pdf renderer c# : Add a picture to a pdf SDK Library service wpf asp.net html dnn OPI_simoreg_DC_0707_en3-part1882

Siemens AG    6RX1700-0AD76 
3-9 
SIMOREG DC-MASTER    Operating Instructions 
3.4.4  Converters 3AC 400V, 850A to 2000A, 1Q 
Order No. 
6RA70 . . – 6DS22 
6RA70 . . – 4DS22 
87
91
93
95
Rated supply voltage armature  1) 
3AC 400  (+15% / – 20%) 
Rated input current armature   2) 
705 
995 
1326 
1658 
Rated supply voltage electronics 
power supply 
2AC 380 (– 25%) to 460 (+15%);  I
n
=1A or 
1AC 190 (– 25%) to 230 (+15%);  I
n
=2A 
(– 35% for 1min) 
Rated supply voltage fan 
3AC 400 (±15%) 50Hz
3AC 460 (±10%) 60Hz 
3AC 400 (±10%) 50Hz
3AC 460 (±10%) 60Hz 
3AC 400 (±10%) 50Hz 
3AC 460 (±10%) 60Hz 
50Hz 
60Hz 
50Hz 
60Hz 
Fan rated current 
0.3  8) 
1.0  9) 
1.25  9) 
1.0  9) 
1.25  9) 
Air flow rate 
m3/h 
570 
1300 
1300 
2400 
2400 
Fan noise level 
dBA 
73 
83 
87 
83 
87 
Rated supply voltage field   1) 
2AC 400  (+15% / – 20%)   7) 
Rated frequency 
Hz 
45 to 65   10) 
Rated DC voltage   1) 
485 
Rated DC current 
850 
1200 
1600 
2000 
Overload capability   6) 
max. 180% of rated DC current 
Rated output 
kW 
412 
582 
776 
970 
Power loss at rated DC current 
(approx.) 
2420 
4525 
5710 
6810 
Rated DC voltage field   1) 
max. 325 
Rated DC current field 
30 
40 
Operational ambient temperature 
°C 
0 to 40 at I
rated   
3)
forced-cooled 
Storage and transport 
temperature 
°C 
– 25 to +70 
Installation altitude above sea level 
≤ 1000 m at rated DC current   4) 
Control stability 
∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and
digital 
setpoint 
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog 
setpoint    5) 
Environmental class 
DIN IEC 60 721-3-3 
3K3 
Degree of protection 
DIN EN 60529 
IP00 
Dimensions (HxWxD) 
mm 
700x268x362 
780x410x362 
880x450x500 
Dimension diagram see Section 
5.1.5 
5.1.6 
5.1.7 
Weight (approx.) 
kg 
40 
80 
125 
Explanation at end of list of tables 
Add a picture to a pdf - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
how to add image to pdf reader; add picture to pdf in preview
Add a picture to a pdf - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
adding a jpeg to a pdf; add signature image to pdf
3-10
Siemens AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
3.4.5  Converters 3AC 460V, 30A to 125A, 1Q 
Order No. 
6RA70 . . – 6FS22 
18
25
28
31
Rated supply voltage armature  1) 
3AC 460  (+15% / – 20%) 
Rated input current armature   2) 
25 
50 
75 
104 
Rated supply voltage electronics 
power supply 
2AC 380 (– 25%) to 460 (+15%);  I
n
=1A or 
1AC 190 (– 25%) to 230 (+15%);  I
n
=2A 
(– 35% for 1min) 
Rated supply voltage field   1) 
2AC 460  (+15% / – 20%) 
Rated frequency 
Hz 
45 to 65   10) 
Rated DC voltage   1) 
550 
Rated DC current 
30 
60 
90 
125 
Overload capability   6) 
max. 180% of rated DC current 
Rated output 
kW 
16.5 
33 
49.5 
68.7 
Power loss at rated DC current 
(approx.) 
172 
248 
363 
417 
Rated DC voltage field   1) 
max. 375 
Rated DC current field 
10 
Operational ambient temperature  °C 
0 to 45 at I
rated   
3)
self-cooled 
Storage and transport 
temperature 
°C 
– 25 to +70 
Installation altitude above sea level 
≤ 1000 m at rated DC current   4) 
Control stability 
∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and
digital setpoint 
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog 
setpoint    5) 
Environmental class 
DIN IEC 60 721-3-3 
3K3 
Degree of protection 
DIN EN 60529 
IP00 
Dimensions (HxWxD) 
mm 
385x265x239 
385x265x313 
Dimension diagram see Section 
5.1.1 
5.2.1 
Weight (approx.) 
kg 
11 
15 
17 
17 
Explanation at end of list of tables 
C# TIFF: How to Insert & Burn Picture/Image into TIFF Document
Support adding image or picture to an existing or new new REImage(@"c:\ logo.png"); // add the image powerful & profession imaging controls, PDF document, tiff
add image to pdf acrobat; add jpg to pdf file
VB.NET Image: Image Cropping SDK to Cut Out Image, Picture and
VB.NET image cropper control SDK; VB.NET image cropping method to crop picture / photo; you can adjust the size of created cropped image file, add antique effect
add multiple jpg to pdf; add photo to pdf in preview
Siemens AG    6RX1700-0AD76 
3-11 
SIMOREG DC-MASTER    Operating Instructions 
3.4.6  Converters 3AC 460V, 210A to 600A, 1Q 
Order No. 
6RA70 . . – 6FS22 
75
78
82
85
Rated supply voltage armature  1) 
3AC 460  (+15% / – 20%) 
Rated input current armature   2) 
175 
233 
374 
498 
Rated supply voltage electronics 
power supply 
2AC 380 (– 25%) to 460 (+15%);  I
n
=1A or 
1AC 190 (– 25%) to 230 (+15%);  I
n
=2A 
(– 35% for 1min) 
Rated supply voltage fan 
DC 24V internal 
1AC 230 (±10%) 
50Hz 
60Hz 
Fan rated current 
0.55 
0.75 
Air flow rate 
m3/h 
100 
570 
570 
Fan noise level 
dBA 
40 
73 
76 
Rated supply voltage field   1) 
2AC 460  (+15% / – 20%) 
Rated frequency 
Hz 
45 to 65   10) 
Rated DC voltage   1) 
550 
Rated DC current 
210 
280 
450 
600 
Overload capability   6) 
max. 180% of rated DC current 
Rated output 
kW 
115 
154 
247 
330 
Power loss at rated DC current 
(approx.) 
700 
792 
1519 
1845 
Rated DC voltage field   1) 
max. 375 
Rated DC current field 
15 
25 
Operational ambient temperature 
°C 
0 to 40 at I
rated   
3)
forced-cooled 
Storage and transport 
temperature 
°C 
– 25 to +70 
Installation altitude above sea level 
≤ 1000 m at rated DC current   4) 
Control stability 
∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and
digital setpoint 
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog 
setpoint    5) 
Environmental class 
DIN IEC 60 721-3-3 
3K3 
Degree of protection 
DIN EN 60529 
IP00 
Dimensions (HxWxD) 
mm 
385x265x313 
625x268x318 
Dimension diagram see Section 
5.2.2 
5.2.3 
Weight (approx.) 
kg 
17 
18 
32 
Explanation at end of list of tables 
VB.NET TIFF: How to Draw Picture & Write Text on TIFF Document in
drawing As RaterEdgeDrawing = New RaterEdgeDrawing() drawing.Picture = "RasterEdge" drawing provide powerful & profession imaging controls, PDF document, tiff
add jpg to pdf preview; how to add image to pdf in acrobat
VB.NET Image: VB.NET Codes to Add Antique Effect to Image with .
mature technology to replace a picture's original colors add the glow and noise, and add a little powerful & profession imaging controls, PDF document, image
pdf insert image; add an image to a pdf form
3-12
Siemens AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
3.4.7  Converters 3AC 460V, 850A to 1200A, 1Q 
Order No. 
6RA70 . . – 6FS22 
87
91
Rated supply voltage armature  1) 
3AC 460  (+15% / – 20%) 
Rated input current armature   2) 
705 
995 
Rated supply voltage electronics 
power supply 
2AC 380 (– 25%) to 460 (+15%);  I
n
=1A or 
1AC 190 (– 25%) to 230 (+15%);  I
n
=2A 
(– 35% for 1min) 
Rated supply voltage fan 
1AC 230 (±10%) 
1AC 230 (±10%) 
50Hz 
60Hz 
50Hz 
60Hz 
Fan rated current 
0.55 
0.75 
2.6 
3.3 
Air flow rate 
m3/h 
570 
570 
1300 
1300 
Fan noise level 
dBA 
73 
76 
82 
85 
Rated supply voltage field   1) 
2AC 460  (+15% / – 20%) 
Rated frequency 
Hz 
45 to 65   10) 
Rated DC voltage   1) 
550 
Rated DC current 
850 
1200 
Overload capability   6) 
max. 180% of rated DC current 
Rated output 
kW 
467 
660 
Power loss at rated DC current 
(approx.) 
2514 
4620 
Rated DC voltage field   1) 
max. 375 
Rated DC current field 
30 
Operational ambient temperature  °C 
0 to 40 at I
rated   
3)
forced-cooled 
Storage and transport 
temperature 
°C 
– 25 to +70 
Installation altitude above sea level 
≤ 1000 m at rated DC current   4) 
Control stability 
∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and
digital setpoint 
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog 
setpoint    5) 
Environmental class 
DIN IEC 60 721-3-3 
3K3 
Degree of protection 
DIN EN 60529 
IP00 
Dimensions (HxWxD) 
mm 
700x268x362 
780x410x362 
Dimension diagram see Section 
5.2.4 
5.1.6 
Weight (approx.) 
kg 
42 
80 
Explanation at end of list of tables 
VB.NET Image: Image Scaling SDK to Scale Picture / Photo
Framework application; VB.NET sample code for how to scale image / picture; Frequently asked questions about RasterEdge VB.NET image scaling control SDK add-on.
add jpeg to pdf; add photo to pdf for
VB.NET Image: Create Code 11 Barcode on Picture & Document Using
file, apart from above mentioned .NET core imaging SDK and .NET barcode creator add-on, you also need to buy .NET PDF document editor add-on, namely, RasterEdge
adding image to pdf in preview; how to add an image to a pdf
Siemens AG    6RX1700-0AD76 
3-13 
SIMOREG DC-MASTER    Operating Instructions 
3.4.8  Converters 3AC 575V, 60A to 600A, 1Q 
Order No. 
6RA70 . . – 6GS22 
25
31
75
81
85
Rated supply voltage armature  1) 
3AC 575  (+10% / – 20%) 
Rated input current armature   2) 
50 
104 
175 
332 
498 
Rated supply voltage electronics 
power supply 
2AC 380 (– 25%) to 460 (+15%);  I
n
=1A or 
1AC 190 (– 25%) to 230 (+15%);  I
n
=2A 
(– 35% for 1min) 
Rated supply voltage fan 
DC24V 
internal 
3AC 400 (±15%) 50Hz 
3AC 460 (±10%) 60Hz 
Fan rated current 
0.3  8) 
Air flow rate 
m3/h 
100 
570 
Fan noise level 
dBA 
40 
73 
Rated supply voltage field   1) 
2AC 460  (+15% / – 20%) 
Rated frequency 
Hz 
45 to 65   10) 
Rated DC voltage   1) 
690 
Rated DC current 
60 
125 
210 
400 
600 
Overload capability   6) 
max. 180% of rated DC current 
Rated output 
kW 
41 
86 
145 
276 
414 
Power loss at rated DC current 
(approx.) 
265 
454 
730 
1550 
1955 
Rated DC voltage field   1) 
max. 375 
Rated DC current field 
10 
15 
25 
Operational ambient temperature 
°C 
0 to 45 at I
rated   
3)
self-cooled 
0 to 40 at I
rated   
3)
forced-cooled 
Storage and transport 
temperature 
°C 
– 25 to +70 
Installation altitude above sea level 
≤ 1000 m at rated DC current   4) 
Control stability 
∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and
digital setpoint 
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog 
setpoint    5) 
Environmental class 
DIN IEC 60 721-3-3 
3K3 
Degree of protection 
DIN EN 60529 
IP00 
Dimensions (HxWxD) 
mm 
385x265x283 
625x268x318 
Dimension diagram see Section 
5.1.2 
5.1.3 
5.1.4 
Weight (approx.) 
kg 
14 
16 
30 
Explanation at end of list of tables 
C# Word - Paragraph Processing in C#.NET
Add references: C# users can set paragraph properties and create content such as run, footnote, endnote and picture in a paragraph.
acrobat add image to pdf; add photo to pdf file
VB.NET Image: Image Resizer Control SDK to Resize Picture & Photo
NET Method to Resize Image & Picture. Here we this VB.NET image resizer control add-on, can provide powerful & profession imaging controls, PDF document, image
how to add a jpeg to a pdf file; how to add an image to a pdf file
3-14
Siemens AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
3.4.9  Converters 3AC 575V, 800A to 2200A, 1Q 
Order No. 
6RA70 . . – 6GS22 
6RA70 . . – 4GS22 
87
90
93
95
96
Rated supply voltage armature  1) 
3AC 575  (+10% / – 20%) 
Rated input current armature   2) 
663 
829 
1326 
1658 
1824 
Rated supply voltage electronics 
power supply 
2AC 380 (– 25%) to 460 (+15%);  I
n
=1A or 
1AC 190 (– 25%) to 230 (+15%);  I
n
=2A 
(– 35% for 1min) 
Rated supply voltage fan 
3AC 400 (±15%) 50Hz
3AC 460 (±10%) 60Hz 
3AC 400 (±10%) 50Hz
3AC 460 (±10%) 60Hz 
3AC 400 (±10%) 50Hz 
3AC 460 (±10%) 60Hz 
50Hz 
60Hz 
50Hz 
60Hz 
Fan rated current 
0.3  8) 
1.0  9) 
1.25  9) 
1.0  9) 
1.25  9) 
Air flow rate 
m3/h 
570 
1300 
1300 
2400 
2400 
Fan noise level 
dBA 
73 
83 
87 
83 
87 
Rated supply voltage field   1) 
2AC 460  (+15% / – 20%) 
Rated frequency 
Hz 
45 to 65   10) 
Rated DC voltage   1) 
690 
Rated DC current 
800 
1000 
1600 
2000 
2200 
Overload capability   6) 
max. 180% of rated DC current 
Rated output 
kW 
552 
690 
1104 
1380 
1518 
Power loss at rated DC current 
(approx.) 
2638 
4130 
5942 
7349 
7400 
Rated DC voltage field   1) 
max. 375 
Rated DC current field 
30 
40 
85 
Operational ambient temperature  °C 
0 to 40 at I
rated   
3)
forced-cooled 
Storage and transport 
temperature 
°C 
– 25 to +70 
Installation altitude above sea level 
≤ 1000 m at rated DC current   4) 
Control stability 
∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and
digital 
setpoint 
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog 
setpoint    5) 
Environmental class 
DIN IEC 60 721-3-3 
3K3 
Degree of protection 
DIN EN 60529 
IP00 
Dimensions (HxWxD) 
mm 
700x268x362 
780x410x362 
880x450x500 
Dimension diagram see Section 
5.1.5 
5.1.6 
5.1.7 
Weight (approx.) 
kg 
40 
80 
125 
Explanation at end of list of tables 
Siemens AG    6RX1700-0AD76 
3-15 
SIMOREG DC-MASTER    Operating Instructions 
3.4.10  Converters 3AC 690V, 720A to 2000A, 1Q 
Order No. 
6RA70 . . – 6KS22 
6RA70 . . – 4KS22 
86
88
93
95
Rated supply voltage armature  1) 
3AC 690  (+10% / – 20%) 
Rated input current armature   2) 
597 
788 
1244 
1658 
Rated supply voltage electronics 
power supply 
2AC 380 (– 25%) to 460 (+15%);  I
n
=1A or 
1AC 190 (– 25%) to 230 (+15%);  I
n
=2A 
(– 35% for 1min) 
Rated supply voltage fan 
3AC 400 (±15%) 50Hz
3AC 460 (±10%) 60Hz 
3AC 400 (±10%) 50Hz
3AC 460 (±10%) 60Hz 
3AC 400 (±10%) 50Hz 
3AC 460 (±10%) 60Hz 
50Hz 
60Hz 
50Hz 
60Hz 
Fan rated current 
0.3  8) 
1.0  9) 
1.25  9) 
1.0  9) 
1.25  9) 
Air flow rate 
m3/h 
570 
1300 
1300 
2400 
2400 
Fan noise level 
dBA 
73 
83 
87 
83 
87 
Rated supply voltage field   1) 
2AC 460  (+15% / – 20%) 
Rated frequency 
Hz 
45 to 65   10) 
Rated DC voltage   1) 
830 
Rated DC current 
720 
950 
1500 
2000 
Overload capability   6) 
max. 180% of rated DC current 
Rated output 
kW 
598 
789 
1245 
1660 
Power loss at rated DC current 
(approx.) 
2720 
4380 
6706 
8190 
Rated DC voltage field   1) 
max. 375 
Rated DC current field 
30 
40 
Operational ambient temperature 
°C 
0 to 40 at I
rated   
3)
forced-cooled 
Storage and transport 
temperature 
°C 
– 25 to +70 
Installation altitude above sea level 
≤ 1000 m at rated DC current   4) 
Control stability 
∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and
digital 
setpoint 
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog 
setpoint    5) 
Environmental class 
DIN IEC 60 721-3-3 
3K3 
Degree of protection 
DIN EN 60529 
IP00 
Dimensions (HxWxD) 
mm 
700x268x362 
780x410x362 
880x450x500 
Dimension diagram see Section 
5.1.5 
5.1.6 
5.1.7 
Weight (approx.) 
kg 
40 
80 
125 
Explanation at end of list of tables 
3-16
Siemens AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
3.4.11  Converters 3AC 830V, 900A to 1900A, 1Q 
Order No. 
6RA70 . . – 6LS22 
6RA70 . . – 4LS22 
88
93
95
Rated supply voltage armature  1) 
3AC 830  (+10% / – 20%) 
Rated input current armature   2) 
746 
1244 
1575 
Rated supply voltage electronics 
power supply 
2AC 380 (– 25%) to 460 (+15%);  I
n
=1A or 
1AC 190 (– 25%) to 230 (+15%);  I
n
=2A 
(– 35% for 1min) 
Rated supply voltage fan 
3AC 400 (±10%) 50Hz 
3AC 460 (±10%) 60Hz 
3AC 400 (±10%) 50Hz 
3AC 460 (±10%) 60Hz 
50Hz 
60Hz 
50Hz 
60Hz 
Fan rated current 
1.0  9) 
1.25  9) 
1.0  9) 
1.25  9) 
Air flow rate 
m3/h 
1300 
1300 
2400 
2400 
Fan noise level 
dBA 
83 
87 
83 
87 
Rated supply voltage field   1) 
2AC 460  (+15% / – 20%) 
Rated frequency 
Hz 
45 to 65   10) 
Rated DC voltage   1) 
1000 
Rated DC current 
900 
1500 
1900 
Overload capability   6) 
max. 180% of rated DC current 
Rated output 
kW 
900 
1500 
1900 
Power loss at rated DC current 
(approx.) 
4638 
6778 
8700 
Rated DC voltage field   1) 
max. 375 
Rated DC current field 
30 
40 
Operational ambient temperature  °C 
0 to 40 at I
rated   
3)
forced-cooled 
Storage and transport 
temperature 
°C 
– 25 to +70 
Installation altitude above sea level 
≤ 1000 m at rated DC current   4) 
Control stability 
∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and
digital setpoint 
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog 
setpoint    5) 
Environmental class 
DIN IEC 60 721-3-3 
3K3 
Degree of protection 
DIN EN 60529 
IP00 
Dimensions (HxWxD) 
mm 
780x410x362 
880x450x500 
Dimension diagram see Section 
5.1.6 
5.1.7 
Weight (approx.) 
kg 
80 
125 
Explanation at end of list of tables 
Siemens AG    6RX1700-0AD76 
3-17 
SIMOREG DC-MASTER    Operating Instructions 
3.4.12  Converters 3AC 400V, 15A to 125A, 4Q 
Order No. 
6RA70 . . – 6DV62 
13
18
25
28
31
Rated supply voltage armature  1) 
3AC 400  (+15% / – 20%) 
Rated input current armature   2) 
13 
25 
50 
75 
104 
Rated supply voltage electronics 
power supply 
2AC 380 (– 25%) to 460 (+15%);  I
n
=1A or 
1AC 190 (– 25%) to 230 (+15%);  I
n
=2A 
(– 35% for 1min) 
Rated supply voltage field   1) 
2AC 400  (+15% / – 20%)   7) 
Rated frequency 
Hz 
45 to 65   10) 
Rated DC voltage   1) 
420 
Rated DC current 
15 
30 
60 
90 
125 
Overload capability   6) 
max. 180% of rated DC current 
Rated output 
kW 
6.3 
12.6 
25 
38 
52.5 
Power loss at rated DC current 
(approx.) 
117 
163 
240 
312 
400 
Rated DC voltage field   1) 
max. 325 
Rated DC current field 
10 
Operational ambient temperature 
°C 
0 to 45 at I
rated   
3)
self-cooled 
Storage and transport 
temperature 
°C 
– 25 to +70 
Installation altitude above sea level 
≤ 1000 m at rated DC current   4) 
Control stability 
∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and
digital setpoint 
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog 
setpoint    5) 
Environmental class 
DIN IEC 60 721-3-3 
3K3 
Degree of protection 
DIN EN 60529 
IP00 
Dimensions (HxWxD) 
mm 
385x265x239 
385x265x283 
Dimension diagram see Section 
5.1.9 
5.1.10 
Weight (approx.) 
kg 
11 
11 
14 
14 
16 
Explanation at end of list of tables 
3-18
Siemens AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
3.4.13  Converters 3AC 400V, 210A to 600A, 4Q 
Order No. 
6RA70 . . – 6DV62 
75
78
81
85
Rated supply voltage armature  1) 
3AC 400  (+15% / – 20%) 
Rated input current armature   2) 
175 
233 
332 
498 
Rated supply voltage electronics 
power supply 
2AC 380 (– 25%) to 460 (+15%);  I
n
=1A or 
1AC 190 (– 25%) to 230 (+15%);  I
n
=2A 
(– 35% for 1min) 
Rated supply voltage fan 
DC 24V internal 
3AC 400 (±15%) 50Hz 
3AC 460 (±10%) 60Hz 
Fan rated current 
0.3  8) 
Air flow rate 
m3/h 
100 
570 
Fan noise level 
dBA 
40 
73 
Rated supply voltage field   1) 
2AC 400  (+15% / – 20%)   7) 
Rated frequency 
Hz 
45 to 65   10) 
Rated DC voltage   1) 
420 
Rated DC current 
210 
280 
400 
600 
Overload capability   6) 
max. 180% of rated DC current 
Rated output 
kW 
88 
118 
168 
252 
Power loss at rated DC current 
(approx.) 
676 
800 
1328 
1800 
Rated DC voltage field   1) 
max. 325 
Rated DC current field 
15 
25 
Operational ambient temperature  °C 
0 to 40 at I
rated   
3)
forced-cooled 
Storage and transport 
temperature 
°C 
– 25 to +70 
Installation altitude above sea level 
≤ 1000 m at rated DC current   4) 
Control stability 
∆n = 0.006% of the rated motor speed, valid for pulse encoder operation and
digital setpoint 
∆n = 0.1% of the rated motor speed, valid for analog tacho or analog 
setpoint    5) 
Environmental class 
DIN IEC 60 721-3-3 
3K3 
Degree of protection 
DIN EN 60529 
IP00 
Dimensions (HxWxD) 
mm 
385x265x283 
625x268x318 
Dimension diagram see Section 
5.1.10 
5.1.11 
Weight (approx.) 
kg 
16 
17 
30 
Explanation at end of list of tables 