SIEMENS AG    6RX1700-0AD76 
9-15 
SIMOREG DC-MASTER    Operating Instructions 
9.4.7  Limitation after ramp-function generator 
Since the input signal can be freely selected, this limiter stage can be used completely independently 
of the ramp-function generator. 
A special feature of this limiter is that the lower limit can also be set to positive values and the upper 
limit to negative values (see P300 and P301). This type of limit setting then acts as a lower limit 
(minimum value) for the ramp generator output signal in the other sign direction. 
Example:  P632.01-04 = 1 (= 100.00%) 
P300 = 100.00 (%) 
P301 = 10.00 (%) 
P633.01-04 = 9 (= -100.00%) 
results in a limitation of the value range for K0170 to between +10.00% and +100.00% 
9.4.8  Velocity signal dv/dt (K0191) 
This signal specifies the change in the ramp-function generator output K0190 in the time period set in 
P542. 
9.5  Inching 
See also Section 8, Sheet G129 
The INCHING function can be preset via the binectors selected with indices .01 to .08 of parameter 
P435 or via bits 8 and 9 of control word 1 (logic operation, see function diagram in Section 8). 
When the control word option is used, the following operating modes are possible (see also Section 8, 
Sheet 33): 
P648 = 9:   The control bits in control word 1 are input bit-serially. The binectors selected in P668 
and P669 determine bits 8 and 9 of control word 1 and thus the input of the INCH 
command. 
P648 ≠ 9:   The connector selected in P648 is used as control word 1. Bits 8 and 9 of this word 
control the input of the INCH command. 
The "Inching" function can be executed only if "Shutdown" and "Operating enable" are applied. 
The "Inch" command is input when one or several of the named sources (binectors, bits in control 
word) change to the log. "1" state. In this case, a setpoint selected in parameter P436 is assigned to 
each source. 
An inching setpoint of 0 is applied if the inch command is input by two or more sources 
simultaneously. 
Parameter P437 can be set to define for each possible inch command source (binector, bit in control 
word - logic operation, see block diagram in Section 8) whether or not the ramp-function generator 
must be bypassed. When the ramp generator is bypassed, it operates with ramp-up/down times of 0. 
Sequence of operations for entering Inching command: 
If the "Inch" command is entered, the line contactor is energized via the "Line contactor closed" relay 
and the inching setpoint applied via the ramp-function generator (for exact sequence, see the 
description of "Switch-on / Shutdown" in Section 9.3.3). 
Sequence of operations for cancellation of Inching: 
After the "Inch" command has been cancelled, the sequence of operations commences in the same 
way as for "Shutdown" (see Section 9.3.3). After n < n
min
has been reached, the controllers are 
disabled and the line contactor opened after a parameterizable delay (P085) of between 0 and 60 s 
(operating state 07.0 or higher). The drive remains in operating state 01.3 while the parameterizable 
delay period (max. 60.0 s) runs down. 
Adding images to a pdf document - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
add image to pdf java; adding images to pdf forms
Adding images to a pdf document - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
add an image to a pdf with acrobat; add jpg to pdf online
9-16 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
9.6  Crawling 
See also Section 8, Sheet G130 
The "Crawling" function can be activated in operating state o7 and, with "Operation enabled", in the 
Run state. 
The "Crawl" command is entered when one or several of the binectors selected in P440 switches to 
the log. "1" state. A setpoint selected in parameter P441 is assigned to each binector. If the "Crawl" 
command is entered via several binectors, the setpoint values are added (limited to ±200%). 
Parameter P442 can be set to define for each possible crawl command source (binector) whether or 
not the ramp-function generator must be bypassed. When the ramp generator is bypassed, it operates 
with ramp-up/down times of 0. 
Level / edge 
P445 = 0:  Level-triggered 
Binector selected in P440 = 0: No crawl 
Binector selected in P440 = 1: Crawl 
P445 = 1:  Edge-triggered 
The input of "Crawl" is stored when the binector state changes from 0 → 1 (see Section 
8, Sheet G130). The binector selected in P444 must be in the log. "1" state at the same 
time. The memory is reset when the latter binector changes state to log. "0" (see also 
example circuit in Section 9.3.3, Switch-on / Shutdown).  
Sequence of operations for entering Crawl command: 
If the "Crawl" command is entered in operating state o7
, the line contactor is energized via the "Line 
contactor closed" relay and the crawling setpoint applied via the ramp-function generator. 
If the "Crawl" command is entered in the "Run"
state, the drive decelerates from the operating speed 
to the crawling setpoint via the ramp-function generator. 
Sequence of operations for cancellation of Crawling: 
With "Crawling" active, but no "Switch-on" command applied: 
If all bits which activate the "Crawling" function switch to log. "0", the controllers are disabled 
after n < n
min
is reached and the line contactor de-energized (operating state o7.0 or higher). 
With "Crawling" active from "Run" operating state: 
If all bits which activate the "Crawling" function switch to log. "0" and if the conditions for the "Run" 
operating state are still fulfilled, then the drive accelerates from the set crawling speed to the operating 
speed via the ramp-function generator. 
See also Section 9.3.3 (switch-on / shutdown) with regard to edge triggering, automatic restart and the 
effect of the current and torque limits during braking. 
9.7  Fixed setpoint 
See also Section 8, Sheet G127 
The "Fixed setpoint" function can be activated in the "Run" state with the "Enable controllers" signal 
applied. 
The "Fixed setpoint" function can be input via the binectors selected via indices .01 to .08 of 
parameter P430 and via bits 4 and 5 of control word 2 (= bits 20 and 21 of complete control word) 
(see function diagram in Section 8 for logic operation). 
VB.NET PDF Page Insert Library: insert pages into PDF file in vb.
DLLs for Adding Page into PDF Document in VB.NET Class. Add necessary references: RasterEdge.Imaging.Basic.dll. RasterEdge.Imaging.Basic.Codec.dll.
add photo pdf; adding a jpeg to a pdf
VB.NET PDF Library SDK to view, edit, convert, process PDF file
Feel free to define text or images on PDF document and extract accordingly. Capable of adding PDF file navigation features to your VB.NET program.
add image to pdf online; how to add an image to a pdf in reader
SIEMENS AG    6RX1700-0AD76 
9-17 
SIMOREG DC-MASTER    Operating Instructions 
When the control word method is used, the following operating modes are possible (see also Section 
8, Sheet G181): 
P649 = 9:   The control bits in control word 2 are input bit-serially. The binectors selected via P680 
and P681 determine bits 4 and 5 of control word 2 (= bits 20 and 21 of complete control 
word), and thus input of the "Fixed setpoint" function. 
P649 ≠ 9:   The connector selected via P649 is used as control word 2. Bits 4 and 5 of this word 
control the input of "Fixed setpoint”. 
The "Fixed setpoint" function is input when one or several of the named sources (binectors, bits in 
control word) switch to the log. "1" state. In this case, a setpoint selected in parameter P431 is 
assigned to each source. If "Fixed setpoint" is input via several sources simultaneously, the 
associated setpoints are added (limited to ±200%). 
Parameter P432 can be set to define for each possible fixed setpoint source (binector, bit in control 
word - logic operation, see block diagram in Section 8) whether or not the ramp-function generator 
must be bypassed. When the ramp generator is bypassed, it operates with ramp-up/down times of 0. 
Sequence for entering Fixed Setpoint function: 
The fixed setpoint is injected instead of the main setpoint. 
Sequence for cancellation of Fixed Setpoint function: 
When all the possible sources for injecting the fixed setpoint (binectors, bits in control word) have 
changed back to log. "0", the setpoint selected in parameter P433 (main setpoint) is switched through 
again.  
9.8  Safety shutdown (E-Stop) 
The task of the E-STOP function is to open the relay contacts (terminals 109/110) for energizing the 
main contactor within about 15 ms, independently of semiconductor components and the functional 
status of the microprocessor board (basic electronics). If the basic electronics are operating correctly, 
the closed-loop control outputs an I = 0 command to de-energize the main contactor. When an E-
STOP command is given, the drive coasts to a standstill. 
The E-STOP function can be triggered by one of the following methods: 
•  Switch operation:  
(switch between terminals XS-105 and XS-106; XS-107 open; XS-108 open) 
E-STOP is activated when the switch between terminals XS-105 and XS-106 opens. 
•  Pushbutton operation:  
(Stop pushbutton with NC contact
between terminals XS-107 and XS-106; Reset pushbutton with 
NO contact
between terminals XS-108 and XS-106; XS-105 open) 
Opening an NC contact between terminals XS-106 and XS-107 triggers the E-STOP function and 
stores the shutdown operation. Closing an NO contact between terminals XS-106 and XS-108 
resets the function. 
When the E-STOP function is reset, the drive switches to the “Starting lockout” state. This status 
needs to be acknowledged through activation of the “Shutdown” function, e.g. by opening terminal 37. 
Note
The E-STOP function is not an EMERGENCY STOP function according to EN 60204-1 
C# PDF insert text Library: insert text into PDF content in C#.net
Library. Best and multifunctional Visual Studio .NET PDF SDK supports adding and inserting text content to adobe PDF document in C#.
add image in pdf using java; adding jpg to pdf
C# PDF Page Insert Library: insert pages into PDF file in C#.net
This C# .NET PDF document page inserting & adding component from RasterEdge is written in managed C# code and designed particularly for .NET class applications
add jpg to pdf; add jpeg signature to pdf
9-18 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Sequence of operations for entering E-STOP command: 
1.  Enter "E-STOP" command 
2.  Disable ramp-function generator, n and I controllers 
3.  I
set
= 0 is applied 
4.  a) U616 = 0: E-Stop has same effect as OFF2 (as soon as I = 0, the firing pulses are disabled) 
b) U616 = 1: E-Stop disables the output of firing pulses immediately (without waiting for I = 0) 
5.  Output signal "Close operating brake" (binector B0250 = 0, when P080 = 2) 
6.  Converter reaches operating state o10.0 or higher 
7.  An "older" actual field current value (K0265) is input as the field current setpoint upper limit 
(function is "released" in operating states of ≤o5)  
8.  Relay ”Power contactor on” (terminal 109/110) drops out 
9.  Drive coasts to a standstill (or is braked by the operating brake) 
10.  Parameterizable delay time (P258) runs down 
11.  The field is reduced to a parameterizable value (P257) 
12.  When n < n
min
(P370, P371) has been reached, the "Close holding brake" signal is output 
(binector B0250 = 0, when P080 = 1) 
Note:
15ms after entry of "E Stop" the hardware causes relay "Power contactor on" (terminal 109/110).to 
drop out (even if Item 8 of this sequence has not yet been reached). 
9.9  Activation command for holding or operating brake (low active) 
The signal for controlling the brake is available at binector B0250
log. "0" state = Close brake 
log. "1" state = Release brake 
In order to drive a brake, this binector must be "wired up" to a binary output, e.g. by setting P771 to 
250 for connection to output terminals 46 /47 (see Section 8, Sheet G112, for other possible settings). 
The following parameters influence the action of the brake control signal: 
P080 = 1  The brake is a holding brake:  
"Close brake" command is entered only when n < n
min
(P370, P371) 
P080 = 2  The brake is an operating brake: 
The "Close brake" command is entered even when the motor is running 
P087 
Brake release time: 
A positive
value prevents the motor from acting against the brake as it is released 
A negative
value causes the motor to act against the brake while it is still closed in 
order to prevent the occurrence of a brief, torque-free interval 
P088 
Brake closing time: 
Causes the motor to produce a torque while the brake is closing 
P319 
Delay time for enabling ramp-function generator 
After the controllers have been enabled, a setpoint of 0 is input for the time set 
here. This time should be set such that the brake has actually been released when 
the timer runs down. This is of particular importance when P087 is set to a 
negative value. 
The following diagrams illustrate the chronological sequence of the brake control function with a signal 
level change at inputs "Switch-on / Shutdown" (e.g. terminal 37) and "Operating enable " (terminal 38). 
With respect to the brake control, input commands "Inching", "Crawling" or "Fast stop" have the same 
affect as "Switch-on / Shutdown", and input commands "Voltage disconnection" or "E-Stop" the same 
affect as cancelling the "Operating enable" command. 
The command "Close brake" is output during the optimization run for precontrol and current controller 
(P051 = 25). 
VB.NET Image: How to Draw Annotation on Doc Images with Image SDK
other image annotating tutorials besides adding annotation using PDF document, image to pdf files and converting, compressing and stroing images, documents and
add an image to a pdf acrobat; adding an image to a pdf in acrobat
C# PDF Library SDK to view, edit, convert, process PDF file for C#
protecting PDF file by adding password and digital signatures with C# sample code in .NET Class. Feel free to define text or images on PDF document and extract
how to add a jpeg to a pdf file; adding a png to a pdf
SIEMENS AG    6RX1700-0AD76 
9-19 
SIMOREG DC-MASTER    Operating Instructions 
Operating brake (P080 = 2), positive brake release time (P087) 
*
*
*
P088
P087
P087
o1.1 
I,II,- - 
o1.0
o1.0
t
o7.0 
3)
5)
o7.0 
*
3)
1)
I,II,- - 
n < n     (P370,P371)
P319
P319
min
B0164
"disable"
"close"
"OFF"
"ON"
"enable"
"release"
Brake contr. signal
(B0255)
Oper. state
Actual speed
Internal contr. enable
Switch-on/shutdown
(term. 37)
Oper. enable
(term. 38)
Speed setpoint
Holding brake (P080 = 1), positive brake release time (P087) 
P088
P087
t
n < n     (P370,P371)
o1.1 
I,II,- - 
o1.0
o7.0 
o7.0 
I,II,- - 
*
*
3)
5)
*
2) 
P319
min
B0164
"disable"
"close"
"OFF"
"ON"
"enable"
"release"
Brake contr. signal
(B0255)
Oper. state
Actual speed
Internal contr. enable
Switch-on/shutdown
(term. 37)
Oper. enable
(term. 38)
Speed setpoint
*
1)  Drive is braked mechanically by means of operating brake 
*
2)  Drive coasts to standstill, "Close holding brake" not output until n < n
min 
*
3)  Time for the brake to open before the motor produces a torque (P087 positive) 
*
5)  Time for the brake to close while the motor is still producing a torque (P088) 
VB.NET PDF File & Page Process Library SDK for vb.net, ASP.NET
page, you will find detailed guidance on creating, loading, merge and splitting PDF pages and Files, adding a page into PDF document, deleting unnecessary page
how to add a jpg to a pdf; adding image to pdf form
VB.NET PDF insert text library: insert text into PDF content in vb
Multifunctional Visual Studio .NET PDF SDK library supports adding text content to adobe PDF document in VB.NET WinForms and ASP.NET.
pdf insert image; add picture to pdf
9-20 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Operating brake (P080 = 2), negative brake release time (P087) 
P319
P319
P088
t
n < n      (P370,P371)
*
*
4)
5)
*
1)
o1.1 
I,II,- - 
o7.0 
o7.0 
I,II,- - 
P087
*
4)
P087
min
B0164
"disable"
"close"
"OFF"
"ON"
"enable"
"release"
Brake contr. signal
(B0255)
Oper. state
Actual speed
Internal contr. enable
Switch-on/shutdown
(term. 37)
Oper. enable
(term. 38)
Speed setpoint
Holding brake (P080 = 1), negative brake release time (P087) 
P088
t
n < n      (P370,P371)
P319
o1.1 
I,II,- - 
o7.0 
o7.0 
I,II,- - 
*
5)
*
2) 
*
4)
P087
min
B0164
"disable"
"close"
"OFF"
"ON"
"enable"
"release"
Brake contr. signal
(B0255)
Oper. state
Actual speed
Internal contr. enable
Switch-on/shutdown
(term. 37)
Oper. enable
(term. 38)
Speed setpoint
*
1)  Drive is braked mechanically by means of operating brake 
*
2)  Drive coasts to standstill, "Close holding brake" not output until n < n
min 
*
4)  In this case, the motor is still rotating against the closed brake (P087 negative) 
*
5)  Time for the brake to close while the motor is still producing torque (P088) 
C# PDF Annotate Library: Draw, edit PDF annotation, markups in C#.
C#.NET: Add Text Box to PDF Document. Provide users with examples for adding text box to PDF and edit font size and color in text box field in C#.NET program.
how to add image to pdf; how to add an image to a pdf in preview
SIEMENS AG    6RX1700-0AD76 
9-21 
SIMOREG DC-MASTER    Operating Instructions 
9.10  Switch on auxiliaries 
The function acts as a switch-on command for auxiliaries (e.g. motor fan). 
The "Switch on auxiliaries" signal is available at binector B0251
log. "0" state = Auxiliaries OFF 
log. "1" state = Auxiliaries ON 
To act as the auxiliaries drive signal, this binector must be "wired up" to a binary output, e.g. by setting 
P771 to 251 for connection to output terminals 46 / 47 (see Section 8, Sheet G112, for other possible 
settings). 
The "Switch on auxiliaries" signal switches to "high" at the same time as the "Switch on" command. 
The converter then waits in operating state o6.0 for a parameterizable delay period (P093). The line 
contactor is closed on expiry of the delay. 
When the "Shutdown" command is entered, the firing pulses are disabled when n < n
min
is reached 
and the line contactor drops out. The "Switch on auxiliaries" signal switches to "low" after a 
parameterizable delay period (P094). However, if the "Switch on" command is entered again before 
this delay has expired, then the converter does not stay in operating state o6.0, but the line contactor 
is closed immediately instead. 
9.11  Switch over parameter sets 
See also in Section 9.1 under heading "Data sets" 
WARNING
Parameter sets can be switched over while the converter is in operation (online). As a result, 
depending on the setting of the control bits when the motor is running, the configuration or 
functions
may be altered in such a way as to produce dangerous operating conditions. 
For this reason, we strongly recommend that a "basic" parameter set containing all basic 
parameter settings is created first and then copied into the other parameter sets. The 
intentional changes of the "basic" version should then be entered in each parameter set. 
The "Switch over parameter sets" function affects function parameters (identified by an ".F" next to 
parameter number in block diagrams in Section 8) and Bico parameters (identified by a ".B" next to 
parameter number in block diagrams in Section 8). 
The following operating modes are possible (see also Section 8, Sheet G181): 
P649 = 9:   The control bits in control word 2 are input bit-serially. 
The binectors selected in P676 and P677 determine bits 0 and 1 of control word 2 (= bits 
16 and 17 of complete control word), and thus the input of the function data set. 
The binector selected in P690 determines bit 14 of control word 2 (= bit 30 of complete 
control word), and thus the input of the Bico data set. 
P649 ≠ 9:   The connector selected in P649 is used as control word 2. 
Bits 0 and 1 of control word 2 (bits 16 and 17 of complete control word) control the input 
of the function data set. Bit 14 (= bit 30 of complete control word) controls the input of the 
Bico data set. 
9-22 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Control word 
Active function data set 
Bit 16 
Bit17 
(active index) 
Control word 
Active Bico data set 
Bit30 
(active index) 
Caution
The parameter set selection must not be changed while the optimization run is in progress. 
Error message F041 will otherwise be output after 0.5 s. 
When the "Switch over parameter sets" function is activated, a time delay of up to 25ms may occur 
before the newly selected parameter set actually becomes operative. 
For information about copying parameter sets, please see Section 11 (Parameter List), parameters 
P055 and P057. 
9.12  Speed controller 
See also Section 8, Sheets G151 and G152 
Control signals for speed controller 
The control signals for "Enable speed controller droop", "Enable speed controller" and "Switch over 
master/slave drive" are supplied by control word 2. The following operating modes are possible (see 
also Section 8, Sheet G181): 
P649 = 9:   The control bits in control word 2 are input bit-serially. 
The binectors selected in P684, P685 and P687 determine bits 8, 9 and 11 of control 
word 2 (= bits 24, 25 and 27 of complete control word), and thus the functions "Enable 
speed controller droop", "Enable speed controller" and "Switch over master/slave drive". 
P649 ≠ 9:   The connector selected in P649 is used as control word 2. 
Bits 8, 9 and 11 control the functions "Enable speed controller droop", "Enable speed 
controller" and "Switch over master/slave drive". 
Enable speed controller:
0 =  Disable controller, controller output (K0160) = 0, P component (K0161) = 0, I 
component (K0162) = value of connector selected in P631 
1 =  Enable controller 
Enable droop
0 =  Droop is not active 
1 =  Droop is active 
SIEMENS AG    6RX1700-0AD76 
9-23 
SIMOREG DC-MASTER    Operating Instructions 
Switch over master/slave drive
0 = Master drive 
1 = Slave drive 
When "Slave drive" is selected, the I component of the speed controller is  
made to "track" such that M(set,n contr.) = M(set,limit.), the speed setpoint is set to equal 
the actual speed (K0179) (enable tracking with P229). 
Set I component
(selection of control signal via parameter P695): 
When 0 ⇒ 1 signal transition of selected binector, the I component is set to the setting 
value (selected in parameter P631) 
Stop I component
(selection of control signal via parameter P696): 
0 = I component enabled 
1 = Stop I component 
Limitation active
This signal is in the log. "1" state when the upper or lower torque limitation is violated, the 
speed limiting controller is active, the current limitation is active or when the firing angle 
for the armature circuit reaches the α
G
-limit. 
In this case, the I component of the speed controller is stopped. 
Switch over to P controller:
The P controller function is activated (I component = 0) when the speed drops to below 
the changeover value. 
D component in actual value channel or setpoint/actual value deviation channel 
As a basis for selecting the correct derivative action time, it is necessary to calculate the maximum 
possible rate of rise at the derivative action element input, i.e. the period of time required by the input 
signal to change from 0 to 100% at this maximum rate of rise. The derivative action time should 
preferably be set to a shorter value than this period. 
9.13  Serial interfaces 
The SIMOREG 6RA70 converter is equipped with the following serial interfaces: 
−  G-SST1 (serial interface 1) 
Connector X300 on board A7005 (operator panel) 
USS
® 
protocol 
provided for the purpose of connection the OP1S operator panel 
−  G-SST2 (serial interface 2) 
Terminal strip X172 (terminals 56 to 60) on board A7001 
USS
®
and peer-to-peer protocol, parameterizable 
Additionally if board A7006 (terminal expansion) is installed: 
−  G-SST3 (serial interface 3) 
Terminal strip X162 (terminals 61 to 65) 
USS
®
and peer-to-peer protocol, parameterizable 
Interface hardware 
The hardware of G-SST1 is designed to operate in RS232 and RS485 standard / two-wire mode, and 
G-SST2 and G-SST3 in RS485 standard / two and four-wire mode. For connectors and terminal 
assignments, see Section 8, Sheets G170 to G174. 
The maximum cable length for a peer-to-peer connection from the transmitter to the last receiver 
connected to the same transmission output is 1000 m. The same maximum cable length applies to the 
bus cable of a USS connection. The maximum cable length is only 500 m for both types of connection 
if a baud rate of 187500 bd is selected. 
9-24 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
USS: 
A maximum of 32 nodes can be connected in the bus configuration (i.e. 1 master and max. 31 slaves). 
The bus connector must be activated on the two bus nodes which form each end of the bus circuit. 
Peer-to-peer: 
Up to 31 other drives can be connected in parallel to the transmit cable of one drive. With a "parallel 
connection", the bus connector must be activated on the last connected drive. 
9.13.1  Serial interfaces with USS
®
protocol 
Specification for the USS
® 
protocol: Order No. E20125-D0001-S302-A1 
The SIEMENS USS
®
protocol is implemented in all digital converter devices supplied by SIEMENS. It 
can be used to provide a point-to-point or bus-type link to a master station. Any mixture of converter 
types can be connected up to the same bus line. The USS protocol makes it possible to access all 
relevant process data, diagnostic information and parameters of the SIMOREG converter. 
The USS protocol is a pure master-slave protocol. In this case, a converter device can only ever 
function as slave. Converter devices will transmit a telegram to the master only if they have received 
one from it first. In other words, converters linked via the USS protocol cannot exchange data directly 
with one another (they can do this only via a peer-to-peer link). 
Useful data which can be transferred via the USS protocol 
Sheets G170 to G172 in Section 8 show how useful data can be interconnected and list the 
parameters relevant for configuring USS interfaces. 
If parameters need to be read and/or written via the USS interface, then "Parameter data length" 
(P782, P792, P802) must be set to 3, 4 or 127 (select setting 4 only if double word parameters need to 
be transferred). If parameters do not need to be transferred, the "Parameter data length" must be set 
to 0. 
The number of process data words to be transferred is basically identical for the transmit and receive 
directions and can be set in "Process data length" (P781, P791, P801). Numeric representation "100% 
equals 4000h = 16384d" applies to all connectors. 
Transfer of double-word connectors: 
In the receive direction, the values of any two adjacent connectors (K) are combined to form a double-
word connector (KK) (e.g. K2002 and K2003 to KK2032). These double-word connectors can be 
connected in the usual way to other function blocks. For details of how to connect with double-word 
connectors, see Section 9.1, subsection "The following rules apply to the selection of double-word 
connectors". 
In the transmission direction, a double-word connector is applied by entering the same double-word 
connector at two contiguous indices of the selection parameter. 
Examples: 
.04
.01
.03
.02
P784
32
401
K0032
KK9498
KK9498
K0401
Word
L-Word
Word
H-Word
9498
9498
K
K
K
K
.04
.01
.03
.02
P784
Word
H-Word
Word
H-Word
2 different
double-word connectors
K0032
KK9498
KK9499
K0401
32
401
9498
9499
K
K
K
K
 