pdf renderer c# : Adding a jpeg to a pdf application SDK utility azure wpf .net visual studio OPI_simoreg_DC_0707_en51-part1906

SIEMENS AG    6RX1700-0AD76 
11-45 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P357 
FDS 
Threshold for tachometer interruption monitoring 
F042 is suppressed if the actual EMF value is lower than the value set in 
P357. 
The setting is entered as a % of the ideal mean DC voltage value at α=0, 
i.e. as a % of P078.001 
*
1.35 
10 to 70 
[%] 
1% 
Ind: 4 
FS=10 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P360 
(G180)  
(G181) 
Response delay for external faults and alarms 
The fault message or alarm is not activated on the converter until the 
appropriate input or corresponding control word bit (as selected in P675, 
P686, P688 or P689) has been in the LOW state for at least the time period 
set in this parameter (see also Section 8, Sheets G180 and G181). 
i001:  Delay for external fault 1 
i002:  Delay for external fault 2 
i003:  Delay for external alarm 1 
i004:  Delay for external alarm 2 
0 to 10000 
[ms] 
1ms 
Ind: 4 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P361 
FDS 
Delay time for the undervoltage monitoring 
[SW 1.7 and later] 
Activation of the fault message F006 (line undervoltage) is delayed by the 
time that can be set in this parameter. During this delay time firing pulses 
are output! 
Another time which is parameterized for automatic restarting (P086) only 
begins after the time set here has elapsed. 
0 to 60000 
[ms] 
1ms 
Ind: 4 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
on-line 
P362 
FDS 
Delay time for the overvoltage monitoring 
[SW 1.7 and later] 
Activation of the fault message F007 (line overvoltage) is delayed by the 
time that can be set in this parameter. During this delay time firing pulses 
are output! 
Another time which is parameterized for automatic restarting (P086) only 
begins after the time set here has elapsed. 
0 to 60000 
[ms] 
1ms 
Ind: 4 
FS=10000 
Type: O2 
P052 = 3 
P051 = 40 
on-line 
P363 
FDS 
Threshold for the minimum line frequency  
[SW 1.8 and later] 
If the line frequency falls below the value set here and does not rise above it 
again within the "restart" time set in P086, the fault message F008 is 
activated. As long as the line frequency is below the value set here, the 
drive is kept in operating state o4 or o5.  
[values < 45.0 Hz can be set in SW 1.9 and later]  
CAUTION
Operation in the extended frequency range between 23 Hz and 110 Hz 
is available on request. 
23.0 to 60.0 
[Hz] 
0.1 Hz 
Ind: 4 
FS=45.0 
Type: O2 
P052 = 3 
P051 = 40 
on-line 
P364 
FDS 
Threshold for the maximum line frequency  
[SW 1.8 and later] 
If the line frequency rises above the value set here and does not fall below it 
again within the "restart" time set in P086, the fault message F009 is 
activated. As long as the line frequency is above the value set here, the 
drive is kept in operating state o4 or o5.  
CAUTION
Operation in the extended frequency range between 23 Hz and 110 Hz 
is available on request. 
50.0 to 110.0 
[Hz] 
0.1 Hz 
Ind: 4 
FS=65.0 
Type: O2 
P052 = 3 
P051 = 40 
on-line 
11.19  Setting values for limit-value monitors 
(see also Section 8, Sheet G187 und G188) 
n < n
min
 signal 
P370 
FDS 
(G187) 
Speed threshold n
min
Speed threshold for n < n
min
limit-value monitor. 
Note: 
This threshold also affects the sequence of control operations for 
"Shutdown", "Fast stop", cancellation of the "Inching" or "Crawling" 
command, the "Braking with field reversal" function and the brake control 
operation (see Section 9). 
0.00 to 199.99 
[%] 
0.01% of maximum 
speed 
Ind: 4 
FS=0,50 
Type: O2 
P052 = 3 
P051 = 40 
Online 
Adding a jpeg to a pdf - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
add an image to a pdf form; add an image to a pdf with acrobat
Adding a jpeg to a pdf - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
add photo to pdf for; how to add an image to a pdf file
11-46 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P371 
FDS 
(G187) 
Hysteresis for n < n
min
signal 
This value is added to the response threshold if n < n
min
is active. 
0.00 to 199.99 
[%] 
0.01% of maximum 
speed 
Ind: 4 
FS=0,50 
Type: O2 
P052 = 3 
P051 = 40 
Online 
n < n
comp.
signal 
P373 
FDS 
(G187) 
Speed threshold n
comp.
Speed threshold for n < n
comp. 
signal 
0.00 to 199.99 
[%] 
0.01% of maximum 
speed 
Ind: 4 
FS=100.00 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P374 
FDS 
(G187) 
Hysteresis for < n
comp.
signal (n < n
comp.
signal) 
This value is added to the response threshold if n < n
comp.
is active. 
0.00 to 199.99 
[%] 
0.01% of maximum 
speed 
Ind: 4 
FS=3.00 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P375 
FDS 
(G187) 
OFF delay for n < n
comp.
signal 
0.0 to 100.0 
[s] 
0.1s 
Ind: 4 
FS=3.0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
Setpoint/actual value deviation 2 
P376 
FDS 
(G187) 
Permissible setpoint/actual value deviation 2 
[SW 1.9 and later] 
0.00 to 199.99 
[%] 
0.01% of maximum 
speed 
Ind: 4 
FD=3.00 
Type: O2 
P052 = 3 
P051 = 40 
on-line 
P377 
FDS 
(G187) 
Hysteresis for setpoint/actual value deviation 2 signal 
[SW 1.9 and later] 
This value is added to the response threshold if a setpoint/actual value 
deviation signal is active 
0.00 to 199.99 
[%] 
0.01% of maximum 
speed 
Ind: 4 
FS=1.00 
Type: O2 
P052 = 3 
P051 = 40 
on-line 
P378 
FDS 
(G187) 
Response delay for setpoint/actual value deviation signal 2 
[SW 1.9 and later] 
0.0 to 100.0 
[s] 
0.1s 
Ind: 4 
FS=3.0 
Type: O2 
P052 = 3 
P051 = 40 
on-line 
Overspeed 
P380 
FDS 
(G188) 
Maximum speed in positive direction of rotation 
0.0 to 199.9 
[%] 
0.1% of maximum 
speed 
Ind: 4 
FS=120.0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P381 
FDS 
(G188) 
Maximum speed in negative direction of rotation 
-199.9 to 0.0 
[%] 
0.1% of maximum 
speed 
Ind: 4 
FS=-120.0 
Type: I2 
P052 = 3 
P051 = 40 
Online 
Setpoint/actual value deviation 1 
P388 
FDS 
(G187) 
Permissible deviation between setpoint and actual value 1 
0.00 to 199.99 
[%] 
0.01% of maximum 
speed 
Ind: 4 
FS=3.00 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P389 
FDS 
(G187) 
Hysteresis for setpoint/actual value deviation signal 1 
This value is added to the response threshold if a setpoint/actual value 
deviation signal is active 
0.00 to 199.99 
[%] 
0.01% of maximum 
speed 
Ind: 4 
FS=1.00 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P390 
FDS 
(G187) 
Response delay for setpoint/actual value deviation signal 1 
0.0 to 100.0 
[s] 
0.1s 
Ind: 4 
FS=3.0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
VB.NET PDF Library SDK to view, edit, convert, process PDF file
Capable of adding PDF file navigation features to your VB.NET program. Capable of adding PDF file navigation features to your VB.NET program. How To Tutorials.
how to add a jpg to a pdf; how to add jpg to pdf file
VB.NET PDF Page Insert Library: insert pages into PDF file in vb.
Support adding PDF page number. Offer PDF page break inserting function. DLLs for Adding Page into PDF Document in VB.NET Class. Add necessary references:
add a picture to a pdf file; how to add image to pdf in preview
SIEMENS AG    6RX1700-0AD76 
11-47 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
I
f
< I
f min
signal 
P394 
FDS 
(G188) 
Field current threshold I
f min
Field current threshold for I
f
< I
f min
limit-value monitor
.
Note: 
This threshold affects the sequence of control operations for the "Direction 
of rotation reversal using field reversal" and "Braking with field reversal" 
functions (see Section 9). 
The I
f
< I
f min
signal is connected to binector B0215, the actual value at 
field current controller input K0265 is applied as I
f
B0215 = 0 when K0265 > threshold set in P394  
B0215 = 1 when K0265 < threshold set in P394 + hysteresis set in P395 
 1 transition takes place when K0265 < P394  
 0 transition takes place when K0265 > P394 + P395 
0.00 to 199.99 
[%] 
0.01% of converter 
rated field DC 
current (r073.i02) 
Ind: 4 
FS=3.00 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P395 
FDS 
(G188) 
Hysteresis for I
f
< I
f min
signal 
This value is added to the response threshold if I
f
< I
f min 
is active. 
(see also P394) 
0.00 to 100.00 
[%] 
0.01% of converter 
rated field DC 
current (r073.i02) 
Ind: 4 
FS=1.00 
Type: O2 
P052 = 3 
P051 = 40 
Online 
Field current monitoring 
Fault message F005 (fault value 4) is activated if the actual field current (K0265) is lower than the percentage of the field current setpoint 
(K0268) set in P396 for longer than the time set in parameter P397.  
F005 is also triggered if  "I 
Field extern
< I 
f min
" (see P265) is the case for longer than the time set at P397. 
Note: 
Fault message F005 is only activated, however, if the field current setpoint is > 2% of the converter rated DC current of the field (r073.i02) 
ist. 
P396 
FDS 
(G167) 
Threshold for field current monitoring 
[SW 1.9 and later]
1 to 100 
[%] 
0.01% of setpoint at 
field current con-
troller input (K0268) 
Ind: 4 
FS=50 
Type: O2 
P052 = 3 
P051 = 40 
on-line 
P397 
FDS 
(G167) 
Field current monitoring time 
[SW 1.9 and later] 
0.02 to 60.00 
[s] 
0.01s 
Ind: 4 
FS=0.50 
Type: O2 
P052 = 3 
P051 = 40 
on-line 
I
f
< I
f x
signal 
P398 
FDS 
(G188) 
Field current threshold I
f x
Setpoint-oriented field current threshold for I
f
< I
f x 
limit-value monitor. 
Note: 
This threshold affects the sequence of control operations for the "Direction 
of rotation reversal using field reversal" and "Braking with field reversal" 
functions (see Section 9). 
The I
f
< I
f x
signal is connected to binector B0216, the actual value at field 
current controller input K0265 is applied as I
f
B0216 = 0 when K0265 > threshold set in P398  
B0216 = 1 when K0265 < threshold set in P398 + hysteresis set in P399 
 1 transition takes place when K0265 < P398  
 0 transition takes place when K0265 > P398 + P399 
0.00 to 199.99 
[%] 
0.01% of setpoint at 
field current 
controller input 
(K0268) 
Ind: 4 
FS=80.00 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P399 
FDS 
(G188) 
Hysteresis for I
f
< I
f x
signal 
This value is added to the response threshold if I
f
< I
f x 
is active. 
(see also P398) 
0.00 to 100.00 
[%] 
0.01% of converter 
rated field DC 
current (r073.i02) 
Ind: 4 
FS=1.00 
Type: O2 
P052 = 3 
P051 = 40 
Online 
11.20  Settable fixed values 
Function:  The value set in the parameter is applied to the specified connector 
P401 
FDS 
(G120) 
K401 fixed value 
is applied to connector K0401  
-199.99 to 199.99 
[%] 
0.01% 
Ind: 4 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
C# PDF Page Insert Library: insert pages into PDF file in C#.net
are capable of adding and inserting (empty) PDF page or pages from various file formats, such as PDF, Tiff, Word, Excel, PowerPoint, Bmp, Jpeg, Png, Gif, and
how to add an image to a pdf; how to add image to pdf acrobat
C# PDF insert text Library: insert text into PDF content in C#.net
Supports adding text to PDF in preview without adobe reader installed in ASP.NET. Powerful .NET PDF edit control allows modify existing scanned PDF text.
adding an image to a pdf; how to add image to pdf in acrobat
11-48 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P402 
FDS 
(G120) 
K402 fixed value 
is applied to connector K0402  
-199.99 to 199.99 
[%] 
0.01% 
Ind: 4 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P403 
FDS 
(G120) 
K403 fixed value 
is applied to connector K0403  
-199.99 to 199.99 
[%] 
0.01% 
Ind: 4 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P404 
FDS 
(G120) 
K404 fixed value 
is applied to connector K0404  
-199.99 to 199.99 
[%] 
0.01% 
Ind: 4 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P405 
FDS 
(G120) 
K405 fixed value 
is applied to connector K0405  
-199.99 to 199.99 
[%] 
0.01% 
Ind: 4 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P406 
FDS 
(G120) 
K406 fixed value 
is applied to connector K0406  
-199.99 to 199.99 
[%] 
0.01% 
Ind: 4 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P407 
FDS 
(G120) 
K407 fixed value 
is applied to connector K0407  
-199.99 to 199.99 
[%] 
0.01% 
Ind: 4 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P408 
FDS 
(G120) 
K408 fixed value 
is applied to connector K0408  
-199.99 to 199.99 
[%] 
0.01% 
Ind: 4 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P409 
FDS 
(G120) 
K409 fixed value 
is applied to connector K0409  
-199.99 to 199.99 
[%] 
0.01% 
Ind: 4 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P410 
FDS 
(G120) 
K410 fixed value 
is applied to connector K0410  
-199.99 to 199.99 
[%] 
0.01% 
Ind: 4 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P411 
FDS 
(G120) 
K411 fixed value 
is applied to connector K0411  
-199.99 to 199.99 
[%] 
0.01% 
Ind: 4 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P412 
FDS 
(G120) 
K412 fixed value 
is applied to connector K0412  
-32768 to 32767 
Ind: 4 
FS=0 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P413 
FDS 
(G120) 
K413 fixed value 
is applied to connector K0413  
-32768 to 32767 
Ind: 4 
FS=0 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P414 
FDS 
(G120) 
K414 fixed value 
is applied to connector K0414  
-32768 to 32767 
Ind: 4 
FS=0 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P415 
FDS 
(G120) 
K415 fixed value 
is applied to connector K0415  
-32768 to 32767 
Ind: 4 
FS=0 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P416 
FDS 
(G120) 
K416 fixed value 
is applied to connector K0416  
-32768 to 32767 
Ind: 4 
FS=0 
Type: I2 
P052 = 3 
P051 = 40 
Online 
11.21  Fixed control bits 
Function:  The value set in the parameter is applied to the specified binector 
P421 
FDS 
(G120) 
B421 fixed bit 
is applied to binector B0421  
0 to 1 
Ind: 4 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P422 
FDS 
(G120) 
B422 fixed bit 
is applied to binector B0422  
0 to 1 
Ind: 4 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P423 
FDS 
(G120) 
B423 fixed bit 
is applied to binector B0423  
0 to 1 
Ind: 4 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P424 
FDS 
(G120) 
B424 fixed bit 
is applied to binector B0424  
0 to 1 
Ind: 4 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P425 
FDS 
(G120) 
B425 fixed bit 
is applied to binector B0425  
0 to 1 
Ind: 4 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P426 
FDS 
(G120) 
B426 fixed bit 
is applied to binector B0426  
0 to 1 
Ind: 4 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P427 
FDS 
(G120) 
B427 fixed bit 
is applied to binector B0427  
0 to 1 
Ind: 4 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
C# PDF Digital Signature Library: add, remove, update PDF digital
PDF to Word, VB.NET extract text from PDF, VB.NET convert PDF to Jpeg, VB.NET Help to Improve the Security of Your PDF File by Adding Digital Signatures.
adding images to pdf files; how to add image to pdf
VB.NET PDF insert text library: insert text into PDF content in vb
VB.NET PDF - Insert Text to PDF Document in VB.NET. Providing Demo Code for Adding and Inserting Text to PDF File Page in VB.NET Program.
add jpg to pdf; add jpeg signature to pdf
SIEMENS AG    6RX1700-0AD76 
11-49 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P428 
FDS 
(G120) 
B428 fixed bit 
is applied to binector B0428  
0 to 1 
Ind: 4 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
11.22  Digital setpoint input (fixed setpoint, inching and crawling setpoints) 
(see also Section 8, Sheets G127, G129 and G130) 
Fixed setpoint  
Function:  Up to 8 connectors can be selected in P431 indices .01 to .08. These can be applied as an additional fixed setpoint (K0204, 
K0209) via the binectors selected in P430, indices .01 to .08 (setpoint is applied when binector switches to log. "1" state). P432 
indices .01 to .08 can be set to define for each setpoint individually whether the ramp-function generator must be bypassed on 
setpoint injection. 
If fixed setpoint injection is not selected, the connector set in P433 is applied to K0209. 
P430 
(G127) 
Source for fixed-setpoint injection 
Selection of binector to control injection of the fixed setpoint 
("1" state = fixed setpoint injected). 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 8 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P431 
(G127) 
Source for fixed setpoint 
Selection of connector to be injected as the fixed setpoint 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 8 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P432 
(G127) 
Source for selection of ramp-function generator bypass 
Selection as to whether or not ramp-function generator must be bypassed 
when the fixed setpoint is injected. 
The ramp-function generator is bypassed if the AND operation between the 
binector selected via an index of P430 and the setting in the same index of 
P432 produces a log. "1" 
0 to 1 
Ind: 8 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P433 
FDS 
(G127) 
Source for standard setpoint 
Selection of the connector to be applied if fixed-setpoint injection is not 
selected 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 4 
FS=11 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
Inching setpoint  
Function:  Up to 8 connectors can be selected in P436 indices .01 to .08. These can be applied as an inching setpoint (K0202, K0207) via 
the binectors selected in P435, indices .01 to .08 (setpoint is applied when binector switches to log. "1" state). P437 indices .01 
to .08 can be set to define for each setpoint individually whether the ramp-function generator must be bypassed on setpoint 
injection. If more than one inching setpoint is injected, an output value corresponding to inching setpoint = 0% is applied. 
If inching setpoint injection is not selected, the connector set in P438 is applied to K0207. 
P435 
(G129) 
Source for injection of inching setpoint 
Selection of binector to control injection of the inching setpoint 
("1" state = inching setpoint injected). 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 8 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P436 
(G129) 
Source for inching setpoint 
Selection of connector to be injected as the inching setpoint 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 8 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
C# PDF File & Page Process Library SDK for C#.net, ASP.NET, MVC
text from PDF, VB.NET convert PDF to Jpeg, VB.NET splitting a PDF to two and four new PDF files are Provides you with examples for adding an (empty) page to a
adding images to pdf; how to add an image to a pdf file in acrobat
C# Create PDF Library SDK to convert PDF from other file formats
What's more, you can also protect created PDF file by adding digital signature (watermark) on PDF using C# code. Create PDF from Jpeg, png, images.
add picture pdf; add picture to pdf
11-50 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P437 
(G129) 
Source for selection of ramp-function generator bypass 
Selection as to whether or not ramp-function generator must be bypassed 
when the inching setpoint is injected. 
The ramp-function generator is bypassed if the AND operation between the 
binector selected via an index of P435 and the setting in the same index of 
P437 produces a log. "1". 
0 to 1 
Ind: 8 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P438 
FDS 
(G129) 
Source for standard setpoint 
Selection of the connector to be applied if inching-setpoint injection is not 
selected 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 4 
FS=208 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
Crawling setpoint 
Function:  Up to 8 connectors can be selected in P441 indices .01 to .08. These can be applied as an additional crawling setpoint (K0201, 
K0206) via the binectors selected in P440, indices .01 to .08. P445 can be set to define whether the setpoint must be applied 
when the selected binectors have reached the log. "1" state (when P445=0) or in response to a 0 → 1 transition (when 
P445=1). When setpoint injection in response to a 0 → 1 transition is selected, the setpoint injection function is reset when the 
binector selected in P444 switches to the log. "0" state. P442 indices .01 to .08 can be set to define for each setpoint 
individually whether the ramp-function generator must be bypassed on setpoint injection. 
If crawling setpoint injection is not selected, the connector set in P443 is applied to K0206. 
P440 
(G130) 
Source for injection of crawling setpoint 
Selection of binector to control injection of the crawling setpoint. 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 8 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P441 
(G130) 
Source for crawling setpoint 
Selection of connector to be injected as the crawling setpoint 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 8 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P442 
(G130) 
Source for selection of ramp-function generator bypass 
Selection as to whether or not ramp-function generator must be bypassed 
when the crawling setpoint is injected. 
The ramp-function generator is bypassed if the AND operation between the 
binector selected via an index of P440 and the setting in the same index of 
P442 produces a log. "1". 
0 to 1 
Ind: 8 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P443 
FDS 
(G130) 
Source for standard setpoint 
Selection of the connector to be applied if crawling-setpoint injection is not 
selected 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 4 
FS=207 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P444 
BDS 
(G130) 
Source for standstill command 
Selection of the binector to control the standstill operation (OFF1) or 
resetting of crawling setpoint injection when P445=1 (log. "0" state = reset). 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
C# PDF Library SDK to view, edit, convert, process PDF file for C#
Capable of adding PDF file navigation features to your C# program. Perform annotation capabilities to mark, draw, and visualize objects on PDF document page.
add image to pdf java; how to add image to pdf form
SIEMENS AG    6RX1700-0AD76 
11-51 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P445 
(G130) 
Selection of level/edge for switch-on/crawling 
Selection to define whether ON command must be input via terminal 37 and 
the crawling setpoint injected in response to a log. "1" level or to a 0 → 
transition 
ON with log. "1" state at terminal 37 and 
injection of crawling setpoint with binectors selected in P440 in 
log. "1" state 
ON in response to 0 → 1 transition at terminal 37 and 
injection of crawling setpoint in response to 0 → 1 transition of 
binectors selected in P440 
With this setting, the ON command or injection command for the 
crawling setpoint is stored. The memory is reset when the 
binector selected in P444 switches to the log. "0" state. 
0 to 1 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
11.23  Position sensing with pulse encoder 
See parameters P140 to P148 for pulse encoder definition and monitoring 
P450 
FDS 
(G145) 
Resetting of position counter 
Reset position counter OFF 
Reset position counter with zero marker 
Reset position counter with zero marker when LOW signal is 
applied to terminal 39 
Reset position counter when LOW signal is applied to terminal 
39 
Note: Counter resetting with P450 = 2 and 3 is executed in the hardware 
and is not affected by how the binectors controlled by terminal 39 are 
interconnected 
0 to 3 
Ind: 4 
FS=1 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P451 
FDS 
(G145) 
Position counter hysteresis 
Hysteresis for rotational direction reversal OFF 
Hysteresis for rotational direction reversal ON (the first pulse 
encoder input pulse after a change in rotational direction is not 
counted) 
0 to 1 
Ind: 4 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P452 
BDS 
(G145) 
Source for "Reset position counter" command  
[SW 1.9 and later] 
Selection of binector to control resetting of the position counter. 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
off-line 
P453 
BDS 
(G145) 
Source for "Enable zero marker counter" command   [SW 1.9 and later] 
Selection of binector to control enabling of the zero marker counter 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 2 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
off-line 
11.24  Connector selector switches 
(see also Section 8, Function Diagram Sheet G124) 
P455 
(G124) 
Source for inputs of connector selector switch 1 
[SW 1.9 and later]
Selection of connectors for the input signals for connector selector switch 1. 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
off-line 
P456 
(G124) 
Source for control of connector selector switch 1  
[SW 1.9 and later] 
Selection of binectors to control connector selector switch 1. 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
off-line 
11-52 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P457 
(G124) 
Source for inputs of connector selector switch 2 
[SW 1.9 and later]
Selection of connectors for the input signals for connector selector switch 2. 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
off-line 
P458 
(G124) 
Source for control of connector selector switch 2  
[SW 1.9 and later] 
Selection of binectors to control connector selector switch 2. 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
off-line 
11.25  Motorized potentiometer 
(see also Section 8, Sheet G126) 
P460 
FDS 
(G126) 
Control word for motorized potentiometer ramp-function generator 
The motorized potentiometer ramp generator is bypassed in 
Automatic mode (same effect as for P462 and P463 = 0.01, i.e. 
the generator output is made to follow the automatic setpoint 
without delay) 
Motorized potentiometer ramp generator is active in Manual and 
Automatic modes  
0 to 1 
Ind: 4 
FS=1 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P461 
FDS 
(G126) 
Source for setpoint in Automatic mode 
Selection of the connector to be applied as the Automatic setpoint to the 
ramp-function generator in the motorized potentiometer 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 4 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P462 
FDS 
(G126) 
Ramp-up time for motorized potentiometer 
0.01 to 300.00 
[s] 
0.01s 
Ind: 4 
FS=10.00 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P463 
FDS 
(G126) 
Ramp-down time for motorized potentiometer 
0.01 to 300.00 
[s] 
0.01s 
Ind: 4 
FS=10.00 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P464 
FDS 
(G126) 
Time difference for dy/dt 
Setting of dt
for the output of dy/dt at a connector, 
i.e. on K0241 the change in the output quantity (K0240) is output within the 
time set in P464, multiplied by the factor set in P465  
(unit of time setting is [s] if P465=0 or [min] if P465=1) 
Example: -  The ramp-function generator is currently ramping up with a 
ramp-up time of P462=5s, i.e. a ramp-up operation from y=0% 
to y=100% takes 5s. 
 A time difference dt of P464=2s is set. 
 A dy/dt of 40% appears at connector K0241 since the dy 
within the set dt of 2 s equals (2s/5s)*100%. 
0.01 to 300.00 
[s] 
0.01s 
Ind: 4 
FS=10.00 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P465 
FDS 
(G126) 
Factor of expansion for motorized potentiometer 
The effective ramp-up time, ramp-down time or time difference for dy/dt is 
the product of the time setting in parameter P462, P463 and P464 
respectively, multiplied by the factor set in this parameter. 
Parameters P462, P463 and P464 are multiplied by a factor of 1
Parameters P462, P463 and P464 are multiplied by a factor of 60
0 to 1 
Ind: 4 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P466 
FDS 
(G126) 
Source for motorized potentiometer setting value 
Selection of the connector to be injected as the motorized potentiometer 
setting value 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 4 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P467 
FDS 
(G126) 
Motorized potentiometer starting value 
Starting value of motorized potentiometer after ON when P473 = 0 
-199.9 to 199.9 
[%] 
0.1% 
Ind: 4 
FS=0.0 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P468 
FDS 
(G126) 
Setpoint for "Raise motorized potentiometer” 
Motorized potentiometer manual operation: Setpoint for "Raise motorized 
potentiometer" 
-199.99 to 199.99 
[%] 
0.01% 
Ind: 4 
FS=100.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
SIEMENS AG    6RX1700-0AD76 
11-53 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P469 
FDS 
(G126) 
Setpoint for "Lower motorized potentiometer ” 
Motorized potentiometer manual operation: Setpoint for "Lower motorized 
potentiometer" 
-199.99 to 199.99 
[%] 
0.01% 
Ind: 4 
FS=-100.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P470 
BDS 
(G126) 
Source for clockwise/counter-clockwise switchover 
Selection of binector to control "Clockwise/counter-clockwise 
switchover" 
("0" state = clockwise). 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P471 
BDS 
(G126) 
Source for manual/automatic switchover 
Selection of binector to control "Manual/automatic switchover" 
("0" state = manual). 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P472 
BDS 
(G126) 
Source for set motorized potentiometer 
Selection of binector to control "Set motorized potentiometer" 
("0" to "1" transition = set motorized potentiometer). 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P473 
FDS 
(G126) 
Storage of output value 
No storage of output value:
The output is set to 0 in all operating states of >o5. 
The starting point after ON is determined by P467 (MOP starting 
value). 
Non-volatile storage of output value:
The output value remains stored in all operating states and after 
voltage disconnection or failure. The last value stored is output 
again after voltage recovery/reconnection. 
0 to 1 
Ind: 4 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
11.26  Oscillation 
Function:   
Parameters P480 to P483 define the waveshape of a rectangular signal (oscillation setpoint K0203). The value set in P480 determines the 
signal level for the time period set in P481 and the value set in P482 the signal level for the time period set in P483.  
Oscillation:
Selected in P485. The free-running rectangular signal is switched through to the output K0208. 
P480 
FDS 
(G128) 
Oscillation setpoint 1 
-199.9 to 199.9 
[%] 
0.1% of maximum 
speed 
Ind: 4 
FS=0,5 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P481 
FDS 
(G128) 
Oscillation time 1 
0.1 to 300.0 
[s] 
0.1s 
Ind: 4 
FS=0.1 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P482 
FDS 
(G128) 
Oscillation setpoint 2 
-199.9 to 199.9 
[%] 
0.1% of maximum 
speed 
Ind: 4 
FS=-0,4 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P483 
FDS 
(G128) 
Oscillation time 2 
0.1 to 300.0 
[s] 
0.1s 
Ind: 4 
FS=0.1 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P484 
FDS 
(G128) 
Source for standard setpoint 
Selection of connector to be injected as the output value when the 
"Oscillation" function is not selected 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 4 
FS=209 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
11-54 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P485 
BDS 
(G128) 
Source for oscillation selection 
Selection of binector to control activation of the "Oscillation" function 
(log. "1" state = oscillation active) 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
11.27  Definition of "Motor interface" 
(see also Section 8, Sheets G185 und G186) 
CAUTION!
The encoders for measurement and monitoring of the brush length, bearing condition, air flow and motor temperature must be 
safely isolated from the power circuit. 
P490 
(G185) 
Selection of temperature sensor for analog monitoring of motor 
temperature 
i001:  Temperature sensor at terminals 22 / 23: 
i002:  Temperature sensor at terminals 204 / 205: 
Settings: 
No temperature sensor 
KTY84 
PTC thermistor with R=600  1) 
PTC thermistor with R=1200  1) 
PTC thermistor with R=1330  1) 
PTC thermistor with R=2660  1) 
1)  PTC thermistor according to DIN 44081 / 44082 with specified R at rated 
response temperature, 1330 on Siemens motors (setting 4 must be 
selected). When a PTC thermistor is selected as the temperature 
sensor, it is not necessary to set parameters P491 and P492 (alarm and 
trip temperatures). These two temperatures are predetermined by the 
type of PTC thermistor installed. Whether an alarm or fault is output 
when the operating point of the PTC thermistor is reached depends on 
how the relevant input is parameterized (P493.F or P494.F). 
0 to 5 
Ind: 2 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P491 
FDS 
(G185) 
Analog monitoring of motor temperature: Alarm temperature 
Operative only when P490.x=1. 
0 to 200 
[°C] 
1°C 
Ind: 4 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P492 
FDS 
(G185) 
Analog monitoring of motor temperature: Trip temperature 
Operative only when P490.x=1. 
0 to 200 
[°C] 
1°C 
Ind: 4 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P493 
FDS 
(G185) 
Motor temperature analog 1 (temperature sensor at terminals 22 / 23): 
Tripping of alarm or fault message 
Motor temperature grasped with KTY84 
Monitoring deactivated 
Alarm (A029) at temperature > P491 
Fault message (F029) at temperature > P492 
Alarm (A029) at temperature > P491 and 
fault message (F029) at temperature > P492 
Motor temperature grasped with PTC thermistor 
Monitoring deactivated 
Alarm message (A029) when operating point of PTC thermistor 
is reached 
Fault message (F029) when operating point of PTC thermistor is 
reached 
Illegal setting 
0 to 3 
Ind: 4 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 