SIEMENS AG    6RX1700-0AD76 
9-5 
SIMOREG DC-MASTER    Operating Instructions 
Example 2:  The contents of connectors K0401 and K0402 must be output on the connector displays 
(parameter r043)  
The following settings need to be made to create the correct links: 
P044.index01 = 401:  Links connector K0401 to the 1
st
connector display 
P044.index02 = 402:  Links connector K0402 to the 2
nd
connector display 
Section 8, Sheet G121:
.01
.02
.03
.04
.05
.06
.07
P044 (0)
K
K
K
K
K
K
K
r043.01
r043.02
r043.03
r043.04
r043.05
r043.06
r043.07
401
402
The following values are now displayed in parameter r043: 
r043.index01:  Contents of connector K0401 
r043.index02:  Contents of connector K0402 
r043.index03 
to 
r043.index07:  Parameter P044.index.03 to 07 remain at the works setting (0) (value in 
brackets next to parameter number) in this example, i. e. the contents 
of connector K0000 (=fixed value 0) are displayed on r043.index.03 to 
.07. 
Setting parameters 
(see also Section "Data sets") 
In addition to the parameters that are used to select a signal (connector, binector), there are also 
parameters which define an operating mode
or the parameter value of some function
Representation in function diagrams: 
Apart from parameter numbers, the function diagrams may also contain the factory setting, function 
and value range of parameters as supplementary information. 
P109 (0)
Setting parameter 
Parameter number = P109, factory setting = 0 
P462.F(10.00s)
(0.01...300.00s)
Ramp-up time
Setting parameter in function parameter set (".F" after parameter number) 
Parameter number = P462, factory setting = 10.00s 
Value range = 0.01...300.00s 
Parameter for setting ramp-up time 
Examples:  P700 in Section 8, Sheet G113 defines the signal type of the analog input 
(voltage input ±10V, current input 0...20mA, current input 4...20mA). 
P705 in Section 8, Sheet G113 defines the filter time for the analog input (adjustable 
in ms). 
Parameters P520 to P530 in Section 8, Sheet G153 determine the shape of the friction 
characteristic. 
P465 in Section 8, Sheet G126 determines whether the time settings must be multiplied 
by a factor of 1 or 60. 
Add jpg signature to pdf - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
adding an image to a pdf file; add jpg signature to pdf
Add jpg signature to pdf - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
how to add a photo to a pdf document; add png to pdf preview
9-6 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Data sets 
See also Section "Switch over parameter sets" 
Switch over function parameters (function data sets):
4 different sets of some parameters (function parameters) are available and can be selected by 
means of the "Switch over function parameters" function. The switchover operation is controlled by 
control word 2 (bits 16 and 17, see Section 8, Sheets G181 and G175). Index .01, .02, .03 or .04 of 
these parameters is operative depending on the status of the control bit. 
The parameters of this parameter set are identified by an ".F" next to the parameter number in the 
function diagrams and by "FDS" under the parameter number in the tabulated parameter list. 
The parameters belonging to the function parameter set must not be confused with other parameters 
which, by chance, also have 4 indices. The latter parameters are not affected by the "Switch over 
function parameters" function. 
Switch over binector and connector parameters (Bico data sets):
2 different sets of some selection switches are available and can be selected by means of the "Switch 
over binector and connector parameters" function. The switchover function is controlled by control 
word 2 (bit 30, see Section 8, Sheets G181 and G175). The status of the control bit determines 
whether index.01 or index .02 of the parameter is operative. 
The parameters of the Bico data set are identified by a ".B" next to the parameter number in the 
function diagrams and by "BDS" under the parameter number in the tabulated parameter list. 
The parameters belonging to the Bico data set must not be confused with other parameters which, by 
chance, also have 2 indices. The latter parameters are not affected by the "Switch over binector and 
connector parameters" function. 
Display parameters 
The values of certain signals can be output using display parameters (r parameters, n parameters). 
Connector displays (Section 8, Sheet G121) can be used to link all connectors with display 
parameters so that they can be displayed. 
Representation in function diagrams: 
Apart from the parameter number, the function diagrams may also include a function description for 
the parameter as supplementary information. 
r316
RFG status
Display parameter 
Parameter number = r316 
Display of RFG (ramp-function generator) status 
9.2  Computation cycles, time delay 
Functions associated with analog inputs, analog outputs, binary inputs, binary outputs and interfaces, 
as well as function blocks associated with the motorized potentiometer, setpoint generation, ramp-
function generator and closed-loop speed and armature current controls, are called up and calculated 
in synchronism with the armature firing pulses
(i.e. every 3.333 ms at a line frequency of 50 Hz). 
Function blocks associated with the closed-loop EMF and field current controls (shown in Section 8, 
Sheets G165 and G166) are called and calculated in synchronism with the field firing pulses
(i.e. every 
10 ms at a line frequency of 50 Hz). 
The parameter settings are processed in a further computation cycle with a cycle time of 20 ms. The 
execution of optimization runs is also controlled from this cycle. 
With regard to the transfer of parameter values via interfaces, it is important to remember that some 
transferred parameters must be converted to this 20 ms cycle before they can be applied, for 
example, in the armature firing pulse cycle. 
JPG to JBIG2 Converter | Convert JPEG to JBIG2, Convert JBIG2 to
original images without any affecting; Ability to convert image swiftly between JPG & JBIG2 in Also can be used as add-on for RasterEdge .NET Imaging SDK. Start
how to add image to pdf document; acrobat add image to pdf
JPEG Image Viewer| What is JPEG
JPEG, JPG. excluded in the standard RasterEdge .NET Imaging SDK, you may add it on images into other file formats, including Bitmap, Png, Gif, Tiff, PDF, MS-Word
add image pdf document; add a picture to a pdf
SIEMENS AG    6RX1700-0AD76 
9-7 
SIMOREG DC-MASTER    Operating Instructions 
9.3  Switch-on, shutdown, enabling 
9.3.1  OFF2 (voltage disconnection)  -  control word 1, bit 1 
The OFF2 signal is low active (log."0" state = voltage disconnection). 
The following operating modes are possible: 
P648 = 9:   The control bits in control word 1 are input bit-serially. OFF2 is generated from the AND 
operation between the binectors selected with P655, P656 and P657 (see Section 8, 
Sheet G180). 
P648 ≠ 9:   The connector selected via P648 is used as control word 1. Bit 1 of this word then 
controls the OFF2 function. 
Sequence of operations for "Disconnect voltage": 
1.  Input "Disconnect voltage" command 
2.  Disable ramp-function generator, n and I controllers 
3.  I
set
= 0 is applied 
4.  The pulses are disabled when I = 0 
5.  Output signal "Close operating brake" (binector B0250 = 0, when P080 = 2) 
6.  Converter reaches operating state o10.0 or higher 
7.  An "older" actual field current value (K0265) is input as the field current setpoint upper limit 
(function is "released" in operating states of ≤o5)  
8.  The "Line contactor closed" relay drops out 
9.  Drive coasts to a standstill (or is braked by the operating brake) 
10.  Parameterizable delay time (P258) runs down 
11.  The field is reduced to a parameterizable value (P257) 
12.  When n < n
min
(P370, P371) has been reached, the "Close holding brake" signal is output 
(binector B0250 = 0, when P080 = 1) 
9.3.2  OFF3 (Fast stop)  -  control word 1, bit 2 
The OFF3 signal is LOW active (log."0" state = fast stop). 
The following operating modes are possible: 
P648 = 9:   The control bits in control word 1 are input bit-serially. OFF3 is generated from the AND 
operation between the binectors selected with P658, P659 and P660 (see Section 8, 
Sheet G180). 
P648 ≠ 9:   The connector selected via P648 is used as control word 1. Bit 2 of this word then 
controls the OFF3 function. 
Sequence of operations for ”Fast stop”: 
1.  Input "Fast stop" command (e.g. binary input wired up to "Fast stop") 
2.  Ramp-function generator is disabled 
3.  Enter n
set
= 0  
4.  up to SW 1.84:  Decelerate along current limit 
from SW 1.90:  Decelerate along reversal ramp acc. to P296, P297, P298 
5.  Wait until n < n
min
(P370, P371) 
6.  Output signal "Close operating or holding brake" (binector B0250 = 0) 
7.  Wait for brake closing time (P088) to run down 
8.  Enter I
set
= 0  
9.  Ramp-function generator and n controller are disabled 
10.  The pulses are disabled when I = 0 
11.  The "Line contactor closed" relay drops out 
12.  Converter reaches operating state o9.0 or higher 
13.  Delay time for field current reduction (P258) runs down 
14.  The field is reduced to a parameterizable value in P257 
XDoc.HTML5 Viewer for .NET, All Mature Features Introductions
and Communications in Medicine; Raster Image Files: BMP, GIF, JPG, PNG, JBIG2PDF NET document and image viewer allows users to add various annotations Signature.
add image field to pdf form; add picture to pdf in preview
VB.NET PDF Convert to Images SDK: Convert PDF to png, gif images
Create image files including all PDF contents, like watermark and signature. Convert PDF to Jpg, Png, Bmp, Gif, Tiff and Bitmap in ASP Add necessary references:
add photo to pdf preview; add image pdf
9-8 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Sequence of operations for cancellation of "Fast stop": 
1.  Stop applying "Fast stop" command 
2.  Enter "Standstill" command (e.g. via "Switch-on/shutdown" terminal) 
3.  Converter exits operating state o8 
P258
P088
P087
n < n      (P370,P371)
n > n
n < n      
ON
External fast stop
Sandstill field
Shutdown
Controller disabled
Switch-on/Shutdown
Fast stop
Internal fast stop
Internal controller enable
Internal setpoint enable
Actual speed
Brake control signal (B0255)
(holding brake)
Internal standstill
field input
min
No fast stop
No fast stop
Controller enabled
Setpoint enabled
Setpoint reached
min
Release brake
No standstill field
Internal fast stop
Setpoint =0
min
Setpoint reached
Close brake
P087  Brake release time (positive in this example)  
P088  Brake closing time 
P258  Delay for automatic field current reduction 
−  The "Fast stop" command need only be applied as a short pulse (> 10 ms). It is then stored 
internally. The memory can be reset only by applying the "Shutdown" command. 
−  All "Fast stop" commands are ANDed by the SIMOREG converter, i.e. all commands must be set 
to "No fast stop" before the function can be deactivated. 
−  When n < n
min
(P370, P371) is reached for the first time, an internal interlock is activated which 
prevents the drive from attempting to brake again if the motor is turned by external forces.  
The n < n
min 
signal then disappears again. 
9.3.3  Switch-on / shutdown (ON / OFF) terminal 37  -  control word 1, bit 0 
The "Switch-on / shutdown" (ON / OFF) function is controlled via the "Switch-on command of ON / 
OFF1" (= ANDing between signal from terminal 37 and binector selected in parameter P654, level- or 
edge-triggered, see below) and bit 0 of connector selected as the control word in P648. 
The following operating modes are possible: 
P648 = 9:  The control bits in control word 1 are input bit-serially. "ON / OFF" is controlled via the 
"Switch-on command of ON / OFF1". 
P648 ≠ 9:  The connector selected in P648 is used as control word 1. Bit 0 of the control word is 
ANDed with the "Switch-on command of ON / OFF1" to produce the "ON / OFF" 
command (ON only if both signals are log. "1"). 
P445 = 0:  The "Switch-on command of ON / OFF1" is generated as an AND operation between the 
signal from terminal 37 and the binector selected in P654 (level-triggered, 0 = shutdown, 
1  = switch-on). 
JPEG to PDF Converter | Convert JPEG to PDF, Convert PDF to JPEG
similar software; Support a batch conversion of JPG to PDF with amazingly high speed; Get a compressed PDF file after conversion; Support
acrobat insert image into pdf; add photo to pdf for
JPG to DICOM Converter | Convert JPEG to DICOM, Convert DICOM to
Image Converter Pro - JPEG to DICOM Converter. Convert JPEG (JPG) Images to, from DICOM Images on Windows.
add a jpeg to a pdf; how to add photo to pdf in preview
SIEMENS AG    6RX1700-0AD76 
9-9 
SIMOREG DC-MASTER    Operating Instructions 
P445 = 1:  Edge triggering of "Switch-on command of ON / OFF1": 
The switch-on command is stored on the 0 
1 transition (see Section 8, Sheet G130). 
The binector selected in P444 must be in the log. "1" state. The memory is reset when 
this binector switches to the log. "0" state. 
In the following example circuit, the ON key (NO contact) is connected to terminal 37 and the 
shutdown key (NC contact) to terminal 36. Connector K3003 (= Receive data from 1
st
CB/TB, word 3) 
is used as control word 1. 
The following parameter values must be set: 
P444=10  Connects binector 10 (= status of terminal 36) to the reset input of the memory for the ON 
signal (and to the reset input of the memory for the CRAWL command) 
P445=1 
Selects edge triggering of "Switch-on command of ON / OFF1" (and injection of the 
crawling setpoint) 
P648=3003  Connector K3003 is assigned status of control word 1. 
The combination of the control bit for ON/OFF from the DPRAM control word (K3003.bit0 in this 
example) and the switch-on command from the converter terminal is shown in the boxes with dot-dash 
line borders. 
P24_S
34
24V
5V
36
M
M
35
24V
5V
37
M
B0010
.01
.02
.03
D Q
R
1
1
1
0
<1>
&
D Q
R
1
1
1
1
0
1
....
<1>
P440 (0)
B
B
B
P444.B (0)
B
P445 = 1
P654.B (1)
B
10
1
P648.B (9)
K
3003
1
&
9
=/9
1
P648
CUD1
Switch-on / shutdown
Selection for
shutdown
Selection for
switch-on / shutdown
Select 
injection of
crawing setpoint
Level / 
Edge
Bit No.
0=OFF1, Shutdown
1=ON, op. cond.
Meaning
(When P648 = 9 bit-serial
input of control bits)
Switch-on c.
of ON/OFF1
ON
Shut-
down
Control word 1
Switch-on comm.
of ON/OFF1
Control
word
bit 0
Section 8, Sheet G110
Section 8, Sheet G130
Section 8, Sheet G180
Bit 0
Bit 1
K3003.bit0
Sequence of operations for switching on drive: 
1.  Enter the "Switch-on" command (e.g. via terminal "Switch-on/shutdown”) 
2.  The converter exits operating state 07 
3.  The "Line contactor closed" relay picks up 
4.  The field current reduction command is cancelled 
If "Enable operation" signal is applied: 
5.  With a positive brake release time (P087), output signal "Release holding or operating brake" 
(binector B0250 = 1) and wait for P087 in operating state 01.0, 
with a negative brake release time (PO87 negative), go to step 6 immediately, brake remains 
closed (binector B0250 = 0) 
6.  Ramp-function generator, n controller and I controller are enabled 
7.  When a negative brake release time (P087) has run down, output signal "Release holding or 
operating brake" (binector B0250 = 1). 
JPG to PNG Converter | Convert JPEG to PNG, Convert PNG to JPG
Image Converter Pro - JPEG to PNG Converter. Convert JPEG (JPG) Images to, from PNG Images on Windows.
how to add image to pdf form; add photo to pdf reader
JPG to GIF Converter | Convert JPEG to GIF, Convert GIF to JPG
Converter. Convert JPEG (JPG) Images to, from GIF Images on Windows. JPEG to GIF Converter can directly convert GIF files to JPG files.
add picture to pdf file; how to add an image to a pdf
9-10 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Sequence of operations for shutting down drive: 
1.  Enter the "Shutdown" command (e.g. via terminal "Switch-on / shutdown”) 
2.  Decelerate along ramp-function generator ramp 
3.  Wait until n < n
min
(P370, P371) 
4.  Output signal "Close holding or operating brake" (binector B0250 = 0) 
5.  Wait for brake closing time (P088) to run down 
6.  Input i
set 
= 0  
7.  Ramp-function generator and n controller are disabled 
8.  The pulses are disabled when I = 0 
9.  The "Line contactor closed" relay drops out 
10.  The converter reaches operating state o7.0 or higher 
11.  Delay for field current reduction (P258) runs down 
12.  The field is reduced to a parameterizable value (P257) 
P258
P088
P087
n < n      (P370,P371)
n > n      
n < n      
ON
Sandstill field
Shutdown
Controller disabled
Switch-on/Shutdown
Internal controller enable
Internal setpoint enable
Actual speed
Brake control signal (B0255)
(holding brake)
Internal standstill
field input
min
Controller enabled
Setpoint reached
min
Release brake
No standstill field
Setpoint =0
min
Setpoint reached
Close brake
Setpoint enabled
P087  Brake release time (positive in this example) 
P088  Brake closing time 
P258  Delay for automatic field current reduction 
−  When n < n
min
(P370, P371) is reached for the first time, an internal interlock is activated which 
prevents the drive from attempting to brake again if the motor is turned by external forces. The 
n < n
min 
signal then disappears again. 
−  Changing the parameter setting between level and edge triggering affects the "Switch-on", 
"Shutdown" and "Crawl" commands. 
−  The "Switch-on" and "Crawl" commands are applied alternately when edge triggering is selected, 
i.e. a "Switch-on" edge at terminal 37 cancels a "Crawl" function triggered beforehand, and a 
"Crawl" edge at a binector selected in P440 cancels an active "Switch-on" edge. 
−  The converter cannot be restarted automatically after a brief failure of the electronics power supply 
when edge triggering is selected. 
−  In order to ensure that "Shutdown" still works after "rewiring of parameters", if lower
current or 
torque limits are applied or when additional setpoints are injected, certain functions are 
automatically deactivated when the "Shutdown" command is entered. 
All torque limits are made inoperative while the drive brakes down to n < n
min
. Of all the current 
limits, only the system current limit (P171 and P172), the speed-dependent current limit and the 
limit derived from I
2
t monitoring of the power section remain operative. 
SIEMENS AG    6RX1700-0AD76 
9-11 
SIMOREG DC-MASTER    Operating Instructions 
9.3.4  Operating enable (enable) terminal 38  -  control word 1, bit 3 
The Enable signal is HIGH active (log."1" state =  Enable). 
The following operating modes are possible: 
P648 = 9:  The control bits in control word 1 are input bit-serially. The operating enable command is 
generated from the AND operation between the enable signal from terminal 38 and the 
binector selected in P661 (see Section 8, Sheet G180). 
P648 ≠ 9:  The connector selected in P648 is used as control word 1. Bit 3 of this connector is 
ANDed with the signal that is generated as for P648=9 to produce the operating enable 
signal. 
To ensure that the "Operating enable" function can be activated, the conditions defined in the 
following diagram must be fulfilled: 
&
9
9-12 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
9.4.1  Definitions 
Ramp-up
 Acceleration from low, positive to high, positive speeds (e.g. from 10% to 90%) or from 
low, negative to high, negative speeds (e.g. from -10% to -90%) 
Ramp-down
= Deceleration from high, positive to low, positive speeds (e.g. from 90% to 10%) or from 
high, negative to low, negative speeds (e.g. from -90% to -10%) 
On transition from negative to positive speeds, e.g. -10% to +50%: 
From -10% to 0 = ramp-down and  
From 0 to +50% = ramp-up and vice versa 
Ramp-up time
refers to the time required by the ramp-function generator to reach the 100% output 
value, with a lower and upper transition rounding of 0 and a step change in the input 
quantity from 0 to 100% or from 0 to -100%. The rate of rise at the output is the same in 
response to smaller step changes in the input quantity. 
Ramp-down time
refers to the time required by the ramp-function generator to reach the 100% output 
value, with a lower and upper transition rounding of 0 and a step change in the input 
quantity from 100% to 0 or from -100% to 0. The rate of rise at the output is the same in 
response to smaller step changes in the input quantity. 
9.4.2  Operating principle of ramp-function generator 
HLZ
HLZ
RLZ
RLZ
AR
ER
AR
1)
AR
AR
AR
ER
2)
AR
3)
AR/2
ER/2
AR/2
AR/2
ER/2
(K0192)
(K0190)
K0190
K0192
100%
-100%
K0191
(dv/dt)
t
t
dy/dt (K0191)
Ramp generator setpoint
Ramp generator outout
HLZ ... Ramp-up time (H303, H307, H311),                    RLZ ... Ramp-down time (H304, H308, H312)
AR   ... Lower transition rounding (H305, H309, H313),  ER   ... Upper transition rounding (H306, H310, H314)
1)  Transition from ramp-down gradient to ramp-up gradient
2)  The lower rounding switches to the upper rounding before the maximum ramp-down gradient is reached
3)  Due to the input step change, only the last part of the upper transition rounding is executed here
SIEMENS AG    6RX1700-0AD76 
9-13 
SIMOREG DC-MASTER    Operating Instructions 
9.4.3  Control signals for ramp-function generator 
The ramp-function generator operating mode can be preset by the following control signals: 
Ramp-function generator start
(control word 1.bit 5): 
 =  Setpoint is injected at ramp-function generator input 
 =  Ramp-function generator is stopped at current value (generator output is injected as generator 
input). 
Enable setpoint
(control word 1.bit 6): 
 =  Setpoint enabled at ramp-function generator input 
 =  Ramp-function generator setting 1 is activated and 0 applied at the input (generator output is 
reduced to 0) 
Set ramp-function generator:
 =  The ramp-function generator output is set to the setting value (selected in P639) 
Enable ramp-function generator
(control word 1.bit 4): 
 =  Ramp generator disabled, generator output is set to 0 
 =  Ramp-function generator enabled 
Ramp-up integrator operation
(parameter P302): 
See below and Section 11, Parameter List, parameter P302 
Enable switchover of ramp-up integrator
(select via P646): 
See below 
Ramp-function generator settings 2 and 3
See below 
Ramp-function generator tracking ON
(parameter P317): 
See below and Section 11, Parameter List, parameter P317 
Set ramp-function generator on shutdown
(parameter P318): 
See Section 11, Parameter List, parameter P318 
Bypass ramp-function generator:
 =  Ramp-function generator operates with ramp-up/ramp-down time of 0 
The function is controlled via the binector selected in P641. 
The ramp generator can also be bypassed in INCHING, CRAWLING and INJECTION OF FIXED 
SETPOINT modes. 
9.4.4  Ramp-function generator settings 1, 2 and 3 
Selection via binectors selected in parameters P637 and P638 
Status of binector 
Effective 
Effective 
Effective 
Effective 
Selected via parameter 
R-F generator 
ramp-up 
ramp- 
lower  
upper 
P637 
P638 
setting 
time 
down time 
rounding 
rounding 
P303 
P304 
P305 
P306 
P307 
P308 
P309 
P310 
P311 
P312 
P313 
P314 
Not permitted, activates fault message F041 (selection not clear)  
The ramp-function generator settings preset via the binectors selected in P637 and P638 have priority 
over the generator setting specified via the ramp-up integrator. 
9-14 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
9.4.5  Ramp-up integrator 
The ramp-up integrator is activated by setting P302 = 1, 2 or 3. After an "ON" command ("Switch-on", 
"Inching", "Crawling"), ramp-function generator setting 1 (P303 to P306) is applied until the ramp-
function generator output reaches the required setpoint for the first time. 
The remaining sequence of operations is controlled by the "Enable switchover of ramp-up integrator" 
function (binector selected in P646). 
Enable switchover of ramp-up integrator = 1: 
As soon as the ramp-function generator output reaches the required setpoint for the first time 
after the "ON" command, the ramp generator setting selected in P302 is activated automatically. 
Enable switchover of ramp-up integrator = 0: 
Ramp-function generator setting 1 (P303 to P306) remains active after the generator output has 
reached its setpoint until the "Enable switchover of ramp-up integrator" function is switched to 1. 
The ramp-function generator setting selected in P302 is then activated. 
When the enable signal for ramp-up integrator switchover is cancelled (→ 0), ramp-function generator 
setting 1 is activated again and, with a new enable command (→ 1), this setting continues to remain 
active until the generator output has reached its setpoint again. The ramp generator setting selected in 
P302 is then activated again. 
When a "Shutdown" command is given, the drive is shut down according to setting 1. 
Note
Activation of "Ramp-function generator setting 2" (P307 to P310, selected in P637), or "Ramp-function 
generator setting 3" (P311 to P314, selected in P368), has priority over the generator setting selected 
by means of the "Ramp-up integrator" function. 
9.4.6  Ramp-function generator tracking 
The ramp-function generator output (K0190) is limited to the following values when ramp-function 
generator tracking is activated: 
act
p
limit
act
p
limit
n
K
1.25
M
output
RFG
n
K
1.25
M
+
+
<
<
+
When P170 = 1 (torque control), the following equation applies: 
act
p
motor
A,limit
act
p
motor
A,limit
n
K
1.25
I
output
RFG
n
K
1.25
I
+
∗Φ
+
<
<
+
∗Φ
When P170 = 0 (current control), the following equation applies: 
act
p
A,limit
act
p
A,limit
n
K
1.25
I
output
RFG
n
K
1.25
I
+
+
<
<
+
Φ
motor 
Normalized motor flux (1 at rated field current) 
n
act
Actual speed value (K0167) 
+ M
limit 
Lowest positive torque limit (K0143) 
– M
limit 
Lower negative torque limit (K0144) 
+ I
A, limit 
Lowest positive current limit (K0131) 
– I
A, limit 
Lowest negative current limit (K0132) 
K
p 
Effective speed controller gain 
However, if the value added to n
act
were to correspond to less than 1%, then +1% or –1% would be 
added. 
The purpose of the "Ramp-function generator tracking" function is to ensure that the ramp generator 
value cannot deviate excessively from the actual speed value once the torque or current limit has 
been reached. 
Note
When ramp-function generator tracking is selected, the filter time for the speed setpoint should be set 
to a low value in P228 (preferably to 0). 