SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P701 
FDS 
(G113) 
Normalization of "Main setpoint" analog input 
This parameter specifies the percentage value which is generated for an 
input voltage of 10V (or an input current of 20mA) at the analog input. 
The following generally applies: 
For voltage input: 
P
V
Y
X
701
10
[%] =
X .. Input voltage in volts 
Y .. % value which is generated for input 
voltage X 
With current input: 
P
mA
Y
X
701
20
[%] =
X .. Input current in mA 
Y .. % value which is generated for input 
current X 
-1000.0 to 1000.0 
[%] 
0.1% 
Ind: 4 
FS=100.0 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P702 
(G113) 
Offset for "Main setpoint" analog input 
-200.00 to 199.99 
[%] 
0.01% 
Ind: None 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P703 
(G113) 
Mode of signal injection at "Main setpoint" analog input 
0 =  Injection of signal with sign 
1 =  Injection of absolute value of signal 
2 =  Injection of signal with sign, inverted 
3 =  Injection of absolute value of signal, inverted 
0 to 3 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P704 
(G113) 
Source for selection of sign reversal at "Main setpoint" analog input 
Selection of binector to control sign reversal at the analog input ("1" state 
= reverse sign) 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P705 
(G113) 
Filtering time for "Main setpoint" analog input 
Note: Hardware filtering of approximately 1 ms is applied as standard. 
0 to 10000 
[ms] 
1ms 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P706 
(G113) 
Source for enabling of "Main setpoint" analog input 
Selection of binector to control enabling of the analog input ("1" state = 
enabled) 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: None 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
How to add an image to a pdf in reader - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
adding an image to a pdf in acrobat; add picture to pdf preview
How to add an image to a pdf in reader - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
how to add jpg to pdf file; add picture to pdf form
11-76 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P707 
(G113) 
Resolution of "Main setpoint" analog input 
The voltage applied to the analog input is converted to a digital value (A/D 
conversion) for further processing. The method used calculates an average 
value of the input voltage over a specific measuring time. 
The A/D conversion process produces a scale for the voltage range of 0 to ± 
10V, the number of steps (divisions) along this scale can be set in P707 (i.e. 
the smallest possible differentiable change in the input voltage 
(quantization) can be set in this parameter). The number of scale steps or 
intervals is referred to as "Resolution". 
The resolution is normally specified in bits: 
± 11 bits means 2 * 2048 scale divisions 
± 12 bits means 2 * 4096 scale divisions 
± 13 bits means 2 * 8192 scale divisions 
± 14 bits means 2 * 16384 scale divisions 
The following applies: 
The higher the resolution, the longer the averaging time and thus also the 
delay period between the application of an analog step change and the 
earliest possible moment of availability of the digital value for further 
processing. 
For this reason, it is important to find a compromise between the resolution 
and delay period. 
Param.  Resolution 
Quantization 
Delay period 
value 
better than 
11 
± 11 bits 
4.4 mV 
0.53 ms 
12 
± 12 bits 
2.2 mV 
0.95 ms 
13 
± 13 bits 
1.1 mV 
1.81 ms 
14 
± 14 bits 
0.56 mV 
3.51 ms 
If the analog input is operating as a current input (0 to 20 mA or 4 to 20 mA), 
the above applies analogously. 
11 to 14 
[Bit] 
1 bit 
Ind: None 
FS=12 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
Analog input terminals 6 / 7 (analog selectable input 1) 
P710 
(G113) 
Signal type of "Analog selectable input 1" 
0 =  Voltage input 0 to ±10 V 
1 =  Current input 0 to ±20 mA 
2 =  Current input 4 to 20 mA 
0 to 2 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P711 
FDS 
(G113) 
Normalization of "Analog selectable input 1" 
This parameter specifies the percentage value which is generated for an 
input voltage of 10V (or an input current of 20mA) at the analog input. 
The following generally applies: 
For voltage input: 
P
V
Y
X
711
10
[%] =
X .. Input voltage in volts 
Y .. % value which is generated for input 
voltage X 
With current input: 
P
mA
Y
X
711
20
[%] =
X .. Input current in mA 
Y .. % value which is generated for input 
current X 
-1000.0 to 1000.0 
[%] 
0.1% 
Ind: 4 
FS=100.0 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P712 
(G113) 
Offset for "Analog selectable input 1" 
-200.00 to 199.99 
[%] 
0.01% 
Ind: None 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P713 
(G113) 
Mode of signal injection at "Analog selectable input 1" 
0 =  Injection of signal with sign 
1 =  Injection of absolute value of signal 
2 =  Injection of signal with sign, inverted 
3 =  Injection of absolute value of signal, inverted 
0 to 3 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
C# Imaging - Scan Barcode Image in C#.NET
RasterEdge Barcode Reader DLL add-in enables developers to add barcode image recognition & types, such as Code 128, EAN-13, QR Code, PDF-417, etc.
adding an image to a pdf file; how to add a picture to a pdf file
C# PDF Image Extract Library: Select, copy, paste PDF images in C#
Get image information, such as its location, zonal information, metadata, and so on. Able to edit, add, delete, move, and output PDF document image.
how to add image to pdf in acrobat; add jpg to pdf preview
SIEMENS AG    6RX1700-0AD76 
11-77 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P714 
(G113) 
Source for selection of sign reversal at "Analog selectable input 1" 
Selection of binector to control sign reversal at the analog input ("1" state 
= reverse sign) 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P715 
(G113) 
Filtering time for "Analog selectable input 1" 
Note: Hardware filtering of approximately 1 ms is applied as standard. 
0 to 10000 
[ms] 
1ms 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P716 
(G113) 
Source for enabling of "Analog selectable input 1" 
Selection of binector to control enabling of the analog input ("1" state = 
enabled) 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: None 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P717 
(G113) 
Resolution of "Analog selectable input 1" 
See P707 
10 to 14 
[Bit] 
1 bit 
Ind: None 
FS=12 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
Analog input terminals 8 / 9 (analog selectable input 2) 
P721 
FDS 
(G114) 
Normalization of "Analog selectable input 2" 
This parameter specifies the percentage value which is generated for an 
input voltage of 10V (or an input current of 20mA) at the analog input. 
The following generally applies: 
For voltage input: 
P
V
Y
X
721
10
[%] =
X .. Input voltage in volts 
Y .. % value which is generated for input 
voltage X 
With current input: 
P
mA
Y
X
721
20
[%] =
X .. Input current in mA 
Y .. % value which is generated for input 
current X 
-1000.0 to 1000.0 
[%] 
0.1% 
Ind: 4 
FS=100.0 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P722 
(G114) 
Offset for "Analog selectable input 2" 
-200.00 to 199.99 
[%] 
0.01% 
Ind: None 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P723 
(G114) 
Mode of signal injection at "Analog selectable input 2" 
0 =  Injection of signal with sign 
1 =  Injection of absolute value of signal 
2 =  Injection of signal with sign, inverted 
3 =  Injection of absolute value of signal, inverted 
0 to 3 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P724 
(G114) 
Source for selection of sign reversal at "Analog selectable input 2" 
Selection of binector to control sign reversal at the analog input ("1" state 
= reverse sign) 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P725 
(G114) 
Filtering time for "Analog selectable input 2" 
Note: Hardware filtering of approximately 1 ms is applied as standard. 
0 to 10000 
[ms] 
1ms 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P726 
(G114) 
Source for enabling of "Analog selectable input 2" 
Selection of binector to control enabling of the analog input ("1" state = 
enabled) 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: None 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
VB.NET PDF Image Extract Library: Select, copy, paste PDF images
DLLs for PDF Image Extraction in VB.NET. In order to run the sample code, the following steps would be necessary. Add necessary references:
how to add image to pdf acrobat; adding an image to a pdf
VB.NET PDF Password Library: add, remove, edit PDF file password
VB: Add Password to PDF with Permission Settings Applied. This VB.NET example shows how to add PDF file password with access permission setting.
acrobat insert image in pdf; add an image to a pdf with acrobat
11-78 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
Analog input terminals 10 / 11 (analog selectable input 3) 
P731 
FDS 
(G114) 
Normalization of "Analog selectable input 3" 
This parameter specifies the percentage value which is generated for an 
input voltage of 10V (or an input current of 20mA) at the analog input. 
The following generally applies: 
For voltage input: 
P
V
Y
X
731
10
[%] =
X .. Input voltage in volts 
Y .. % value which is generated for input 
voltage X 
With current input: 
P
mA
Y
X
731
20
[%] =
X .. Input current in mA 
Y .. % value which is generated for input 
current X 
-1000.0 to 1000.0 
[%] 
0.1% 
Ind: 4 
FS=100.0 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P732 
(G114) 
Offset for "Analog selectable input 3" 
-200.00 to 199.99 
[%] 
0.01% 
Ind: None 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P733 
(G114) 
Mode of signal injection at "Analog selectable input 3" 
0 =  Injection of signal with sign 
1 =  Injection of absolute value of signal 
2 =  Injection of signal with sign, inverted 
3 =  Injection of absolute value of signal, inverted 
0 to 3 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P734 
(G114) 
Source for selection of sign reversal at "Analog selectable input 3" 
Selection of binector to control sign reversal at the analog input ("1" state 
= reverse sign) 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P735 
(G114) 
Filtering time for "Analog selectable input 3" 
Note: Hardware filtering of approximately 1 ms is applied as standard. 
0 to 10000 
[ms] 
1ms 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P736 
(G114) 
Source for enabling of "Analog selectable input 3" 
Selection of binector to control enabling of the analog input ("1" state = 
enabled) 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: None 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
Analog input terminals 103 / 104 (main actual value) 
P741 
FDS 
(G113) 
Normalization for "Main actual value” 
Rated value of input voltage at n
max
(=tachometer voltage at maximum 
speed) 
This parameter defines the maximum speed when P083=1. 
-270.00 to 270.00 
[V] 
0.01V 
Ind: 4 
FS=60.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P742 
(G113) 
Offset for "Main actual value" analog input 
-200.00 to 199.99 
[%] 
0.01% 
Ind: None 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P743 
(G113) 
Mode of signal injection at "Main actual value" analog input 
0 =  Injection of signal with sign 
1 =  Injection of absolute value of signal 
2 =  Injection of signal with sign, inverted 
3 =  Injection of absolute value of signal, inverted 
0 to 3 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P744 
(G113) 
Source for selection of sign reversal at "Main actual value" analog 
input 
Selection of binector to control sign reversal at the analog input ("1" state 
= reverse sign) 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
C# PDF Password Library: add, remove, edit PDF file password in C#
C# Sample Code: Add Password to PDF with Permission Settings Applied in C#.NET. This example shows how to add PDF file password with access permission setting.
add image to pdf online; add picture to pdf
XImage.Barcode Scanner for .NET, Read, Scan and Recognize barcode
VB.NET Write: Add Image to PDF; VB.NET Protect: Add Password to VB.NET Annotate: PDF Markup & Drawing. XDoc.Word for C#; XDoc.Excel for C#; XDoc.PowerPoint for
acrobat add image to pdf; pdf insert image
SIEMENS AG    6RX1700-0AD76 
11-79 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P745 
(G113) 
Filtering time for "Main actual value" analog input 
Note: Hardware filtering of approximately 1 ms is applied as standard. 
0 to 10000 
[ms] 
1ms 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P746 
(G113) 
Source for enabling of "Main actual value" analog input 
Selection of binector to control enabling of the analog input ("1" state = 
enabled) 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: None 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
11.39  Analog outputs 
(see also Section 8, Sheets G115 and G116) 
Analog output terminals 12 / 13 (actual current display) 
P749 
(G115) 
Control word for terminal 12 (actual current display) 
Output with correct sign 
(positive voltage: Current in torque direction MI) 
(negative voltage: Current in torque direction MII) 
Output of absolute value (positive voltage only) 
Output with sign, inverted 
(positive voltage: Current in torque direction MII) 
(negative voltage: Current in torque direction MI) 
Output of absolute value, inverted (negative voltage only) 
0 to 3 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
Analog output terminals 14 / 15 
P750 
(G115) 
Source for output value at analog output 1 
Selection of connector whose value is to applied to the analog output 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Online 
P751 
(G115) 
Mode of signal injection at analog output 1 
0 =  Injection of signal with correct sign 
1 =  Injection of absolute value of signal 
2 =  Injection of signal with sign, inverted 
3 =  Injection of absolute value of signal, inverted 
0 to 3 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P752 
(G115) 
Filtering time for analog output 1 
0 to 10000 
[ms] 
1ms 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P753 
(G115) 
Normalization of analog output 1 
y V
x
P
[ ]
%
= ∗
753
100
x = Normalization input (corresponds to filtering output) 
y = Normalization output (corresponds to output voltage at analog output 
with offset = 0) 
-200.00 to 199.99 
[V] 
0.01V 
Ind: None 
FS=10.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P754 
(G115) 
Offset for analog output 1 
-10.00 to 10.00 
[V] 
0.01V 
Ind: None 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
Analog output terminals 16 / 17 
P755 
(G115) 
Source for output value at analog output 2 
Selection of connector whose value is to applied to the analog output 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Online 
C# PDF Sticky Note Library: add, delete, update PDF note in C#.net
Evaluation library and components enable users to annotate PDF without adobe PDF reader control installed. Able to add notes to PDF using C# source code in
how to add image to pdf; how to add an image to a pdf file in acrobat
C# Create PDF from images Library to convert Jpeg, png images to
List<Bitmap> images = new List<Bitmap>(); images.Add(new Bitmap(Program.RootPath + "\\" 1.gif")); / Build a PDF document with GIF image.
how to add picture to pdf; add photo to pdf for
11-80 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P756 
(G115) 
Mode of signal injection at analog output 2 
0 =  Injection of signal with correct sign 
1 =  Injection of absolute value of signal 
2 =  Injection of signal with sign, inverted 
3 =  Injection of absolute value of signal, inverted 
0 to 3 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P757 
(G115) 
Filtering time for analog output 2 
0 to 10000 
[ms] 
1ms 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P758 
(G115) 
Normalization of analog output 2 
y V
x
P
[ ]
%
= ∗
758
100
x = Normalization input (corresponds to filtering output) 
y = Normalization output (corresponds to output voltage at analog output 
with offset = 0) 
-200.00 to 199.99 
[V] 
0.01V 
Ind: None 
FS=10.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P759 
(G115) 
Offset for analog output 2 
-10.00 to 10.00 
[V] 
0.01V 
Ind: None 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
Analog output terminals 18 / 19 
P760 
(G116) 
Source for output value at analog output 3 
Selection of connector whose value is to applied to the analog output 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Online 
P761 
(G116) 
Mode of signal injection at analog output 3 
0 =  Injection of signal with correct sign 
1 =  Injection of absolute value of signal 
2 =  Injection of signal with sign, inverted 
3 =  Injection of absolute value of signal, inverted 
0 to 3 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P762 
(G116) 
Filtering time for analog output 3 
0 to 10000 
[ms] 
1ms 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P763 
(G116) 
Normalization of analog output 3 
y V
x
P
[ ]
%
= ∗
763
100
x = Normalization input (corresponds to filtering output) 
y = Normalization output (corresponds to output voltage at analog output 
with offset = 0) 
-200.00 to 199.99 
[V] 
0.01V 
Ind: None 
FS=10.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P764 
(G116) 
Offset for analog output 3 
-10.00 to 10.00 
[V] 
0.01V 
Ind: None 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
Analog output terminals 20 / 21 
P765 
(G116) 
Source for output value at analog output 4 
Selection of connector whose value is to applied to the analog output 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Online 
P766 
(G116) 
Mode of signal injection at analog output 4 
0 =  Injection of signal with correct sign 
1 =  Injection of absolute value of signal 
2 =  Injection of signal with sign, inverted 
3 =  Injection of absolute value of signal, inverted 
0 to 3 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P767 
(G116) 
Filtering time for analog output 4 
0 to 10000 
[ms] 
1ms 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
SIEMENS AG    6RX1700-0AD76 
11-81 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P768 
(G116) 
Normalization of analog output 4 
y V
x
P
[ ]
%
= ∗
768
100
x = Normalization input (corresponds to filtering output) 
y = Normalization output (corresponds to output voltage at analog output 
with offset = 0) 
-200.00 to 199.99 
[V] 
0.01V 
Ind: None 
FS=10.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
P769 
(G116) 
Offset for analog output 4 
-10.00 to 10.00 
[V] 
0.01V 
Ind: None 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
11.40  Binary outputs 
(see also Section 8, Sheet G112) 
P770 
(G112)  
(G200) 
Control word for binary selectable outputs 
i001:  0  Binary selectable output at terminal 46 is not inverted 
 Binary selectable output at terminal 46 is inverted 
i002:  0  Binary selectable output at terminal 48 is not inverted 
 Binary selectable output at terminal 48 is inverted 
i003:  0  Binary selectable output at terminal 50 is not inverted 
 Binary selectable output at terminal 50 is inverted 
i004:  0  Binary selectable output at terminal 52 is not inverted 
 Binary selectable output at terminal 52 is inverted 
0 to 1 
Ind: 4 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P771 
(G112)  
(G200) 
Source for output value at binary output 1 
Selection of binector to be injected at binary selectable output, terminal 46 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Online 
P772 
(G112)  
(G200) 
Source for output value at binary output 2 
Selection of binector to be injected at binary selectable output, terminal 48 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Online 
P773 
(G112) 
Source for output value at binary output 3 
Selection of binector to be injected at binary selectable output, terminal 50 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Online 
P774 
(G112) 
Source for output value at binary output 4 
Selection of binector to be injected at binary selectable output, terminal 52 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Online 
P775 
(G112)  
(G200) 
Delay for output value at binary output 1 
The logic level at the binary selectable output changes only if the internal 
signal level remains constant for the set delay period (internal signal level 
changes which do not last as long as this delay period are not switched 
through to the output) 
0 to 10000 
[ms] 
1ms 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P776 
(G112)  
(G200) 
Delay for output value at binary output 2 
The logic level at the binary selectable output changes only if the internal 
signal level remains constant for the set delay period (internal signal level 
changes which do not last as long as this delay period are not switched 
through to the output) 
0 to 10000 
[ms] 
1ms 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P777 
(G112) 
Delay for output value at binary output 3 
The logic level at the binary selectable output changes only if the internal 
signal level remains constant for the set delay period (internal signal level 
changes which do not last as long as this delay period are not switched 
through to the output) 
0 to 10000 
[ms] 
1ms 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
11-82 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P778 
(G112) 
Delay for output value at binary output 4 
The logic level at the binary selectable output changes only if the internal 
signal level remains constant for the set delay period (internal signal level 
changes which do not last as long as this delay period are not switched 
through to the output) 
0 to 10000 
[ms] 
1ms 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
11.41  Configuration of serial interfaces on basic converter 
G-SST 1 (RS485 / RS232 on X300)  (see also Section 8, Sheet G170 and Section 9) 
P780 
(G170) 
Selection of protocol for G-SST1 basic converter interface 
Setting has no function 
USS protocol 
for factory purposes 
For internal factory test purposes 
0, 2, 8, 9 
Ind: None 
FS=2 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P781 
(G170) 
Number of process data for G-SST1 
When P780 = 0 or 9 is selected:
Parameter is irrelevant 
When USS protocol (P780=2) is selected:
Number of PZD elements 
No process data are expected or sent in the USS protocol 
1...16  Number of process data words in USS protocol (same number 
applies to transmission and receipt) 
The received PZD elements (1 to max. 16) are available at 
connectors (K2001 to K2016) and, in some cases, bit-serially at 
binectors for "internal wiring" purposes. 
The PZD elements to be transmitted (1 to max. 16) are selected 
in parameters P784.01 to P784.16. 
0 to 16 
Ind: None 
FS=2 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P782 
(G170) 
Length of parameter jobs for G-SST1 
This parameter is effective only when P780=2 (USS protocol). 
No PKW data
are expected or sent in the USS protocol. 
3, 4 
3 or 4 PKW data words
are expected in the USS protocol and 3 
or 4 PKW data words are also sent (for transmission of 
parameter values). 
127 
Number of PKWs is determined by the telegram length 
0, 3, 4, 127 
Ind: None 
FS=127 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P783 
(G170) 
Baud rate for G-SST1 
300 baud 
600 baud 
1200 baud 
2400 baud 
4800 baud 
9600 baud 
19200 baud 
38400 baud 
56700 baud 
11 
93750 baud 
13 
187500 baud 
1 to 13 
Ind: None 
FS=6 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P784 
(G170) 
Source for transmit data for G-SST1 
Selection of connectors to be transferred as transmit data to the USS 
master via USS interface 1. 
i001:  Selection for word 1 
i002:  Selection for word 2 
... 
i016:  Selection for word 16 
Applicable settings: 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 16 
FS= 
i001: 32 
i002: 167 
i003: 0 
i004: 33 
i005-i016: 0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
SIEMENS AG    6RX1700-0AD76 
11-83 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P785 
(G170) 
Options for G-SST1 
i001:  0 = Bus terminator OFF 
1 = Bus terminator ON 
i002:  0 = Bit 10 of the 1
st
receive word does not
function as "Control 
by PLC". 
1 = Bit 10 of the 1
st
receive word does function as "Control by 
PLC“, i.e. when bit 10 = 0, all other bits of the 1
st
receive word, 
as well as receive words 2 to 16, are not
written to connectors 
K2001 to K2016, or to binectors B2100 to B2915. All these 
connectors and binectors retain their old values. 
0 to 1 
1 
Ind: 2 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P786 
(G170) 
USS bus address for G-SST1 
This parameter is functional only when P780=2 (USS protocol). Address via 
which the unit can be addressed in USS bus operation. 
0 to 30 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P787 
(G170) 
Telegram failure time for G-SST1 
The failure time set in this parameter is valid when setting P780=2 (USS 
protocol) is selected. 
0.000 
No time monitoring 
0.001...65.000  Time which may elapse between the receipt of two 
telegrams addressed to the unit before a fault message 
is activated. 
Fault message F011 is activated if no valid telegram is received within this 
time period. 
Note: 
The telegram monitoring function is active  
 from the receipt of the first error-free telegram after connection of the 
electronics power supply 
 from the receipt of the first error-free telegram after the telegram monitor 
has responded (i.e. monitoring timeout). 
0.000 to 65.000 
[s] 
0.001s 
Ind: None 
FS=0.000 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P788 
(G170) 
Source for activation of F011 
Selection of binector which will activate fault message F011 when it 
switches to log. "1" 
2030 = binector B2030 
2031 = binector B2031 
2030, 2031 
Ind: None 
FS=2030 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
r789 
(G170) 
Diagnostic information for G-SST1 
Free-running counter, overflow at 65535 
i001:  Number of error-free
telegrams 
i002:  Number of errored
telegrams: 
Byte frame, parity, overrun or BCC error 
i003:  Number of byte frame errors 
i004:  Number of overrun errors 
i005:  Parity error 
i006:  STX error: 
Start interval before STX not observed, 
telegram residual transfer time not observed,  
delay time of LGE character too long, 
erroneous STX, i.e.  02 
i007:  Violation of telegram residual transfer time 
i008:  Block check error 
i009:   Incorrect telegram length: 
With P782=3 or 4 only: 
The length of the received telegram is  P781 + P782 
(Note: If the received values are correct, they will be processed 
even when this error has been detected) 
i010:  Timeout error: 
No valid telegram has been received for a period exceeding the 
setting in P787. After the occurrence of a timeout error, this 
counter is not activated again until the next valid telegram is 
received. 
Ind: 10 
Type: O2 
P052 = 3 
11-84 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
G-SST 2 (RS485 on X172)  (see also Section 8, Sheets G171 and G173 and Section 9) 
P790 
(G171)  
(G173) 
Selection of protocol for G-SST2 basic converter interface 
Setting has no function 
USS protocol 
”Peer-to-peer” communication 
Communication with the SIMOREG CCP 
For internal factory test purposes 
0, 2, 5, 6, 9 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P791 
(G171)  
(G173) 
Number of process data for G-SST2 
When P790 = 0 or 9 is selected:
Parameter is irrelevant 
When USS protocol (P790=2) is selected:
Number of PZD elements 
No process data are expected or sent in the USS protocol 
1...16  Number of process data words in USS protocol (same number 
applies to transmission and receipt) 
The received PZD elements (1 to max. 16) are available at 
connectors (K6001 to K6016) and, in some cases, bit-serially at 
binectors for "internal wiring" purposes. 
The PZD elements to be transmitted (1 to max. 16) are selected 
in parameters P794.01 to P794.16. 
When peer-to-peer (P790= 5) is selected
: Number of transferred words 
Illegal setting 
1...5  Number of transferred words 
6...16  Illegal setting 
0 to 16 
Ind: None 
FS=2 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P792 
(G171) 
Length of parameter jobs for G-SST2 
This parameter is effective only when P790=2 (USS protocol). 
No PKW data
are expected or sent in the USS protocol. 
3, 4 
3 or 4 PKW data words
are expected in the USS protocol and 3 
or 4 PKW data words are also sent (for transmission of 
parameter values). 
127 
Number of PKWs is determined by the telegram length 
0, 3, 4, 127 
Ind: None 
FS=127 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P793 
(G171)  
(G173) 
Baud rate for G-SST2 
300 baud 
600 baud 
1200 baud 
2400 baud 
4800 baud 
9600 baud 
19200 baud 
38400 baud 
56700 baud 
11 
93750 baud 
13 
187500 baud 
1 to 13 
Ind: None 
FS=6 
Type: O2 
P052 = 3 
P051 = 40 
Offline 