SIEMENS AG    6RX1700-0AD76 
7-53 
SIMOREG DC-MASTER    Operating Instructions 
Value 
Meaning 
n732.027  
or  
n732.059 
Software identifier 
(extended software version identifier, see also r065) 
n732.028  
or  
n732.060 
Date of generation of CBD software (day and month) 
(e.g. "2508“ = 25th August) 
n732.029  
or  
n732.061 
Date of generation of CBD software (year) 
Fault and alarm messages: 
For details about fault messages, see Section 10. 
Fault F080  
An error occurred as board CBD was being initialized, e.g. incorrect value of a CB 
parameter, incorrect bus address or defective board. 
Fault F081  
The heartbeat counter (counter on CBD) which is monitored by SIMOREG for "signs of life" 
from the board has not changed for at least 800 ms. 
Fault F082  
Failure of PZD telegrams or a fault in the transmission channel. 
Alarm A081  
Idle condition alarm; a PZD telegram of length = 0 has been received either in the "poll" or 
"bit strobe I/O message channel". The alarm is reset when a PZD telegram of normal length 
is received. 
Faulty CAN messages of this type are ignored. The last transmitted data remain valid. 
Alarm A083 (error alarm) 
Telegrams containing errors are being received or transmitted and the error counter on the 
supplementary board has exceeded the alarm limit. 
The faulty telegrams are ignored. The last transmitted data remain valid. If the faulty 
telegrams contain process data, fault message F082 with fault value 10 may be generated 
as a function of the telegram failure time set in U722. 
Alarm A084  
Faulty DeviceNet CAN telegrams have been received or transmitted, causing the internal 
error counter to overrun. 
Faulty CAN messages of this type are ignored. The last transmitted data remain valid. 
Add signature image to pdf - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
how to add a picture to a pdf file; add photo to pdf form
Add signature image to pdf - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
how to add an image to a pdf file in acrobat; how to add image to pdf
7-54
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
7.7.8  Sequence of operations for starting up the serial I/O board (SCB1): 
With the power supply disconnected, insert the SCB1 board into slot 2 (or, if you have 
installed a technology board, into slot 3).  
Set bus address on SCI using DIP-Fix switch S1 (each SCI slave requires its own address 
number): 
Slave 1 
Slave 2 
Address number 
Switch setting S1 
open 
closed 
Mount the interface board(s) on the rail, make the connection to the 24 V power supply and 
the fiber optic connection between SCB1 and SCI. 
The SCB1 board is used in conjunction with the SIMOREG DC-MASTER only as the master 
for SCI slaves.  
Depending on the type of SCI slaves used and the functions required, the following 
parameters are relevant with respect to board operation (for details, see function diagrams 
in Section 7, and parameter list in Section 11): 
U690  Configuration of analog inputs of SCI1 
The type of input signal for each input is parameterized via the indices. 
- U691 Smoothing time constant of analog inputs of SCI1 
Filtering of the input signal for each input is parameterized via the indices. 
U692  Zero calibration of analog inputs of SCI1 
The input signal for each input is zero calibrated via the indices. 
U693 Actual value output via analog outputs of SCI1 
A connector number is selected via the indices to define the output quantity at each 
output. 
U694 Gain of analog outputs of SCI1 
The gain for each output is parameterized via the indices. 
U695  Zero calibration of analog outputs of SCI1 
The output signal for each output is zero calibrated via the indices. 
U698  Binector selection for binary outputs of SCI1 
Selection of binectors whose states are output via the binary outputs of the SCIs. 
Display parameters n697 (diagnostic information) and n699 (display of input/output data) 
facilitate troubleshooting during start-up. 
Switch the electronics power supply off and on again or set U710.001 or U710.002 to "0" to 
transfer the values of parameters U690 to U698 to the supplementary board. 
Note: This initialization process will interrupt the communication of any supplementary board 
that has already been started up. 
C# PDF Digital Signature Library: add, remove, update PDF digital
Verify the validity of PDF signature. Add necessary references CHINA SHANGHAI"; cert.Reason = "Reason"; cert.APMode = APMode.Text; // APMode.Text | APMode.Image.
add image field to pdf form; adding image to pdf in preview
VB.NET PDF Digital Signature Library: add, remove, update PDF
Verify the validity of PDF signature. Add necessary references: CHINA SHANGHAI" cert.Reason = "Reason" cert.APMode = APMode.Text ' APMode.Text | APMode.Image.
add photo to pdf in preview; add signature image to pdf
SIEMENS AG    6RX1700-0AD76 
7-55 
SIMOREG DC-MASTER    Operating Instructions 
Option board SCB1 (Serial Communication Board 1) is used to link the SIMOREG DC-MASTER 
6RA70 to board SCI1 or SCI2 (Serial Communication Interface) using a fiber optic connection 
(recommendation: Siemens plastic fiber optic cable, CA-1V2YP980/1000,200A or Siemens glass-
fiber cable, CLY-1V01S200/230,10A). These boards can be used if the CUD2 terminal expansion 
module is not large enough or safe electrical isolation via fiber optics is an absolute necessity. 
This board only allows the SCB1 master to exchange data with the SCI slaves. Data cannot be 
exchanged between the SCI slaves themselves.  
A maximum of 2 SCIs, of either the same or different types, can be connected to the SCB1. 
SCI1 or SCI2 are terminal expansion boards which are mounted on a rail outside the SIMOREG 
DC-MASTER and supplied with 24 V DC voltage (-17% +25%, 1A) from an external source. 
The interface boards extend the converter by the following additional inputs/outputs: 
SCI1 
SCI2 
10  binary inputs 
16  binary inputs 
 binary outputs 
12  binary outputs 
 analog inputs 
 analog outputs 
Reception of SCI data by the SCB1 or transmission to the SCIs is synchronized, i.e. the data of two 
slaves is received simultaneously or transmitted simultaneously.  
Details about the functions and connections of inputs and outputs are shown in the function 
diagrams in Section 8. 
CAUTION
SCI boards have no external enclosure to protect them against direct contact or ingress of 
pollutants. To protect them against damage, they must be installed in a housing or in the 
control cabinet of a higher-level system. 
The maximum permissible length of fiber optic cables is 10m. 
An input filter must be fitted for the external power supply of the interface boards. 
Ground SCI at X80 using a short lead. 
Analog inputs on SCI1: Only the voltage input or the current input may be used for each 
channel. 
Analog outputs on SCI1: Only the voltage input or the current input may be used for each 
channel. The outputs are short-circuit-proof. 
The binary driver outputs are short-circuit-proof. Relays may only be connected to these 
outputs in conjunction with an external power supply. 
The binary relay outputs are not designed for protective separation. 
To protect them against static discharge, the boards may only be placed on conductive 
surfaces. 
C# HTML5 Viewer: Load, View, Convert, Annotate and Edit PDF
convert PDF to multi-page Tiff image files and to PDF, including freehand signature, text and date signature. If you need to add your own signatures such as
how to add a photo to a pdf document; add image pdf
C# HTML5 Viewer: Load, View, Convert, Annotate and Edit Tiff
For examples, add text signature to Tiff image, insert date signature to Tiff or create freehand signature to Tiff.
adding a png to a pdf; add jpg to pdf preview
7-56
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Recommended circuit for connecting SCB1 to SCI1 and SCI2 using fiber optic cables: 
SCB1
SCI2
SCI1
U121
U125
U425
U421
U435
U431
X427
X437
24V
X428
X429
X438
X439
WARNING
If the 24 V voltage supply for an SCI slave fails which data are being exchanged between the 
SCB1 and an SCI, then the "1" signal applied at a binary input is sent to the SCB1 or 
SIMOREG as an "0" shortly before the power finally fails. 
In contrast, the "1" remains applied in the SIMOREG in the event of an interruption in the fiber 
optic connection. 
If an external voltage (logical "1") has already been applied to a binary input when the electronics 
supply voltage is switched on, this status will not be registered until the external voltage is 
disconnected and reconnected again. 
7.7.8.1  Diagnostic tools: 
LED display on SCB1: 
LED on 
Reset state 
LED flashing 
Normal operation 
LED off 
Error 
LED display on SCI1 or SCI2 slave: 
LED on 
Reset state 
LED flashing 
12Hz frequency  No telegram traffic (e.g. fiber optic cable not 
connected) 
5Hz frequency  Faulty telegram traffic (e.g. fiber optic ring  
interrupted or other slave has no supply 
voltage) 
0.5Hz frequency  Normal operation 
LED off 
Error 
Details about fault or alarm messages which may occur in relation to SCB1 or SCI (F070 to F079 
and A049 and A050) can be found in Section 10. 
C# WPF Viewer: Load, View, Convert, Annotate and Edit Tiff
users can perform Tiff viewing and multiple Tiff image manipulation functionalities. convert Tiff file to PDF, add annotations to Tiff, Create signature on tiff
adding an image to a pdf form; add image to pdf preview
C# WinForms Viewer: Load, View, Convert, Annotate and Edit Tiff
load Tiff to WinForms Viewer easily and view Tiff image on it in preview, such as convert Tiff file to PDF, add annotations to Tiff, Create signature on tiff
add a jpeg to a pdf; add image to pdf acrobat reader
SIEMENS AG    6RX1700-0AD76 
7-57 
SIMOREG DC-MASTER    Operating Instructions 
7.7.9  Structure of request/response telegrams 
There is no basic difference between the useful data area in the request and response telegrams 
for PROFIBUS and CAN Bus. There are differences, for example, in the protocol frame and in the 
sequence in which H and L bytes are transmitted. The structures shown here are those of a 
SIMOREG DC-MASTER n735, for example. The structure of the protocol frame and the 
transmission sequence of bytes are therefore described where necessary in the sections 
containing the start-up description for the appropriate board. 
Each request and each response basically comprises three areas apart from the telegram frame 
with header and trailer: 
Header
Trailer
Index
IND
Parameter value
PWE
Parameter identifier
PKE
The parameter identifier (PKE) contains a request or response identifier (i.e. type of request or 
response) and the number of the addressed parameter. The spontaneous signaling bit SPM (bit11) 
is not used on the SIMOREG DC-MASTER. 
Header
Trailer
Index
IND
SPM
Parameter value
PWE
Parameter identifier
PKE
Task/ response 
identifier
Parameter number (PNU)
Bits 0 to 10 contain the number of the parameter specified in the request. 
Owing to the length restriction of the bit field (11 bits), a parameter number (PNU) higher than 
1999 must be converted to another code for use in the parameter identifier; the Page Select Bit in 
the index is used for this purpose: 
Parameter 
area 
Displayed 
number 
Input on OP1S 
PNU in parameter 
identifier 
Page Select Bit 
(index bit 15) 
Pxxx, rxxx 
0 - 999 
0 - 999 
Basic unit 
Uxxx, nxxx 
2000 - 2999 
0 - 999 
Hxxx, dxxx 
1000 - 1999 
1000 - 1999 
Technology 
board 
Lxxx, cxxx 
3000 - 3999 
1000 - 1999 
In the case of a request, for example, which specifies parameter U280 (2280), therefore, PNU = 
280 must be entered in the parameter identifier and bit 15 set in the index. 
.NET PDF SDK - Description of All PDF Processing Control Feastures
Create signatures in existing PDF signature fields; Create signatures in new fields which hold the signature; Add signature image to PDF file. PDF Hyperlink Edit
add an image to a pdf with acrobat; add an image to a pdf in preview
How to C#: Basic SDK Concept of XDoc.PDF for .NET
In general, image extraction, editing, drawing, and You may add PDF document protection functionality into your C# PDF password and digital signature, and set
add jpeg signature to pdf; add image to pdf java
7-58
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Bits 12 to 15 contain the request identifier or the associated response identifier as shown in the 
following list: 
Response identifier 
Request 
identifier 
Meaning 
positive 
negative 
No request 
Request parameter value (word or double word) 
1 or 2 
Modify parameter value (word) 
Modify parameter value (double word) 
Request descriptive element 
Reserved 
Request parameter value (array) (word or double word) 
4 or 5 
Modify parameter value (array - word) 
Modify parameter value (array-double word) 
Request number of array elements 
10 
Reserved 
11 
Modify parameter value (array-double word) and store in EEPROM 
12 
Modify parameter value (array-word) and store in EEPROM 
13 
Modify parameter value (double word) and store in EEPROM 
14 
Modify parameter value (word) and store in EEPROM 
15 
Request text 
15 
7 or 8 
If the drive has been unable to process the request, it does not return the associated response 
identifier, but error identifier 7 (or 8) instead.  
In this case, an error code defining the error in more detail as shown in the following list is returned 
as a parameter value: 
Error code   
Meaning 
Illegal parameter number (PNU) 
No PNU specified 
Parameter value cannot be modified 
Visualization parameter 
Lower or upper value limit violated 
Faulty subindex 
Parameter is not indexed (no array) 
Incorrect data type 
Parameter value can only be reset 
Descriptive element cannot be modified 
PPO Write (acc. to "Information Report") is not available 
Parameter description is not available 
10 
Incorrect access level 
11 
No parameterizing enable (P927) 
12 
Keyword missing 
Key parameter P051 incorrectly set 
13 
Text cannot be read cyclically 
15 
No text 
16 
PPO Write missing 
17 
Incorrect operating state 
19 
Value cannot be read cyclically 
101 
Parameter number currently deactivated 
102 
Channel not wide enough 
SIEMENS AG    6RX1700-0AD76 
7-59 
SIMOREG DC-MASTER    Operating Instructions 
Error code   
Meaning 
103 
PKW number incorrect 
Applies only to serial interfaces 
104 
Illegal parameter value 
Applies to BiCo selection parameters 
105 
Indexed parameter 
106 
Request not implemented in drive 
107 
Text cannot be modified 
108 
Incorrect number of parameter values 
Applies to "Change all indices" request 
The index IND contains a "0" for non-indexed parameters; a 8-bit long index value is entered (in 
the low-order byte) for indexed parameters.  
Bit 15 (Page Select bit) has a special function. This is used to identify parameter numbers higher 
than 1999 (see above for details of recoding parameter numbers).  
Exception: In the case of cyclical PROFIBUS services, the L and H byte sequence is reversed (see 
"Start-up of PROFIBUS boards"). 
Header
Trailer
Index
IND
Bit
15
Parameter value
PWE
Parameter identifier
PKE
Index, L byte
Index, H byte
An index value of 255 means that the request applies to all indices of the relevant parameter. In the 
case of a modification request, the parameter values for all indices of the parameter must be 
transferred. Conversely, the drive supplies all index values in its response to a read request. 
The parameter value PWE is treated like a double word (PWE1 and PWE2). The high word is set 
to 0 when a single word is transferred. 
Header
Trailer
Index
IND
PWE2
PWE1
Parameter value
PWE
Parameter identifier
PKE
7-60
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
7.7.10  Transmission of double-word connectors for technology and 
communication modules 
In the receive direction, the values of two adjacent connectors (K) are combined to form a single 
double-word connector (KK) (e.g. K3002 and K3003 to KK3032). These double-word connectors 
can themselves be connected to other function blocks in the usual way. For details of how to 
connect double-word connectors, see Section 9.1, subsection, " The following rules apply to the 
selection of double-word connectors ". 
In the transmit direction, a double-word connector is applied by entering the same double-word 
connector in two contiguous indices of the selection parameter. 
Example: 
.04
.01
.03
.02
U734
32
9498
9498
401
K0032
KK9498
KK9498
K0401
Word
L-Word
Word
H-Word
2x the same KK - number
.04
.01
.03
.02
U734
32
9498
9499
401
K0032
KK9498
KK9499
K0401
Word
H-Word
Word
H-Word
2 different KKs !
SIEMENS AG    6RX1700-0AD76 
8-1 
SIMOREG DC-MASTER    Operating Instructions 
Function diagrams 
General
Page 
Key to symbols .......................................................................................................................  8-5 
Basic functions 
G100  Overview.................................................................................................................................  8-6 
G101  Hardware configuration ..........................................................................................................  8-7 
Inputs and outputs 
G110  Binary inputs terminals 36 to 39 (CUD1)................................................................................  8-8 
G111  Binary inputs terminals 40 to 43 (CUD2)................................................................................  8-9 
G112  Binary outputs terminals 46/47 and 48/54 (CUD1) ..............................................................  8-10 
Binary outputs terminals 50/51 and 52/53 (CUD2) ..............................................................  8-10  
G113  Analog inputs terminals 4/5, 6/7 (CUD1), and 103/104 (power interface) ...........................  8-11 
G114  Analog inputs terminals 8/9 and 10/11 (CUD2)....................................................................  8-12 
G115  Analog outputs terminals 12/13, 14/15, and 16/17 (CUD1) .................................................  8-13 
G116  Analog outputs terminals 18/19 and 20/21 (CUD2) .............................................................  8-14 
G117  E-Stop, Relay output line contactor (power interface)..........................................................  8-15 
Setpoint generation 
G120  Fixed values..........................................................................................................................  8-16 
Fixed control bits...................................................................................................................  8-16 
Constant fixed values and control bits..................................................................................  8-16 
G121  Connector and binector displays ..........................................................................................  8-17 
G124  Connector selector switch ....................................................................................................  8-18 
G125  Evaluation of a 4-step master switch....................................................................................  8-19 
G126  Motorized potentiometer.......................................................................................................  8-20 
G127  Fixed setpoint .......................................................................................................................  8-21 
G128  Oscillation / square-wave generator.....................................................................................  8-22 
G129  Inching setpoint.....................................................................................................................  8-23 
G130  Crawling setpoint / terminal 37 .............................................................................................  8-24 
G135  Setpoint processing..............................................................................................................  8-25 
G136  Ramp-function generator (1) ................................................................................................  8-26 
G137  Ramp-function generator (2) ................................................................................................  8-27 
Internal control 
G140  Brake control.........................................................................................................................  8-28 
Actual speed value 
G145  Pulse generator evaluation...................................................................................................  8-29 
Controllers 
G150  Starting pulse - speed controller...........................................................................................  8-30 
G151  Speed controller (1)..............................................................................................................  8-31 
G152   Speed controller (2)..............................................................................................................  8-32 
G153  Friction compensation ..........................................................................................................  8-33 
Compensation of moment of inertia (dv/dt injection)............................................................  8-33 
G160  Torque limitation,
speed limit controller................................................................................  8-34 
G161  Current limitation...................................................................................................................  8-35 
G162  Closed-loop armature current control...................................................................................  8-36 
G163  Auto-reversing stage, armature gating unit ..........................................................................  8-37 
G165  Closed-loop EMF control......................................................................................................  8-38 
G166  Closed-loop field current control, field gating unit ................................................................  8-39 
G167  Field current monitoring........................................................................................................  8-40 
8-2
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Page 
Serial interfaces 
G169  Serial interfaces: connector-type converters ........................................................................ 8-41 
G170  USS interface 1 (PMU) ......................................................................................................... 8-42 
G171  USS interface 2 (CUD1) ....................................................................................................... 8-43 
G172  USS interface 3 (CUD2) ....................................................................................................... 8-44 
G173  Peer-to-peer interface 2 (CUD1)........................................................................................... 8-45 
G174  Peer-to-peer interface 3 (CUD2)........................................................................................... 8-46 
Program structure 
G175  Data sets............................................................................................................................... 8-47 
Control words, status words 
G180  Control word 1....................................................................................................................... 8-48 
G181  Control word 2....................................................................................................................... 8-49 
G182  Status word 1........................................................................................................................ 8-50 
G183  Status word 2........................................................................................................................ 8-51 
Miscellaneous 
G185  Motor interface (1)................................................................................................................. 8-52 
G186  Motor interface (2) / binary inputs, terminals 211 to 214 ...................................................... 8-53 
G187  Messages (1) ........................................................................................................................ 8-54 
G188  Messages (2) ........................................................................................................................ 8-55 
G189  Fault memory ........................................................................................................................ 8-56 
G195  Paralleling interface .............................................................................................................. 8-57 
G200  Field reversal with SIMOREG single-quadrant device ......................................................... 8-58 