SIEMENS AG    6RX1700-0AD76 
11-5 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
11.1  Operating status display 
r000 
Operating status display 
Status display, fault and alarm messages  
Torque direction M0, MI or MII  (=RUN) 
- - 
No torque direction active 
Torque direction I active (MI) 
I I 
Torque direction II active (MII) 
o1 
Waiting for operating enable  (=READY) 
o1.0  Brake release delay time running. 
o1.1  Waiting for operating enable at terminal 38. 
o1.2  Waiting for operating enable via binector (acc. to selection in 
P661) or control word, bit 3 (acc. to selection in P648) 
o1.3  Inching command cancellation delay time running. 
o1.4  Waiting for field to be reversed. 
Waiting for cancellation of command "Brake by field reversal" 
o1.5  Waiting for operating enable from optimization run 
(the optimization run does not output the operating enable signal 
at the end until n<n
min
has been reached and SHUTDOWN 
input). 
o1.6  Waiting for cancellation of immediate pulse disable via binector 
(acc. to selection with P177) 
[SW 1.8 and later] 
o2 
Wait for setpoint > P091.002 
o2.0  If |n-set| (|K0193|) and |n-actual| (K0166) are less than 
P091.002, the firing pulses are disabled and the drive goes into 
state o2.0. 
[SW 2.0 and later] 
o3 
Test phase 
o3.0  Waiting for completion of thyristor check (selectable function). 
o3.1  Waiting for completion of line symmetry check. 
o3.2  Waiting for a DC contactor to pick up 
o3.3  Waiting for "Main contactor checkback" 
(control word 2 bit 31, see P691) 
[SW 1.8 and later] 
o4 
Waiting for voltage (armature) 
o4.0  Waiting for voltage at power terminals 1U1, 1V1, 1W1. The 
voltage and frequency must be within the range specified with 
parameters P351, P352, P353, P363 and P364. See also 
P078.001. 
o4.1  Waiting for fuse monitoring to signal OK 
[SW 1.7 and later] 
o4.5  Waiting until the chopper capacitors of the SIMOREG CCP are 
completely precharged 
[SW 2.2 and later] 
o5 
Waiting for field current 
o5.0  Waiting until actual field current K0266 equals > P396 (FS=50% 
of field current setpoint K0275) and for  "I 
field extern
> I 
f min
(see P265). 
o5.1  Waiting for voltage at power terminals 3U1, 3W1. The voltage 
and frequency must be within the range specified with 
parameters P351, P352, P353, P363 and P364. See also 
P078.002. 
NOTE
The converter dwells in states o4 and o5 for a maximum total delay time 
that is set in parameter P089. The appropriate fault message is output if 
the corresponding conditions are still not fulfilled at the end of this 
period. 
o6 
Wait status before the line contactor is closed 
o6.0  Waiting for auxiliaries to be switched on (delay in P093) 
o6.1  Waiting for a setpoint  ≤ P091 to be applied to the ramp-function 
generator input (K0193) 
Ind: None 
Type: O2 
P052 = 3 
Add picture pdf - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
how to add an image to a pdf file in acrobat; adding jpg to pdf
Add picture pdf - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
acrobat insert image in pdf; how to add an image to a pdf in acrobat
11-6 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
o7 
Waiting for switch-on command  (=READY TO SWITCH ON) 
o7.0  Waiting for switch-on command via terminal 37. 
o7.1  Waiting for switch-on command via binector (acc. to selection in 
P654) or control word, bit 0 (acc. to selection in P648). 
o7.2  Waiting for cancellation of internal shutdown through input of an 
internal shutdown command or 
waiting for cancellation of command "Braking with field reversal" 
o7.3  Waiting for completion of "Restore factory settings" operation. 
o7.4  Waiting for switch-on command before execution of an 
optimization run 
o7.5  Wait for completion of "Read in parameter set" operation. 
o7.6  Wait for completion of "Load MLFB" operation (performed at 
factory) 
o7.9  reserved for firmware download for optional supplementary 
modules 
[SW 2.0 and later] 
o8 
Waiting for acknowledgement of starting lockout 
o8.0  Waiting for acknowledgement of starting lockout through input of 
SHUTDOWN command (OFF1). 
o8.1  Simulation operation active (see under U840) [SW1.7 and later] 
o9 
Fast stop (OFF3) 
o9.0  Fast stop has been input via binector (acc. to selection in P658) 
or control word, bit 2 (acc. to selection in P648). 
o9.1  Fast stop has been input via binector (acc. to selection in P659).
o9.2  Fast stop has been input via binector (acc. to selection in P660).
o9.3  Fast stop is stored internally (memory can be reset by cancelling 
FAST STOP command and entering SHUTDOWN). 
o10 
Voltage disconnection (OFF2) 
o10.0  Voltage disconnection has been input via binector (acc. to 
selection in P655) or control word, bit 1 (acc. to selection in 
P648). 
o10.1  Voltage disconnection has been input via binector (acc. to 
selection in P656). 
o10.2  Voltage disconnection has been input via binector (acc. to 
selection in P657). 
o10.3  E-Stop (safety shutdown) has been input via terminal 105 or 107
o10.4  Wait for receipt of a valid telegram on G-SST1 (only if telegram 
failure time monitoring is set with P787 ≠ 0) 
o10.5  Waiting for receipt of a valid telegram on G-SST2 (only if 
telegram failure time monitoring is set with P797 ≠ 0) 
o10.6  Waiting for receipt of a valid telegram on G-SST3 (only if 
telegram failure time monitoring is set with P807 ≠ 0) 
o11 
Fault  
o11.0  = Fxxx  Fault message is displayed, red LED lights up. 
o12 
Electronics initialization in progress 
o12.1  Basic converter electronics initialization in progress 
o12.2  Supplementary board is sought in module plug-in location 2 
o12.3  Supplementary board is sought in module plug-in location 3 
o12.9  Restructuring of parameters in non-volatile storage after 
software update (takes approx. 15s) 
C# TIFF: How to Insert & Burn Picture/Image into TIFF Document
Support adding image or picture to an existing or new new REImage(@"c:\ logo.png"); // add the image powerful & profession imaging controls, PDF document, tiff
add jpg to pdf form; how to add image to pdf file
VB.NET Image: Image Cropping SDK to Cut Out Image, Picture and
VB.NET image cropper control SDK; VB.NET image cropping method to crop picture / photo; you can adjust the size of created cropped image file, add antique effect
add jpg to pdf; add picture to pdf reader
SIEMENS AG    6RX1700-0AD76 
11-7 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
o13 
Software update in progress 
o13.0  Waiting for arrival of start command from HEXLOAD PC routine
(press the DOWN key to abort this status and start a RESET) 
o13.1  Deletion of Flash EPROM in progress 
xxxxx  Display of address currently being programmed 
o13.2  The Flash EPROM has been successfully programmed 
(a RESET is performed automatically after approx. 1 second) 
o13.3  Programming of the Flash EPROM has failed
(press UP key to return to operating state o13.0) 
o14 
Loading of boot sector in progress 
(this operation is performed only in factory) 
o15 
Electronics not connected to voltage 
Dark display: Waiting for voltage at terminals 5U1, 5W1 
(electronics supply voltage). 
11.2  General visualization parameters 
r001 
(G113) 
Display of terminals 4 and 5 (main setpoint) 
-200.0 to 199.99 
[%] 
0.01% 
Ind: None 
Type: I2 
P052 = 3 
r002 
(G113) 
Analog input, terminals 103 and 104 (main actual value) 
-200.0 to 199.99 
[%] 
0.01% 
Ind: None 
Type: I2 
P052 = 3 
r003 
(G113) 
Analog input, terminals 6 and 7 (selectable input 1) 
-200.0 to 199.99 
[%] 
0.01% 
Ind: None 
Type: I2 
P052 = 3 
r004 
(G114) 
Analog input, terminals 8 and 9 (selectable input 2) 
-200.0 to 199.99 
[%] 
0.01% 
Ind: None 
Type: I2 
P052 = 3 
r005 
(G114) 
Analog input, terminals 10 and 11 (selectable input 3) 
-200.0 to 199.99 
[%] 
0.01% 
Ind: None 
Type: I2 
P052 = 3 
r006 
(G115) 
Analog output, terminals 14 and 15 
Display of output value before
normalization and offset 
-200.0 to 199.99 
[%] 
0.01% 
Ind: None 
Type: I2 
P052 = 3 
r007 
(G115) 
Analog output, terminals 16 and 17 
Display of output value before
normalization and offset 
-200.0 to 199.99 
[%] 
0.01% 
Ind: None 
Type: I2 
P052 = 3 
r008 
(G116) 
Analog output, terminals 18 and 19 
Display of output value before
normalization and offset 
-200.0 to 199.99 
[%] 
0.01% 
Ind: None 
Type: I2 
P052 = 3 
r009 
(G116) 
Analog output, terminals 20 and 21 
Display of output value before
normalization and offset 
-200.0 to 199.99 
[%] 
0.01% 
Ind: None 
Type: I2 
P052 = 3 
VB.NET TIFF: How to Draw Picture & Write Text on TIFF Document in
drawing As RaterEdgeDrawing = New RaterEdgeDrawing() drawing.Picture = "RasterEdge" drawing provide powerful & profession imaging controls, PDF document, tiff
add jpg to pdf preview; how to add image to pdf
VB.NET Image: VB.NET Codes to Add Antique Effect to Image with .
mature technology to replace a picture's original colors add the glow and noise, and add a little powerful & profession imaging controls, PDF document, image
add image to pdf reader; adding a jpg to a pdf
11-8 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
r010 
(G110) 
Display of status of binary inputs 
Representation on operator panel (PMU): 
3
2
1
0
4
5
6
7
8
9
10
11
12
13
14
15
Segment ON: 
Corresponding terminal is activated 
(HIGH level is applied) 
Segment OFF: 
Corresponding terminal is not activated 
(LOW level is applied) 
Segment or bit 
0 ........ Terminal 36 
1 ........ Terminal 37 (switch-on) 
2 ........ Terminal 38 (operating enable) 
3 ........ Terminal 39 
4 ........ Terminal 40 
5 ........ Terminal 41 
6 ........ Terminal 42 
7 ........ Terminal 43 
8 ........ Terminal 211 
9 ........ Terminal 212 
10 ........ Terminal 213 
11 ........ Terminal 214 
12 ........ Safety shutdown (E-Stop is applied)   1) 
13 ........ (not used) 
14 ........ (not used) 
15 ........ (not used) 
1)  The safety shutdown command is applied (segment dark) if 
 terminal XS-105 is open (switch operation, see also Section 9) 
or 
 terminal XS-107 (Stop pushbutton) is opened briefly and terminal XS-
108 (Reset pushbutton) is not yet activated (pushbutton operation,   
see also Section 9) 
Ind: None 
Type: V2 
P052 = 3 
r011 
(G112)  
(G117) 
Display of status of binary outputs 
Representation on operator panel (PMU): 
3
2
1
0
4
5
6
7
8
9
10
11
12
13
14
15
Segment ON: 
Corresponding terminal is activated 
(HIGH level is applied) or overloaded or short-circuited 
Segment OFF: 
Corresponding terminal is not activated 
(LOW level is applied) or not overloaded or not short-
circuited 
Display of status of binary output terminals: 
Segment or bit 
0 ..... Terminal 46 
1 ..... Terminal 48 
2 ..... Terminal 50 
3 ..... Terminal 52 
7 ..... Terminal 109/110 (relay contact for line contactor) 
Display of overloading of binary outputs: 
Segment or bit 
8 ..... Terminal 46 
9 ..... Terminal 48 
10 .... Terminal 50 
11 .... Terminal 52 
12 .... Terminal 26 (15V output) 
13 .... Terminal 34, 44 and/or 210 (24V output) 
Ind: None 
Type: V2 
P052 = 3 
VB.NET Image: Image Scaling SDK to Scale Picture / Photo
Framework application; VB.NET sample code for how to scale image / picture; Frequently asked questions about RasterEdge VB.NET image scaling control SDK add-on.
acrobat add image to pdf; add a picture to a pdf file
VB.NET Image: Create Code 11 Barcode on Picture & Document Using
file, apart from above mentioned .NET core imaging SDK and .NET barcode creator add-on, you also need to buy .NET PDF document editor add-on, namely, RasterEdge
add an image to a pdf with acrobat; add an image to a pdf form
SIEMENS AG    6RX1700-0AD76 
11-9 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
r012 
(G185) 
Motor temperature 
Display of motor temperature when a KTY 84 temperature sensor is 
connected (P490.x=1). 
A value of "0" is always output in r012 when a PTC thermistor or no 
temperature sensor is installed. 
i001:  Motor temperature 1 (sensor at terminals 22 / 23) 
i002:  Motor temperature 2 (sensor at terminals 204 / 205) 
-58 to +318 
[°C] 
1°C 
Ind: 2 
Type: I2 
P052 = 3 
r013 
Heatsink temperature 
Display of heatsink temperature 
-47 to +200 
[°C] 
1°C 
Ind: None 
Type: I2 
P052 = 3 
r014 
Temperature rise 
i001:  Calculated motor temperature rise (see P114) 
i002:  Calculated thyristor temperature rise (see P075) 
0.0 to 200.0 
[%] 
0.1% 
Ind: 2 
Type: O2 
P052 = 3 
r015 
Display of line voltage (armature) 
(generated as arithmetic rectification average, RMS value display applies to 
sinusoidal voltage, average over 3 line-to-line voltages) 
0.0 to 2800.0 
[V] 
0.1V 
Ind: None 
Type: O2 
P052 = 3 
r016 
Display of line voltage (field) 
(generated as arithmetic rectification average, RMS value display applies to 
sinusoidal voltage) 
0.0 to 800.0 
[V] 
0.1V 
Ind: None 
Type: O2 
P052 = 3 
r017 
Display of line frequency 
0.00 to 120.00 
[Hz] 
0.01Hz 
Ind: None 
Type: O2 
P052 = 3 
r018 
(G163) 
Display of firing angle (armature) 
0.00 to 180.00  
[degrees] 
0.01degrees 
Ind: None 
Type: O2 
P052 = 3 
r019 
(G162) 
Display of actual armature current 
The internal actual armature current value is displayed (arithmetic average 
over the last 6 current peaks in each case) 
-400.0 to 400.0 
[% of P100] 
0.1% of P100 
Ind: None 
Type: I2 
P052 = 3 
r020 
(G162) 
Display of the absolute value of armature current setpoint 
0.0 to 300.0 
[% of P100] 
0.1% of P100 
Ind: None 
Type: I2 
P052 = 3 
r021 
(G160) 
Display of torque setpoint after torque limitation 
Steps: 1 =
0.1% of rated motor torque (=rated motor armature current 
(P100) * magnetic flux at rated motor field current (P102)) 
-400.0 to 400.0 
[%] 
0.1% (see column on 
left) 
Ind: None 
Type: I2 
P052 = 3 
r022 
(G160) 
Display of torque setpoint before torque limitation 
Steps: 1 =
0.1% of rated motor torque (=rated motor armature current 
(P100) * magnetic flux at rated motor field current (P102)) 
-400.0 to 400.0 
[%] 
0.1% (see column on 
left) 
Ind: None 
Type: I2 
P052 = 3 
r023 
(G152) 
Display of speed controller setpoint/actual value deviation 
-200.00 to 199.99 
[%] 
0.01% 
Ind: None 
Type: I2 
P052 = 3 
r024 
(G145) 
Display of actual speed value from pulse encoder 
-200.00 to 199.99 
[%] 
0.01% 
Ind: None 
Type: I2 
P052 = 3 
r025 
(G151) 
Display of actual speed controller value 
-200.0 to 199.99 
[%] 
0.01% 
Ind: None 
Type: I2 
P052 = 3 
r026 
(G152) 
Display of speed controller setpoint 
-200.0 to 199.99 
[%] 
0.01% 
Ind: None 
Type: I2 
P052 = 3 
r027 
(G136) 
Display of ramp-function generator output 
-200.00 to 199.99 
[%] 
0.01% 
Ind: None 
Type: I2 
P052 = 3 
r028 
(G136) 
Display of ramp-function generator input 
-200.00 to 199.99 
[%] 
0.01% 
Ind: None 
Type: I2 
P052 = 3 
r029 
(G135) 
Display of main setpoint before limitation 
-200.00 to 199.99 
[%] 
0.01% 
Ind: None 
Type: I2 
P052 = 3 
r034 
(G166) 
Display of firing angle (field) 
0.00 to 180.00  
[degrees] 
0.01degrees 
Ind: None 
Type: O2 
P052 = 3 
r035 
(G166) 
Display of field current controller actual value 
0.0 to 199.9 
[% of P102] 
0.1% of P102 
Ind: None 
Type: O2 
P052 = 3 
C# Word - Paragraph Processing in C#.NET
Add references: C# users can set paragraph properties and create content such as run, footnote, endnote and picture in a paragraph.
adding image to pdf file; add image pdf document
VB.NET Image: Image Resizer Control SDK to Resize Picture & Photo
NET Method to Resize Image & Picture. Here we this VB.NET image resizer control add-on, can provide powerful & profession imaging controls, PDF document, image
add image to pdf acrobat reader; add photo to pdf online
11-10 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
r036 
(G166) 
Display of field current controller setpoint 
0.0 to 199.9 
[% of P102] 
0.1% of P102 
Ind: None 
Type: O2 
P052 = 3 
r037 
(G165) 
Display of actual EMF value 
-1500.0 to 1500.0 
[V] 
0.1V 
Ind: None 
Type: I2 
P052 = 3 
r038 
Display of actual armature voltage value 
-1500.0 to 1500.0 
[V] 
0.1V 
Ind: None 
Type: I2 
P052 = 3 
r039 
(G165) 
Display of EMF setpoint 
This parameter displays the EMF setpoint which is applied as the control 
quantity in the field-weakening range. 
This value is calculated from: 
Umotor
rated 
– Imotor
rated 
*
RA (= P101 – P100 
*
P110)  
0.0 to 1500.0 
[V] 
0.1V 
Ind: None 
Type: O2 
P052 = 3 
r040 
Display of limitations: 
Representation on operator panel (PMU): 
3
2
1
0
4
5
6
7
8
9
10
11
12
13
14
15
Segment ON: 
Corresponding limitation is reached 
Segment OFF: 
Corresponding limitation is not reached 
Segment or bit 
0  
α
W
limit (field) reached (P251) 
1  
Negative current limit (field) reached (K0274) 
2  
α
W
limit (armature) reached (α
W
acc. to P151 
for continuous current, 165° for discontinuous current) 
3 ....... Negative current limit (armature) reached (K0132) 
4 ....... Negative maximum speed reached (P513) 
Speed limiting controller responds (B0201) 
5 ....... Negative torque limit reached (B0203) 
6 ....... Neg. limitation at ramp generator output reached (K0182) 
7 ....... Neg. limitation at ramp generator input reached (K0197) 
8 ....... α
G
limit (field) reached (P250) 
9 ....... Positive current limit (field) reached (K0273) 
10 ....... α
G
limit (armature) reached (P150) 
11 ....... Positive current limit (armature) reached (K0131) 
12 ....... Positive maximum speed reached (P512) 
Speed limiting controller responds (B0201) 
13 ....... Positive torque limit reached (B0202) 
14 ....... Pos. limitation at ramp generator output reached (K0181) 
15 ....... Pos. limitation at ramp generator input reached (K0196) 
Note:  This parameter has the same bit assignments as connector K0810. 
Ind: None 
Type: V2 
P052 = 3 
Connector and binector displays 
r041 
(G121) 
High-resolution connector display:  
i001:  Display of connector selected in P042.01  
i002:  Display of connector selected in P042.02  
The display value is filtered with a time constant of 300ms (see Section 8, 
Sheet G121) 
-200.00 to 199.99 
[%] 
0.01% 
Ind: 2 
Type: I2 
P052 = 3 
P042 
(G121) 
High-resolution connector display:  
i001:  Selection of connector to be displayed in r041.01  
i002:  Selection of connector to be displayed in r041.02  
The display value is filtered with a time constant of 300ms (see Section 8, 
Sheet G121) 
All connector 
numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Online 
r043 
(G121) 
Connector display:  
i001:  Display of connector selected in P044.01 
i002:  Display of connector selected in P044.02 
i003:  Display of connector selected in P044.03 
i004:  Display of connector selected in P044.04 
i005:  Display of connector selected in P044.05 
i006:  Display of connector selected in P044.06 
i007:  Display of connector selected in P044.07 
-200.0 to 199.9 
[%] 
0.1% 
Ind: 7 
Type: I2 
P052 = 3 
SIEMENS AG    6RX1700-0AD76 
11-11 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P044 
(G121) 
Connector display:  
i001:  Selection of connector displayed in r043.01 
i002:  Selection of connector displayed in r043.02 
i003:  Selection of connector displayed in r043.03 
i004:  Selection of connector displayed in r043.04 
i005:  Selection of connector displayed in r043.05 
i006:  Selection of connector displayed in r043.06 
i007:  Selection of connector displayed in r043.07 
All connector 
numbers 
Ind: 7 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Online 
r045 
(G121) 
Binector display: 
i001:  Display of binector selected in P046.01 
i002:  Display of binector selected in P046.02 
i003:  Display of binector selected in P046.03 
i004:  Display of binector selected in P046.04 
0 to 1 
Ind: 4 
Type: O2 
P052 = 3 
P046 
(G121) 
Binector display: 
i001:  Selection of binector displayed in r045.01 
i002:  Selection of binector displayed in r045.02 
i003:  Selection of binector displayed in r045.03 
i004:  Selection of binector displayed in r045.04 
All binector numbers 
Ind: 4 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Online 
r047 
Display of fault diagnostic memory 
Provides more detailed information about the cause of a fault after activation 
of a fault message (see Section 10). 
i001  Word 1 (fault value) 
i002  Word 2 
... 
i016  Word 16 (fault number) 
0 to 65535 
Ind: 16 
Type: O2 
P052 = 3 
r048 
(G189) 
Hours run 
Display of time (hours) in which drive has been operating in states I, II or - -. 
All times of ≥ approx. 0.1 s are included in the count. 
0 to 65535 
[hours] 
1 hour 
Ind: None 
Type: O2 
P052 = 3 
r049 
(G189) 
Fault time 
Display of time at which the current fault, and the last 7 acknowledged 
faults, were activated. 
i001:  Current fault 
hours 
i002:  1
st
acknowledged fault  hours 
i003:  2
nd
acknowledged fault  hours 
i004:  3
rd
acknowledged fault  hours 
i005:  4
th
acknowledged fault  hours 
i006:  5
th
acknowledged fault  hours 
i007:  6
th
acknowledged fault  hours 
i008:  7
th
acknowledged fault  hours 
0 to 65535 
[hours] 
1 hour 
Ind: 8 
Type: O2 
P052 = 3 
P050 
Language 
Language of plaintext display on optional OP1S operator panel and in 
DriveMonitor PC service routine 
0: 
German 
1: 
English 
2:  
Spanish 
3: 
French 
4: 
Italian 
0 to 4 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 ≥ 0 
Online 
11-12 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
11.3  Access authorization levels 
P051 
Key parameters 
No access authorization 
Do not set (for use by DriveMonitor) 
Do not set (for use by DriveMonitor) 
Do not set (for use by DriveMonitor) 
21 
Restore factory settings 
All parameters are reset to their defaults (factory settings). 
Parameter P051 is then automatically reset to factory setting 
"40". 
22 
Execute internal offset compensation (see Section 7.4) 
25 
Optimization run for precontrol and current controller (armature 
and field) (see Section 7.5) 
26 
Optimization run for speed controller (see Section 7.5) 
27 
Optimization run for field weakening (see Section 7.5) 
28 
Optimization run for compensation of friction and moment of 
inertia (see Section 7.5)  
29 
Optimization run for the speed controller with an oscillating 
mechanical system (see Section 7.5)  
30 
Automatic setting of the parameters for SIMOREG CCP  Altered 
parameters:  
P351.i001, U577, U578, U800,  
in the event of a fault, P790 if appropriate 
40 
Access authorization to parameter values for authorized service 
personnel 
see column on left 
Ind: None 
FS=40 
Type: O2 
P052 = 3 
P051 ≥ 0 
Online 
P052 
Selection of display parameters 
 Display only parameters that are not set to original factory 
settings 
Display only parameters for simple applications 
Display all parameters used 
0, 1, 3 
Ind: None 
FS=3 
Type: O2 
P052 = 3 
P051 ≥ 0 
Online 
P053 
Control word for the permanent memory 
[SW 1.7 and later] 
Disabling or enabling write accesses to the permanent memory 
i001:  Disabling or enabling write accesses to the parameter memory
 Only save parameter P053 in the permanent memory; 
parameter changes are active immediately but the changed 
values are only stored temporarily and are lost when the 
electronics supply voltage is switched off 
 Save all parameter values in the permanent memory 
i002:  Disabling or enabling write accesses to the memory of the 
nonvolatile process data
 Do not save nonvolatile process data in the permanent 
memory 
 Save all nonvolatile process data in the permanent memory 
If the nonvolatile process data are not stored (P053.002=0), 
data are lost when the electronics supply of the SIMOREG DC-
MASTER is switched off, i.e. they have the value 0 after the 
electronics supply is switched on again:  
K0240: Setpoint of the motor potentiometer 
K0309: Motor heating  
K0310: Thyristor heating 
K9195: Output of the 1st tracking/storage element 
K9196: Output of the 2nd tracking/storage element 
0 to 1 
Ind: 2 
FS=1 
Type: O2 
P052 = 3 
P051 = 0 
on-line 
P054 
OP1S – Background lighting 
ON continuously 
ON when panel is in use 
0, 1 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 ≥ 0 
Online 
SIEMENS AG    6RX1700-0AD76 
11-13 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P055 
(G175) 
Copy function data set 
This parameter allows parameter set 1, 2, 3 or 4 to be copied
to parameter 
set 1, 2, 3 or 4. This function is applicable only to parameters with 4 indices 
in the function data set (see also Section 9.1, Data sets and Section 9.11, 
and Section 8, Sheet G175). 
0xy 
Do nothing
, automatic resetting value at the end of a copy 
operation. 
1xy 
The contents of parameter set x (source data set, x=1, 2, 3 or 4) 
are copied
to parameter set y (target data set, y=1, 2, 3 or 4) 
(parameter set x remains unchanged, the original contents of 
parameter set y are overwritten). 
x and y are the respective parameter set numbers (1, 2, 3 or 4) 
of the source and target parameter sets. 
The copy operation is started by switching P055 over into parameter mode 
when P055=1xy. 
During the copy operation, the numbers of the parameters being copied are 
displayed on the operator panel (PMU). 
At the end of the copy operation, P055 is reset to P055=0xy.  
011 to 143 
Ind: None 
FS=012 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
r056 
(G175) 
Display of active function data set 
1 to 4 
Ind: None 
Type: O2 
P052 = 3 
P057 
(G175) 
Copy Bico data set 
This parameter allows parameter set 1 or 2 to be copied
to parameter set 1 
or 2. This function is applicable only to parameters with 2 indices in the Bico 
data set (see also Section 9.1, Data sets and Section 9.11, and Section 8, 
Sheet G175). 
0xy 
Do nothing
, automatic resetting value at the end of a copy 
operation. 
1xy 
The contents of parameter set x (source data set, x=1 or 2) are 
copied
to parameter set y (target data set, y=1 or 2) (parameter 
set x remains unchanged, the original contents of parameter set 
y are overwritten). 
x and y are the respective parameter set numbers (1 or 2) of the 
source and target parameter sets. 
The copy operation is started by switching P057 over into parameter mode 
when P057=1xy. 
During the copy operation, the numbers of the parameters being copied are 
displayed on the operator panel (PMU). 
At the end of the copy operation, P057 is reset to P057=0xy. 
011 to 121 
Ind: None 
FS=012 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
r058 
(G175) 
Display of active Bico data set 
1 to 2 
Ind: None 
Type: O2 
P052 = 3 
r059 
Display of operating state 
Meaning as for r000 
0.0 to 14.5 
0.1 
Ind: None 
Type: O2 
P052 = 3 
11.4  Definition of SIMOREG DC-MASTER converter 
r060 
(G101) 
Software version 
Converter software release 
i001:  CUD 
i002:  Slot D (board location 2) 
i003:  Slot E (board location 2) 
i004:  Slot F (board location 3) 
i005:  Slot G (board location 3) 
0.0 to 9.9 
0.1 
Ind: 5 
Type: O2 
P052 = 3 
r061 
(G101) 
Creation date of software 
i001:  Year 
i002:  Month 
i003:  Day 
i004:  Hour 
i005:  Minute 
Ind: 5 
Type: O2 
P052 = 3 
r062 
(G101) 
Checksum 
i001:  Converter firmware checksum 
i002:  Boot sector checksum 
Ind: 2 
Type: L2 
P052 = 3 
11-14 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
r063 
(G101) 
Board code 
Identification code of boards mounted in locations 1 to 3 of electronics box. 
CUDx
F
D
E
G
1
3
2
Arrangement of
board locations 1 to 3
and slots D to G in
electronics box
i001:  Board in location 1 
71: CUD1 
72: CUD1 + CUD2 
i002:  Board in slot D (upper slot of location 2) 
111: 
Pulse encoder board (SBP)   [SW 1.8 and later]
131 to 139: 
Technology board 
141 to 149: 
Communications board 
151, 152, 161:  Special board (EB1, EB2, SLB) 
i003:  Board in slot E (lower slot of location 2) 
111: 
Pulse encoder board (SBP)   [SW 1.8 and later]
131 to 139: 
Technology board 
141 to 149: 
Communications board 
151, 152, 161:  Special board (EB1, EB2, SLB) 
i004:  Board in slot F (upper slot of location 3) 
111: 
Pulse encoder board (SBP)   [SW 1.8 and later]
141 to 149: 
Communications board 
151, 152, 161:  Special board (EB1, EB2, SLB) 
i005:  Board in slot G (lower slot of location 3) 
111: 
Pulse encoder board (SBP)   [SW 1.8 and later]
141 to 149: 
Communications board 
151, 152, 161:  Special board (EB1, EB2, SLB) 
Ind: 5 
Type: O2 
P052 = 3 
r064 
(G101) 
Board compatibility 
Compatibility identifier of boards in locations 1 to 3 of electronics box. 
The compatibility identifier is bit-coded. To ensure the compatibility of a 
board, it must have a "1" setting at the same bit location of the parameter 
value as the CUD (in location 1 / index i001). 
Indices: 
i001:  Compatibility identifier of board in location 1 
i002:  Compatibility identifier of board in slot D 
i003:  Compatibility identifier of board in slot E 
i004:  Compatibility identifier of board in slot F 
i005:  Compatibility identifier of board in slot G 
Example: 
Index  Value 
Bit representation 
Compatible with CUD 
i001  253 
0000 0000 1111 1101 
i002  002 
0000 0000 0000 0010 
no 
i003  001 
0000 0000 0000 0001 
yes 
Ind: 5 
Type: O2 
P052 = 3 
r065 
(G101) 
Software identifiers 
Extended software version identifiers in locations 1, 2, and 3 of the 
electronics box 
Indices: 
i001:  Software identifier of the board in location 1 
i002:  Software identifier of the board in slot D 
i003:  Software identifier of the board in slot E 
i004:  Software identifier of the board in slot F 
i005:  Software identifier of the board in slot G 
Ind: 5 
Type: O2 
P052 = 3 