SIEMENS AG    6RX1700-0AD76 
10-25 
SIMOREG DC-MASTER    Operating Instructions 
Fault 
Description 
No. 
Cause as a function of fault value 
(r047.001, r949.001 or r949.009 with acknowledged error) 
Further information (r047.002 to r047.016) 
Fault value: 
12  No connection to slave 1 
22  No connection to slave 2 
F073  SCB1: Current below 4mA minimum value at analog input1 of slave 1 
(active in all operating states) 
The cause of the fault may be a cable break 
F074  SCB1: Current below 4mA minimum value at analog input2 of slave 1 
(active in all operating states) 
The cause of the fault may be a cable break 
F075  SCB1: Current below 4mA minimum value at analog input3 of slave 1 
(active in all operating states) 
The cause of the fault may be a cable break 
F076  SCB1: Current below 4mA minimum value at analog input1 of slave 2 
(active in all operating states) 
The cause of the fault may be a cable break 
F077  SCB1: Current below 4mA minimum value at analog input2 of slave 2 
(active in all operating states) 
The cause of the fault may be a cable break 
F078  SCB1: Current below 4mA minimum value at analog input3 of slave 2 
(active in all operating states) 
The cause of the fault may be a cable break 
F079  SCB1: Telegram failure 
(active in all operating states) 
Check function of SCB1 (activity LEDs) and connection to SCI slaves (fiber optics) 
F080  Error in initialization of a CB/TB board 
Possible causes for fault values 1 and 6: 
♦  CB/TB board is defective 
♦  CB/TB board is not installed correctly 
♦  CB/TB board is taking too long to run up (e.g. due to very complex TB configuration) 
Fault value (r949 index 001): 
r047 index 002 to 016: 
The "Heartbeat counter“ of the CB/TB has not started to 
count within 20 s 
i015  Code number of board: 
TB or 1
st
CB 
2
nd
CB 
The product version of the installed CT/TB board is not 
compatible with the SIMOREG 6RA70 converter 
i002  Code number of slot containing incompatible board: 
Slot D 
Slot E 
Slot F 
Slot G 
CB when configuration includes TB 
Parameters P918, U711 to U721 are not correctly set or 
not accepted after a change by means of U710 = 0 
setting. (The meanings of these parameters are defined 
in the manual for the relevant CB board, see also function 
diagrams, Section 8, Sheets Z110 and Z111) 
i015  Code number of board: 
TB or 1
st
CB 
2
nd
CB 
The initialization run for a CB/TB board has not been 
completed within 40 s 
i015  Code number of board: 
TB or 1
st
CB 
2
nd
CB 
F081  CB/TB heartbeat error 
CB/TB has not incremented the monitoring counter for a period 
of 800 ms 
Possible causes of fault 
♦  CB/TB board is defective 
•  CB/TB board is not correctly installed 
i015  Code number of board: 
TB or 1
st
CB 
2
nd
CB 
Acrobat add image to pdf - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
add an image to a pdf acrobat; adding images to pdf files
Acrobat add image to pdf - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
adding an image to a pdf; adding images to a pdf document
10-26
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Fault 
Description 
No. 
Cause as a function of fault value 
(r047.001, r949.001 or r949.009 with acknowledged error) 
Further information (r047.002 to r047.016) 
F082  CB/TB message timeout or error in data exchange 
Possible causes of fault 
♦  CB/TB PZD message timeout (with fault value 10) 
♦  Excessive EMC-related interference 
(e.g. due to unprotected contactors, unscreened cables, loose screen connections) 
♦  CB/TB board is defective 
♦  CB/TB board is not correctly inserted 
Fault value (r949 index 001): 
r047 Index 002 to 016: 
Fault in alarm channel from CB to basic unit 
i015  Code number of board: 
TB or 1
st
CB 
2
nd
CB 
Fault in alarm channel from TB to basic unit 
Fault in fault channel from TB to basic unit 
Fault in parameter job channel from CB to basic unit 
i015  Code number of board: 
TB or 1
st
CB 
2
nd
CB 
Fault in parameter response channel from basic unit to 
CB 
i015  Code number of board: 
1
st
TB or 1
st
CB 
2
nd
CB 
Fault in parameter job channel from TB to basic unit 
Fault in parameter response channel from basic unit to 
TB 
10  CB/TB process data failure (message timeout period set 
in U722) 
i015  Code number of board: 
TB or 1
st
CB 
2
nd
CB 
11  Fault in parameter job channel from PMU to TB 
12  Fault in parameter response channel from TB to PMU 
15  Fault in setpoint channel from CB/TB to basic unit 
i015  Code number of board: 
TB or 1
st
CB 
2
nd
CB 
16  Fault in actual value channel from basic unit to CB/TB 
i015  Code number of board: 
TB or 1
st
CB 
2
nd
CB 
10.1.2.14  Fault messages from supplementary boards 
F101 
to 
F147 
This group of fault messages is activated by supplementary boards 
Please refer to the operating manual of the relevant supplementary board for explanation of the fault messages and fault values 
.NET PDF Document Viewing, Annotation, Conversion & Processing
Convert image files to PDF. File & Page Process. Annotate & Comment. Add, insert PDF native annotations to PDF file. Support for all the print modes in Acrobat PDF
add a picture to a pdf document; add jpg signature to pdf
C# PDF Converter Library SDK to convert PDF to other file formats
without using other external third-party dependencies like Adobe Acrobat. you can easily perform file conversion from PDF document to image or document
how to add a jpg to a pdf; add a picture to a pdf
SIEMENS AG    6RX1700-0AD76 
10-27 
SIMOREG DC-MASTER    Operating Instructions 
10.2  Alarm messages 
Alarm message display: 
On the PMU:  A (Alarm) and a three-digit number. The red LED (Fault) flashes. 
On the OP1S:  On the bottom line of the operational display. The red LED (Fault) flashes. 
An alarm message cannot be acknowledged, but disappears automatically when the cause has been 
eliminated. 
Several alarm messages can be active at the same time, these are then displayed in succession. 
Many alarms (see List of Alarm Messages) can only be active in certain operating states. 
The system responses to an alarm are as follows: 
•  Alarm message is displayed on the operator panel (PMU, OP1S) 
•  B0114 ( = status word 1, bit 7) is set and B0115 is cancelled 
(see also special alarm bits in status word 2, e.g. for an external alarm, overload, etc.) 
•  The corresponding bit in one of the alarm words r953 (K9801) to r960 (K9808) is set 
Alarm 
No. 
Description 
A015 
Simolink start 
(active in all operating states) 
Although the board has been initialized, it cannot yet exchange telegrams (parameters have not yet been correctly configured on 
all nodes or the boards have not yet been linked via fiber optics to form a closed ring).  
A018 
Short circuit at binary outputs 
(active in all operating states) 
Hardware monitoring function to check for short circuit at one of the binary select outputs (see also F018 and r011). 
A019 
Alarm message from free function block FB256
(active in all operating states) 
The binector wired via parameter U104 Index.002 is in the state log.”1” 
A020 
Alarm message from free function block FB257
(active in all operating states) 
The binector wired via parameter U105 Index.002 is in the state log.”1” 
A021 
External alarm 1 
(active in all operating states) 
Bit 28 in control word 2 was in the log. "0" state for longer than the time set in P360 index 003. 
A022 
External alarm 2 
(active in all operating states) 
Bit 29 in control word 2 was in the log. "0" state for longer than the time set in P360 index 004. 
A023 
Alarm message from free function block FB6
(active in all operating states) 
The binector wired via parameter U104 Index.001 is in the state log.”1” 
A024 
Alarm message from free function block FB7
(active in all operating states) 
The binector wired via parameter U105 Index.001 is in the state log.”1” 
C# Windows Viewer - Image and Document Conversion & Rendering in
without using other external third-party dependencies like Adobe Acrobat. Image and Document Conversion Supported by Windows Viewer. Convert to PDF.
add image pdf; add picture pdf
C# powerpoint - PowerPoint Conversion & Rendering in C#.NET
using other external third-party dependencies like Adobe Acrobat. file conversion from PowerPoint document to image or document PowerPoint to PDF Conversion.
adding an image to a pdf in acrobat; how to add an image to a pdf in preview
10-28
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Alarm 
No. 
Description 
A025 
Brush length too short 
(active in all operating states) 
When parameter P495=1 (binary sensing of brush length): 
Alarm in response to log. “0” signal (longer than 10s) at terminal 211 
Possible causes 
♦  Encoder for brush length has responded 
♦  Interruption in encoder cable 
A026 
Poor bearing condition 
(active in all operating states) 
When parameter P496=1 (bearing condition sensing): 
Alarm in response to log. “0” signal (longer than 2s) at terminal 212 
Possible causes 
♦  Encoder for bearing condition has responded 
A027 
Air flow monitoring
(active in operating states of < o6) 
When parameter P497=1 (air flow monitoring): 
Alarm in response to log. “0” signal (longer than 40s) at terminal 213 
Possible causes 
♦  Encoder for fan monitoring has responded  
♦  Interruption in encoder cable 
A028 
Motor overtemperature 
(active in all operating states) 
When parameter P498=1 (thermostat connected): 
Alarm in response to log. “0” signal (longer than 10s) at terminal 214 
Possible causes 
♦  Thermostat for monitoring motor temperature has responded 
♦  Interruption in encoder cable 
A029 
Motor overtemperature 
(active in all operating states) 
Selection via P493=1 or 3 (thermostat at terminals 22 / 23) or 
P494=1 or 3 (thermostat at terminals 204 / 205) 
When parameter P490.01=1 (KTY84 at terminals 22 / 23) or P490.02=1 (KTY84 at terminals 204 / 205):
The alarm is activated if the motor temperature reaches or exceeds the values set in parameter P492. 
When parameter P490.01=2, 3, 4 or 5 (PTC thermistor at terminals 22 / 23) or P490.02=2, 3, 4 or 5 (PTC thermistor at terminals 
204 / 205):
The alarm is activated if the motor temperature reaches or exceeds the trip value of the selected PTC. 
A030 
Commutation failure or overcurrent has occurred 
(active in operating states of  – –, I, II) 
Possible error causes 
♦  Mains voltage dip in regenerative feedback mode 
♦  Current control loop not optimized 
A031 
Speed controller monitoring 
(active in operating states of  – –, I, II) 
The monitor responds when the difference between the connectors selected in P590 and P591 (factory setting: Setpoint/actual 
value difference of speed controller) exceeds the limit set in parameter P388 for longer than the time set in parameter P390. 
Possible causes 
♦  Control loop interrupted 
♦  Controller is not optimized 
♦  P590 or P591 is not correctly parameterized 
C# Word - Word Conversion in C#.NET
without using other external third-party dependencies like Adobe Acrobat. perform file conversion from Word document to image or document Word to PDF Conversion.
add image to pdf preview; add picture to pdf preview
VB.NET PDF: How to Create Watermark on PDF Document within
this VB.NET Imaging PDF Watermark Add-on, you watermark that consists of text or image (such as users need no external application plugin, like Adobe Acrobat.
attach image to pdf form; add photo to pdf for
SIEMENS AG    6RX1700-0AD76 
10-29 
SIMOREG DC-MASTER    Operating Instructions 
Alarm 
No. 
Description 
A032 
SIMOREG CCP not ready 
(active in operating states of  < o4.0) 
Possible causes 
•  No voltage at U, V, W terminals of SIMOREG CCP 
•  Voltage at C-D on CCP does not match voltage at C-D on SIMOREG DC-MASTER 
•  Surge absorbing capacitors of SIMOREG CCP have not reached setpoint voltage 
•  Paralleling interface cable is not connected to SIMOREG CCP assigned to paralleling master 
•  No connection between SIMOREG DC-MASTER and SIMOREG CCP via G-SST2 serial interface 
•  No connection between parallel SIMIOREG CCPs 
•  Contents of technical data memory on SIMOREG CCP (MLFB, rated values, serial number) invalid 
•  I2t value of voltage chopper 1 is too high (> 100%) 
•  I2t value of voltage chopper 2 is too high (> 50%) 
A033 
Alarm message from free function block FB8
(active in all operating states) 
The binector connected via parameter U106 Index.001  is in the log. "1" state 
A034 
Alarm message from free function block FB9
(active in all operating states) 
The binector connected via parameter U107 Index.001  is in the log. "1" state 
A035 
Drive blocked 
(active in operating states of  – –, I, II) 
The monitoring function responds if the following conditions are fulfilled for longer than the time set in parameter P355: 
♦  Positive or negative torque or armature current limit reached 
♦  Armature current is greater than 1% of converter rated armature DC current 
♦  The actual speed value is less than 0.4% of maximum speed 
A036 
No armature current can flow 
(active in operating states of  – –, I, II) 
This monitoring function responds if the armature firing angle is at the rectifier stability limit for more than 500 ms and the 
armature current is less than 1% of the converter rated armature DC current. 
A037 
I
2
t motor monitor has responded 
(active in operating states of  – –, I, II) 
The alarm is activated when the calculated I
2
t value of the motor reaches the value which corresponds to the final temperature 
at 100% of permissible continuous motor current (= P113*P100). 
A038 
Overspeed 
(active in operating states of  – –, I, II) 
The monitoring function responds if the actual speed value (selected in P595) exceeds the positive (P512) or negative (P513) 
threshold by 0.5%. 
Possible causes 
♦  Lower current limit has been input 
♦  Current-controlled operation 
♦  P512, P513 are set too low 
♦  Tachometer cable contact fault in operation close to maximum speed 
A039 
I
2
t value of power section too high 
(active in all operating states) 
This alarm is activated if the permissible I
2
t value for the relevant power section is reached. At the same time, the current limit is 
set to P077 * 100% of the converter rated DC current. This limit is not cancelled again until the setpoint drops below 100% of the 
converter rated DC current. See also Fault F039 and Parameter P075. 
A043 
Automatic field current reduction if EMF is too high in operation 
(active in operating states of  – –, I, II) 
This alarm is active only when parameter P272=1 and activated if the following equation applies to firing angle α (armature) 
before limitation (K101): 
α > (α
W
(inverter stability limit acc. to P151) – 5 degrees) or , at a low (pulsating) current 
α > (165 degrees – 5 degrees) 
AND armature current setpoint K0118 filtered with P190.F is > 1% of r072.002 
The field is reduced simultaneously with A043, implemented through control of the armature firing angle to (α
W
(or 165 degrees) 
- 5 degrees) using a P controller whose output reduces the EMF controller setpoint. For this reason, “Field weakening operation 
through internal EMF control” (PO81=1) must be parameterized. 
When a change in torque direction is requested, both torque directions are inhibited until the calculated control angle (K101) is 
<165 degrees for the armature current requested in the new torque direction, i.e. until the field, and thus the EMF, have been 
reduced accordingly. 
See also parameter P082. 
VB.NET PowerPoint: VB Code to Draw and Create Annotation on PPT
free hand, rubber stamp, callout, embedded image, and ellipse no more plug-ins needed like Acrobat or Adobe Users need to add following implementations to your
add photo to pdf form; how to add image to pdf in acrobat
BMP to PDF Converter | Convert Bitmap to PDF, Convert PDF to BMP
Also designed to be used add-on for .NET Image SDK, RasterEdge Powerful image converter for Bitmap and PDF files; No need for Adobe Acrobat Reader & print
how to add an image to a pdf file; adding image to pdf
10-30
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Alarm 
No. 
Description 
A044 
An alarm is active on one slave connected to the paralleling interface 
(active in all operating states) 
A046 
Analog select input for main setpoint (terminals 4 and 5) faulty 
(active in operating states of ≤ o6) 
This alarm is activated when P700=2 (current input 4 to 20 mA) and the input current is less than 3mA. 
A047 
Analog select input 1 (terminals 6 and 7) faulty 
(active in operating states of ≤ o6) 
This alarm is activated when P710=2 (current input 4 to 20 mA) and the input current is less than 3mA. 
A049 
SCB1: No SCI slave connected 
(active in all operating states) 
A050 
SCB1: Not all required SCI slaves are available 
(active in all operating states) 
The SCI slave required to perform the parameterized functions is not available 
A053 
Alarm message from free function block FB258
(active in all operating states) 
The binector connected via parameter U106 Index.002  is in the log. "1" state 
A054 
Alarm message from free function block FB259
(active in all operating states) 
The binector connected via parameter U107 Index.002  is in the log. "1" state 
A059 
Remaining time for temporary enabling of the S00 technology option is now less than 100 operating hours 
(active in all operating statuses) 
Remaining time for temporary enabling of the S00 technology option is now less than 100 operating hours. The functions will 
soon be unavailable. 
If you wish to continue using technology option S00, please contact to your nearest Siemens Regional Office for a PIN number 
for permanent enabling of technology option S00. 
You will need to know the serial number of your SIMOREG DC-MASTER. For further details, please refer to the description of 
parameters U977 and n978 in Chapter 11 of the Parameter List. 
A060 
Current total processor utilization (n009.i001, K9990) > 95.5%  
(active in all operating states) 
A067 
Converter cooling faulty 
(active in all operating states) 
The heat sink temperature is higher than the permissible value (depending on the MLFB). 
The monitoring function is activated 6s after the electronics supply is connected. 
(The current heat sink temperature is indicated at parameter r013 and on connector K050) 
A081  
to 
A088 
CB alarm of 1
st
CB 
(active in all operating states ≤ o11) 
The meaning of these alarms depends on the type of board used.  
For further information, refer to Section 7.7, Start-Up of Optional Supplementary Boards, in the relevant board description. 
A089  
to 
A096 
CB alarm of 2
nd
CB 
(active in all operating states ≤ o11) 
The meaning of these alarms depends on the type of board used.  
For further information, refer to Section 7.7, Start-Up of Optional Supplementary Boards, in the relevant board description. 
A097  
to 
A128 
TB alarms 
(active in operating states ≤ o11) 
For more information about TECH BOARD alarms, please refer to Operating Instructions or Configuring Guide of the relevant 
board. 
JPEG to PDF Converter | Convert JPEG to PDF, Convert PDF to JPEG
It can be used standalone. JPEG to PDF Converter is able to convert image files to PDF directly without the software Adobe Acrobat Reader for conversion.
add photo to pdf file; add png to pdf acrobat
PDF to WORD Converter | Convert PDF to Word, Convert Word to PDF
out transformation between different kinds of image files and Word Converter has accurate output, and PDF to Word need the support of Adobe Acrobat & Microsoft
add photo to pdf in preview; how to add a jpeg to a pdf
SIEMENS AG    6RX1700-0AD76 
11-1 
SIMOREG DC-MASTER    Operating Instructions 
11  Parameter list 
Overview 
Range of parameter 
numbers 
Function 
r000 
Operating display 
r001 - P050 
General visualization parameters 
P051- r059 
Access authorization levels  
r060 - r065 
Definition of SIMOREG DC-MASTER converter 
P067 - P079 
Definition of SIMOREG DC-MASTER power section 
P080 - P098 
Setting values for converter control 
P100 - P139 
Definition of motor 
P140 - P148 
Definition of pulse encoder, speed sensing using pulse encoder 
P150 - P165 
Closed-loop armature current control, auto-reversing stage, armature gating unit 
P169 - P191 
Current limitation, torque limitation 
P192 - P193 
Auto-reversing stage, armature gating unit 
P200 - P236 
Speed controller (further parameters for the speed controller P550 - P567) 
P250 - P265 
Closed-loop field current control, field gating unit 
P272 - P284 
Closed-loop EMF control 
P295 - P319 
Ramp-function generator 
P320 - P323 
Setpoint processing 
P330 
Ramp-function generator 
P351 - P364 
Setting values for monitoring functions and limits 
P370 - P399 
Setting values for limit-value monitors 
P401 - P416 
Settable fixed values 
P421 - P428 
Fixed control bits 
P430 - P445 
Digital setpoint input (fixed setpoint, inching and crawling setpoints) 
P450 - P453 
Position sensing with pulse encoder 
P455 - P458 
Connector selector switches 
P460 - P473 
Motorized potentiometer 
P480 - P485 
Oscillation 
P490 - P498 
Definition of "Motor interface” 
P500 - P503 
Configuring of torque shell input 
P509 - P515 
Speed limiting controller 
P519 - P530 
Friction compensation 
P540 - P546 
Compensation of moment of inertia (dv/dt injection) 
P550 - P567 
Speed controller (further parameters for the speed controller P200 - P236) 
P580 - P583 
Field reversal 
P590 - P597 
Input quantities for signals 
P600 - P647 
Configuring of closed-loop control 
P648 - P691 
Control word, status word 
P692 - P698 
Further configuring measures 
P700 - P746 
Analog inputs (main actual value, main setpoint, selectable inputs) 
P749 - P769 
Analog outputs 
P770 - P778 
Binary outputs 
P780 - P819 
Configuration of serial interfaces on basic converter 
P820 - P821 
Deactivation of monitoring functions 
r824 - r829 
Compensation values 
P830 
Thyristor diagnosis 
P831 - P899 
Parameters for DriveMonitor and OP1S 
P918 - P927 
Profile parameters 
r947 - P952 
Fault memory 
r953 - r960 
Visualization parameters: Alarms 
11-2 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Range of parameter 
numbers 
Function 
r964 
Device identification 
r967 - r968 
Visualization parameters: Control and status word 
P970 - r999 
Resetting and storing parameters, list of existing and modified P and r parameters 
U005 - U007 
Password protection, key/lock mechanism  
n009 
Processor utilization 
n024 - U098 
Miscellaneous 
U116 - U118 
Binector / connector converter for the serial interfaces  
n560 - U583 
Commutation monitoring 
U607 - U608 
Setpoint reduction  
U616 
Definition of the function of inputs and outputs 
U619 
Definition of the function of the relay output at terminals 109 / 110  
U651 - U657 
Starting pulse speed controller  
U660 - U668 
Evaluation of a 4-step master switch for cranes  
U690 - n699 
Configuration of SCB1 with SCI1 
U710 - n739 
Configuration of supplementary boards in board locations 2 and 3 
U740 - U753 
Configuration of the SIMOLINK board  
U755 - n770 
Configuration of the EB1 expansion board  
U773 - n788 
Configuration of the EB2 expansion board  
U790 - U796 
Configuration of the SBP pulse encoder board  
U800 - n813 
Configuration of paralleling interface 
U819 - U835 
Parameters for SIMOREG DC-MASTER Control Module (SIMOREG CM) 
U838 
Rated DC current of external field device 
U840 
Simulation operation  
U845 - U909 
Parameters for DriveMonitor 
U910 
Slot deactivation 
U911 - n949 
Parameters for DriveMonitor 
n953 - n959 
Parameters for DriveMonitor 
U979 
Parameter access for experts 
n980 - n999 
List of existing and modified U and n parameters 
SIEMENS AG    6RX1700-0AD76 
11-3 
SIMOREG DC-MASTER    Operating Instructions 
Parameters for technology software in the basic converter, S00 option  
("freely assignable function blocks")
Range of parameter 
numbers 
Function 
n010 - n023 
Displays 
U099 
Settable fixed values  
U100 - U107 
Triggering of faults and alarms 
U110 - U115 
Connector/binector converters, binector/connector converters 
U120 - U171 
Mathematical functions 
U172 - U173 
Processing of connectors (averager)  
U175 - U218 
Limiter, limit-value monitors 
U220 - U259 
Processing of connectors 
U260 - U299 
Integrators, DT1 elements, characteristics, dead zones, setpoint branching 
U300 - U303 
Simple ramp-function generator 
U310 - U313 
Multiplexer 
n314 - U317 
Counter 
U318 - U411 
Logic functions 
U415 - U474 
Storage elements, timers and binary signal selector switches 
U480 - U512 
Technology controller 
U515 - U523 
Velocity/speed calculators 
U525 - U529 
Variable moment of inertia  
U530 - U545 
PI controller  
U550 - U554 
Closed-loop control elements  
U670 - U677 
Position/positional deviation acquisition 
U680 - U684 
Root extractor 
U950 - U952 
Sampling times 
U960 - U969 
Altering the processing sequence of function blocks 
U977 - n978 
Enabling of technology software in basic unit, S00 option ("freely assignable function blocks") 
11-4 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Overview of abbreviations 
Example: 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting  
Type 
See 
Change 
(Access / 
Status) 
P520 
1)
FDS 
2) 
8)  9)
(G153) 
10) 
Friction at 0% speed 
Setting as % of converter rated DC current or converter rated torque 
0.0 to 100.0 
[%] 
0.1%
4)
Ind: 4 
FS=0.0 
5)
Type: O2 
3)
P052 = 3 
P051 ≥ 20 
Online
6)
1)
An  
*
under the parameter number means that the parameter requires confirmation, i.e. the altered value 
does not take effect until the P key is pressed. 
2) 
Abbreviation indicating that the parameter belongs to a data set (refers only to indexed parameters) (see 
Section 9.11 “Switch over parameter sets“) 
FDS 
Parameter belongs to the function data set  (see Section 9.1, subsection "Data sets") 
BDS 
Parameter belongs to the BICO data set  (see Section 9.1, subsection "Data sets") 
3)
Specification of parameter type 
O2 
Unsigned 16-bit value 
I2 
Signed 16-bit value 
O4 
Unsigned 32-bit value 
I4 
Signed 32-bit value 
V2 
Bit-coded quantity 
L2 
Nibble-coded quantity 
4)
Setting steps for access via PKW mechanism
5)
Factory setting  
6) 
Minimum setting required (P052) to allow display of the relevant parameter 
Minimum access level required (P051) to allow modification of the relevant parameter 
Online: The parameter can be changed in all converter operating states 
Offline: The parameter can only be changed in converter operating states of ≥ o1.0 
8) 
S00 
Parameter belongs to the technology software in the basic converter, S00 option 
9)  The "OP parameter number" (i.e. the number to be entered via the OP1S operator panel) is specified in 
brackets in the "PNU" column for all parameters which are not "P parameters" or "r parameters": e.g. (2010) 
under n010 or (2100) under U100. 
10) The parameter is shown in the specified function diagram in Section 8 (here G153). 