SIEMENS AG    6RX1700-0AD76 
9-75 
SIMOREG DC-MASTER    Operating Instructions 
9.17  Automatic restart 
The "Automatic restart" function is controlled by the setting in parameter P086: 
P086 = 0 
No automatic restart 
P086 = 0.1s to 2.0s 
”Automatic restart" in seconds 
The purpose of the "Automatic restart" function is to prevent the SIMOREG converter from switching 
immediately to the "FAULT" state, but allow it to return to the "Run" state after the elimination of 
certain fault conditions such as brief failures in supply voltages, brief undervoltage or overvoltage, very 
high or very low line frequencies or in the case of an excessive deviation between the field current 
actual value and setpoint. 
The appropriate fault message is output only if one of the following fault conditions prevails 
continuously for longer than the "Automatic restart time" set in P086 (maximum time delay within 
which fault condition must be eliminated for "Automatic restart"): 
F001  Failure of electronics supply in operation (5U1, 5W1) 
F004  Armature supply phase failure (1U1, 1V1, 1W1) 
F005  Fault in field circuit (field supply phase failure (3U1, 3W1) or 
I
field act
< 50% I
field set
F006  Undervoltage (armature or field supply) 
F007  Overvoltage (armature or field supply) 
F008  Line frequency (armature or field supply) less than 45Hz 
F009  Line frequency (armature or field supply) greater than 65 Hz 
When one of the fault conditions associated with faults F003 to F006, F008, F009 is active and the 
automatic restart time delay is still running, the converter dwells in operating state 04.0 (with armature 
line voltage faults) or 05.0 (with field line voltage or field current faults). 
Failures in the electronics supply lasting up to several 100 ms are bridged by the back-up power 
supply. With longer failures, the failure time is measured by measuring the voltage across one 
"discharge capacitor" and, if the failure has not lasted as long as the "Restart time" set in P086, the 
converter restarted again immediately provided that the corresponding control signals (e.g. "Switch-
on", "Operating enable") are still applied. 
When the "Switch-on", "Shutdown" and "Crawl" functions are edge-triggered
(see P445 = 1), the 
converter cannot be restarted automatically
after the power supply backup has been used. 
9.18  Field reversal  
(also refer to Section 8 “Function diagrams” Sheet G200)
By reversing the current polarity in the field winding of the DC motor (i.e. through field reversal), a 
drive which incorporates a SIMOREG 6RA70 single-quadrant converter (with only a single armature 
conduction direction) will be able to operate in other quadrants of the speed/torque characteristic 
(reversal of rotational direction and braking). Two contactors in the field circuit (1, 2) are required to 
reverse the polarity of the field voltage.  
The signal level of binectors B0260 ("Close field contactor 1") and B0261 ("Close field contactor 2") 
are defined in an internal operating sequence involving functions "Direction of rotation reversal using 
field reversal" and "Braking with field reversal". These binectors are used to control the two reversing 
contactors for changing the field polarity. A snubber circuit must be installed in the field circuit. 
Level of B0260:  0  No contactor control 
 Control for one contactor for switching through positive field direction
Level of B0261:  0  No contactor control 
 Control for one contactor for switching through negative field direction
Add jpeg signature to pdf - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
adding an image to a pdf in acrobat; add a picture to a pdf file
Add jpeg signature to pdf - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
add png to pdf preview; add image to pdf reader
9-76 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
9.18.1  Direction of rotation reversal using field reversal 
This function is controlled by the binector selected in P580. 
The "Direction of rotation reversal using field reversal" has a switch function and defines the field 
direction
and, if a positive
speed setpoint is applied, also the direction of rotation. 
Level:  0 
Positive field direction is selected 
(”Close field contactor 1” (B0260) = 1, ”Close field contactor 2” 
(B0261) = 0) 
Negative field direction is selected 
(”Close field contactor 1” (B0260) = 0, ” Close field contactor 2” 
(B0261) = 1) 
Changing the logic level of the binector controlling the "Direction of rotation reversal using field 
reversal" function initiates an internal sequence which brakes the motor and accelerates it in the 
opposite direction. 
While the field reversal process is in progress, the logic level of the controlling binector is irrelevant, 
i.e. once the function has commenced, it is completed without interruption. Only on completion is 
another check made to establish whether the logic level of the controlling binector actually coincides 
with the currently selected field direction. 
Note: 
Only positive speed setpoints are meaningful. 
Sequence of control operations when "Direction of rotation reversal using field reversal" is 
applied: 
1. 
Drive is rotating in rotational direction 1 (or is at standstill) 
2. 
Logic level of binector controlling the "Direction of rotation reversal using field reversal" changes 
3. 
Internal field reversal process takes place (only if a braking operation has not already been 
activated by pushbutton function "Braking with field reversal"): 
3.1  Wait for armature current I
= 0 and then armature pulse disable 
(drive then dwells in operating state ≥ o1.4) 
3.2  Disable field firing pulses (also causes K0268=0) 
3.3  Wait for I
field
(K0265)
< I
field min
(P394) 
3.4  Waiting time according to P092.i001 (0.0 to 10.0 s, factory setting 3.0 s)  
3.5  Open current field contactor (B0260 = 0 or B0261 = 0) 
3.6  Waiting time according to P092.i002 (0,0 to 10,0 s, factory setting 0,2 s)  
3.7  Close new field contactor (B0261 = 1 or B0260 = 1) 
3.8  Reverse polarity of actual speed value (except when P083 = 3 ... EMF as actual speed 
value) 
3.9  Waiting time according to P092.i003 (0,0 to 10,0 s, factory setting 0,1 s)  
3.10  Enable field firing pulses 
3.11  Wait for I
field
(K0265) > I
field set
(K0268)*P398/100% 
3.12  Waiting time according to P092.i004 (0,0 to 10,0 s, factory setting 3,0 s)  
3.13  Enable armature firing pulses  
(It is possible to exit operating mode o1.4)  
4. 
Drive brakes and then accelerates in rotational direction 2 (or remains at standstill) 
Note
If the actual speed value polarity is reversed internally as a result of field reversal, P083 (but not 
P083=3) is supplied with inverted signal values (see Section 8, Sheet G152). When the ramp-function 
generator is in use, it is advisable to set P228=0 (no speed controller setpoint filtering). Otherwise, 
initial braking along the current limit may occur in connection with the actual speed value polarity 
reversal and setting of the ramp-function generator output (to (reversed) actual speed value (or to 
value set in P639) in operating state o1.4). 
C# PDF Digital Signature Library: add, remove, update PDF digital
text from PDF, VB.NET convert PDF to Jpeg, VB.NET Add a signature or an empty signature field in any PDF file Search unsigned signature field in PDF document.
how to add a picture to a pdf document; add picture pdf
VB.NET PDF Digital Signature Library: add, remove, update PDF
C# Online Dicom Viewer, C# Online Jpeg images Viewer VB.NET PDF - Add Digital Signatures to PDF in VB allows PDF such security setting via digital signature.
how to add jpg to pdf file; how to add a picture to a pdf file
SIEMENS AG    6RX1700-0AD76 
9-77 
SIMOREG DC-MASTER    Operating Instructions 
9.18.2  Braking with field reversal 
This function is controlled by the binector selected in P581. 
"Braking with field reversal" has a pushbutton function
If the logic level of the binector controlling the "Braking with field reversal" function = 1 (for at least 
30 ms) and the converter is in an operating state ≤ o5 (line contactor closed), an internal process
is 
activated for braking the drive down to n < n
min
The original field direction is then selected. 
The motor cannot accelerate again in the original rotational direction until the braking command has 
been cancelled (binector level = 0) and an acknowledgement given with "Shutdown" and "Switch-on". 
Sequence of control operations when "Braking with field reversal" is applied: 
1. 
Drive rotates in direction 1 
2. 
The binector controlling the "Braking with field reversal" function = 1 for more than 30 ms 
3. 
Internal field reversal process takes place (only if the line contactor is closed (in operating state 
of ≤ o5) and the drive is not already in braking mode. Braking is detected by a negative internal 
actual speed (resulting from reversal of the real actual speed polarity in the negative field 
direction): 
3.1  Wait for armature current I
= 0 and then armature pulse disable 
(drive then dwells in operating state ≥ o1.4) 
3.2  Disable field firing pulses (also causes K0268=0) 
3.3  Wait for I
field
(K0265)
< I
field min
(P394) 
3.4  Waiting time according to P092.i001 (0,0 to 10,0 s, factory setting 3,0 s)  
3.5  Open current field contactor (B0260 = 0 or B0261 = 0) 
3.6  Waiting time according to P092.i002 (0,0 to 10,0 s, factory setting 0,2 s)  
3.7  Close new field contactor (B0261 = 1 or B0260 = 1) 
3.8  Reverse polarity of actual speed value (except when P083 = 3 ... EMF as actual speed 
value) 
3.9  Waiting time according to P092.i003 (0,0 to 10,0 s, factory setting 0,1 s)  
3.10  Enable field firing pulses 
3.11  Wait for I
field
(K0265) > I
field set
(K0268)*P398/100% 
3.12  Waiting time according to P092.i004 (0,0 to 10,0 s, factory setting 3,0 s)  
3.13  Enable armature firing pulses (It is possible to exit operating mode o1.4) 
4. 
Internal sequence for braking the drive: 
4.1  Internal setting of n
set
= 0 at the ramp function generator input, the drive brakes 
4.2  Wait for n < n
min
(P370) 
4.3  Wait for armature current I
A
= 0 and thus armature pulse disable 
(drive then switches to operating state o7.2) 
4.4  Wait for cancellation of braking command through binector level = 0 (as long as 
level = 1, drive is held in operating state o7.2) 
5. 
Internal sequence for switching over to original field direction (only if the current field direction is 
not the same as the direction requested by the "Direction of rotation reversal using field 
reversal" function): 
5.1  Wait for armature current I
= 0 and then armature pulse disable 
(drive then dwells in operating state ≥ o1.4) 
5.2  Disable field firing pulses (also causes K0268=0) 
5.3  Wait for I
field
(K0265)
< I
field min
(P394) 
5.4  Waiting time according to P092.i001 (0,0 to 10,0 s, factory setting 3,0 s)  
5.5  Open current field contactor (B0260 = 0 or B0261 = 0) 
5.6  Waiting time according to P092.i002 (0,0 to 10,0 s, factory setting 0,2 s)  
5.7  Close new field contactor (B0261 = 1 or B0260 = 1) 
5.8  Reverse polarity of actual speed value (except when P083 = 3 ... EMF as actual speed 
value) 
5.9  Waiting time according to P092.i003 (0,0 to 10,0 s, factory setting 0,1 s)  
5.10  Enable field firing pulses 
5.11  Wait for I
field
(K0265) > I
field set
(K0268)*P398/100% 
5.12  Waiting time according to P092.i004 (0,0 to 10,0 s, factory setting 3,0 s)  
5.13  Armature firing pulses are possible again 
C# HTML5 Viewer: Load, View, Convert, Annotate and Edit Raster
Signature feature for protecting images. supports various images formats, including JPEG, GIF, BMP Supported annotation features includes add text comments to
adding a jpg to a pdf; how to add a photo to a pdf document
C#: XDoc.HTML5 Viewer for .NET Online Help Manual
Office 2003 and 2007, PDF, DICOM, Gif, Png, Jpeg, Bmp. 6. Click to save created signature with customized name. Click to add a rectangle redaction on the file.
how to add image to pdf reader; how to add an image to a pdf in reader
9-78 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
6. 
Drive is in operating state o7.2 
Drive can be accelerated in original rotational direction after acknowledgement by an external 
"Shutdown" and "Switch-on" command. 
Please also read the Note at the end of the section 9.18.1. 
Delay times for field reversal (parameter P092) 
P394
P092.001
P092.002
P092.003
K268 * P398
P092.004
B260
B261
Field contactor 1
Field contactor 2
closed
open
closed
open
I
A
I
F
Bild 9.18.1  
VB.NET PDF Library SDK to view, edit, convert, process PDF file
NET program. Password, digital signature and PDF text, image and page redaction will be used and customized. PDF Annotation Edit.
add jpg to pdf preview; adding an image to a pdf in preview
How to C#: Basic SDK Concept of XDoc.PDF for .NET
can convert Word, Excel, PowerPoint Tiff, Jpeg, Bmp, Png You may add PDF document protection functionality into your C# APIs for handling digital signature in a
add jpg signature to pdf; add an image to a pdf with acrobat
SIEMENS AG    6RX1700-0AD76 
9-79 
SIMOREG DC-MASTER    Operating Instructions 
9.19  Status description of some bits of status word ZSW1 
0  1
I
II
- -
I ,II ,- -
o1
o2
o3
o4
o5
o6
o7
o8
o9
o10
o11
o12
0  1
0  1
0  1
0  1
0  1
0  1
Code
Operating status
M0, MI or MII
(=RUN)
Waiting for operating enable 
(=READY)
reserved
Test phase
Wait for voltage
(armature)
Wait for field current
Wait status before closing
the line contactor
Wait for switch-on
(=READY TO SWITCH-ON)
Wait for acknowledgement
of the switch-on inhibit
Fast stop (OFF3)
Voltage disconnect (OFF2)
Fault
Electronics not
initialized
Bit 6
Switch-on inhibit
Bit 5 (low active)
Fast stop (OFF3)
Bit 4 (low active)
Voltage disconnect (OFF2)
Bit 3
Fault
Bit 2
Run
Bit 1
Ready
Bit 0
Ready to switch-on
VB.NET PDF: Basic SDK Concept of XDoc.PDF
can convert Word, Excel, PowerPoint Tiff, Jpeg, Bmp, Png You may add PDF document protection functionality into your VB APIs for handling digital signature in a
how to add an image to a pdf file; acrobat insert image into pdf
.NET PDF SDK - Description of All PDF Processing Control Feastures
PDF to text; Convert PDF to Jpeg images; More protected PDF; Allow users to add password to Create signatures in existing PDF signature fields; Create signatures
add image to pdf online; add a picture to a pdf
9-80 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
9.20  12-pulse series connection 
This function is facilitated by the parameter setting P079 = 2 and is available in SW 2.1 and later. 
Two SIMOREG units with identical power are connected in series on the output side
and supply a DC 
motor. 
These two units, which are parameterized as a 12-pulse series master
and a 12-pulse series slave
are coupled via the paralleling interface and fed with electrically isolated line voltages of identical 
magnitude with a 30 degree phase displacement. 
The power sections of both converters must be supplied with a clockwise phase sequence. The three-
phase system connected on the slave device must lag the system on the master device by 30 
degrees. 
Balancing resistors
must be connected in parallel with the two series-connected single converters. 
This is essential to ensure that with low armature currents, or if the armature current = 0, the total 
armature voltage is symmetrically divided between the two individual units. It also enables the 
armature voltage and the EMF to be correctly calculated internally. 
The parameter setting P079 = 2 has the following effect: 
•  The firing pulses of the 12-pulse series slave device are output 30 degrees later than the firing 
pulses of the master device. Long pulses
(pulse duration up to approx. 0.1 ms before next 
pulse) are output every 30 degrees
on the armature gating unit of both devices, to enable 
current to flow if the armature current pulsates. 
•  Precontrol
for the armature current controller is switched over
from 6-pulse operation to 12-
pulse series connection operation. The EMF input value for precontrol (K0122, selection with 
P162, P193) must contain half the “total EMF” of the motor.  
•  P110 and P111 only have an effect on half
the set total motor value. The resistive + inductive 
total armature voltage drop is automatically halved for the internal EMF calculation (K0123, 
K0124, K0287). If the total armature voltage is symmetrically divided between the two 
individual units, then half the total EMF of the motor is calculated. Since the EMF setpoint for 
field weakening control (K0289) is also calculated with half the armature circuit resistance 
P110/2 (K0289 = P101 - P100*P110 / 2), half the actual rated armature voltage of the motor 
must be parameterized at P101. 
The slave device must be disconnected from the line and bridged on the output side in order to 
perform an optimization run for the current controller and precontrol (P051 = 25) on the 12-pulse 
series master device. U800 = 0 must be set on the master device for the duration of the current 
controller and precontrol optimization run. The total armature circuit values P110 and P111 for the 
motor are set correctly after the current controller and precontrol have been optimized. P156 is also 
correct. Only the automatically calculated current controller P gain P155 still needs to be “manually” 
halved. In addition, P826.01 to 06 must be set to 0. 
For details of the 12-pulse series connection, see the description of applications entitled “12-pulse 
operation” (see Section 17). 
SIEMENS AG    6RX1700-0AD76 
10-1 
SIMOREG DC-MASTER    Operating Instructions 
10  Faults and alarms 
When a fault or alarm message is activated, it is displayed both on the simple operator control panel 
(PMU) and on the OP1S user-friendly operator control panel (see also Section 7.2, Operator control 
panels). 
An alarm stops being displayed immediately the cause of the alarm signal has been eliminated. 
A fault message must be cancelled by pressing the P key on the PMU or Reset key on the OP1S 
(panel must be in "Operational display" status) as soon as the cause has been eliminated. 
NOTE 
Setting parameters when fault or alarm message is active 
On the PMU: 
You can shift an active fault message or alarm "to the background" by pressing the P key and 
Higher key simultaneously on the PMU. 
If you do not press any key on the PMU within a 30 s period, the fault message or active alarm in 
the background is automatically displayed again. 
You can fetch a message back to the foreground earlier by pressing the P key and Lower key 
simultaneously on the PMU when the parameter number level is selected. 
On the OP1S: 
You can set parameters normally even if a fault message or alarm is active. 
10-2
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
10.1  Fault messages 
10.1.1  General information about faults 
Fault message display: 
On the PMU:  F (fault) and a three-digit number. The red LED (Fault) lights up. 
On the OP1S: On bottom line of operational display: The red LED (Fault) lights up. 
Only one
current fault message can be displayed at a time, i.e. other simultaneously active faults are 
ignored. 
Many fault messages (see List of Fault Messages) can only be active in certain operating states. 
The system responses to a fault are as follows: 
•  The armature current is reduced, the firing pulses are disabled and the SIMOREG unit switches to 
operating state o11.0 (fault) 
•  Fault message is displayed on the operator panel (PMU, OP1S) 
•  B0106 ( = status word 1, bit 3) is set and B0107 cancelled (see also alarm bits for special faults 
such as undervoltage, overtemperature, external faults, etc.) 
•  The following parameters are refreshed: 
r047  fault diagnostic memory 
(The displayed values are decimal. For bit-serial evaluation, the values must be  
converted from decimal to binary notation, e.g. to be able to determine the  
relevant terminal in the case of F018) 
r049  Fault time 
r947  fault memory, see also r947 in Section 11, Parameter List 
r949  fault value 
(The displayed values are decimal. For bit-serial evaluation, the values must be  
converted from decimal to binary notation, e.g. to be able to determine the  
relevant terminal in the case of F018) 
P952  number of faults 
A text is also displayed for each individual fault in parameter r951 (fault text list). These texts can, for 
example, be displayed on the OP1S. 
If a fault is not acknowledged before the electronics supply voltage is switched off, then fault message 
F040 will be displayed when the supply is next switched on. 
10.1.2  List of fault messages 
NOTE 
Further information about the causes of fault messages 
When a fault message is activated, values providing more information about the fault cause are 
stored in parameter r047. Where the values can be interpreted by the user, they are included in 
the following list of fault messages. 
The value in r047.001 is referred to as the "fault value". This is also stored in r949 which also 
contains the fault values belonging to older fault messages. The values in r047 are overwritten 
when the next fault message occurs. 
Values for r047 which are not included in the list below can help a SIEMENS specialist to locate a 
fault cause. For this reason, all indices of parameter r047 should be read out whenever a fault 
message occurs, even if the meaning of the individual indices of parameter r047 is not specified 
for every fault message listed below. 
Please note: Before you contact SIEMENS with any query regarding a fault message, please 
make a note of the contents of all indices
of parameter r047. 
SIEMENS AG    6RX1700-0AD76 
10-3 
SIMOREG DC-MASTER    Operating Instructions 
Fault 
Description 
No. 
Cause as a function of fault value 
(r047.001, r949.001 or r949.009 with acknowledged error) 
Further information (r047.002 to r047.016) 
10.1.2.1  Supply faults 
F001  Failure of electronics power supply 
(active in all operating states) 
Failure of the electronics supply voltage (terminals 5U1, 5W1, 5N1) in “RUN” state for longer than the “restart” time set in 
parameter P086 or the electronics are operating on undervoltage. 
Possible fault causes: 
♦  Line contactor has opened in “RUN” state 
♦  Brief supply failure 
♦  Supply voltage too low 
Fault value: 
r047 Index 002 to 016: 
Electronics supply voltage in “RUN” has been interrupted 
for longer than setting in P086 
i002  Duration of actual supply failure in 1/10 seconds 
Supply failure prewarning responds periodically 
Supply failure prewarning is active for longer than 1.28 s  - 
F004  Phase failure in armature supply 
(active in operating states of ≤ o4) 
The supply voltage RMS value, calculated from the area of each supply half-wave (rectified average value * peak factor), must be 
greater than the response value for phase failure monitoring 
100%
P353
P078.001 ∗
The distance between two identical supply zero passages of a phase must not exceed 450 degrees. 
If one of these two conditions remains unfulfilled for longer than the “restart time” set in P086, a fault message is activated. 
After switch-on, the converter waits in operating states o4 and o5 together for a period not exceeding the setting in P089 for 
voltage to appear at the power terminals (and for field current) before activating the fault message. 
Possible fault causes: 
♦  Parameter P353 is incorrectly set 
♦  Armature phase has failed 
♦  Line contactor opened in operation 
♦  Fuse has blown on three-phase side in armature circuit 
♦  Fuse has blown in power section 
♦  Interruption in a thyristor firing pulse cable (auxiliary cathodes at connectors X12, X14, X16 are voltage carriers). 
Fault value: 
Voltage failure has occurred in armature supply (1U1, 1V1, 1W1) (when P086=0) 
Delay time set in parameter P089 has expired in operating state o4  
Fuse has blown in power section 
Voltage failure has lasted longer than period set in P086 (if this is >0) 
The "Main contactor checkback" (control word 2 bit 31) [see also P691] did not switch to "1" before the time set in P095 ran 
out, or switched back to "0" during operation [V1.8 and later]. 
10-4
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Fault 
Description 
No. 
Cause as a function of fault value 
(r047.001, r949.001 or r949.009 with acknowledged error) 
Further information (r047.002 to r047.016) 
F005  Fault in the field circuit 
(active in operating states of ≤ o5) 
The line voltage RMS value calculated from the area of each network half-wave (rectification average value 
*
peak factor) must 
be greater than the response value for phase failure monitoring 
100%
P353
P078.002∗
The distance between two identical network zero passages of the voltage for the field converter must not exceed 450 degrees. 
The actual field current K0265 equals < 50% of the required field current setpoint K0268 for more than 500ms. This monitoring 
function is effective only if the field current setpoint corresponds to >2% of the converter rated field current. 
[In SW 1.9 and later, the percentage (50%) and time (500ms) can be altered in P396 and P397 respectively] 
If one of the fault conditions described persists in operation (or ≤ o4) for longer than the “restart” time set in P086, the fault 
message is output. 
After the converter is switched on, it waits in operating state o5 for a period not exceeding the setting in P089 for the field supply 
voltage or sufficiently high field current before this fault message is activated. 
Monitoring for timeout as the field decays or builds up after initiation of field reversal (fault values 6 and 7) is not implemented 
until SW 1.7 and later. 
Possible fault causes 
♦  Threshold for phase failure (P353) set incorrectly 
♦  Undervoltage / overvoltage threshold (P351, P352) set incorrectly 
♦  Field phase failed 
♦  Line contactor opened during operation 
♦  Fuse blown in the field circuit 
♦  Field current controller and/or field current precontrol not optimized or badly optimized (check P112, P253 to P256; possibly 
execute current controller optimization) 
♦  Check P396 (field current monitoring threshold) and P397 (field current monitoring time) 
♦  If the fault value is 6: Offset fault in the actual field current value sensing, relevant parameter: P825.i01-i03 (Offset depends 
on P076.i02) or P394, P395 (Threshold and hysteresis for message I_field < I_field_min) must be checked 
♦  If the fault value is 7: Circuit for the "new" field direction is interrupted (e.g. because the contactor for "new" field direction 
does not pick up), P398, P399 (Threshold and hysteresis for message I_field < I_field_x) must be checked 
Fault value: 
Voltage failure occurred in the field supply (terminals 3U1 and 3W1) (if P086 = 0) 
Delay time according to P089 elapsed in state o5.1. Wait until the voltage and frequency at the field power section are 
within the tolerance range (P351, P352, P353, P363, P364). 
Delay time according to P089 elapsed in state o5.0 
Wait until I
Field act
(K0265) > 50% of the instantaneous field current setpoint K0268 [as of SW 1.9, can be altered by 
means of P396] and until "I 
Field extern
> I 
f min
" (see P265) 
After P086 > 0 has elapsed (time for automatic restart) in operating state ≤ o4: 
Voltage failure in the field supply or  
I
Field act 
(K0265) < 50% I
Field set 
(K0268) for longer than 500 ms [as of SW 1.9, can be altered by means of P396 or 
P397]  
or "I 
Field extern
> I 
f min
" (see P265) 
When P086 = 0 (no automatic restart) in operating state ≤ o4: 
I
Field act 
(K0265) < 50% I
Field set 
(K0268) for longer than 500 ms [as of SW 1.9, can be altered by means of P396 or 
P397]  
or "I 
Field extern
> I 
f min
" (see P265) 
If field reduction before field reversal, I_field ≤ I_field_min (P394) is not reached within 30 s  
If field build-up after field reversal, I_field > I_field_x (P398) is not reached within 30 s  