pdf renderer c# : How to add an image to a pdf in acrobat software SDK cloud windows wpf web page class OPI_simoreg_DC_0707_en38-part1891

SIEMENS AG    6RX1700-0AD76 
9-25 
SIMOREG DC-MASTER    Operating Instructions 
Numeric representation of parameter numbers and values on serial interfaces 
The mode of numeric representation of a parameter value is determined by the parameter "type" 
assigned to each parameter in the Parameter List. The different types of parameter are explained at 
the beginning of the list. Parameters are always transmitted in the form specified in the "Value range" 
column of the Parameter List; any decimal point, however, is omitted (example: display value 
123.45 
the number 12345d = 3039h is transferred via the serial interface). 
Diagnostics and monitoring functions for USS interfaces 
All transmitted and received useful data words can be checked (directly at the internal software 
transfer point from/to USS driver) by means of display parameters r810 / r811, r812 / r813 or r814 / 
r815. 
Diagnostic parameters r789, r799 or r809 provide information about the chronological distribution of 
errored and error-free telegrams, as well as the nature of any communication errors that have 
occurred. 
A watchdog can be set in P787, P797 or P807 which can initiate a shutdown on faults (F011, F012 or 
F013) in the case of timeout. By connecting binectors B2031, B6031 or B9031 to the fault message 
triggers (using P788=2031 / P798=6031 / P808=9031), it is possible to acknowledge these fault 
messages even if the fault is active continuously, thereby ensuring that the drive can still be operated 
manually after the USS interface has failed. 
Important ! 
The serial interfaces for the USS protocol are parameterized with the same parameters used to 
configure the peer-to-peer protocol, although the setting ranges are different in some cases (see 
Notes for relevant parameters in Parameter List, Section 11). 
How to add an image to a pdf in acrobat - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
add image to pdf in preview; attach image to pdf form
How to add an image to a pdf in acrobat - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
add photo to pdf file; how to add an image to a pdf file in acrobat
9-26 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
USS protocol: Brief start-up guide for SIMOREG 6RA70 converters 
G-SST1 
RS232 / RS485 
G-SST1 
RS485 
for connection of an OP1S 
G-SST2 / G-SST3 
RS485 
Select USS protocol 
P780 = 2 
P780 = 2 
P790 / P800 = 2 
Baud rate
P783 = 1 to 13, corresponding to 
300 to 187500 baud
P783 =   6 (9600 Bd) or  
7 (19200 Bd) 
The baud rate setting must be 
identical for every node in bus 
operation
P793 / P803 = 1 to 13, 
corresponding to 300 to 187500 
baud
No. of process data (PZD No.) 
(applies to Receive and Send)
P781 = 0 to 16
P781 = 2
P791 / P801 = 0 to 16
PZD assignment for control word 
and setpoints 
(received process data)
All received process data are 
taken to connectors and must be 
wired up as required
If the control bits from the OP1S 
are to be used: 
Word 1 (connector K2001):
Wiring up of control bits 
from OP1S, see Sec. 7.2.2 
Word 2 (connector K2002): 
Not used
All received process data are 
taken to connectors and must be 
wired up as required
No. of PKW
P782 = 
0: 
No PKW data 
3 / 4:  3 / 4 PKW data words 
127:  Variable data length for 
slave 
master
P782 = 127  variable data length
P792 / P802 = 
0: 
No PKW data 
3 / 4:  3 / 4 PKW data words  
127:  Variable data length for 
slave 
master
PZD assignment for actual 
values 
(transmitted process data)
Selection of transmitted values 
via P784
Word 1:  P784.i01=32 
(stat. word 1 K0032) 
Word 2:  P784.i02=0 
Selection of transmitted values 
via P794 / P804
Node address
P786 = 0 to 30
P786 = 0 to 30 
Every node must have its own, 
unique address for bus operation
P796 / P806 = 0 to 30
Telegram failure time
P787 = 0.000 to 65.000s
P787 = 0.000s
P797 / P807 = 0.000 to 65.000s
Bus termination 
P785 = 0: Bus term. OFF 
1: Bus term. ON 
P785 =  0: Bus term. OFF 
1: Bus term. ON 
P795 / P805 = 
0: Bus term. OFF 
1: Bus term. ON 
Bus / point-to-point 
communication
RS232: Only point-to-point
operation possible 
RS485: Bus operation possible
Bus operation possible
Bus operation possible
2-wire / 4-wire  transmission 
via RS485 interface
2-wire operation is selected 
automatically
2-wire operation is selected 
automatically
2-wire operation is selected 
automatically
Cable
Connector assignments, see 
Sect. 6.8 or Sheet G170 in  
Sect. 8
See operating instructions for 
OP1S operator panel
Connector assignments, see 
Sect. 6.8 or Sheets G171, G172 
in Sect. 8
.NET PDF Document Viewing, Annotation, Conversion & Processing
Convert image files to PDF. File & Page Process. Annotate & Comment. Add, insert PDF native annotations to PDF file. Support for all the print modes in Acrobat PDF
adding image to pdf file; add image to pdf preview
C# PDF Converter Library SDK to convert PDF to other file formats
without using other external third-party dependencies like Adobe Acrobat. you can easily perform file conversion from PDF document to image or document
add image to pdf file; add an image to a pdf in preview
SIEMENS AG    6RX1700-0AD76 
9-27 
SIMOREG DC-MASTER    Operating Instructions 
Connection example for a USS bus 
4
11
14
+
8
6
4
SIMATIC S5
-
Rx
Tx
12
10
X3
X3
150 
1)
2)
Rx
Tx
6RA70
-
+
+
Rx
Tx
6RA70
-
+
+
Rx
Tx
6RA70
-
+
+
59
58
59
58
59
58
CP524 with RS485
-module ...0AA43
(Jumper X3: 20-18 -->
2-wire cable)
SUB-D connector
15-pin
Master
(Bus terminating
resistors activated)
Slave 1
(Bus terminating
resistors deactivated)
Slave 2
(Bus terminating
resistors deactivated)
Slave n (n<=31))
(Bus terminating
resistors activated)
1) The interface cable shields must be connected directly on the converter with the lowest possible
impedance to converter or cubicle earth (e.g. via clamp).
2) Twisted cable, e.g. LIYCY 2x0.5 sqmm; with longer cables, an  equipotential bonding conductor
must be used to ensure that the difference in frame potentials between nodes stays below 7 V.
9.13.2  Serial interfaces with peer-to-peer protocol 
The term "Peer-to-peer link" refers to a "Link between partners of equal status". In contrast to the 
classic master/slave bus system (e.g. USS and PROFIBUS), the same converter can function as both 
the master (setpoint source) and the slave (setpoint receiver) in a peer-to-peer link. 
Signals can be transferred in fully digital form from one converter to another via the peer-to-peer link, 
for example: 
−  Velocity setpoints for producing a setpoint cascade, e.g. on paper, foil and wire-drawing 
machines and on fiber-drawing machinery. 
−  Torque setpoints for closed-loop load distribution controls on drives that are coupled 
mechanically or via the material, e.g. longitudinal-shaft drives on printing presses or S-roll drives 
−  Acceleration setpoints (dv/dt) for acceleration precontrol on multi-motor drives. 
−  Control commands 
Useful data which can be transferred via the peer-to-peer link 
Sheets G173 and G174 in Section 8 show how useful data can be interconnected and list the 
parameters relevant for configuring peer-to-peer links. Any connectors can be parameterized as 
transmit data (numeric representation: 100% equals 4000h = 16384d). 
Parameters cannot be transferred via the peer-to-peer link. 
Transfer of double-word connectors: 
In the receive direction, the values of any two adjacent connectors (K) are combined to form a double-
word connector (KK) (e.g. K6001 and K6002 to KK6081). These double-word connectors can be 
connected in the usual way to other function blocks. For details of how to connect with double-word 
connectors, see Section 9.1, subsection "The following rules apply to the selection of double-word 
connectors". 
In the transmission direction, a double-word connector is applied by entering the same double-word 
C# Windows Viewer - Image and Document Conversion & Rendering in
without using other external third-party dependencies like Adobe Acrobat. Image and Document Conversion Supported by Windows Viewer. Convert to PDF.
how to add a picture to a pdf file; how to add an image to a pdf file
VB.NET PDF: How to Create Watermark on PDF Document within
Using this VB.NET Imaging PDF Watermark Add-on, you can a watermark that consists of text or image (such as And with our PDF Watermark Creator, users need no
adding images to a pdf document; how to add image to pdf file
9-28 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
connector at two contiguous indices of the selection parameter. 
Examples: 
.04
.01
.03
.02
P794
KK9498
KK9498
K0401
K0402
L-Word
H-Word
Word
Word
401
9498
9498
K
K
K
402
K
.04
.01
.03
.02
P794
KK9498
KK9499
K0401
K0402
H-Word
H-Word
Word
Word
401
9498
9499
K
K
K
402
K
2 different
double-word connectors
Diagnostics and monitoring functions for peer-to-peer link 
All transmitted and received useful data words can be checked (directly at the internal software 
transfer point from/to peer driver) by means of display parameters r812 / r813 or r814 / r815. 
Diagnostic parameters r799 or r809 provide information about the chronological distribution of errored 
and error-free telegrams, as well as the nature of any communication errors that have occurred. A 
watchdog can be set in  P797 or P807 which can initiate a shutdown on faults (F012 or F013) in the 
case of timeout. By connecting binectors B6031 or B9031 to the fault message triggers (using 
P798=6031 / P808=9031), it is possible to acknowledge these fault messages even if the fault is 
active continuously, thereby ensuring that the drive can still be operated manually after the peer-to-
peer interface has failed. 
Important ! 
The serial interfaces for the peer-to-peer protocol are parameterized with the same parameters used 
to configure the USS protocol, although the setting ranges are different in some cases (see Notes for 
relevant parameters in Parameter List, Section 11). 
Peer-to-peer communication, 4-wire operation
Serial linking of converter to converter (partners of equal status). 
The signal flow can pass through the drives, for example, in a series connection. In this case, each 
drive forwards the data after processing only to the next drive (classic setpoint cascade). 
C# powerpoint - PowerPoint Conversion & Rendering in C#.NET
using other external third-party dependencies like Adobe Acrobat. SDK to convert PowerPoint document to PDF document code for PowerPoint to TIFF image conversion
how to add image to pdf reader; add jpeg to pdf
C# Word - Word Conversion in C#.NET
using other external third-party dependencies like Adobe Acrobat. Word SDK to convert Word document to PDF document. demo code for Word to TIFF image conversion
how to add image to pdf in preview; add picture to pdf online
SIEMENS AG    6RX1700-0AD76 
9-29 
SIMOREG DC-MASTER    Operating Instructions 
Brief start-up guide for SIMOREG 6RA70 converters 
G-SST2 
RS485
G-SST3 
RS485
Select peer-to-peer protocol 
P790 = 5
P800 = 5
Baud rate
P793 = 1 to 13 corresponding to 300 to 187500 
baud
P803 = 1 to 13 corresponding to 300 to 187500 
baud
No. of process data (PZD No.)  
(applies to Receive and Send)
P791 = 1 to 5
P801 = 1 to 5
PZD assignment for control word 
and setpoints 
(received process data)
All received process data are taken to connectors 
and must be wired up as required
All received process data are taken to connectors 
and must be wired up as required
No. of PKW
No parameters can be transferred
No parameters can be transferred
PZD assignment for actual 
values 
(transmitted process data)
Selection of transmitted values via P794 
(indices .01 to .05)
Selection of transmitted values via P804 
(indices .01 to .05)
Telegram failure time
P797 = 0.000 to 65.000s
P807 = 0.000 to 65.000s
Bus termination 
P795 = 0: Bus term. OFF 
1: Bus term. ON 
(depending on type of link)
P805 = 0: Bus term. OFF 
1: Bus term. ON 
(depending on type of link)
2-wire / 4-wire transmission 
via RS485 interface
"4-wire" operation is automatically selected
"4-wire" operation is automatically selected
Cable 
Terminal assignments, see Section 6.8 or Sheet 
G173 in Section 8 
Terminal assignments, see Section 6.8 or Sheet 
G174 in Section 8 
Examples of peer-to-peer links 
Rx
Tx
2)
+
56
57
58
59
-
-
+
+
6RA70
Rx
Tx
+
56
57
58
59
-
-
+
+
6RA70
Rx
Tx
+
56
57
58
59
-
-
+
+
6RA70
Rx
Tx
+
56
57
58
59
-
-
+
+
6RA70
Peer link type "Series connection"
Each drive receives its own individual setpoint from the drive connected upstream (classic setpoint cascade)
1) The interface cable shields must be connected directly on the converter with the lowest possible
impedance to converter or cubicle earth (e.g. via a clamp).
2) Twisted cable, e.g. LIYCY 2x0.5 sqmm; with longer cables, an equipotential bonding conductor
must be used to ensure that the difference in frame potentials between nodes stays below 7 V.
3) 
Optional data feedback loop via which drive 1 can monitor operation of the entire peer chain.
Drive 1
(Activate bus terminating
resistors when a data feed-
back loop is used)
Drive 2
(Bus terminating
resistors activated)
Drive 3
(Bus terminating
resistors activated)
Drive n
n=any number
(Bus terminating
resistors activated)
Data feedback loop   3)
BMP to PDF Converter | Convert Bitmap to PDF, Convert PDF to BMP
Also designed to be used add-on for .NET Image SDK, RasterEdge Bitmap to PDF Converter can Powerful image converter for Bitmap and PDF files; No need for
add picture to pdf reader; how to add image to pdf in acrobat
PDF to WORD Converter | Convert PDF to Word, Convert Word to PDF
out transformation between different kinds of image files and Word Converter has accurate output, and PDF to Word need the support of Adobe Acrobat & Microsoft
add photo to pdf form; add jpg to pdf document
9-30 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
2)
1)
Rx
Tx
+
56
57
58
59
-
-
+
+
6RA70
Rx
Tx
+
56
57
58
59
-
-
+
+
6RA70
Rx
Tx
+
56
57
58
59
-
-
+
+
6RA70
Rx
Tx
+
56
57
58
59
-
-
+
+
6RA70
Peer link type "Parallel connection"
Up to 31 drives receive identical setpoints from drive 1
1) The interface cable shields must be connected directly on the converter with the lowest possible
impedance to converter or cubicle earth (e.g. via a clamp).
2) 
Twisted cable, e.g. LIYCY 2x0.5 sqmm; with longer cables, an equipotential bonding conductor
must be used to ensure that the difference in frame potentials between nodes stays below 7V.
Drive 1
Drive 2
(Bus terminating
resistors deactivated)
Drive 3
(Bus terminating
resistors deactivated)
Drive n  (n <= 32)
(Bus terminating
resistors activated)
2)
1)
Rx
+
56
57
58
59
-
-
+
+
6RA70
Rx
+
56
57
58
59
- +
6RA70
Rx
+
56
57
58
59
-
+
+
6RA70
Rx
+
56
57
58
59
-
+
+
6RA70
1
0
Tx
-
+
1
0
Tx
1
0
Tx
1
0
Tx
-
-
Peer link type "Bus connection"
Up to 31 drives receive identical setpoints from one drive. The setpoint source drive is selected with
"Enable transmit" = 1. "Enable transmit" = 0 must be preset for all other drives.
1) The interface cable sheilds must be connected  directly on the converter with the lowest possible
impedance to converter or or cubicle earth (e.g. via a clamp).
2) Twisted cable, e.g. LIYCY 2x0.5 sqmm; with longer cables, an equipotential bonding conductor
must be used to ensure that the difference in frame potentials between nodes stays below 7V.
Bus terminating
resistors deactivated
Bus terminating
resistors deactivated
Bus terminating
resistors activated
Transm.
data
Enable
transmit=1
Bus terminating
resistors activated
Enable
transmit=0
Enable
transmit=0
Enable
transmit=0
JPEG to PDF Converter | Convert JPEG to PDF, Convert PDF to JPEG
It can be used standalone. JPEG to PDF Converter is able to convert image files to PDF directly without the software Adobe Acrobat Reader for conversion.
add jpg to pdf form; how to add a jpeg to a pdf
VB.NET PowerPoint: VB Code to Draw and Create Annotation on PPT
as a kind of compensation for limitations (other documents are compatible, including PDF, TIFF, MS VB.NET PPT: VB Code to Add Embedded Image Object to
add picture pdf; add photo to pdf in preview
SIEMENS AG    6RX1700-0AD76 
9-31 
SIMOREG DC-MASTER    Operating Instructions 
9.14  Thermal overload protection of DC motor 
(I2t monitoring of motor) 
The I2t monitoring function is parameterized in parameters P100, P113 and P114. If these parameters 
are adapted correctly, the motor is protected against overloading (not all-round motor protection). 
This monitoring function is disabled in the factory setting of the parameters (P820 i006 = 37). 
Adaptation 
P114: 
A time constant T
motor
in minutes for the I2t monitoring function must be entered in 
parameter P114. 
P113, P100: The permissible continuous current of the motor must be defined by parameters P100 
and P113. 
The permissible continuous current is the product of the calculation P113 * P100. 
Warning characteristic / switch-off characteristic 
If the motor is loaded constantly, for example, with about 125% of the permissible continuous motor 
current, then alarm A037 is triggered after a time constant (P114) has elapsed. If the load is not 
reduced, then the drive is shut down when the switch-off characteristic is reached and fault message 
F037 displayed. 
Warning/switch-off times for other loads can be calculated from the diagram. 
Alarm message triggering by motor I2t monitoring function 
This diagram shows how long it takes for an alarm message to be triggered if, after a long preloading 
period (> 5 
T_th), a new constant load value is injected abruptly. 
T_th = P114 .. thermal time constant of motor 
0
0,5
1
1,5
2
2,5
3
3,5
4
4,5
5
0
0,5
1
1,5
2
2,5
3
Time / thermal time constant of motor
Load current / permissible continuous current (P100 x P113)
0%  preloading
20% preloading
40% preloading
60% preloading
80% preloading
9-32 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Fault message triggering by motor I2t monitoring function 
This diagram shows how long it takes for a fault message to be triggered if, after a long preloading 
period (> 5 
T_th), a new constant load value is injected abruptly. 
T_th = P114 .. thermal time constant of motor 
0
0,5
1
1,5
2
2,5
3
3,5
4
4,5
5
0
0,5
1
1,5
2
2,5
3
Time / thermal time constant of motor
Load current / permissible continuous current (P100 x P113)
0%  preloading
20% preloading
40% preloading
60% preloading
80% preloading
CAUTION
When the electronics power supply fails for longer than 2 s, the calculated motor preloading 
value is lost. When the supply is reconnected, the system assumes that the connected motor 
has not been loaded at all! 
If the electronics power supply fails and the converter is switched on again within 2 s (e.g. via 
the "Automatic restart" function), then the temperature calculation is based on the last calculated 
l2t value of the motor.. 
The I2t monitoring function reproduces only a rough thermal image of the motor, i.e. it does not 
provide all-round motor protection. 
If P114 (T
motor
) is set to zero, then the I2t monitoring function is deactivated. 
SIEMENS AG    6RX1700-0AD76 
9-33 
SIMOREG DC-MASTER    Operating Instructions 
Calculation of thermal equivalent time constant (P114) 
It must be noted that the thermal equivalent time constant is dependent on the maximum overcurrent. 
Thermal equivalent time constant of 1G . 5/1H . 5 DC motors according to Catalog DA12. 
100
120
140
160
180
200
1
40
2
4
3
5
6
8
10
20
30
P114
I
[%]
I
I
rated
I
rated
... Rated motor armature current (=P100) 
  ...     Maximum overcurrent at which motor is operated 
NOTES
•  When other motor types are connected, the manufacturer's specifications apply. 
•  If you are using DC motors 1G.5 / 1H.5 as specified in catalog DA12, parameter P113 must 
be set to 1.00 
9-34 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
9.15  Dynamic overload capability of power section 
9.15.1  Overview of functions 
The converter rated DC current specified on the rating plate (= maximum permissible continuous 
direct current when P077 = 1.00) may be exceeded in operation. The amount and permissible 
duration of the overload are subject to limits which are explained in more detail below. 
The absolute upper limit for the absolute value of overload currents corresponds to 1.8 times the 
converter rated DC current * P077 (= r072.001 * P077). The maximum overload period depends both 
on the time characteristic of the overload current and on the load history of the converter and differs 
depending on the installed power section. 
Every overload must be preceded by an "underload" (load phase at load current < P077 * rated DC 
current). After the maximum permissible overload period has expired, the load current must be 
reduced to a value of at least ≤ P077 * converter rated DC current. 
The dynamic overload period is made possible by a thermal monitoring function
(I2t monitor) in the 
power section. This uses the time characteristic of the actual load current to calculate the time 
characteristic of the thyristor temperature rise over ambient temperature. When the converter is 
switched on, the calculation commences with the initial values that were calculated before the 
converter power supply was last switched off/last failed. Allowance can be made for ambient 
conditions (ambient temperature, installation altitude) by the setting in parameter P077. 
In the delivery state, the ambient temperature is always set to the maximum permissible value  
(i.e. 45°C for naturally cooled converters and 40°C for converters with forced cooling). 
The I2t monitoring function responds when the calculated thyristor temperature rises exceeds the 
permissible limit. Two alternative responses to the monitor can be parameterized: 
P075 = 1:  Alarm A039 with reduction of armature current setpoint to P077 * converter rated DC 
current 
P075 = 2:  Fault F039 followed by converter shutdown 
The I2t monitoring function can be deactivated. In this case, the armature current is limited to the 
setting in P077 * converter rated DC current (= P077 * r072.001). 
Connector K310 contains the calculated thyristor overtemperature as a % of the maximum
permissible 
converter-specific thyristor overtemperature: 
80°C on 15A to 60A converters 
85°C on 90A to 140A converters 
90°C on converters of > 200A converter rated armature DC current. 
Documents you may be interested
Documents you may be interested