065, value of P101.004 = 0190h = 400d (PWE2 remains unused because 
it is not a double word parameter) 
SIEMENS AG    6RX1700-0AD76 
7-51 
SIMOREG DC-MASTER    Operating Instructions 
Modify parameter U099.001 using SET Single (for details in the shaded data area, see also 
Section 7, Starting up PROFIBUS boards): 
Byte 
DeviceNet identification 
[FRAG] [XID] [SRC/DST MAC ID] 
[Fragmentation Protocol] 
[R/R] [Service] 
0x10  [Set_Attribute_Single] 
Class 
100 
[PKW object] manufacturer-specific 
Instance 
[Instance number] always set to 1 
Attribute 
[Attribute number] always set to 1 
0x63  Parameter ID, L byte 
PKE 
0x70  Parameter ID, H byte 
0x01  Parameter Index, L byte 
10 
IND 
0x80  Parameter Index, H byte 
11 
0xC8  Parameter value, L word, L byte 
12 
PWE1 
0x00  Parameter value, L word, H byte 
13 
0x00  Parameter value, H word, L byte 
14 
PWE2 
0x00  Parameter value, H word, H byte 
Request identifier = 7063h (modify parameter value (array) U099), index = 0001h = 1d (bit 15 is 
also set in the H byte in order to address the parameter number range from 2000 to 4000), value = 
00C8h = 200d 
Response by SIMOREG: 
Byte 
DeviceNet identification 
[FRAG] [XID] [SRC/DST MAC ID] 
[R/R] [Service] 
0x90  [Set_Attribute_Single] 
0x63  Parameter ID, L byte 
PKE 
0x40  Parameter ID, H byte 
0xC8  Parameter value, L word, L byte 
PWE1 
0x00  Parameter value, L word, H byte 
0x00  Parameter value, H word, L byte 
PWE2 
0x00  Parameter value, H word, H byte 
Response identifier = 0x4063, value of U099.001 = 00C8h = 200d (PWE2 remains unused 
because SIMOREG 6RA70 has no double word parameters) 
Information about PKW transmission: 
The length of a request from the master is two words (for GET Single) or 4 words (SET Single). 
The length of a SIMOREG response is always 3 words. 
The low-order byte or word is always sent before the high-order byte or word. 
The master may generate a new PKW request only after it has received a response from the slave 
to the previous request. 
The master identifies the response to the transmitted request by 
evaluating the response identifier 
evaluating the parameter number 
evaluating the parameter value (if further identification is needed) 
The CBD slave does not respond to a parameter request until it has received the relevant data 
from the drive. The time delay depends on the type of request, but is at least 20 ms. During the 
initialization phase after Power ON or a re-initialization operation due to a change in a CB 
parameter setting, requests may not be processed at all, in which case the ensuing delay could be 
as much as 40 s.  
7-52
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
7.7.7.1  Diagnostic tools: 
LED displays on the CBD (steadily flashing LEDs indicate normal operation): 
Red 
Status of CBD (software working correctly) 
Yellow 
Communication between SIMOREG and CBD 
Green 
PZD data exchange between CBD and DeviceNet 
LED 
red 
yellow 
green 
Status 
flashing 
flashing 
flashing 
Normal operation 
flashing 
off 
on 
CBD waiting for commencement of initialization by SIMOREG 
flashing 
on 
off 
CBD waiting for end of initialization by SIMOREG 
flashing 
flashing 
off 
No PZD data exchange via DeviceNet 
flashing 
on 
on 
CBD defective 
Diagnostic parameter n732: 
Indices i001 to i032 apply to a CBD as the first communication board, while indices i033 to i064 
apply to a CBD as the second communication board. 
Value 
Meaning 
n732.001  
or  
n732.033 
17 
Ok 
Fault F080/fault value 5 is displayed under fault conditions: 
DeviceNet MAC ID (P918 / slave address) incorrect 
DeviceNet polled I/O produced connection path (U711) incorrect 
DeviceNet polled I/O produced consumed path (U712) incorrect 
Baud rate (U720) incorrect 
n732.002  
or  
n732.034 
The displayed decimal values must be converted to hexadecimal values. In hexadecimal 
notation, every digit of the 16-bit data word has a meaning: 
Bit8
Bit9
Bit10
Bit11
Thousands place
Units place
Tens place
Thousands place: 
(Idle Indicator) 
0 = device not idle; A 
poll or bit strobe 
request with length 
other than 0 was last 
received  
1 = device idle; A 
poll or bit strobe 
request with length 
equal to 0 was last 
received 
Hundreds place: 
(Channel Allocation)
The meaning of 
individual bits is as 
follows 
Bit8: 1 = Explicit 
Channel allocated 
Bit9: 1 = I/O Poll 
Channel allocated 
Bit10: 1 = I/O Bit 
Strobe Channel 
allocated 
Bit11: 1 = Reserved 
Tens place: 
Reserved 
Units place: 
(network status) 
0 = CBD not online 
(Dup_MAC_ID test 
not yet complete) 
1 = CBD online, but 
not assigned to a 
master 
2 = CBD online and 
assigned to the 
master 
3 = data cannot be 
exchanged via bus 
(multiple MAC IDs or 
Bus Off) 
n732.003  
or  
n732.035 
Number of correctly received telegrams since Power ON. The value contains all Group2 
DeviceNet messages including those that are not addressed to this CBD. 
n732.008  
or  
n732.040 
Number of correctly received PZD telegrams since Power ON 
n732.009  
or  
n732.041 
Number of Bus Off states since Power ON (alarm A084) 
n732.019  
or  
n732.051 
Number of correctly transmitted telegrams since Power ON 
n732.026  
or  
n732.058 
Software version of CBDs 
( e.g. "12“ = Version 1.2, see also r060) 
Documents you may be interested
Documents you may be interested