SIMOREG DC-MASTER    Operating Instructions 
Fault 
Description 
No. 
Cause as a function of fault value 
(r047.001, r949.001 or r949.009 with acknowledged error) 
Further information (r047.002 to r047.016) 
F006  Undervoltage 
(active in operating states of ≤ o4) 
The voltage across terminals 1U1, 1V1 or 1W1 and 3U1, 3W1 was lower than the response threshold for longer than the "restart 
time" set at P086 and the delay time according to P361 has expired. 
Response threshold for armature supply voltage: 
)
100%
P351
(1
P078.001
∗ +
Response threshold for field supply voltage: 
)
100%
P351
(1
P078.002
∗ +
Possible fault causes 
♦  Line undervoltage 
♦  Monitoring values set too sensitively or incorrectly (P351, P078) 
Fault value: 
r047 Index 002 to 016: 
Undervoltage has occurred (when P086=0) 
i002  Number of phase that has activated fault message 
0...Phase UV 
1...Phase VW 
2...Phase WU 
3...Phase field 
i003  Incorrect voltage value (normalized to 16384) 
Undervoltage persists for longer than time set in 
parameter P086 (if this is set to >0)  
F007  Overvoltage 
(active in operating states of ≤ o4) 
The voltage across terminals 1U1, 1V1 or 1W1 and 3U1, 3W1 was higher than the response threshold for longer than the "restart 
time" set at P086 and the delay time according to P362 has expired. 
Response threshold for armature supply voltage: 
)
100%
P352
(1
P078.001
∗ +
Response threshold for field supply voltage: 
)
100%
P352
(1
P078.002
∗ +
Possible fault causes 
♦  Line overvoltage 
♦  Monitoring values set too sensitively or incorrectly (P352, P078) 
NOTICE
This monitoring function is deactivated in the delivery state. It can be activated via parameter P820. 
Fault value: 
r047 Index 002 to 016: 
Overvoltage has occurred 
002  Number of phase that has activated fault message 
0...Phase UV 
1...Phase VW 
2...Phase WU 
3...Phase field 
i003  Incorrect voltage value (normalized to 16384) 
Undervoltage persists for longer than time set in 
parameter P086 (if this is >0)  
F008  Line frequency less than the minimum line frequency acc. to parameter P363 
(active in operating states of ≤ o5) 
This fault message is activated if the line frequency is less than the minimum line frequency (for longer than the “restart time” set 
in parameter P086). 
Note:
Up to software version 1.7 the threshold for activation of the fault message (minimum line frequency) is 45Hz.  
Adding images to pdf - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
add an image to a pdf; add jpg to pdf form
Adding images to pdf - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
add image to pdf preview; adding images to pdf files
10-6
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Fault 
Description 
No. 
Cause as a function of fault value 
(r047.001, r949.001 or r949.009 with acknowledged error) 
Further information (r047.002 to r047.016) 
Fault value: 
Frequency of the armature supply < minimum line frequency 
Frequency of the field supply < minimum line frequency 
Line frequency less than the minimum line frequency for longer than set in parameter P086 (if >0) 
F009  Line frequency greater than the maximum line frequency acc. to parameter P364 
(active in operating states of ≤ o5) 
This fault message is activated if the line frequency is greater than the maximum line frequency (for longer than the “restart time” 
set in parameter P086). 
Note:
Up to software version 1.7 the threshold for activation of the fault message (maximum line frequency) is 65Hz 
Fault value: 
Frequency of the armature supply > maximum line frequency 
Frequency of the field supply > maximum line frequency 
Line frequency greater than the maximum line frequency for longer than set in parameter P086 (if >0) 
10.1.2.2  Interface error 
F011  Telegram failure at GSST1 
when P780 = 2
USS telegram failure at G-SST1 
(active from the first receipt of a valid protocol in all operating states) 
After the receipt of the first valid protocol, no further telegrams have been received within the time period set in parameter P787. 
Possible fault causes 
♦  Cable break 
♦  Error in USS master 
F012  Telegram failure at GSST2 
when P790 = 2
USS telegram failure at G-SST2 
(active from the first receipt of a valid protocol in all operating states) 
After the receipt of the first valid protocol, no further telegrams have been received within the time period set in parameter P797. 
Possible fault causes 
♦  Cable break 
♦  Error in USS master 
when P790 = 4 or 5
Peer-to-peer telegram failure at G-SST2 
(active in operating states of ≤ o6) 
After the receipt of the first valid protocol, no further telegrams have been received within the time period set in parameter P797. 
Possible fault causes 
♦  Interruption in connecting cable 
♦  EMC interference on connecting cable 
♦  P797 is set too low 
VB.NET PDF Library SDK to view, edit, convert, process PDF file
Feel free to define text or images on PDF document and extract accordingly. Capable of adding PDF file navigation features to your VB.NET program.
adding an image to a pdf file; adding images to pdf forms
VB.NET PDF Page Insert Library: insert pages into PDF file in vb.
Support adding PDF page number. Offer PDF page break inserting function. DLLs for Adding Page into PDF Document in VB.NET Class. Add necessary references:
how to add image to pdf; add png to pdf acrobat
SIEMENS AG    6RX1700-0AD76 
10-7 
SIMOREG DC-MASTER    Operating Instructions 
Fault 
Description 
No. 
Cause as a function of fault value 
(r047.001, r949.001 or r949.009 with acknowledged error) 
Further information (r047.002 to r047.016) 
F013  Telegram failure at GSST3 
when P800 = 2
USS telegram failure to G-SST3 
(active from the first receipt of a valid protocol in all operating states) 
After the receipt of the first valid protocol, no further telegrams have been received within the time period set in parameter P807. 
Possible fault causes 
♦  Cable break 
♦  Error in USS master 
when P800 = 4 or 5
Peer-to-peer telegram failure at G-SST3 
(active in operating states of ≤ o6) 
After the receipt of the first valid protocol, no further telegrams have been received within the time period set in parameter P807. 
Possible fault causes 
♦  Interruption in connecting cable 
♦  EMC interference on connecting cable 
♦  P807 is set too low 
F014  Telegram failure at paralleling interface 
(active when U800 = 1 or 2
from the first receipt of a valid protocol in all operating states) 
After the receipt of the first valid protocol, no further telegrams have been received within the time period set in parameter U807. 
Possible fault causes 
♦  Interruption in connecting cable 
♦  EMC interference on connecting cable 
♦  U807 is set too low 
F015  Telegram failure on one SIMOLINK board 
(active when U741 > 0 
as soon as the first valid telegram is received) 
After receipt of one valid telegram, no further valid telegrams have arrived within the period set in parameter U741. 
Possible fault causes 
♦  Break in connecting cable 
♦  Parameter setting change during telegram exchange (for parameters see Section 11 "Configuration of SIMOLINK board) 
♦  U741 is set to low 
Fault value: 
1   Telegram failure on 1
st
SLB 
2   Reserved 
F016  Hardware fault on expansion board EB1 
Fault value: 
Fault on first EB1 
Fault on second EB1 
F017  Hardware fault on expansion board EB2 
Fault value: 
Fault on first EB2 
Fault on second EB2 
C# PDF Page Insert Library: insert pages into PDF file in C#.net
By using reliable APIs, C# programmers are capable of adding and inserting (empty) PDF page or pages from various file formats, such as PDF, Tiff, Word, Excel
adding images to a pdf document; add multiple jpg to pdf
C# PDF insert text Library: insert text into PDF content in C#.net
Supports adding text to PDF in preview without adobe reader installed in ASP.NET. Powerful .NET PDF edit control allows modify existing scanned PDF text.
add an image to a pdf in preview; add photo to pdf online
10-8
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Fault 
Description 
No. 
Cause as a function of fault value 
(r047.001, r949.001 or r949.009 with acknowledged error) 
Further information (r047.002 to r047.016) 
F018  Short circuit or overloading of binary outputs 
(active in all operating states) 
Possible fault causes 
♦  Short circuit or overload at terminals 46, 48, 50 or 52 and 26 or 34 
Fault value: 
r047 Index 002 to 016: 
Short circuit or overload at binary outputs 
i002  Bit 8 = 1:  Overload at terminal 46 
Bit 9 = 1:  Overload at terminal 48 
Bit 10 = 1:  Overload at terminal 50 
Bit 11 = 1:  Overload at terminal 52 
Bit 12 = 1:  Overload at terminal 26 (15 V output) 
Bit 13 = 1:  Overload at terminal 34, 44 and/or 210 
(24 V output) 
NOTICE
This monitoring function is deactivated in the delivery state. It can be activated via parameter P820. 
10.1.2.3  External faults 
Fault message from free function block FB286
(active in all operating states) 
Fault value: 
F019 
the binector wired via parameter U100 Index.005 is in the state log.”1” 
the binector wired via parameter U100 Index.006 is in the state log.”1” 
the binector wired via parameter U100 Index.007 is in the state log.”1” 
the binector wired via parameter U100 Index.008 is in the state log.”1” 
Fault message from free function block FB287
(active in all operating states) 
Fault value: 
F020 
the binector wired via parameter U101 Index.005 is in the state log.”1” 
the binector wired via parameter U101 Index.006 is in the state log.”1” 
the binector wired via parameter U101 Index.007 is in the state log.”1” 
the binector wired via parameter U101 Index.008 is in the state log.”1” 
F021  External fault 1 
(active in all operating states) 
Bit 15 in control word 1 was in the log. "0" state for longer than the time set in P360 index 001 
F022  External fault 2 
(active in all operating states) 
Bit 26 in control word 2 was in the log. "0" state for longer than the time set in P360 index 002 
Fault message from free function block FB2
(active in all operating states) 
Fault value: 
F023 
the binector wired via parameter U100 Index.001 is in the state log.”1” 
the binector wired via parameter U100 Index.002 is in the state log.”1” 
the binector wired via parameter U100 Index.003 is in the state log.”1” 
the binector wired via parameter U100 Index.004 is in the state log.”1” 
Fault message from free function block FB3
(active in all operating states) 
Fault value: 
F024 
the binector wired via parameter U101 Index.001 is in the state log.”1” 
the binector wired via parameter U101 Index.002 is in the state log.”1” 
the binector wired via parameter U101 Index.003 is in the state log.”1” 
the binector wired via parameter U101 Index.004 is in the state log.”1” 
VB.NET Image: How to Draw Annotation on Doc Images with Image SDK
to mark and annotate your local images (such as page TIFF, Microsoft Office Word and PDF file other image annotating tutorials besides adding annotation using VB
add jpg to pdf acrobat; add jpeg to pdf
VB.NET Image: Adding Line Annotation to Images with VB.NET Doc
NET full sample codes for printing line annotation on images. VB.NET Image Line Annotation Overview. Mature image processing library for adding line annotation
add image pdf; add image in pdf using java
SIEMENS AG    6RX1700-0AD76 
10-9 
SIMOREG DC-MASTER    Operating Instructions 
Fault 
Description 
No. 
Cause as a function of fault value 
(r047.001, r949.001 or r949.009 with acknowledged error) 
Further information (r047.002 to r047.016) 
10.1.2.4  Fault messages from motor sensors 
F025  Brush length too short 
(active in operating states of ≤ o3) 
When parameter P495=2 (binary sensing of brush length), fault message at log.”0” signal (longer than 10s) at terminal 211 
Possible fault causes 
♦  Encoder for brush length has responded 
♦  Open circuit in encoder cable 
F026  Bearings in bad condition 
(active in operating states of ≤ o6) 
When parameter P496=2 (bearing condition sensing) fault message at log. “1” signal (longer than 2 s) at terminal 212 
Possible fault causes 
♦  Encoder for bearing condition has responded 
F027  Air-flow monitoring of motor fan
(active in operating states of < o6) 
When parameter P497=2 (air-flow monitoring), fault message at log ”0” signal (longer than 40s) at terminal 213 
Possible fault causes 
♦  Encoder for fan monitoring has responded  
♦  Open circuit in encoder cable 
F028  Motor overtemperature 
(active in operating states of ≤ o6) 
When parameter P498=2 (thermostat connected), fault message at log. “0” signal (longer than 10s) at terminal 214 
Possible fault causes 
♦  Thermostat for monitoring motor temperature has responded 
♦  Open circuit in encoder cable 
F029  Motor overtemperature 
(active in all operating states) 
Select via 
P493=2 or 3 (temperature sensor at terminals 22 / 23) or 
P494=2 or 3 (temperature sensor at terminals 204 / 205) 
When parameter P490.01=1 (KTY84 at terminals 22 / 23) or P490.02=1 (KTY84 at terminals 204 / 205):
The fault message is activated if the motor temperature reaches or exceeds the value set in parameter P492. 
When parameter P490.01=2, 3, 4 or 5 (PTC thermistor at terminals 22 / 23) or P490.02=2, 3, 4 or 5 (PTC thermistor at terminals 
204/ 205):
The fault message is activated if the motor temperature reaches or exceeds the response value of the selected PTC thermistor. 
Fault value: 
Fault activation through temperature sensor at terminals 22 / 23 
Fault activation through temperature sensor at terminals 204 / 205 
10.1.2.5  Drive faults 
NOTICE
The monitoring functions F031, F035, F036, and F037 are deactivated in the delivery state.  
They can be activated via parameter P820.  
F030  Commutation failure or overcurrent has occurred or test command has been issued via U583 
(active in all operating states) 
Possible error causes 
•  Mains voltage dip in regenerative feedback mode 
•  Current control loop not optimized 
Fault value: 
r047 Index 002 to 016: 
The blocking voltage time area for the commutating 
thyristor pair was too small 
The current crest curve breaks upwards 
for i001= 1 to 3 and 5, i002 to i006 are valid 
for i001= 4, i002 to i015 is invalid 
C# PDF Library SDK to view, edit, convert, process PDF file for C#
Support protecting PDF file by adding password and digital signatures with C# sample code in .NET Class. Feel free to define text or images on PDF document and
how to add image to pdf in preview; how to add an image to a pdf file in acrobat
VB.NET PDF insert text library: insert text into PDF content in vb
VB.NET PDF - Insert Text to PDF Document in VB.NET. Providing Demo Code for Adding and Inserting Text to PDF File Page in VB.NET Program.
add jpeg signature to pdf; how to add image to pdf file
10-10
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Fault 
Description 
No. 
Cause as a function of fault value 
(r047.001, r949.001 or r949.009 with acknowledged error) 
Further information (r047.002 to r047.016) 
The maximum current value was higher than 250% of the 
actual rated device current according to r072i002 
i002  Delay angle (K0100) in case of error 
i003  Actual EMF (K0287) in case of error 
i004  Trigger circuitry diagnostics (K0989) in case of error 
i005  Actual field current (K0265) in case of error 
i006  Number of pulses (K0105) in case of error 
A paralleled SIMOREG DC-MASTER has detected a 
commutation failure or overcurrent 
test command has been issued via U583 
F031  Speed controller monitoring 
(active in operating states of  – –, I, II) 
The monitor responds when the difference between the connectors selected in P590 and P591 (factory setting: Setpoint/actual 
value difference of speed controller) exceeds the limit set in parameter P388 for longer than the time set in parameter P390. 
Possible fault causes 
•  Open control loop 
•  Controller not optimized 
•  P590 or P591 is not correctly parameterized 
F032  SIMOREG CCP not ready 
(active in operating states of  < o4.0)  
Possible error causes 
•  No connection or cable break at X172 (G-SST2) 
•  No connection or cable break at X165 (paralleling interface master) in a parallel connection 
•  No connection or cable break at X29_PAR or X30_PAR (extinction-pulse interface) in a parallel connection 
•  Hardware defective in charging circuit of extinguishing capacitors 
•  Blown fuse in the line-side or motor-side armature circuit 
•  Blown fuse in the precharging circuit for the chopper capacitors 
•  Required cooling phase for chopper resistors still in progress 
•  MLFB (order number) data of the SIMOREG CCP (n570, n571, n572) are invalid or nonexistent 
Fault value: 
r047 Index 002 to 016: 
No voltage at U, V, W terminals of SIMOREG CCP 
Voltage at C-D on CCP does not match voltage at C-D on 
SIMOREG DC-MASTER 
Surge absorbing capacitors of SIMOREG CCP have not 
reached setpoint voltage 
Paralleling interface cable is not connected to SIMOREG 
CCP assigned to paralleling master 
No connection between SIMOREG DC-MASTER and 
SIMOREG CCP via G-SST2 serial interface 
(r799.i001 is not incremented) 
No connection between parallel SIMOREG CCPs 
Contents of technical data memory on SIMOREG CCP 
(MLFB, rated values, serial number) invalid 
11  I2t value (n575) of voltage chopper 1 is too high (> 100%)
12  I2t value (n576) of voltage chopper 2 is too high (> 50%) 
20  Chopper capacitors not completely precharged in time 
set with P089 or the condition in accordance with fault 
value 5 is satisfied 
for i001= 1 to 12, i002 to i006 are valid 
for i001= 20, only i002 is valid 
i002  SIMOREG CCP status (K0574) in case of error 
i003  I2t value of chopper 1 (K0575) in case of error 
i004  I2t value of chopper 2 (K0576) in case of error 
i005  Actual armature voltage (r038) in case of error in 0.1 V  
for i005 > 32767: U
ARMATURE
[V] = (65536-r047i005)/10 
i006  effective time until the fault initiation in 20 ms 
10.1.2.6  External faults 
Fault message from free function block FB4
(active in all operating states) 
Fault value: 
F033 
the binector wired via parameter U102 Index.001 is in the state log.”1” 
the binector wired via parameter U102 Index.002 is in the state log.”1” 
the binector wired via parameter U102 Index.003 is in the state log.”1” 
the binector wired via parameter U102 Index.004 is in the state log.”1” 
F034  Fault message from free function block FB5
(active in all operating states) 
Fault value: 
C# PDF Annotate Library: Draw, edit PDF annotation, markups in C#.
Provide users with examples for adding text box to PDF and edit font size and color in text box field in C#.NET program. C#.NET: Draw Markups on PDF File.
add an image to a pdf in preview; add jpg to pdf document
SIEMENS AG    6RX1700-0AD76 
10-11 
SIMOREG DC-MASTER    Operating Instructions 
Fault 
Description 
No. 
Cause as a function of fault value 
(r047.001, r949.001 or r949.009 with acknowledged error) 
Further information (r047.002 to r047.016) 
the binector wired via parameter U103 Index.001 is in the state log.”1” 
the binector wired via parameter U103 Index.002 is in the state log.”1” 
the binector wired via parameter U103 Index.003 is in the state log.”1” 
the binector wired via parameter U103 Index.004 is in the state log.”1” 
10.1.2.7  Drive faults 
F035  Drive is blocked 
(active in operating states of  – –, I, II) 
This monitoring function responds if the following conditions are fulfilled for longer than the period set in parameter P355: 
♦  Positive or negative torque or armature current limit 
♦  The armature current is higher than 1% of the converter rated armature DC current 
♦  The actual speed is less than 0.4% of maximum speed 
Possible fault causes 
♦  Drive is blocked 
F036  No armature current is flowing 
(active in operating states of  – –, I, II) 
This monitoring function responds if the armature firing angle is at the rectifier stability limit for more than 500 ms and the 
armature current is less than 1% of the converter rated armature DC current. 
Possible fault causes 
♦  Armature circuit is open 
(e.g. DC fuses have blown, open circuit, etc.) 
♦  Rectifier stability limit α
G
(P150) is incorrectly set 
♦  Drive is operating at α
G
limit (e.g. due to supply undervoltage) 
♦  EMF is too high because maximum speed setting is too high, 
refer to P083, P115, P143, P741) 
♦  EMF is too high because field weakening is not selected (refer to P082) 
♦  EMF is too high because field current is set too high (refer to P102) 
♦  EMF is too high because transition speed for field weakening is set too high (refer to P101) ?? 
F037  I
2
t motor monitor has responded 
(active in operating states of  – –, I, II) 
This monitoring function responds when an I
2
t value is reached which corresponds to the final temperature at 110% of the rated 
motor armature current. 
Possible fault causes 
♦  Parameter P114 is incorrectly set 
♦  Drive has been operating for too long at >110% of rated motor armature current 
F038  Overspeed 
(active in operating states of  – –, I, II) 
This fault message is activated if the actual speed value (selected in P595) exceeds the positive (P380) or negative (P381) 
threshold by 0.5%. 
Possible fault causes 
♦  Lower current limit has been input 
♦  Current-controlled operation 
♦  P512, P513 are set too low 
♦  Tachometer cable contact fault in operation close to maximum speed 
F039  I
2
t power section monitor has responded 
(active in operating states of  – –, I, II) 
This monitoring function responds if the calculated I
2
t value of the power section reaches the permissible value for the power 
section concerned (see also P075). 
Possible fault causes 
♦  Drive has been operating at overload for too long 
♦  Parameter P075 is incorrectly set 
♦  Parameter P077 is incorrectly set 
10-12
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Fault 
Description 
No. 
Cause as a function of fault value 
(r047.001, r949.001 or r949.009 with acknowledged error) 
Further information (r047.002 to r047.016) 
F040  Electronics supply disconnected in active fault status 
(active in all operating states) 
This fault message is activated if the electronics power supply has been disconnected, even though a fault was displayed and not 
yet acknowledged. 
Possible fault causes 
♦  Not all fault messages have been acknowledged 
Fault value: 
Last active fault message 
F041  Ambiguous selection of parameter set or ramp-function generator 
(active in all operating states) 
♦  While an optimization run is in progress, the function data set selection must not be changed. Fault F041 is displayed if 
another, different function data set is selected while an optimization run is being executed. 
♦  Check whether ramp-function generator parameter set 1 or 2 or 3 (parameters P303 to P314) is clearly selected. If parameter 
sets 2 and 3 are selected simultaneously for more than 0.5s, then fault message F041 is displayed. While the parameter set 
selection is ambiguous, the system continues to apply the last clearly identified ramp-function generator parameters. 
Possible fault causes 
♦  P676 or P677 (selection of binectors which determine the active function data set in control word 2, bits 16 and 17) is 
incorrectly set 
♦  P637 or P638 (selection of binectors which determine ramp-function generator setting) is incorrectly set 
Fault value: 
The selection of the function data set has been changed during an optimization run 
Ambiguous selection of ramp-function generator parameter set 
F042  Tachometer fault 
(active in operating states of  – –, I, II) 
A check is performed every 20ms to ensure that    
(K0287)
 EMF
Actual
(K0179)
speed
Actual
is > +5%  
If the check result is incorrect for 4 times in succession, the fault message is activated. 
The following rule applies: 
100% actual speed 
= maximum speed 
100% actual EMF 
= ideal average DC voltage at 
α
≥ 0, i.e. when the thyristor bridge is fully gated 
The ideal DC voltage average value at 
α
= 0 is 
π
2
3
P078.001
The monitoring function is effective only if the EMF > a % of 
π
2
3
P078.001
"a" is a percentage that can be set in parameter P357 (default setting 10%). 
The monitoring function is effective only if the armature current is > 2% of the converter rated DC current set in r072.002. 
Possible fault causes 
♦  Open circuit in tachometer or pulse encoder cable. 
♦  Tachometer of pulse encoder cable incorrectly connected. 
♦  Pulse encoder supply has failed. 
♦  Polarity for actual speed value (P743) is incorrectly set. 
♦  Armature circuit data (P110 und P111) are incorrectly set (execute current controller optimization run). 
♦  Tachometer or pulse encoder defective 
♦  Pulse encoder supply voltage is incorrectly set (P140) 
♦  The field polarity is not reversed by the external hardware when the field is reversed. 
Fault value: 
r047 Index 002 to 016: 
Open circuit in tachometer or pulse encoder cable 
i002  Actual speed value (K0179) in case of fault 
Polarity of tachometer or pulse encoder is incorrect 
i003  Actual EMF value (K0287) in case of fault 
SIEMENS AG    6RX1700-0AD76 
10-13 
SIMOREG DC-MASTER    Operating Instructions 
Fault 
Description 
No. 
Cause as a function of fault value 
(r047.001, r949.001 or r949.009 with acknowledged error) 
Further information (r047.002 to r047.016) 
F043  EMF too high for braking operation 
(active in operating states of  – –, I, II) 
This fault message is activated if the following 5 conditions are fulfilled when a torque direction reversal is requested
(selection of 
MI or MII): 
♦  P272=0 (fault message is parameterized and not alarm + field weakening) 
♦  A parameterized, additional, torque-free interval (P160 ≠ 0) has expired 
♦  Parallel drive is ready for engagement of the new torque direction 
♦  The absolute value of the armature current  (K0118, filtered with P190) 
requested in the new torque direction is >1% of 
P072.002
♦  The calculated firing angle (K0101)
for the armature current requested for the new torque direction is >165 degrees
or >P151 
when P192=1 
Possible fault causes 
♦  No “speed-dependent field weakening" (P081=0) is parameterized even though operation in the field weakening range is 
needed for the requested maximum speed 
Note: 
In motor operation, it is possible to reach EMF values corresponding to the peak of the phase-to-phase supply voltage at a 
firing angle of α
G
=30° (rectifier stability limit P150) and low armature currents. 
♦  Setpoint EMF for field weakening operation too high (parameter P101 is set too high) 
♦  Supply voltage dip 
♦  EMF controller or field current controller is not optimized, possibly resulting in excessive EMF on power-up. 
Fault value: 
r047 Index 002 to 016: 
Calculated firing angle (armature) before limitation (K0101) 
i002  Instantaneously measured actual EMF (K0287) 
i003  Armature current controller setpoint (K0118) 
F044  A slave connected to the paralleling interface is not operating 
(active when U800 = 1 or 2 and U806>10 (master)
after receipt of the first valid protocol in operating states  – –, I, II) 
Fault value: 
r047 Index 002 to 006: 
A fault message is active on a slave 
A slave is not in operation (e.g. because its enable input 
is set to "0") 
i00x  = Status word 1 from slave x 
F046  Analog select input for main setpoint (terminals 4 and 5) faulty 
(active in operating states of ≤ o6) 
This fault message is activated when P700=2 (current input 4 to 20 mA) and an input current of less than 2mA is flowing. 
Possible fault causes 
♦  Open circuit in supply cable 
♦  P700 is incorrectly set 
F047  Analog select input 1 (terminals 6 and 7) is faulty 
(active in operating states of ≤ o6) 
This fault message is activated when P710=2 (current input 4 to 20 mA) and an input current of less than 2mA is flowing. 
Possible fault causes 
♦  Open circuit in supply cable 
♦  P710 is incorrectly set 
10-14
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Fault 
Description 
No. 
Cause as a function of fault value 
(r047.001, r949.001 or r949.009 with acknowledged error) 
Further information (r047.002 to r047.016) 
F048  Fault in measuring channel for digital speed sensing using pulse encoder 
(active in all operating states) 
1. Disturbances on encoder cables:
Faults on the encoder cables (transitions to 0 with a 1 signal or to 1 with a 0 signal) are signalled as a rotational direction change 
by the evaluation circuit. Frequent changes in rotational direction can occur only at speeds around 0. 
The fault message is activated if 10 consecutive pulse encoder signal evaluations identify “direction of rotation change” at a 
speed of ≥ 48 rev/min and an EMF > threshold (see below). 
2. Pulse encoder defective:
The fault message is activated if, at an EMF > threshold (see below) 10 consecutive pulse encoder signal evaluations identify 
“implausible characteristics” of these signals (i.e. frequent rotational direction changes, edges too close together, failure of an 
encoder cable or short circuit between two encoder cables). 
Possible fault causes 
♦  EMC-related interference on a pulse encoder signal (terminals 28 to 31) 
♦  Pulse encoder defective 
♦  Interruption in an encoder cable 
♦  Short circuit between an encoder cable and the supply voltage or another encoder cable 
♦  P110 or P111 is incorrectly set (resulting in incorrectly calculation of EMF) 
Note: 
When the speed encoder is operating correctly, signal sequences, which are characteristic of a faulty pulse encoder or 
disturbances on the pulse encoder cables, may occur continuously at the input terminals (e.g. continuous changes in rotational 
direction or short pulse intervals) at about 0 speed, e.g. as the result of slight oscillation around a bright/dark transition on the 
speed encoder disk). 
For this reason, fault F048 is not activated until the EMF > 10% of 
π
2
3
P078.001
Fault value: 
Disturbances on encoder cables 
Defective pulse encoder 
10.1.2.8  Start-up faults 
F050  Optimization run not possible 
(active in all operating states) 
A fault has occurred during an optimization run. 
NOTE
The contents of r047, Index 002 to 016, can provide specialists with more detailed information about fault causes. For this 
reason, please read out and document all the indices associated with this fault and pass them on when you contact Siemens for 
help. 
Fault value: 
Armature current is too low when α=30° and EMF=0.  
(average armature current <75% of I
A, motor
or <75% of I
A, rated
Possible cause: 
•  Armature circuit interrupted 
•  High-resistance load 
•  P150 (Alpha G limit) has been set to excessively high value 
It was not possible to determine the armature circuit resistance (P110) because the armature current was ≥ 37.5 % of P100 
in fewer than 20 of the 150 firing cycles of the measuring phase. 
Possible cause: 
•Armature current of 37.5% of P100 (I
A, motor
) is no longer possible (although a current of 75% of P100 was already 
flowing, maybe a fuse has blown). 
Armature current peaks are too small at α=30° and EMF=0 
(armature current peak value <50% of I
A, motor
or <50% of I
A,rated
Possible cause: 
•  Armature circuit inductance is too high (field supply from armature terminals) 
•  P150 (Alpha G limit) has been set to excessively high value 
Possible remedy: 
•  Reduce P100 (I
A,motor
) while this optimization run is in progress 