SIEMENS AG    6RX1700-0AD76 
11-115 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
Limit-value monitors without filtering 
U197 
(2197) 
S00 
(B137) 
Source for input signal (A) and operating point (B) for 
FB 73 
1
st
limit-value monitor without filtering 
i001:  Input signal 
i002:  Operating point 
Settings: 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 2 
FS= 
i001: 0 
i002: 9186 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U198 
(2198) 
S00 
(B137) 
Settable operating point for limit-value monitor 
FB 73 
Applied to connector K9186  
-200.00 to 199.99 
[%] 
0.01% 
Ind: None 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Offline 
U199 
(2199) 
S00 
(B137) 
Hysteresis for 1
st
limit-value monitor without filtering 
FB 73 
0.00 to 100.00 
[%] 
0.01% 
Ind: None 
FS=0.00 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
U200 
(2200) 
S00 
(B137) 
Source for input signal (A) and operating point (B) for 
FB 74 
2
nd
limit-value monitor without filtering 
i001:  Input signal 
i002:  Operating point 
Settings: 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 2 
FS= 
i001: 0 
i002: 9187 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U201 
(2201) 
S00 
(B137) 
Settable operating point for limit-value monitor 
FB 74 
Applied to connector K9187  
-200.00 to 199.99 
[%] 
0.01% 
Ind: None 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Offline 
U202 
(2202) 
S00 
(B137) 
Hysteresis for 2
nd
limit-value monitor without filtering 
FB 74  0.00 to 100.00 
[%] 
0.01% 
Ind: None 
FS=0.00 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
U203 
(2203) 
S00 
(B137) 
Source for input signal (A) and operating point (B) for 
FB 75 
3
rd
limit-value monitor without filtering 
i001:  Input signal 
i002:  Operating point 
Settings: 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 2 
FS= 
i001: 0 
i002: 9188 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U204 
(2204) 
S00 
(B137) 
Settable operating point for limit-value monitor 
FB 75 
Applied to connector K9188  
-200.00 to 199.99 
[%] 
0.01% 
Ind: None 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Offline 
U205 
(2205) 
S00 
(B137) 
Hysteresis for 3
rd
limit-value monitor without filtering 
FB 75 
0.00 to 100.00 
[%] 
0.01% 
Ind: None 
FS=0.00 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
U206 
(2206) 
S00 
(B137) 
Source for input signal (A) and operating point (B) for 
FB 76 
4
th
limit-value monitor without filtering 
i001:  Input signal 
i002:  Operating point 
Settings: 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 2 
FS= 
i001: 0 
i002: 9189 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U207 
(2207) 
S00 
(B137) 
Settable operating point for limit-value monitor 
FB 76 
Applied to connector K9189  
-200.00 to 199.99 
[%] 
0.01% 
Ind: None 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Offline 
Adding a jpg to a pdf - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
add image pdf; add picture pdf
Adding a jpg to a pdf - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
adding images to pdf; add image pdf document
11-116 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
U208 
(2208) 
S00 
(B137) 
Hysteresis for 4
th
limit-value monitor without filtering 
FB 76  0.00 to 100.00 
[%] 
0.01% 
Ind: None 
FS=0.00 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
U210 
(2210) 
S00 
(B138) 
Source for input signal (A) and operating point (B) for 
FB 77 
5
th
limit-value monitor without filtering 
i001:  Input signal 
i002:  Operating point 
Settings: 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 2 
FS= 
i001: 0 
i002: 9190 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U211 
(2211) 
S00 
(B138) 
Settable operating point for limit-value monitor 
FB 77 
Applied to connector K9190  
-200.00 to 199.99 
[%] 
0.01% 
Ind: None 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Offline 
U212 
(2212) 
S00 
(B138) 
Hysteresis for 5
th
limit-value monitor without filtering 
FB 77  0.00 to 100.00 
[%] 
0.01% 
Ind: None 
FS=0.00 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
U213 
(2213) 
S00 
(B138) 
Source for input signal (A) and operating point (B) for 
FB 78 
6
th
limit-value monitor without filtering 
i001:  Input signal 
i002:  Operating point 
Settings: 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 2 
FS= 
i001: 0 
i002: 9191 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U214 
(2214) 
S00 
(B138) 
Settable operating point for limit-value monitor 
FB 78 
Applied to connector K9191  
-200.00 to 199.99 
[%] 
0.01% 
Ind: None 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Offline 
U215 
(2215) 
S00 
(B138) 
Hysteresis for 6
th
limit-value monitor without filtering 
FB 78  0.00 to 100.00 
[%] 
0.01% 
Ind: None 
FS=0.00 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
U216 
(2216) 
S00 
(B138) 
Source for input signal (A) and operating point (B) for 
FB 79 
7
th
limit-value monitor without filtering 
i001:  Input signal 
i002:  Operating point 
Settings: 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 2 
FS= 
i001: 0 
i002: 9192 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U217 
(2217) 
S00 
(B138) 
Settable operating point for limit-value monitor 
FB 79 
Applied to connector K9192  
-200.00 to 199.99 
[%] 
0.01% 
Ind: None 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Offline 
U218 
(2218) 
S00 
(B138) 
Hysteresis for 7
th
limit-value monitor without filtering 
FB 79 
0.00 to 100.00 
[%] 
0.01% 
Ind: None 
FS=0.00 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
JPG to Word Converter | Convert JPEG to Word, Convert Word to JPG
What's more, using filters, adding morphing effects, watermarks, and do some color Open JPEG to Word Converter first; Load JPG images from local folders in
add image to pdf file; add image to pdf in preview
C# Create PDF Library SDK to convert PDF from other file formats
Gratis control for creating PDF from multiple image formats such as tiff, jpg, png, gif Besides, using this PDF document metadata adding control, you
add image to pdf acrobat reader; add photo to pdf
SIEMENS AG    6RX1700-0AD76 
11-117 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
11.63  Processing of connectors 
Only active with optional technology software S00 
Maximum selection  
FB 80, FB 174, FB 175, FB 176 
The largest of the input values selected by 3 indices each of the parameter (x1, x2, x3) is applied to the output. 
U220 
(2220) 
S00 
(B140) 
Source for maximum selection 
0 = Connector K0000 
1 = Connector K0001 
etc. 
i001:  x1 Maximum selection 1  (FB 80, Output = K9193) 
i002:  x2 Maximum selection 1 
i003:  x3 Maximum selection 1 
SW 1.8 and later: 
i004:  x1 Maximum selection 2  (FB 174, Output = K9460) 
i005:  x2 Maximum selection 2 
i006:  x3 Maximum selection 2 
i007:  x1 Maximum selection 3  (FB 175, Output = K9461) 
i008:  x2 Maximum selection 3 
i009:  x3 Maximum selection 3 
i010:  x1 Maximum selection 4  (FB 176, Output = K9462) 
i011:  x2 Maximum selection 4 
i012:  x3 Maximum selection 4 
All connector 
numbers 
Ind: 12 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
off-line 
Minimum selection  
FB 81, FB 177, FB 178, FB 179 
The smallest of the input values selected by 3 indices each of the parameter (x1, x2, x3) is applied to the output. 
U221 
(2221) 
S00 
(B140) 
Source for minimum selection 
0 = Connector K0000 
1 = Connector K0001 
etc. 
i001:  x1 Minimum selection 1  (FB 81, Output = K9194) 
i002:  x2 Minimum selection 1 
i003:  x3 Minimum selection 1 
SW 1.8 and later: 
i004:  x1 Minimum selection 2  (FB 177, Output = K9463) 
i005:  x2 Minimum selection 2 
i006:  x3 Minimum selection 2 
i007:  x1 Minimum selection 3  (FB 178, Output = K9464) 
i008:  x2 Minimum selection 3 
i009:  x3 Minimum selection 3 
i010:  x1 Minimum selection 4  (FB 179, Output = K9465) 
i011:  x2 Minimum selection 4 
i012:  x3 Minimum selection 4 
All connector 
numbers 
Ind: 12 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
off-line 
Tracking/storage elements 
The tracking/storage elements are storage elements for the parameterized input quantity. The outputs are linked to connectors. 
Transfer of the input quantity is controlled via the RESET, TRACK and STORE functions: 
RESET:  When the controlling binector reaches log. "1", the output is set to 0.00% (y=0) 
TRACK:  When the controlling binector reaches log. "1", the output is set to the input value and then tracks it continuously (y=x). If the 
TRACK signal switches from "1" to "0", the last value applied to the y output is "frozen" 
STORE:  With a "0" to "1" transition of the controlling binector signal, the output is permanently set to the current input value (y=x). This 
value then remains stored 
Priority  1. RESET,  2. TRACK,  3. STORE 
Tracking/storage element 1 
U222 
(2222) 
S00 
(B145) 
Source for input quantity (x) 
FB 82 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
VB.NET Imaging - Generate Barcode Image in VB.NET
as common image files such as png and jpg. quality PLANET postal barcode images in PDF, Word and VB.NET barcode generator component for adding POSTNET barcode
how to add a jpg to a pdf; add an image to a pdf in preview
C# Word - Insert Image to Word Page in C#.NET
VB.NET How-to, VB.NET PDF, VB.NET Word, VB It's a demo code for adding image to word page using C# 0); REImage image = new REImage(@"C:\logo2.jpg"); page.AddImage
add picture to pdf; add photo pdf
11-118 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
U223 
(2223) 
S00 
(B145) 
Source for control signals RESET, TRACK and STORE 
FB 82 
i001:  TRACK 
i002:  STORE 
i003:  RESET 
Settings: 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U224 
(2224) 
S00 
(B145) 
Control word for Power On Mode 
FB 82 
Volatile storage: 
Zero appears at output when voltage recovers 
Non-volatile storage: 
When the voltage is disconnected or fails, the current output 
value is stored and then output when the voltage recovers/is 
reconnected 
0 to 1 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
Tracking/storage element 2 
U225 
(2225) 
S00 
(B145) 
Source for input quantity (x) 
FB 83 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U226 
(2226) 
S00 
(B145) 
Source for control signals RESET, TRACK and STORE 
FB 83 
i001:  TRACK 
i002:  STORE 
i003:  RESET 
Settings: 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U227 
(2227) 
S00 
(B145) 
Control word for Power On Mode 
FB 83 
Volatile storage: 
Zero appears at output when voltage recovers 
Non-volatile storage: 
When the voltage is disconnected or fails, the current output 
value is stored and then output when the voltage recovers/is 
reconnected 
0 to 1 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
Connector memories 
The connector memories are memory elements for the  input quantities selected via the parameters. The outputs are linked to connectors. 
While the SET input is in the log. "1" state, output quantity y tracks input quantity x continuously. If the SET input changes state from log. 
"1" to log. "0", the current value of x is stored and output continuously at y. 
Output (y) = 0 is set on POWER ON. 
Connector memory 1 
U228 
(2228) 
S00 
(B145) 
Source for input quantity (x) 
FB 84 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U229 
(2229) 
S00 
(B145) 
Source for control signal SET 
FB 84 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
Connector memory 2 
U230 
(2230) 
S00 
(B145) 
Source for input quantity (x) 
FB 85 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U231 
(2231) 
S00 
(B145) 
Source for control signal SET 
FB 85 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
C# Image: How to Draw Text on Images within Rasteredge .NET Image
to make this image text adding application work LoadImage = new Bitmap("C:\\1.jpg"); Graphic Text powerful & profession imaging controls, PDF document, tiff
add picture to pdf reader; add signature image to pdf acrobat
VB.NET Image: Visual Basic .NET Guide to Draw Text on Image in .
is the Visual Basic .NET method for adding text on Dim LoadImage As New Bitmap("C:\1.jpg") Dim Text powerful & profession imaging controls, PDF document,
add photo to pdf for; adding a png to a pdf
SIEMENS AG    6RX1700-0AD76 
11-119 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
Connector changeover switches 
Depending on the state of the control signal, one of the two input quantities is applied to the output (connector): 
Control signal = 0:The input quantity selected in index i001 is applied to the output 
Control signal = 1: The input quantity selected in index i002 is applied to the output 
Connector changeover switch 1 (output = K9210) 
U240 
(2240) 
S00 
(B150) 
Source for input quantities 
FB 90 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U241 
(2241) 
S00 
(B150) 
Source for control signal 
FB 90 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
Connector changeover switch 2 (output = K9211) 
U242 
(2242) 
S00 
(B150) 
Source for input quantities 
FB 91 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U243 
(2243) 
S00 
(B150) 
Source for control signal 
FB 91 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
Connector changeover switch 3 (output = K9212) 
U244 
(2244) 
S00 
(B150) 
Source for input quantities 
FB 92 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U245 
(2245) 
S00 
(B150) 
Source for control signal 
FB 92 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
Connector changeover switch 4 (output = K9213) 
U246 
(2246) 
S00 
(B150) 
Source for input quantities 
FB 93 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U247 
(2247) 
S00 
(B150) 
Source for control signal 
FB 93 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
Connector changeover switch 5 (output = K9214) 
U248 
(2248) 
S00 
(B150) 
Source for input quantities 
FB 94 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U249 
(2249) 
S00 
(B150) 
Source for control signal 
FB 94 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
C# PowerPoint - Insert Image to PowerPoint File Page in C#.NET
VB.NET How-to, VB.NET PDF, VB.NET Word, VB.NET Excel, VB.NET pptx"); BasePage page = doc.GetPage(0); REImage image = new REImage(@"C:\logo2.jpg"); page.AddImage
add image to pdf online; how to add an image to a pdf in reader
VB.NET Image: Create Image from Stream; Stream to Image Converter
image sharpening and old photo effect adding, resize source TIF encoder, GIF encoder and JPG encoder powerful & profession imaging controls, PDF document, tiff
attach image to pdf form; how to add an image to a pdf
11-120 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
Connector changeover switches 6 and 11 
U250 
(2250) 
S00 
(B150) 
Source for input quantities 
FB 95 and FB 196 
Output 6 = Connector K9215 
i001:  1st input signal 
i002:  2nd input signal 
Output 11 = Connector K9265 
[SW2.0 and later]
i003:  1st input signal 
i004:  2nd input signal 
Settings: 
0 = Connector K0000 
1 = Connector K0001 
etc. 
All connector 
numbers 
1 
Ind: 4 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U251 
(2251) 
S00 
(B150) 
Source for control signal 
FB 95 and FB 196 
i001:  Switchover for output 6 
i002:  Switchover for output 11 
[SW2.0 and later] 
Settings: 
0 = Binector B0000 
1 = Binector B0001 
etc. 
All binector numbers 
1 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
Connector changeover switches 7 and 12 
U252 
(2252) 
S00 
(B150) 
Source for input quantities 
FB 96 and FB 197 
Output 7 = Connector K9216 
i001:  1st input signal 
i002:  2nd input signal 
Output 12 = Connector K9266 
[SW2.0 and later] 
i003:  1st input signal 
i004:  2nd input signal 
Settings: 
0 = Connector K0000 
1 = Connector K0001 
etc. 
All connector 
numbers 
1 
Ind: 4 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U253 
(2253) 
S00 
(B150) 
Source for control signal 
FB 96 and FB 197 
i001:  Switchover for output 7 
i002:  Switchover for output 12 
[SW2.0 and later] 
Settings: 
0 = Binector B0000 
1 = Binector B0001 
etc. 
All binector numbers 
1 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
Connector changeover switches 8 and 13 
U254 
(2254) 
S00 
(B150) 
Source for input quantities 
FB 97 and FB 198 
Output 8 = Connector K9217 
i001:  1st input signal 
i002:  2nd input signal 
Output 13 = Connector K9267 
[SW2.0 and later] 
i003:  1st input signal 
i004:  2nd input signal 
Settings: 
0 = Connector K0000 
1 = Connector K0001 
etc. 
All connector 
numbers 
1 
Ind: 4 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U255 
(2255) 
S00 
(B150) 
Source for control signal 
FB 97 and FB 198 
i001:  Switchover for output 8 
i002:  Switchover for output 13 
[SW2.0 and later] 
Settings: 
0 = Binector B0000 
1 = Binector B0001 
etc. 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
SIEMENS AG    6RX1700-0AD76 
11-121 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
Connector changeover switches 9 and 14 
U256 
(2256) 
S00 
(B150) 
Source for input quantities 
FB 98 and FB 199 
Output 9 = Connector K9218 
i001:  1st input signal 
i002:  2nd input signal 
Output 14 = Connector K9268 
[SW2.0 and later] 
i003:  1st input signal 
i004:  2nd input signal 
Settings: 
0 = Connector K0000 
1 = Connector K0001 
etc. 
All connector 
numbers 
Ind: 4 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U257 
(2257) 
S00 
(B150) 
Source for control signal 
FB 98 and FB 199 
i001:  Switchover for output 9 
i002:  Switchover for output 14 
[SW2.0 and later] 
Settings: 
0 = Binector B0000 
1 = Binector B0001 
etc. 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
Connector changeover switches 10 and 15 
U258 
(2258) 
S00 
(B150) 
Source for input quantities 
FB 99 and FB 229 
Output 10 = Connector K9219 
i001:  1st input signal 
i002:  2nd input signal 
Output 15 = Connector K9269 
[SW2.0 and later] 
i003:  1st input signal 
i004:  2nd input signal 
Settings: 
0 = Connector K0000 
1 = Connector K0001 
etc. 
All connector 
numbers 
Ind: 4 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U259 
(2259) 
S00 
(B150) 
Source for control signal 
FB 99 and FB 229 
i001:  Switchover for output 10 
i002:  Switchover for output 15 
[SW2.0 and later] 
Settings: 
0 = Binector B0000 
1 = Binector B0001 
etc. 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
11.64  Integrators, DT1 elements, characteristics, dead zones, setpoint branching 
Only active with optional technology software S00 
Integrator 1 (output = K9220) 
U260 
(2260) 
S00 
(B155) 
Source for input quantity 
FB 100 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U261 
(2261) 
S00 
(B155) 
Integral-action time 
FB 100  10 to 65000 
[ms] 
Ind: None 
FS=10 
Type: O2 
P052 = 3 
P051 = 40 
Online 
11-122 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
U262 
(2262) 
S00 
(B155) 
Source for control signals 
FB 100 
i001  Source for "Stop integrator" signal 
(integrator is stopped when binector reaches log. "1" state) 
i002  Source for "Set integrator" signal 
(when binector reaches log. "1" state, the integrator is set to the 
value entered in parameter U263) 
Settings: 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U263 
(2263) 
S00 
(B155) 
Source for setting value 
FB 100 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
Integrator 2 (output = K9221) 
U264 
(2264) 
S00 
(B155) 
Source for input quantity 
FB 101 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U265 
(2265) 
S00 
(B155) 
Integral-action time 
FB 101  10 to 65000 
[ms] 
Ind: None 
FS=10 
Type: O2 
P052 = 3 
P051 = 40 
Online 
U266 
(2266) 
S00 
(B155) 
Source for control signals 
FB 101 
i001  Source for "Stop integrator" signal 
(integrator is stopped when binector reaches log. "1" state) 
i002  Source for "Set integrator" signal 
(when binector reaches log. "1" state, the integrator is set to the 
value entered in parameter U267) 
Settings: 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U267 
(2267) 
S00 
(B155) 
Source for setting value 
FB 101 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
Integrator 3 (output = K9222) 
U268 
(2268) 
S00 
(B155) 
Source for input quantity 
FB 102 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U269 
(2269) 
S00 
(B155) 
Integral-action time 
FB 102 
10 to 65000 
[ms] 
Ind: None 
FS=10 
Type: O2 
P052 = 3 
P051 = 40 
Online 
U270 
(2270) 
S00 
(B155) 
Source for control signals 
FB 102 
i001  Source for "Stop integrator" signal 
(integrator is stopped when binector reaches log. "1" state) 
i002  Source for "Set integrator" signal 
(when binector reaches log. "1" state, the integrator is set to the 
value entered in parameter U271) 
Settings: 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
SIEMENS AG    6RX1700-0AD76 
11-123 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
U271 
(2271) 
S00 
(B155) 
Source for setting value 
FB 102 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
DT1 element 1 (output = K9223, inverted: K9224) 
U272 
(2272) 
S00 
(B155) 
Source for input quantity 
FB 103 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U273 
(2273) 
S00 
(B155) 
Derivative-action time 
FB 103  0 to 1000 
[ms] 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
U274 
(2274) 
S00 
(B155) 
Filter time 
FB 103  0 to 1000 
[ms] 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
DT1 element 2 (output = K9225, inverted: K9226) 
U275 
(2275) 
S00 
(B155) 
Source for input quantity 
FB 104 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U276 
(2276) 
S00 
(B155) 
Derivative-action time 
FB 104 
0 to 1000 
[ms] 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
U277 
(2277) 
S00 
(B155) 
Filter time 
FB 104  0 to 1000 
[ms] 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
DT1 element 3 (output = K9227, inverted: K9228) 
U278 
(2278) 
S00 
(B155) 
Source for input quantity 
FB 105 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U279 
(2279) 
S00 
(B155) 
Derivative-action time 
FB 105 
0 to 1000 
[ms] 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
U280 
(2280) 
S00 
(B155) 
Filter time 
FB 105 
0 to 1000 
[ms] 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
11-124 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
Characteristic blocks 
The curve of the characteristics can be defined by 10 points each: 
Index i001 to i010 of the parameters for the x values (U282, U285, U288):   x values for FB 106, FB 107, FB 108 
Index i001 to i010 of the parameters for the y values (U283, U286, U289): associated y values 
SW1.8 and later: 
Index i011 to i020 of the parameters for the x values (U282, U285, U288): x values for FB 280, FB 282, FB 284 
Index i011 to i020 of the parameters for the y values (U283, U286, U289): associated y values 
Index i021 to i030 of the parameters for the x values (U282, U285, U288): x values for FB 281, FB 283, FB 285  
Index i021 to i030 of the parameters for the y values (U283, U286, U289): associated y values 
for   x = -200.00% up to x value acc. to index i001 (or i011 or i021) of the parameter for the x values gilt:  
y = value acc. to index i001 (or i011 or i021) of the parameter for the y values 
for   x = x value acc. to index i010 (or i020 or i030) of the parameter for the x values to x = 200.00% gilt:   
y = value acc. to index i010 (or i020 or i030) of the parameter for the y values 
The distance between two adjacent x or y values must not be more than 199.99% otherwise deviations from the required shape of the 
characteristic can 
Characteristic block 1 (output = K9229) 
FB 106 
Characteristic block 4 (output = K9410)  [SW1.8 and later] 
FB 280 
Characteristic block 5 (output = K9411)  [SW1.8 and later] 
FB 281 
U281 
(2281) 
S00 
(B160) 
Source for input quantity 
0 = Connector K0000 
1 = Connector K0001 
etc. 
Up to SW 1.7:  
Selected connector = input quantity for FB106 
SW 1.8 and later: 
i001  Input quantity 
for FB106 
i002  Input quantity 
for FB280 
i003  Input quantity 
for FB281 
All connector 
numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
off-line 
U282 
(2282) 
S00 
(B160) 
x values 
i001  1st characteristic point 
for FB106 
i002  2nd characteristic point 
for FB106 
... 
i010  10th characteristic point 
for FB106 
SW 1.8 and later: 
i011  1st characteristic point 
for FB280 
i012  2nd characteristic point 
for FB280 
... 
i020  10th characteristic point 
for FB280 
i021  1st characteristic point 
for FB281 
i022  2nd characteristic point 
for FB281 
... 
i030  10th characteristic point 
for FB281 
-200.00 to 199.99 
[%] 
0.01 
Ind:30 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
on-line 
U283 
(2283) 
S00 
(B160) 
y values 
i001  1st characteristic point 
for FB106 
i002  2nd characteristic point 
for FB106 
... 
i010  10th characteristic point 
for FB106 
SW 1.8 and later: 
i011  1st characteristic point 
for FB280 
i012  2nd characteristic point 
for FB280 
... 
i020  10th characteristic point 
for FB280 
i021  1st characteristic point 
for FB281 
i022  2nd characteristic point 
for FB281 
... 
i030  10th characteristic point 
for FB281 
-200.00 to 199.99 
[%] 
0.01 
Ind: 30 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
on-line 
Documents you may be interested
Documents you may be interested