SIEMENS AG    6RX1700-0AD76 
11-85 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P794 
(G171)  
(G173) 
Source for transmit data for G-SST2 
Selection of connectors to be transferred as transmit data
via basic 
converter interface 2 
When USS protocol (P790=2) is selected:
i001:  Selection for word 1 
i002:  Selection for word 2 
... 
i016:  Selection for word 16 
When peer-to-peer (P790=5) is selected:
i001:  Selection for word 1 
i002:  Selection for word 2 
... 
i005:  Selection for word 5 
i006:  Not used 
... 
i016:  Not used 
Applicable settings: 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 16 
FS= 
i001: 32 
i002: 167 
i003: 0 
i004: 33 
i005-i016: 0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P795 
(G171)  
(G173) 
Options for G-SST2 
i001:  0 = Bus terminator OFF 
1 = Bus terminator ON 
i002:  0 = Bit 10 of the 1
st
receive word does not
function as "Control 
by PLC". 
1 = Bit 10 of the 1
st
receive word does function as "Control by 
PLC“, i.e. when bit 10 = 0, all other bits of the 1
st
receive word, 
as well as receive words 2 to 16, are not
written to connectors 
K6001 to K6016, or to binectors B6100 to B6915. All these 
connectors and binectors retain their old values. 
0 to 1 
1 
Ind: 2 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P796 
(G171) 
USS bus address for G-SST2 
This parameter is functional only when P790=2 (USS protocol). Address via 
which the unit can be addressed in USS bus operation. 
0 to 30 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
Add image to pdf file acrobat - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
adding images to a pdf document; add signature image to pdf
Add image to pdf file acrobat - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
add image to pdf preview; add image to pdf acrobat
11-86 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P797 
(G171)  
(G173) 
Telegram failure time for G-SST2 
The failure time set in this parameter is valid when setting P790=2 (USS 
protocol) or P790=5 (peer-to-peer) is selected. 
0.000 
No time monitoring 
0.001...65.000  Time which may elapse between the receipt of two 
telegrams addressed to the unit before a fault message 
is activated. 
Fault message F012 is activated if no valid telegram is received within this 
time period. 
Note: 
The telegram monitoring function is active  
 from the receipt of the first error-free telegram after connection of the 
electronics power supply 
 from the receipt of the first error-free telegram after the telegram monitor 
has responded (i.e. monitoring timeout). 
Since the telegram transfer time is dependent on the set baud rate, the 
following minimum setting values for P797 are recommended: 
Baud rate as set in P793: 
Recommended minimum value for P797: 
300  baud 
0.520s 
600  baud 
0.260s 
1200  baud 
0.140s 
2400  baud 
0.080s 
 4800  baud 
0.040s 
Note: 
If the "Automatic restart" function is selected (P086>0) on the peer-to-peer 
communication partner, then only a parameter setting of P797>P086 (on the 
communication partner) is meaningful. 
0.000 to 65.000 
[s] 
0.001s 
Ind: None 
FS=0.000 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P798 
(G171)  
(G173) 
Source for activation of F012 
Selection of binector which will activate fault message F012 when it 
switches to log. "1" 
6030 = binector B6030 
6031 = binector B6031 
6030, 6031 
Ind: None 
FS=6030 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
r799 
(G171)  
(G173) 
Diagnostic information for G-SST2 
Free-running counter, overflow at 65535 
i001:  Number of error-free
telegrams 
i002:  Number of errored
telegrams: 
Byte frame, parity, overrun or BCC error 
i003:  Number of byte frame errors 
i004:  Number of overrun errors 
i005:  Parity error 
i006:*)  STX error: 
Start interval before STX not observed, 
telegram residual transfer time not observed,  
delay time of LGE character too long, 
erroneous STX, i.e.  02 
i007:*)  Violation of telegram residual transfer time (USS prot. only) 
i008:*)  Block check error 
i009:*)  Incorrect telegram length: 
With P792=3 or 4 only: 
The length of the received telegram is  P791 + P792 
(Note: If the received values are correct, they will be processed 
even when this error has been detected) 
i010:  Timeout error: 
No valid telegram has been received for a period exceeding the 
setting in P797. After the occurrence of a timeout error, this 
counter is not activated again until the next valid telegram is 
received. 
*) Indices i006 to i009 are irrelevant for communication with the SIMOREG 
CCP (P790 = 6) 
Ind: 10 
Type: O2 
P052 = 3 
.NET PDF Document Viewing, Annotation, Conversion & Processing
Convert image files to PDF. File & Page Process. Add, insert PDF native annotations to PDF file. Edit, update, delete PDF annotations from PDF file. Print.
add an image to a pdf acrobat; add picture to pdf file
C# PDF Converter Library SDK to convert PDF to other file formats
professional PDF document conversion library toolkit in C#, you can easily perform file conversion from PDF document to image or document
add image in pdf using java; add photo to pdf in preview
SIEMENS AG    6RX1700-0AD76 
11-87 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
G-SST 3 (RS485 on X162)  (see also Section 8, Sheets G172 and G174 and Section 9) 
P800 
(G172)  
(G174) 
Selection of protocol for G-SST3 basic converter interface 
Setting has no function 
USS protocol 
”Peer-to-peer” communication 
For internal factory test purposes 
0, 2, 5, 9 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P801 
(G172)  
(G174) 
Number of process data for G-SST3 
When P800 = 0 or 9 is selected:
Parameter is irrelevant 
When USS protocol (P800=2) is selected:
Number of PZD elements 
No process data are expected or sent in the USS protocol 
1...16  Number of process data words in USS protocol (same number 
applies to transmission and receipt) 
The received PZD elements (1 to max. 16) are available at 
connectors (K6001 to K6016) and, in some cases, bit-serially at 
binectors for "internal wiring" purposes. 
The PZD elements to be transmitted (1 to max. 16) are selected 
in parameters P804.01 to P804.16. 
When peer-to-peer (P800= 5) is selected
: Number of transferred words 
Illegal setting 
1...5  Number of transferred words 
6...16  Illegal setting 
0 to 16 
Ind: None 
FS=2 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P802 
(G172) 
Length of parameter jobs for G-SST3 
This parameter is effective only when P800=2 (USS protocol). 
No PKW data
are expected or sent in the USS protocol. 
3, 4 
3 or 4 PKW data words
are expected in the USS protocol and 3 
or 4 PKW data words are also sent (for transmission of 
parameter values). 
127 
Number of PKWs is determined by the telegram length 
0, 3, 4, 127 
Ind: None 
FS=127 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P803 
(G172)  
(G174) 
Baud rate for G-SST3 
300 baud 
600 baud 
1200 baud 
2400 baud 
4800 baud 
9600 baud 
19200 baud 
38400 baud 
56700 baud 
11 
93750 baud 
13 
187500 baud 
1 to 13 
Ind: None 
FS=13 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
C# Windows Viewer - Image and Document Conversion & Rendering in
conversion library toolkit in C#, you can easily perform file conversion from Image and Document Conversion Supported by Windows Viewer. Convert to PDF.
adding images to pdf; add image to pdf form
C# powerpoint - PowerPoint Conversion & Rendering in C#.NET
may easily achieve the following PowerPoint file conversions SDK to convert PowerPoint document to PDF document demo code for PowerPoint to TIFF image conversion
add jpeg to pdf; add an image to a pdf form
11-88 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P804 
(G172)  
(G174) 
Source for transmit data for G-SST3 
Selection of connectors to be transferred as transmit data
via basic 
converter interface 3 
When USS protocol (P800=2) is selected:
i001:  Selection for word 1 
i002:  Selection for word 2 
... 
i016:  Selection for word 16 
When peer-to-peer (P800=5) is selected:
i001:  Selection for word 1 
i002:  Selection for word 2 
... 
i005:  Selection for word 5 
i006:  Not used 
... 
i016:  Not used 
Applicable settings: 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 16 
FS= 
i001: 32 
i002: 167 
i003: 0 
i004: 33 
i005-i016: 0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P805 
(G172)  
(G174) 
Options for G-SST3 
i001:  0 = Bus terminator OFF 
1 = Bus terminator ON 
i002:  0 = Bit 10 of the 1
st
receive word does not
function as "Control 
by PLC". 
1 = Bit 10 of the 1
st
receive word does function as "Control by 
PLC“, i.e. when bit 10 = 0, all other bits of the 1
st
receive word, 
as well as receive words 2 to 16, are not
written to connectors 
K9001 to K9016, or to binectors B9100 to B9915. All these 
connectors and binectors retain their old values. 
0 to 1 
1 
Ind: 2 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P806 
(G172) 
USS bus address for G-SST3 
This parameter is functional only when P800=2 (USS protocol). Address via 
which the unit can be addressed in USS bus operation. 
0 to 30 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
C# Word - Word Conversion in C#.NET
you may easily achieve the following Word file conversions. XDoc.Word SDK to convert Word document to PDF document C# demo code for Word to TIFF image conversion
adding an image to a pdf in preview; add photo to pdf
VB.NET PDF: How to Create Watermark on PDF Document within
Using this VB.NET Imaging PDF Watermark Add-on, you can a watermark that consists of text or image (such as And with our PDF Watermark Creator, users need no
add image to pdf; add picture to pdf in preview
SIEMENS AG    6RX1700-0AD76 
11-89 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P807 
(G172)  
(G174) 
Telegram failure time for G-SST3 
The failure time set in this parameter is valid when setting P800=2 (USS 
protocol) or P800=5 (peer-to-peer) is selected. 
0.000 
No time monitoring 
0.001...65.000  Time which may elapse between the receipt of two 
telegrams addressed to the unit before a fault message 
is activated. 
Fault message F013 is activated if no valid telegram is received within this 
time period. 
Note: 
The telegram monitoring function is active  
 from the receipt of the first error-free telegram after connection of the 
electronics power supply 
 from the receipt of the first error-free telegram after the telegram monitor 
has responded (i.e. monitoring timeout). 
Since the telegram transfer time is dependent on the set baud rate, the 
following minimum setting values for P807 are recommended: 
Baud rate as set in P803: 
Recommended minimum value for P807: 
300  baud 
0.520s 
600  baud 
0.260s 
1200  baud 
0.140s 
2400  baud 
0.080s 
 4800  baud 
0.040s 
Note: 
If the "Automatic restart" function is selected (P086>0) on the peer-to-peer 
communication partner, then only a parameter setting of P807>P086 (on the 
communication partner) is meaningful. 
0.000 to 65.000 
[s] 
0.001s 
Ind: None 
FS=0.000 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P808 
(G172)  
(G174) 
Source for activation of F013 
Selection of binector which will activate fault message F013 when it 
switches to log. "1" 
9030 = binector B9030 
9031 = binector B9031 
9030, 9031 
Ind: None 
FS=9030 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
r809 
(G172)  
(G174) 
Diagnostic information for G-SST3 
Free-running counter, overflow at 65535 
i001:  Number of error-free
telegrams 
i002:  Number of errored
telegrams: 
Byte frame, parity, overrun or BCC error 
i003:  Number of byte frame errors 
i004:  Number of overrun errors 
i005:  Parity error 
i006:  STX error: 
Start interval before STX not observed, 
telegram residual transfer time not observed,  
delay time of LGE character too long, 
erroneous STX, i.e.  02 
i007:  Violation of telegram residual transfer time (USS prot. only) 
i008:  Block check error 
i009:   Incorrect telegram length: 
With PP802=3 or 4 only: 
The length of the received telegram is  P801 + P802 
(Note: If the received values are correct, they will be processed 
even when this error has been detected) 
i010:  Timeout error: 
No valid telegram has been received for a period exceeding the 
setting in P807. After the occurrence of a timeout error, this 
counter is not activated again until the next valid telegram is 
received. 
Ind: 10 
Type: O2 
P052 = 3 
VB.NET PowerPoint: VB Code to Draw and Create Annotation on PPT
as a kind of compensation for limitations (other documents are compatible, including PDF, TIFF, MS VB.NET PPT: VB Code to Add Embedded Image Object to
add image to pdf reader; adding image to pdf in preview
BMP to PDF Converter | Convert Bitmap to PDF, Convert PDF to BMP
Also designed to be used add-on for .NET Image Powerful image converter for Bitmap and PDF files; No Support conversion of Bitmap - PDF files in both single &
add photo to pdf online; add jpg to pdf online
11-90 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
r810 
(G170) 
Receive data on G-SST1 
Display of data received via USS interface 1 
i001:  Display process data word 1 
... 
i016  Display process data word 16 
i017:  Display parameter data word 1 
... 
i020:  Display parameter data word 4 
Ind: 20 
Type: L2 
P052 = 3 
r811 
(G170) 
Transmit data on G-SST1 
Display of the data to be transmitted via USS interface 1  
i001:  Display process data word 1 
... 
i016  Display process data word 16 
i017:  Display parameter data word 1 
... 
i020:  Display parameter data word 4 
Ind: 20 
Type: L2 
P052 = 3 
r812 
(G171)  
(G173) 
Receive data on G-SST2 
When USS protocol (P790=2) is selected:
Display of data received via USS interface 2 
i001:  Display process data word 1 
... 
i016  Display process data word 16 
i017:  Display parameter data word 1 
... 
i020:  Display parameter data word 4 
When peer-to-peer (P790=5) is selected:
Display of data received via peer-to-peer interface 2 
i001:  Receive data word 1 
... 
i005  Receive data word 5 
i006:  Not used 
... 
i020  Not used 
When communication with the SIMOREG CCP is selected (P790 = 6):
Data received from the SIMOREG CCP via interface 2 is displayed 
i001:  Last received 1-byte message 
i002:  Last received header of a multibyte message 
... 
i018  Free-running counter for the number of received 1-byte 
messages 
i019  Free-running counter for the number of received headers of a 
multibyte message 
i020  Free-running counter for the number of received sequence bytes 
of a multibyte message 
Ind: 20 
Type: L2 
P052 = 3 
PDF to WORD Converter | Convert PDF to Word, Convert Word to PDF
If you want to convert document file PDF formats to out transformation between different kinds of image files and Converter has accurate output, and PDF to Word
adding images to pdf files; adding an image to a pdf form
JPEG to PDF Converter | Convert JPEG to PDF, Convert PDF to JPEG
No need for Adobe Acrobat Reader; Seamlessly integrated into RasterEdge .NET Image SDK; high speed; Get a compressed PDF file after conversion;
add a picture to a pdf; add image to pdf file acrobat
SIEMENS AG    6RX1700-0AD76 
11-91 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
r813 
(G171)  
(G173) 
Transmit data on G-SST2 
When USS protocol (P790=2) is selected:
Display of the data to be transmitted via USS interface 2 
i001:  Display process data word 1 
... 
i016  Display process data word 16 
i017:  Display parameter data word 1 
... 
i020:  Display parameter data word 4 
When peer-to-peer (P790=5) is selected:
Display of the data to be transmitted via peer-to-peer interface 2 
i001:  Transmit data word 1 
... 
i005  Transmit data word 5 
i006:  Not used 
... 
i020  Not used 
Ind: 20 
Type: L2 
P052 = 3 
r814 
(G172)  
(G174) 
Receive data on G-SST3 
When USS protocol (P800=2) is selected:
Display of data received via USS interface 3 
i001:  Display process data word 1 
... 
i016  Display process data word 16 
i017:  Display parameter data word 1 
... 
i020:  Display parameter data word 4 
When peer-to-peer (P800=5) is selected:
Display of data received via peer-to-peer interface 3 
i001:  Receive data word 1 
... 
i005  Receive data word 5 
i006:  Not used 
... 
i020  Not used 
Ind: 20 
Type: L2 
P052 = 3 
r815 
(G172)  
(G174) 
Transmit data on G-SST3 
When USS protocol (P800=2) is selected:
Display of the data to be transmitted via USS interface 3 
i001:  Display process data word 1 
... 
i016  Display process data word 16 
i017:  Display parameter data word 1 
... 
i020:  Display parameter data word 4 
When peer-to-peer (P800=5) is selected:
Display of the data to be transmitted via peer-to-peer interface 3 
i001:  Transmit data word 1 
... 
i005  Transmit data word 5 
i006:  Not used 
... 
i020  Not used 
Ind: 20 
Type: L2 
P052 = 3 
Peer-to-peer interfaces: Enable transmission and receipt of telegrams: 
If transmission on a peer-to-peer interface is disabled, the associated output drivers are connected to high impedance. If reception is 
disabled on a peer-to-peer interface, then the telegram failure monitoring function is deactivated. 
P816 
(G173) 
Peer-to-peer 2: Source for data reception enabling command 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: None 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
11-92 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P817 
(G173) 
Peer-to-peer 2: Source for data transmission enabling command 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: None 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P818 
(G174) 
Peer-to-peer 3: Source for data reception enabling command 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: None 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
P819 
(G174) 
Peer-to-peer 3: Source for data transmission enabling command 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: None 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
11.42  Deactivation of monitoring functions 
WARNING 
If monitoring functions are deactivated, there may be a risk to the safety of operating personnel or of 
substantial property damage if a fault or error actually occurs! 
P820 
Deactivation of fault messages 
The numbers of all fault messages to be deactivated must be entered in this 
parameter. Fault numbers can be entered in any order. 0 must be entered 
for any unused indices of the parameter. 
Factory setting: 
i001 = 7 
(overvoltage) 
i002 = 18 
(short circuit at binary outputs) 
i003 = 31 
(monitoring of speed controller) 
i004 = 35 
(drive blocked) 
i005 = 36 
(armature current cannot flow) 
i006 = 37 
(I2t motor monitoring function has responded) 
i007 to i099 = 0 
0 to 147 
Ind: 99 
FS= 
see column 
on left 
Type: O2 
P052 = 3 
P051 = 40 
Online 
P821 
Deactivation of alarms 
The numbers of all alarm messages to be deactivated must be entered in 
this parameter. Alarm numbers can be entered in any order. 0 must be 
entered for any unused indices of the parameter. 
0 to 147 
Ind: 99 
FS= 0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
11.43  Compensation values 
r824 
A7006 compensation values 
These data contain compensation values for the analog section of 
electronics board A7006 
0 to 65535 
Ind: 10 
Type: O2 
P052 = 3 
P825 
Offset compensation for actual field current channel 
These data contain compensation values for the actual field current sensing 
function. They are automatically set during "Restore factory settings" 
(P051=21) and during the automatic offset compensation run (P051=22). 
13000 to 25000 
Ind: 3 
FS=19139 
Type: O2 
P052 = 3 
P051 = 40 
Online 
SIEMENS AG    6RX1700-0AD76 
11-93 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P826 
(G163) 
Correction of natural commutation timing 
If there is a variation in the armature current peak value (in spite of a 
constant firing angle), it can be corrected by offsetting the firing angle 
reference time of the appropriate line phase in parameter P826. One line 
phase (UV, UW, VW, VU, WU, WV) is assigned to each parameter index 
(i001 to i006). 
Increasing the parameter setting by a value of 1 corresponds to an increase 
of 1.333 µs in the firing angle (0.024 degrees at 50Hz line frequency), 
consequently reducing the armature current peak in the appropriate line 
phase. 
P826 is automatically set during the optimization run for precontrol and 
current controller (armature and field) (P051=25) (only when U800=0; when 
U800=1 or 2, parameters P826.001 to 006 are set to 0). 
Caution: 
Even an asymmetrical system causes variations in the magnitude of 
armature current peaks. However, the system asymmetry may also change. 
-100 to 100 * 1.333 
[µs] 
1.333µs 
Ind: 6 
FS=0 
Type: I2 
P052 = 3 
P051 = 40 
Online 
r827 
Internal diagnosis 
i001:  Number of write access operations to EEPROM 
i002:  Number of Page-Write access operations to EEPROM 
i003:  Counter for DUAL-PORT RAM timeouts 
0 to 65535 
Ind: 3 
Type: O2 
P052 = 3 
r828 
MLFB data 
These data contain details about the power section design (model) 
0 to 65535 
Ind: 16 
Type: O2 
P052 = 3 
r829 
A7001 compensation values 
These data contain compensation values for the analog section of 
electronics board A7001 
0 to 65535 
Ind: 68 
Type: O2 
P052 = 3 
11.44  Thyristor diagnosis 
P830 
Control word for thyristor diagnosis 
Thyristor check function deactivated 
Thyristors are checked on initial SWITCH-ON or INCHING 
command after connection of the electronics supply voltage. 
Thyristors are checked on every SWITCH-ON or INCHING 
command. 
Thyristors will be checked on the next SWITCH-ON or INCHING 
command. Parameter P830 is set to 0 if no fault is detected. 
Note: 
The thyristor check function may not be activated (setting P830=0 must be 
selected) 
 when the ”Enable a torque direction for torque direction change by 
parallel drive” function is in use (see also parameter P165) or 
 when the converter is used to supply large inductances (e.g. field supply 
from armature terminals, supply of lifting solenoids, etc.). 
0 to 3 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
11.45  Parameters for DriveMonitor and OP1S 
P831 
to 
r849 
Parameters for the Trace function of DriveMonitor 
These parameters are settings for the data exchange between DriveMonitor 
and the SIMOREG converter. They must not
be changed! 
P052 = 3 
r850 
to 
P899 
Parameters for the OP1S 
These parameters are settings for the data exchange between OP1S and 
the SIMOREG converter. They must not
be changed! 
P052 = 3 
11-94 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
11.46  Profile parameters 
P918 
(Z110) 
(Z111) 
CB bus address 
Protocol-dependent bus address for communication boards 
Note: 
The validity of the bus address is monitored by the communication board. 
(Bus addresses 0 to 2 are reserved for Master stations on PROFIBUS 
boards and must not therefore be set for other purposes). If the value is not 
accepted by the COM BOARD, fault F080 is displayed with fault value 5 
0 to 200 
Ind: 2 
FS=3 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P927 
(G170)  
(G171)  
(G172)  
(Z110) 
(Z111) 
Parameterization enable 
Enabling of interfaces for parameterization. A parameter value can only be 
altered via an enabled interface. 
0: 
None 
1: 
Communications board (CB) 
2: 
Parameterizing unit (PMU) 
4: 
G-SST1 serial interface and OP1S 
8: 
Reserved 
16: 
Technology board (TB) 
32: 
G-SST2 serial interface 
64: 
G-SST3 serial interface 
Setting information: 
Every interface has a numeric code. 
The number for one specific interface, or the sum of various numbers 
assigned to several interfaces, must be entered in this parameter in order to 
enable the relevant interface(s) for use as a parameterization interface. 
Example: 
Factory setting value 6 (=4+2) means that the PMU and G-SST1 interfaces 
are enabled for parameterization purposes. 
0 to 127 
Ind: None 
FS=6 
Type: V2 
P052 = 3 
P051 = 40 
Offline 