SIEMENS AG    6RX1700-0AD76 
11-65 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
Speed controller 
P609 
(G151) 
Source for actual speed controller value 
Selection of connector to be injected as the actual speed controller value 
when P083=4 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
Setting values for configuring of closed-loop field and EMF control 
P610 
(G166) 
Source for gating unit input (field) 
Selection of connector to be applied to the gating unit input (field) 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=252 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P611 
(G165) 
Source for field current controller setpoint 
Limitation at EMF controller output: 
Selection of connectors to be injected as the field current controller 
setpoint. The connectors selected in the four indices are added. 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 4 
FS= 
i001: 277 
i002: 0 
i003: 0 
i004: 0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P612 
(G166) 
Source for actual field current controller value 
Selection of connectors to be injected as the field current controller actual 
value. The two values are added. 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 2 
FS=  
i001: 266 
i002: 0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P613 
(G165) 
Source for variable field current setpoint upper limit 
Limitation at EMF controller output 
Selection of connector to be injected as the variable field current setpoint 
upper limit  
i001..i004 Normalization: 
100% of the connector value corresponds to the rated 
excitation current of the motor (P102) 
i005 
Normalization: 
100% of the connector value corresponds to the actual 
converter rated DC current (field) (r073.002) 
[can be set in SW 1.9 and later] 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 5 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P614 
(G165) 
Source for variable field current setpoint lower limit 
Limitation at EMF controller output 
Selection of connector to be injected as the variable field current setpoint 
lower limit  
i001..i004 Normalization: 
100% of the connector value corresponds to the minimum 
excitation current of the motor (P103) 
i005 
Normalization: 
100% of the connector value corresponds to the actual 
converter rated DC current (field) (r073.002) 
[can be set in SW 1.9 and later] 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 5 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
Add image to pdf file acrobat - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
add jpg to pdf acrobat; add image to pdf in preview
Add image to pdf file acrobat - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
add photo to pdf form; add image to pdf acrobat reader
11-66 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P615 
(G165) 
Source for EMF controller setpoint 
Selection of connectors to be injected as the EMF controller setpoint. The 
connectors selected in the four indices are added. 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 4 
FS= 
i001: 289 
i002: 0 
i003: 0 
i004: 0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P616 
(G165) 
Source for actual EMF controller value 
Selection of connector to be injected as the actual EMF controller value 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=286 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
Configuring of injection of acceleration value 
P619 
(G153) 
Source for acceleration injection value 
Selection of connector to be applied as the acceleration injection value 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=191 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
Speed controller 
Speed controller, setpoint/actual value deviation 
Function:   
The connectors selected in parameters P621 and P622 are added and those selected in P623 and 624 subtracted 
P620 
(G152) 
Source for speed controller setpoint/actual value deviation 
Selection of connector to be injected as the control deviation 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=165 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P621 
(G152) 
Source for speed controller setpoint 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=176 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P622 
(G152) 
Source for speed controller setpoint 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=174 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P623 
(G152) 
Source for actual speed controller value 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=179 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P624 
(G152) 
Source for actual speed controller value 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
Speed controller: Filtering of setpoint and actual value, band-stop filters 
P625 
FDS 
(G152) 
Source for speed controller setpoint 
Selection of connector to be injected as the input signal for speed setpoint 
filtering 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 4 
FS=170 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
.NET PDF Document Viewing, Annotation, Conversion & Processing
Convert image files to PDF. File & Page Process. Add, insert PDF native annotations to PDF file. Edit, update, delete PDF annotations from PDF file. Print.
add a picture to a pdf file; add an image to a pdf
C# PDF Converter Library SDK to convert PDF to other file formats
professional PDF document conversion library toolkit in C#, you can easily perform file conversion from PDF document to image or document
adding images to pdf forms; add picture pdf
SIEMENS AG    6RX1700-0AD76 
11-67 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P626 
FDS 
(G152) 
Source for actual speed controller value 
Selection of connector to be injected as the input signal for actual speed 
value filtering 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 4 
FS=167 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P627 
(G152) 
Source for input of D element 
Selection of connector to be injected as the input signal for the D element 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=178 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P628 
(G152) 
Source for input of band-stop filter 1 
Selection of connector to be injected as the input signal for band-stop filter 1
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=179 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P629 
(G152) 
Source for band-stop filter 2 
Selection of connector to be injected as the input signal for band-stop filter 2
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=177 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
Speed controller droop 
P630 
(G151) 
Source for influencing quantity for speed droop 
Selection of connector to be injected as the influencing quantity 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=162 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
Setting the speed controller I component 
Function:  When the binector selected in P695 switches state from log. "0" to log. "1", the I component of the speed controller is set to the 
value of the connector selected in P631. 
With this function it is possible, for example, to use the same signal (binector) to control controller enabling commands and 
setting of the I component. 
P631 
(G152) 
Source for setting value for speed controller integrator 
Selection of connector to be injected as the setting value for the I 
component 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
Setting values for configuring the setpoint processing function and ramp-function generator 
Limitation at ramp-function generator output (setpoint limitation) 
(see also Section 8, Sheet G136) 
The effective limitations are: 
Upper limit:  
Minimum value of P300 and the four connectors selected with P632 
Lower limit: 
Maximum value of P301 and the four connectors selected with P633 
Note: 
The limiting values for both the positive and negative setpoint limits can have a positive or negative sign. The negative setpoint 
limit, for example, can therefore be parameterized to a positive value and the positive setpoint limit to a negative value. 
P632 
(G137) 
Source for variable positive limitation at ramp-function generator 
output 
Selection of connectors to be injected at the variable positive limitation at 
the ramp-function generator output (setpoint limitation). 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 4 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
C# Windows Viewer - Image and Document Conversion & Rendering in
conversion library toolkit in C#, you can easily perform file conversion from Image and Document Conversion Supported by Windows Viewer. Convert to PDF.
add image pdf; adding a png to a pdf
C# powerpoint - PowerPoint Conversion & Rendering in C#.NET
may easily achieve the following PowerPoint file conversions SDK to convert PowerPoint document to PDF document demo code for PowerPoint to TIFF image conversion
how to add a photo to a pdf document; how to add image to pdf document
11-68 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P633 
(G137) 
Source for variable negative limitation at ramp-function generator 
output 
Selection of connectors to be injected at the variable negative limitation at 
the ramp-function generator output (setpoint limitation). 
0   = connector K0000 
... 
8   = connector K0008 
9   = value as set in parameter P632  (1) 
10  = connector K0010 
etc. 
All connector 
numbers 
Ind: 4 
FS=9 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P634 
(G137) 
Source for limitation input at ramp-function generator output 
Selection of connectors which must be added up to provide the limitation 
input at the ramp-function generator output (setpoint limitation). 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 2 
FS= 
i001: 190 
i002: 0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P635 
FDS 
(G135) 
Source for ramp-function generator setpoint 
Selection of connector to be injected as the ramp-function generator 
setpoint 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 4 
FS=194 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P636 
(G136) 
Source for reduction signal for ramp-function generator times 
Selection of connector to be injected as the reduction signal for the ramp-
function generator times 
i001 acts on ramp-up and ramp-down time (P303, P304) 
i002 acts on lower and upper transition roundings (P305, P306)  
i003 acts on ramp-up time (P303)  
i004 acts on ramp-down time (P304)  
i005 acts on lower transition rounding (P305)  
i006 acts on upper transition rounding (P306) 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 6 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P637 
BDS 
(G136) 
Source for selection of "Ramp-function generator setting 2" 
Selection of binector to control switchover to "Ramp-function generator 
setting 2". 
With a log. "1" signal at the binector, ramp-function generator parameter set 
2 (P307 - P310) is selected. This function has a higher priority than the 
ramp-up integrator function. 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P638 
BDS 
(G136) 
Source for selection of "Ramp-function generator setting 3” 
Selection of binector to control switchover to "Ramp-function generator 
setting 3". 
With a log. "1" signal at the binector, ramp-function generator parameter set 
3 (P311 - P314) is selected. This function has a higher priority than the 
ramp-up integrator function. 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
C# Word - Word Conversion in C#.NET
you may easily achieve the following Word file conversions. XDoc.Word SDK to convert Word document to PDF document C# demo code for Word to TIFF image conversion
add photo to pdf preview; how to add a picture to a pdf document
VB.NET PDF: How to Create Watermark on PDF Document within
Using this VB.NET Imaging PDF Watermark Add-on, you can a watermark that consists of text or image (such as And with our PDF Watermark Creator, users need no
add image field to pdf form; add image pdf document
SIEMENS AG    6RX1700-0AD76 
11-69 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P639 
(G136) 
Source for the ramp-function generator setting values 
Selection of the connectors that are connected as the ramp-function 
generator setting values. 
i001   Setting value for the ramp-function generator output in state log. 
"1" of the binector selected via P640 
i002   Setting value for the ramp-function generator output if the drive 
is not in state "Operating" (B0104=0) and
the binector selected 
via P640 is in state log. "0" 
[i002 only available with SW 1.6 and later] 
0 = Connector K0000 
1 = Connector K0001 
etc. 
All connector 
numbers 
Ind: 2 
FS=167 
Type: L2 
P052 = 3 
P051 = 40 
off-line 
P640 
BDS 
(G136) 
Source for selection of "Set ramp-function generator” 
Selection of binector to control the "Set ramp-function generator" function 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P641 
BDS 
(G136) 
Source for selection of "Bypass ramp-function generator” 
Selection of binector to control the "Bypass ramp-function generator" 
function 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P642 
(G135) 
Source for variable positive limitation of main setpoint 
Selection of connectors to be injected at the variable positive limitation of 
the main setpoint. 
The lowest value in each case of the connectors selected via the 4 indices 
is applied as the limit. 
Note: Negative values at the selected connectors result in a negative 
maximum value at the output of the limitation. 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 4 
FS=2 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P643 
(G135) 
Source for variable negative limitation of main setpoint 
Selection of connectors to be injected at the variable negative limitation of 
the main setpoint. 
The lowest value in each case of the connectors selected via the 4 indices 
is applied as the limit. 
Note: Positive values at the selected connectors result in a positive 
minimum value at the output of the limitation. 
0   = connector K0000 
... 
8   = connector K0008 
9   = value as set in parameter P642  (1) 
10  = connector K0010 
etc. 
All connector 
numbers 
Ind: 4 
FS=9 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P644 
FDS 
(G135) 
Source for main setpoint 
Selection of connector to be injected as the main setpoint 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 4 
FS=206 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P645 
FDS 
(G135) 
Source for additional setpoint 
Selection of connector to be injected as an additional setpoint 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 4 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
VB.NET PowerPoint: VB Code to Draw and Create Annotation on PPT
as a kind of compensation for limitations (other documents are compatible, including PDF, TIFF, MS VB.NET PPT: VB Code to Add Embedded Image Object to
adding a jpg to a pdf; add image to pdf file
BMP to PDF Converter | Convert Bitmap to PDF, Convert PDF to BMP
Also designed to be used add-on for .NET Image Powerful image converter for Bitmap and PDF files; No Support conversion of Bitmap - PDF files in both single &
adding jpg to pdf; add a jpg to a pdf
11-70 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P646 
BDS 
(G136) 
Source for enable signal for ramp-up integrator switchover 
Selection of binector to control enabling of the ramp-function integrator 
switchover function. 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 2 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P647 
BDS 
(G136) 
Source for enable signal for ramp-function generator tracking 
[SW 2.1 and later]
Selection of binector to control enabling of the ramp-function generator 
tracking function. 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 2 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
11.36  Control word, status word 
Selection of sources of control words 1 and 2 
P648 
BDS 
(G180) 
Source for control word 1 
Selection of connector to act as the source for control word 1. 
0   = connector K0000 
... 
8   = connector K0008 
9   = parameters P654 to P675 are effective 
(every individual bit of control word 1 is input by a binector) 
10  = connector K0010 
etc. 
All connector 
numbers 
Ind: 2 
FS=9 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P649 
BDS 
(G181) 
Source for control word 2 
Selection of connector to act as the source for control word 2. 
0   = connector K0000 
... 
8   = connector K0008 
9   = parameters P676 to P691 are effective 
(every individual bit of control word 2 is input by a binector) 
10  = connector K0010 
etc. 
All connector 
numbers 
Ind: 2 
FS=9 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
Display of control words 1 and 2 
r650 
(G180) 
Display of control word 1 
Mode of representation on operator panel (PMU): 
3
2
1
0
4
5
6
7
8
9
10
11
12
13
14
15
Segments 0 to 15 correspond to bits 0 to 15 of the control word 
Segment ON: 
Corresponding bit is in log. "1" state 
Segment OFF: 
Corresponding bit is in log. "0" state 
Ind: None 
Type: V2 
P052 = 3 
r651 
(G181) 
Display of control word 2 
Mode of representation on operator panel (PMU): 
3
2
1
0
4
5
6
7
8
9
10
11
12
13
14
15
Segments 0 to 15 correspond to bits 16 to 31 of the control word 
Segment ON: 
Corresponding bit is in log. "1" state 
Segment OFF: 
Corresponding bit is in log. "0" state 
Ind: None 
Type: V2 
P052 = 3 
PDF to WORD Converter | Convert PDF to Word, Convert Word to PDF
If you want to convert document file PDF formats to out transformation between different kinds of image files and Converter has accurate output, and PDF to Word
adding image to pdf file; how to add an image to a pdf in reader
JPEG to PDF Converter | Convert JPEG to PDF, Convert PDF to JPEG
No need for Adobe Acrobat Reader; Seamlessly integrated into RasterEdge .NET Image SDK; high speed; Get a compressed PDF file after conversion;
add png to pdf preview; adding image to pdf form
SIEMENS AG    6RX1700-0AD76 
11-71 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
Display of status words 1 and 2 
r652 
(G182) 
Display of status word 1 
Mode of representation on operator panel (PMU): 
3
2
1
0
4
5
6
7
8
9
10
11
12
13
14
15
Segments 0 to 15 correspond to bits 0 to 15 of the status word 
Segment ON: 
Corresponding bit is in log. "1" state 
Segment OFF: 
Corresponding bit is in log. "0" state 
Ind: None 
Type: V2 
P052 = 3 
r653 
(G183) 
Display of status word 2 
Mode of representation on operator panel (PMU): 
3
2
1
0
4
5
6
7
8
9
10
11
12
13
14
15
Segments 0 to 15 correspond to bits 16 to 31 of the status word 
Segment ON: 
Corresponding bit is in log. "1" state 
Segment OFF: 
Corresponding bit is in log. "0" state 
Ind: None 
Type: V2 
P052 = 3 
The following parameters are used to select the binectors (some of which are gated with one another or with other signals) to be applied to 
the individual bits of the control word. 
The settings of all these parameters are as follows: 
0 = binector B0000 
1 = binector B0001 
etc. 
The functions and logic operations are also shown on Sheets G180 and G181 in Section 8. 
Control word 1 
P654 
BDS 
(G130) 
Source for control word 1, bit0 
(0=OFF1, 1=ON; ANDed with terminal 37) 
All binector numbers 
Ind: 2 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P655 
BDS 
(G180) 
1st source for control word 1, bit1 
(0=OFF2; ANDed with 2
nd
and 3
rd
sources for bit1) 
All binector numbers 
Ind: 2 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P656 
BDS 
(G180) 
2nd source for control word 1, bit1 
(0=OFF2; ANDed with 1
st
and 3
rd
sources for bit1) 
All binector numbers 
Ind: 2 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P657 
BDS 
(G180) 
3rd source for control word 1, bit1 
(0=OFF2; ANDed with 1
st
and 2
nd
sources for bit1) 
All binector numbers 
Ind: 2 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P658 
BDS 
(G180) 
1st source for control word 1, bit2 
(0=OFF3=Fast stop; ANDed with 2
nd
and 3
rd
sources for bit2) 
All binector numbers 
Ind: 2 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P659 
BDS 
(G180) 
2nd source for control word 1, bit2 
(0=OFF3=Fast stop; ANDed with 1
st
and 3
rd
sources for bit2) 
All binector numbers 
Ind: 2 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P660 
BDS 
(G180) 
3rd source for control word 1, bit2 
(0=OFF3=Fast stop; ANDed with 1
st
and 2
nd
sources for bit2) 
All binector numbers 
Ind: 2 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P661 
BDS 
(G180) 
Source for control word 1, bit3 
(0=pulse disable, 1=enable; ANDed with terminal 38) 
All binector numbers 
Ind: 2 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
11-72 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P662 
BDS 
(G180) 
Source for control word 1, bit4 
(0=set ramp-function generator to zero, 1=enable ramp-function generator) 
All binector numbers 
Ind: 2 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P663 
BDS 
(G180) 
Source for control word 1, bit5 
(0=ramp-function generator stop, 1=ramp-function generator start) 
All binector numbers 
Ind: 2 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P664 
BDS 
(G180) 
Source for control word 1, bit6 
(0=enable setpoint, 1=disable setpoint) 
All binector numbers 
Ind: 2 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P665 
BDS 
(G180) 
1st source for control word 1, bit7 
(01 transition=acknowledge; ORed with 2
nd
and 3
rd
sources for bit7) 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P666 
BDS 
(G180) 
2nd source for control word 1, bit7 
(01 transition=acknowledge; ORed with 1
st
and 3
rd
sources for bit7) 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P667 
BDS 
(G180) 
3rd source for control word 1, bit7 
(01 transition=acknowledge; ORed with 1
st
and 2
nd
sources for bit7) 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P668 
BDS 
(G180) 
Source for control word 1, bit8 
(1=inching bit0) 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P669 
BDS 
(G180) 
Source for control word 1, bit9 
(1=inching bit1) 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P671 
BDS 
(G180) 
Source for control word 1, bit11 
(0=pos. direction of rotation disabled, 1=pos. direction of rotation enabled) 
All binector numbers 
Ind: 2 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P672 
BDS 
(G180) 
Source for control word 1, bit12 
(0= neg. direction of rotation disabled, 1= neg. direction of rotation enabled) 
All binector numbers 
Ind: 2 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P673 
BDS 
(G180) 
Source for control word 1, bit13 
(1=raise motorized potentiometer) 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P674 
BDS 
(G180) 
Source for control word 1, bit14 
(1=lower motorized potentiometer) 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P675 
BDS 
(G180) 
Source for control word 1, bit15 
(0=external fault, 1=no external fault) 
All binector numbers 
Ind: 2 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
Control word 2 
P676 
BDS 
(G181) 
Source for control word 2, bit16 
(select function data set bit 0) 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P677 
BDS 
(G181) 
Source for control word 2, bit17 
(select function data set bit 1) 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P680 
BDS 
(G181) 
Source for control word 2, bit20 
(select fixed setpoint 0) 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P681 
BDS 
(G181) 
Source for control word 2, bit21 
(select fixed setpoint 1) 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
SIEMENS AG    6RX1700-0AD76 
11-73 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P684 
BDS 
(G181) 
Source for control word 2, bit24 
(0=n controller speed droop disabled, 1=enabled) 
All binector numbers 
Ind: 2 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P685 
BDS 
(G181) 
Source for control word 2, bit25 
(0=n controller disabled, 1=n controller enabled) 
All binector numbers 
Ind: 2 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P686 
BDS 
(G181) 
Source for control word 2, bit26 
(0=external fault 2, 1=no external fault 2) 
All binector numbers 
Ind: 2 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P687 
BDS 
(G181) 
Source for control word 2, bit27 
(0=master drive, speed control, 1=slave drive, torque control) 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P688 
BDS 
(G181) 
Source for control word 2, bit28 
(0=external alarm 1, 1=no external alarm 1) 
All binector numbers 
Ind: 2 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P689 
BDS 
(G181) 
Source for control word 2, bit29 
(0=external alarm 2, 1=no external alarm 2) 
All binector numbers 
Ind: 2 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P690 
(G181) 
Source for control word 2, bit30 
(0=select Bico data set 1, 1=select Bico data set 2) 
All binector numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P691 
BDS 
(G181) 
Source for control word 2, Bit31 
[SW 1.8 and later]
Main contactor checkback signal: 
(0 = main contactor dropped out, 1 = main contactor picked up) 
This control input is intended as a means of looping an auxiliary contact of 
the main contactor into the device control. 
During the Power ON routine, this signal must switch to "1" within the time 
period set in P095. If it does not, or it disappears during operation, fault 
message F004 with fault value 6 is activated. 
P691 = 0:  Bit 31 of control word 2 is inoperative. 
(This setting of P691 is always active, regardless of whether 
control word 2 is input in word mode [P649 <> 9] or bit mode 
[P649 = 9]) 
P691 = 1:  Bit 31 of control word 2 is inoperative. 
(This setting of P691 is active only when control word 2 is input 
in bit mode
, i.e. when P649 = 9)  
P691 >= 2: The function of bit 31 of control word 2 has an effect in the case 
of P649=9. 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
11.37  Further configuring measures 
P692 
BDS 
(G166) 
Source for selection of injection of standstill field 
Selection of binector to control injection of the standstill field ("0" state = 
inject standstill field) 
Note:   The delay time set in P258 is not effective when this function is 
active. 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P693 
BDS 
(G165) 
Source for selection of enabling command for EMF controller 
Selection of binector which is to control enabling of the EMF controller 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 2 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
11-74 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P694 
BDS 
(G160) 
Source for selection of enabling command for "Torque limit 
switchover” 
Selection of binector which is to control enabling of the "Torque limit 
switchover" function (1=enable, see also Sheet G160 in Section 8 and P180 
to P183) 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P695 
BDS 
(G152) 
Source for selection of "Set speed controller I component" function 
Selection of binector to control the "Set I component" function 
0 = binector B0000 
1 = binector B0001 
etc. 
When the binector selected in P695 switches from log. "0" to log. "1", the I 
component of the speed controller is set to the value of the connector 
selected in P631. 
With this function it is possible, for example, to use the same signal 
(binector) to control controller enabling commands and setting of the I 
component. 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P696 
BDS 
(G152) 
Source for selection of "Stop speed controller I component" function 
Selection of binector to control the "Stop I component" function 
0 = binector B0000 
1 = binector B0001 
etc. 
When the binector selected in P696 changes to the log. "1" state, the I 
component of the speed controller is stopped. 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P697 
BDS 
(G153) 
Source for selection of enabling of dv/dt injection 
Selection of binector to control enabling of dv/dt injection (state "1" = 
enable) 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 2 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P698 
BDS 
(G152) 
Source for selection of enabling command for speed-dependent speed 
controller PI / P function switchover 
Selection of binector to control enabling of the speed-dependent PI / P 
controller switchover function (see also P222) 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 2 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
11.38  Analog inputs (main actual value, main setpoint, selectable inputs) 
(see also Section 8, Sheets G113 and G114) 
Analog input terminals 4 / 5 (main setpoint) 
P700 
(G113) 
Signal type of "Main setpoint" analog input 
0 =  Voltage input 0 to ±10 V 
1 =  Current input 0 to ±20 mA 
2 =  Current input 4 to 20 mA 
0 to 2 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 