SIEMENS AG    6RX1700-0AD76 
11-95 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
11.47  Fault memory 
r947 
(G189) 
Fault memory 
Display of fault messages generated in response to 8 recent faults. A fault 
value
and fault time
is assigned to each fault number
(see Section 10 for 
details of fault numbers and fault values).The interrelationship between the 
associated parameters is shown in the diagram below. 
The fault numbers
of the last (maximum 8) fault events are stored under the 
indices of parameter P947. r947.001 displays the fault number of the current 
(still not acknowledged) fault, index 9 displays the number of the most 
recent acknowledged fault, index 17 the fault number of the second most 
recent acknowledged fault, etc. An entry of "0" means that no "earlier" fault 
has occurred. Since only one fault message can be stored with respect to 
any fault event on the SIMOREG 6RA70, only indices 1, 9, 17, 25, 33, 41, 
49 and 57 are relevant. 
A fault value
is assigned to each fault number in the corresponding index of 
parameter r949. This provides further information about the nature of the 
fault. 
In addition, the fault time
(the current reading of the hours run counter as 
the fault occurred (r048)), is stored for each fault in r049.  The data for the 
current (not yet acknowledged) fault are stored as the "Hours run counter 
reading" in index 1. The data for earlier, already acknowledged faults are 
stored under the following indices. 
0
0
0
0
0
0
0
0
0
0
0
0
0
0
. . .
0
0
0
0
0
0
0
0
0
0
0
0
0
0
. . .
Index 1
Index 9
Index 17
Current
1
st
acknowl.
Current
r947
Fault number
r949
Fault value
r049
Fault time [h]
Index 1
Index 2
Index 3
Index 4
Index 5
Index 6
Index 7
Index 8
Current
1
st
acknowl.
2
nd
acknowl.
2
nd
acknowl.
1st acknowl.
2nd acknowl.
3rd acknowl.
4th acknowl.
5th acknowl.
6th acknowl.
7
th
acknowl.
Plaintext information about the fault numbers is available under the 
corresponding index of parameter r951. 
Ind: 64 
Type: O2 
P052 = 3 
r949 
(G189) 
Fault value 
Fault value of faults, allows more detailed diagnosis for a variety of 
parameters. 
The fault values are stored in the same indices as the associated fault 
numbers (r947) - see parameter r947. 
Ind: 64 
Type: O2 
P052 = 3 
r951 
Fault text 
0 to 65535 
Ind: 101 
Type: O2 
P052 = 3 
Adding an image to a pdf in preview - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
add jpg to pdf file; add an image to a pdf in preview
Adding an image to a pdf in preview - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
adding image to pdf; add picture to pdf document
11-96 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
P952 
Number of faults 
Settings: 
Deletes the entire fault memory (r947, r949 and r049) by 
resetting to 0 
Note: 
P952 cannot be reset while a fault is pending 
>0 
Display of the faults stored in the fault memory (r947, r949 and 
r049) 
0 to 65535 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
11.48  Visualization parameters: Alarms 
r953 
Alarm parameter 1 
Display of active alarms in bit-coded form (A001 to A016). 
If one of the alarms between 1 and 16 is generated, the corresponding 
segment in the display lights up. 
4
3
2
1
5
6
7
8
9
10
11
12
13
14
15
16
See Section 10.2 for meaning of individual alarms. 
Ind: None 
Type: V2 
P052 = 3 
r954 
Alarm parameter 2 
Display of active alarms in bit-coded form (A017 to A032). 
If one of the alarms between 17 and 32 is generated, the corresponding 
segment in the display lights up. 
20 19 18
17
21
22
23
24
25
26
27
28
29
30
31
32
See Section 10.2 for meaning of individual alarms 
Ind: None 
Type: V2 
P052 = 3 
r955 
Alarm parameter 3 
Parameter alarms 3 
If one of the alarms between 33 and 48 is generated, the corresponding 
segment in the display lights up. 
36 35 34
33
37
38
39
40
41
42
43
44
45
46
47
48
Ind: None 
Type: V2 
P052 = 3 
r956 
Alarm parameter 4 
Parameter alarms 4 
If one of the alarms between 49 and 64 is generated, the corresponding 
segment in the display lights up. 
52 51 50
49
53
54
55
56
57
58
59
60
61
62
63
64
Ind: None 
Type: V2 
P052 = 3 
r957 
Alarm parameter 5 
Parameter alarms 5 
If one of the alarms between 65 and 80 is generated, the corresponding 
segment in the display lights up.. 
68 67 66
65
69
70
71
72
73
74
75
76
77
78
79
80
Ind: None 
Type: V2 
P052 = 3 
C# PDF Page Insert Library: insert pages into PDF file in C#.net
applications. Support adding and inserting one or multiple pages to existing PDF document. Forms. Ability to add PDF page number in preview. Offer
how to add an image to a pdf file; add signature image to pdf acrobat
C# PDF insert text Library: insert text into PDF content in C#.net
Supports adding text to PDF in preview without adobe reader installed in ASP.NET. Powerful .NET PDF edit control allows modify existing scanned PDF text.
how to add an image to a pdf in preview; adding a jpeg to a pdf
SIEMENS AG    6RX1700-0AD76 
11-97 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
r958 
Alarm parameter 6 
Parameter alarms 6 (CB alarms) 
If one of the alarms between 81 and 96 is generated, the corresponding 
segment in the display lights up. 
84 83 82 81
85
86
87
88
89
90
91
92
93
94
95
96
Ind: None 
Type: V2 
P052 = 3 
r959 
Alarm parameter 7 
Parameter alarms 7 (TB alarms 1) 
If one of the alarms between 97 and 112 is generated, the corresponding 
segment in the display lights up. 
100 99 98 97
101
102
103
104
105
106
107
108
109
110
111
112
Ind: None 
Type: V2 
P052 = 3 
r960 
Alarm parameter 8 
Parameter alarms 8 (TB alarms 2) 
If one of the alarms between 113 and 128 is generated, the corresponding 
segment in the display lights up. 
116 115 114 113
117
118
119
120
121
122
123
124
125
126
127
128
Ind: None 
Type: V2 
P052 = 3 
11.49  Device identification 
r964 
Parameters for device identification on the PROFIBUS 
[SW 2.0 and later] 
Display parameters to support overview and diagnosis of all nodes on the 
PROFIBUS-DP during and after commissioning 
(coding according to PROFIBUS profile V3) 
i001:  Display of the manufacturer of the  
SIMOREG DC-MASTER 6RA70 : SIEMENS = 42 
i002:  Display of device type: SIMOREG DC-MASTER 6RA70 = 4110 
i003:  Display of the software version of the SIMOREG DC-MASTER 
6RA70 
(see r060.001) 
i004:  Display of year of generation of the software of the SIMOREG 
DC-MASTER 6RA70: y y y y  
(see r061.001) 
i005:  Display of the month and day of generation of the software of 
the SIMOREG DC-MASTER 6RA70: d d m m 
(see r061.003 and r061.002) 
i006:  Display of the controlled axes of the SIMOREG DC-MASTER 
6RA70: 1 
0 to 65535 
Ind: 6 
Type: O2 
P052 = 1 
11.50  Visualization parameters: Control and status word 
r967 
Display of control word 1 
Visualization parameter for control word 1 (bits 0-15)  
Identical to r650 (control word 1) 
Ind: None 
Type: V2 
P052 = 3 
r968 
Display of status word 1 
Visualization parameter for status word 1 (bits 0 - 15) 
Identical to r652 (status word 1) 
Ind: None 
Type: V2 
P052 = 3 
VB.NET PDF insert text library: insert text into PDF content in vb
Multifunctional Visual Studio .NET PDF SDK library supports adding text content to adobe PDF document in VB.NET Add text to PDF in preview without adobe
how to add a jpeg to a pdf; attach image to pdf form
C# Create PDF Library SDK to convert PDF from other file formats
Load PDF from existing documents and image in SQL server. Besides, using this PDF document metadata adding control, you can add some additional
how to add a jpeg to a pdf file; add jpg signature to pdf
11-98 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
11.51  Resetting and storing parameters,  
list of existing and modified P and r parameters 
P970 
Restore factory setting 
Reset parameters to factory setting (default) 
0: 
Parameter reset: All parameters are reset to their original values 
(factory setting). This parameter is then automatically reset to 1. 
1: 
No parameter reset 
Note: Function can also be selected by setting P051=21. 
0 to 1 
Ind: None 
FS=1 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
P971 
EEPROM transfer 
Transfer of parameter values from RAM to EERPROM on switchover from 0 
to 1. 
It takes approximately 15s to process all values. The PMU remains in value 
mode for this period. 
0 to 1 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
r980 
List of existing parameter numbers, start 
Visualization parameter for displaying the first 100 parameter numbers in 
the P or r parameter range (0 to 999). The parameter numbers are listed in 
ascending sequence. 
Repetition of a number over several indices means that there are no further 
parameter numbers in the 0 to 999 range. 
The list is continued at the parameter whose number is displayed under 
index 101. 
See also r989 
Ind: 101 
Type: O2 
P052 = 3 
r981 
List of existing parameter numbers, continuation 
See r980. 
Ind: 101 
Type: O2 
P052 = 3 
r982 
List of existing parameter numbers, continuation 
See r980. 
Ind: 101 
Type: O2 
P052 = 3 
r983 
List of existing parameter numbers, continuation 
See r980. 
Ind: 101 
Type: O2 
P052 = 3 
r984 
List of existing parameter numbers, continuation 
See r980. 
Ind: 101 
Type: O2 
P052 = 3 
r985 
List of existing parameter numbers, continuation 
See r980. 
Ind: 101 
Type: O2 
P052 = 3 
r986 
List of existing parameter numbers, continuation 
See r980. 
Ind: 101 
Type: O2 
P052 = 3 
r987 
List of existing parameter numbers, continuation 
See r980. 
Ind: 101 
Type: O2 
P052 = 3 
r988 
List of existing parameter numbers, continuation 
See r980. 
Ind: 101 
Type: O2 
P052 = 3 
r989 
List of existing parameter numbers, continuation 
Continuation of the list can be found under index 101. Please note: 
860  
 r860  (TECH BOARD installed) 
2980  =  n980 
See also r980. 
Ind: 101 
Type: O2 
P052 = 3 
r990 
List of modified parameter numbers, start 
Visualization parameter for displaying the first 100 modified parameters in 
the P or r parameter range (0 to 999). The parameter numbers are listed in 
ascending sequence. 
Repetition of a number over several indices means that there are no further 
modified parameters in the 0 to 999 range. 
The list is continued at the parameter whose number is displayed under 
index 101. 
See also r999. 
Ind: 101 
Type: O2 
P052 = 3 
r991 
List of modified parameter numbers, continuation 
See r990. 
Ind: 101 
Type: O2 
P052 = 3 
C# Word - Insert Image to Word Page in C#.NET
Preview Document. Conversion. Convert Word to PDF. Convert Word to HTML5. VB.NET How-to, VB.NET PDF, VB.NET Word It's a demo code for adding image to word page using
add a jpeg to a pdf; add jpeg signature to pdf
C# PowerPoint - Insert Image to PowerPoint File Page in C#.NET
Preview Document. Conversion. Convert PowerPoint to PDF. Convert PowerPoint to Pages. Annotate PowerPoint. Text Search. Insert Image. Thumbnail Create.
acrobat insert image in pdf; how to add image to pdf in preview
SIEMENS AG    6RX1700-0AD76 
11-99 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
r992 
List of modified parameter numbers, continuation 
See r990. 
Ind: 101 
Type: O2 
P052 = 3 
r993 
List of modified parameter numbers, continuation 
See r990. 
Ind: 101 
Type: O2 
P052 = 3 
r994 
List of modified parameter numbers, continuation 
See r990. 
Ind: 101 
Type: O2 
P052 = 3 
r995 
List of modified parameter numbers, continuation 
See r990. 
Ind: 101 
Type: O2 
P052 = 3 
r996 
List of modified parameter numbers, continuation 
See r990. 
Ind: 101 
Type: O2 
P052 = 3 
r997 
List of modified parameter numbers, continuation 
See r990. 
Ind: 101 
Type: O2 
P052 = 3 
r998 
List of modified parameter numbers, continuation 
See r990. 
Ind: 101 
Type: O2 
P052 = 3 
r999 
List of modified parameter numbers, continuation 
Continuation of the list can be found under index 101. Please note: 
2990  =  n990 
See also r990. 
Ind: 101 
Type: O2 
P052 = 3 
11.52  Password protection, key/lock mechanism 
Key/lock mechanism 
To prevent unintended parameterization of the devices and to protect the know-how stored in the parameterization, you can restrict 
access to the (basic converter) parameters and define your own passwords (=pairs of numbers that you can choose). This done in 
parameters: 
 
U005 key and 
 
U006 lock. 
If U005 and U006 are parameterized differently, it is only possible to access the following parameters: 
All visualization parameters (rxxx, nxxx) 
All parameters that can be changed with P051 = 0 (See parameter list) 
All "user parameters" (see Parameter U007) 
All other parameters neither be read nor altered. 
Only when U005 and U006 are parameterized to the same values, are these restrictions removed again. 
When using the key-lock-mechanism you should follow this procedure: 
1. Program the den lock parameter U006 in both parameter indices with your specific password. 
2. Set Parameter P051 to the value 0. This activates the password you have just set (in U006). 
After that, P051 can be set to 40 again and the password protection remains active. 
Examples: 
Lock 
Key 
Result 
U006.1 = 0 (factory setting) 
U006.2 = 0
U005.1 = 0 (factory setting) 
U005.2 = 0 
The key and lock are parameterized identically, 
all parameters are accessible 
U006.1 = 12345 
U006.2 = 54321 
U005.1 = 0 
U005.2 = 0 
The key and lock are parameterized differently
only the visualization parameters, the parameters that can be 
altered with P051=0, and the "user parameters" are accessible 
U006.1 = 12345 
U006.2 = 54321 
U005.1 = 12345 
U005.2 = 54321 
The key and lock are parameterized identically, 
all parameters are accessible 
NOTE:  If you forget or lose your password, you can only regain access to all parameters by restoring the factory setting (P051=21). 
U005 
(2005) 
Key 
[SW 1.7 and later] 
Parameter for entering the keys for the key/lock mechanism 
0 to 65535 
Ind: 2 
FS=0 
Type: O2 
P052 = 3 
P051 = 0 
on-line 
U006 
(2006) 
Lock 
[SW 1.7 and later] 
Parameter for entering the password for the key/lock mechanism 
0 to 65535 
Ind: 2 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
on-line 
C# TIFF: TIFF Editor SDK to Read & Manipulate TIFF File Using C#.
Easy to generate image thumbnail or preview for Tiff to Tiff, like Word, Excel, PowerPoint, PDF, and images. assemblies into your C# project by adding reference
adding jpg to pdf; add png to pdf acrobat
VB.NET PDF copy, paste image library: copy, paste, cut PDF images
Free Visual Studio .NET PDF library, easy to be integrated in .NET WinForms and ASP.NET. Besides image extracting, adding, and removing, RasterEdge
how to add image to pdf; add image in pdf using java
11-100 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
U007 
(2007) 
Numbers of the user parameters 
[SW 1.7 and later] 
Parameters for entering the numbers of those parameters that are to be 
accessible if the key and lock are set differently. 
NOTE: 
Parameters U000 to U999 must be entered as 2000 to 2999 
0 to 999 
2000 to 2005 
2008 to 2999 
Ind: 100 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
on-line 
11.53  Processor utilization 
n009 
(2009) 
Processor utilization 
This parameter is particularly relevant as regards the selection of function 
blocks of technology software in the basic unit (option S00) and the 
definition of the time slices in which these function blocks are processed 
(see also Section 8, Function Diagram B101 and parameters U950 to 
U952). 
i001:  Current total processor utilization (=K9990) 
i002:  Extrapolated total processor utilization for line frequency = 65Hz 
(=K9991) 
i003:   Current total processor utilization by programs in 
time slice 10 (=K9992) 
i004:   Current total processor utilization by programs in  
time slice 4 (=K9993) 
i005:   Current total processor utilization by programs in  
time slice 2 (=K9994) 
i006:  Current total processor utilization by programs in  
time slice 1 (=K9995) 
0.0 to 100.0 
[%] 
0.1% 
Ind: 6 
Type: O2 
P052 = 3 
11.54  Display parameters for technology functions with S00 
Only active with optional technology software S00 
Connector/binector converters 
n010 
(2010) 
S00 
(B120) 
Connector/binector converter 1 (bit field 1) 
FB 10 
Displays the status of the bits in the bit field on the bars of the 7-segment 
display 
3
2
1
0
4
5
6
7
8
9
10
11
12
13
14
15
Segment ON: 
Bit (binector) = log. "1" state 
Segment OFF: 
Bit (binector) = log. "0" state 
Ind: None 
Type: V2 
P052 = 3 
n011 
(2011)  
S00 
(B120) 
Connector/binector converter 2 (bit field 2) 
FB 11 
As for n010 
Ind: None 
Type: V2 
P052 = 3 
n012 
(2012)  
S00 
(B120) 
Connector/binector converter 3 (bit field 3) 
FB 12 
As for n010 
Ind: None 
Type: V2 
P052 = 3 
Binector/connector converters 
n013 
(2013) 
S00 
(B121) 
Binector/connector converter 1 (bit field 4) 
FB 13 
Displays the status of the bits in the bit field on the bars of the 7-segment 
display 
3
2
1
0
4
5
6
7
8
9
10
11
12
13
14
15
Segment ON: 
Bit = log. "1" state 
Segment OFF: 
Bit = log. "0" state 
Ind: None 
Type: V2 
P052 = 3 
SIEMENS AG    6RX1700-0AD76 
11-101 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
n014 
(2014)  
S00 
(B121) 
Binector/connector converter 2 (bit field 5) 
FB 14 
As for n013 
Ind: None 
Type: V2 
P052 = 3 
n015 
(2015)  
S00 
(B121) 
Binector/connector converter 3 (bit field 6) 
FB 15 
As for n013 
Ind: None 
Type: V2 
P052 = 3 
Technology controller 
n016 
(2016) 
S00 
(B170) 
Actual value display 
FB 260 
-200.0 to 199.9 
[%] 
0.1 
Ind: None 
Type: I2 
P052 = 3 
n017 
(2017) 
S00 
(B170) 
Setpoint display 
FB 260 
-200.0 to 199.9 
[%] 
0.1 
Ind: None 
Type: I2 
P052 = 3 
n018 
(2018) 
S00 
(B170) 
Display of effective Kp factor 
FB 260 
0.00 to 30.00 
0.01 
Ind: None 
Type: O2 
P052 = 3 
n019 
(2019) 
S00 
(B170) 
Display of technology controller output 
FB 260 
-200.0 to 199.9 
[%] 
0.1 
Ind: None 
Type: I2 
P052 = 3 
Velocity/speed calculator 
n020 
(2020) 
S00 
(B190) 
Display of actual speed 
FB 261 
-200.0 to 199.9 
[%] 
0.1 
Ind: None 
Type: I2 
P052 = 3 
n021 
(2021) 
S00 
(B190) 
Display of actual velocity 
FB 261 
-32.768 to 32767 
[m/s] 
0.001 
Ind: None 
Type: I2 
P052 = 3 
n022 
(2022) 
S00 
(B190) 
Display of setpoint velocity 
FB 261 
-32.768 to 32767 
[m/s] 
0.001 
Ind: None 
Type: I2 
P052 = 3 
n023 
(2023) 
S00 
(B190) 
Display of setpoint speed 
FB 261 
-200.0 to 199.9 
[%] 
0.1 
Ind: None 
Type: I2 
P052 = 3 
11.55  Miscellaneous 
n024 
(2024) 
(G145) 
(Z120) 
Display of the speed actual value in rpm 
[SW 2.0 and later] 
i001:  Display of the speed actual value from the pulse generator input 
of basic device X173 
i002:  Display of speed actual value from tacho module SBP 
-32768 to 32767 
[rpm] 
Ind: 2 
Type: I2 
P052 = 2 
U040 
to 
U041 
Reserved for later use  
[SW 2.0 and later] 
These parameters must not
be changed by the user! 
P052 = 3 
11-102 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
n042 
(2042) 
Warning memory 
[SW 2.0 and later] 
Warning memory for flagging warnings that have occurred since the 
electronics supply voltage was last switched on.  
The contents of the warning memory are lost when the electronics supply 
voltage is switched off and can be deleted with U043. 
The warnings are displayed in bit code as for r953 to r960 
i001:  Display of warnings 1 to 16 
i002:  Display of warnings 17 to 32 
i003:  Display of warnings 33 to 48 
i004:  Display of warnings 49 to 64 
i005:  Display of warnings 65 to 80 
i006:  Display of warnings 81 to 96 
i007:  Display of warnings 97 to 112 
i008:  Display of warnings 113 to 128 
See Section 10.2 for the meaning of the individual warnings 
Ind: 8 
Type: V2 
P052 = 2 
U043 
(2043) 
Deleting the warning memory 
[SW 2.0 and later] 
Settings: 
Deletes the entire warning memory n042 by resetting it to 0. 
Subsequently the parameter is automatically set back to value 
1. 
Not active 
0 to 1 
Ind: none 
FS=1 
Type: O2 
P052 = 3 
U044 
(2044) 
(G121) 
Connector display, decimal 
[SW 2.0 and later] 
Selects those connectors whose value is to be displayed as a decimal with 
n045  
i001:  Selects the connector to be displayed with n045.01 
i002:  Selects the connector to be displayed with n045.02 
i003:  Selects the connector to be displayed with n045.03 
i004:  Selects the connector to be displayed with n045.04 
i005:    Selects the connector to be displayed with n045.05 
All connector 
numbers 
Ind: 5 
FS=0 
Type: L2 
P052 = 3 
P051 =40 
online 
n045 
(2045) 
(G121) 
Connector display, decimal  
[SW 2.0 and later] 
Decimal display with sign of the values of the connectors selected with 
U044. In the case of double-word connectors the H word is displayed. 
i001:    Display of the connector selected with U044.01 
i002:     Display of the connector selected with U044.02 
i003:    Display of the connector selected with U044.03 
i004:     Display of the connector selected with U044.04 
i005:     Display of the connector selected with U044.05 
-32768 to 32767 
Ind:5 
Type: I2 
P052 = 3 
U046 
(2046) 
(G121) 
Connector display, hexadecimal 
[SW 2.0 and later] 
Selection of connectors whose value is to be displayed as a hexadecimal 
value with n047l 
i001:  Selection of the connector to be displayed with n047.01 
i002:  Selection of the connector to be displayed with n047.02 
i003:  Selection of the connector to be displayed with n047.03 
i004:  Selection of the connector to be displayed with n047.04 
i005:   Selection of the connector to be displayed with n047.05 
All connector 
numbers 
Ind: 5 
FS=0 
Type: L2 
P052 = 3 
P051 =40 
online 
n047 
(2047) 
(G121) 
Connector display, hexadecimal  
[SW 2.0 and later] 
Hexadecimal display of values of connectors selected with U046. In the 
case of double-word connectors the H word is displayed. 
i001:    Display of the connector selected with U046.01 
i002:     Display of the connector selected with U046.02 
i003:    Display of the connector selected with U046.03 
i004:     Display of the connector selected with U046.04 
i005:     Display of the connector selected with U046.05 
0000h to FFFFh 
Ind:5 
Type: L2 
P052 = 3 
SIEMENS AG    6RX1700-0AD76 
11-103 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
U049 
(2049) 
OP1S operating display  
[SW 1.9 and later] 
Function parameter for selecting parameters whose values must be 
included in the operating display of the optional 
OP1S convenience operator panel. 
i001:  1
st
line on left 
i002:  1
st
line on right 
i003:  2
nd
line (actual value), visualization parameter only 
i004:  3
rd
line (setpoint) 
i005:  4
th
line 
0 to 3999 
Ind:5 
FS=  
i001: 19 
i002: 38 
i003: 25 
i004: 28 
i005: 59 
Type: O2 
P052 = 3 
P051 =40 
on-line 
Connector type converters   (only active with optional technology software S00) 
2 connectors are converted into one double word connector. 
U098 
(2098) 
S00 
(B151) 
Operands for 1
st
connector type converter (result = KK9498) 
FB 298 
Operands for 2
nd
connector type converter (result = KK9499) 
FB 299
[SW 1.9 and later] 
i001:  Source for the low word of output connector KK9498 
i002:  Source for the high word of output connector KK9498 
i003:  Source for the low word of output connector KK9499 
i004:  Source for the high word of output connector KK9499 
Settings: 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 4 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
off-line 
11.56  Settable fixed values 
Only active with optional technology software S00 
U099 
(2099) 
S00 
(B110) 
Fixed value  
[SW 1.8 and later] 
The values set in Index .001 to .100 are connected to connectors K9501 to 
K9600 
-199.99 to 199.99 
[%] 
0.01% 
Ind: 100 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
on-line 
11.57  Activation of fault messages and alarm messages 
Only active with optional technology software S00 
U100 
(2100) 
S00 
(B115) 
Source for the activation of F023 and F019 
FB 2, FB 286 
Selection of the binectors that activate fault messages F023 or F019 on log. 
"1" 
0 = Binector B0000 
1 = Binector B0001 
etc. 
Up to SW 1.7: F023 (without fault value) if binector = 1  (FB 2) 
SW 1.8 and later: 
i001:  F023 with fault value 1  (FB 2) 
i002:  F023 with fault value 2 
i003:  F023 with fault value 3 
i004:  F023 with fault value 4 
i005:  F019 with fault value 1  (FB 286) 
i006:  F019 with fault value 2 
i007:  F019 with fault value 3 
i008:  F019 with fault value 4 
All binector numbers 
Ind: 8 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
off-line 
11-104 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
U101 
(2101) 
S00 
(B115) 
Source for the activation of F024 and F020 
FB 3, FB 287 
Selection of the binectors that activate fault messages F024 or F020 on  
log. "1" 
0 = Binector B0000 
1 = Binector B0001 
etc.  
Up to SW 1.7: F024 (without fault value) if binector = 1  (FB 3) 
SW 1.8 and later: 
i001:  F024 with fault value 1  (FB 3) 
i002:  F024 with fault value 2 
i003:  F024 with fault value 3 
i004:  F024 with fault value 4 
i005:  F020 with fault value 1  (FB 287) 
i006:  F020 with fault value 2 
i007:  F020 with fault value 3 
i008:  F020 with fault value 4 
All binector numbers 
Ind: 8 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
off-line 
U102 
(2102) 
S00 
(B115) 
Source for the activation of F033 and F053 
FB 4, FB 288 
Selection of the binectors that activate fault messages F033 or F053 on 
log. "1" 
0 = Binector B0000 
1 = Binector B0001 
etc.  
Up to SW 1.7: F033 (without fault value) if binector = 1  (FB 4) 
SW 1.8 and later: 
i001:  F033 with fault value 1  (FB 4) 
i002:  F033 with fault value 2 
i003:  F033 with fault value 3 
i004:  F033 with fault value 4 
i005:  F053 with fault value 1  (FB 288) 
i006:  F053 with fault value 2 
i007:  F053 with fault value 3 
i008:  F053 with fault value 4 
All binector numbers 
Ind: 8 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
off-line 
U103 
(2103) 
S00 
(B115) 
Source for the activation of F034 and F054 
FB 5, FB 289 
Selection of the binectors that activate fault messages F034 or F054 on log. 
"1" 
0 = Binector B0000 
1 = Binector B0001 
etc.  
Up to SW 1.7: F034 (without Fault value) if binector = 1  (FB 5) 
SW 1.8 and later: 
i001:  F034 with fault value 1  (FB 5) 
i002:  F034 with fault value 2 
i003:  F034 with fault value 3 
i004:  F034 with fault value 4 
i005:  F054 with fault value 1  (FB 289) 
i006:  F054 with fault value 2 
i007:  F054 with fault value 3 
i008:  F054 with fault value 4 
All binector numbers 
Ind: 8 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
off-line 
U104 
(2104) 
S00 
(B115) 
Source for the activation of A023 and A019 
FB 6, FB 256 
Selection of the binectors that activate alarm A023 or A019 on log. "1" 
0 = Binector B0000 
1 = Binector B0001 
etc.  
Up to SW 1.7:   A023 
(FB 6) 
SW 1.8 and later: 
i001:   
A023 
(FB 6) 
i002:   
A019 
(FB 256) 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
off-line 
Documents you may be interested
Documents you may be interested