pdf renderer c# : Acrobat insert image into pdf control SDK system web page winforms windows console OPI_simoreg_DC_0707_en59-part1914

SIEMENS AG    6RX1700-0AD76 
11-125 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
Characteristic block 2 (output = K9230)  
FB 107 
Characteristic block 6 (output = K9412)  [SW1.8 and later] 
FB 282 
Characteristic block 7 (output = K9413)  [SW1.8 and later] 
FB 283 
U284 
(2284) 
S00 
(B160) 
Source for input quantity 
0 = Connector K0000 
1 = Connector K0001 
etc. 
up to SW 1.7:  
Selected connector = input quantity for FB107 
SW 1.8 and later: 
i001  input quantity 
for FB107 
i002  input quantity 
for FB282 
i003  input quantity 
for FB283 
All connector 
numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
off-line 
U285 
(2285) 
S00 
(B160) 
x values 
i001  1st characteristic point 
for FB107 
i002  2nd characteristic point 
for FB107 
... 
i010  10th characteristic point 
for FB107 
SW 1.8 and later: 
i011  1st characteristic point 
for FB282 
i012  2nd characteristic point 
for FB282 
... 
i020  10th characteristic point 
for FB282 
i021  1st characteristic point 
for FB283 
i022  2nd characteristic point 
for FB283 
... 
i030  10th characteristic point 
for FB283 
-200.00 to 199.99 
[%] 
0.01 
Ind: 30 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
on-line 
U286 
(2286) 
S00 
(B160) 
y values 
i001  1st characteristic point 
for FB107 
i002  2nd characteristic point 
for FB107 
... 
i010  10th characteristic point 
for FB107 
SW 1.8 and later: 
i011  1st characteristic point 
for FB282 
i012  2nd characteristic point 
for FB282 
... 
i020  10th characteristic point 
for FB282 
i021  1st characteristic point 
for FB283 
i022  2nd characteristic point 
for FB283 
... 
i030  10th characteristic point 
for FB283 
-200.00 to 199.99 
[%] 
0.01 
Ind: 30 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
on-line 
Characteristic block 3 (Output = K9231)  
FB 108 
Characteristic block 8 (Output = K9414)  [SW1.8 and later] 
FB 284 
Characteristic block 9 (Output = K9415)  [SW1.8 and later] 
FB 285 
U287 
(2287) 
S00 
(B160) 
Source for input quantity 
0 = Connector K0000 
1 = Connector K0001 
etc. 
up to SW 1.7:  
Selected connector = input quantity for FB108 
SW 1.8 and later: 
i001  Input quantity 
for FB108 
i002  Input quantity 
for FB284 
i003  Input quantity 
for FB285 
All connector 
numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
off-line 
Acrobat insert image into pdf - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
how to add image to pdf document; how to add image to pdf in acrobat
Acrobat insert image into pdf - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
how to add a jpeg to a pdf; add jpg to pdf online
11-126 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
U288 
(2288) 
S00 
(B160) 
x values 
i001  1st characteristic point 
for FB108 
i002  2nd characteristic point 
for FB108 
... 
i010  10th characteristic point 
for FB108 
SW 1.8 and later: 
i011  1st characteristic point 
for FB284 
i012  2nd characteristic point 
for FB284 
... 
i020  10th characteristic point 
for FB284 
i021  1st characteristic point 
for FB285 
i022  2nd characteristic point 
for FB285 
... 
i030  10th characteristic point 
for FB285 
-200.00 to 199.99 
[%] 
0.01 
Ind: 30 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
on-line 
U289 
(2289) 
S00 
(B160) 
y values 
i001  1st characteristic point 
for FB108 
i002  2nd characteristic point 
for FB108 
... 
i010  10th characteristic point 
for FB108 
SW 1.8 and later: 
i011  1st characteristic point 
for FB284 
i012  2nd characteristic point 
for FB284 
... 
i020  10th characteristic point 
for FB284 
i021  1st characteristic point 
for FB285 
i022  2nd characteristic point 
for FB285 
... 
i030  10th characteristic point 
for FB285 
-200.00 to 199.99 
[%] 
0.01 
Ind: 30 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
on-line 
Dead zones 
The component of the input quantity (x) whose absolute value exceeds the threshold for the dead zone is applied to the output (y). 
Dead zone 1 (output = K9232) 
U290 
(2290) 
S00 
(B161) 
Source for input quantity 
FB 109 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U291 
(2291) 
S00 
(B161) 
Dead zone 
FB 109  0.00 to 100.00 
[%] 
0.01 
Ind: None 
FS=0.00 
Type: O2 
P052 = 3 
P051 = 40 
Online 
Dead zone 2 (output = K9233) 
U292 
(2292) 
S00 
(B161) 
Source for input quantity 
FB 110 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U293 
(2293) 
S00 
(B161) 
Dead zone 
FB 110  0.00 to 100.00 
[%] 
0.01 
Ind: None 
FS=0.00 
Type: O2 
P052 = 3 
P051 = 40 
Online 
Dead zone 3 (output = K9234) 
U294 
(2294) 
S00 
(B161) 
Source for input quantity 
FB 111 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U295 
(2295) 
S00 
(B161) 
Dead zone 
FB 111  0.00 to 100.00 
[%] 
0.01 
Ind: None 
FS=0.00 
Type: O2 
P052 = 3 
P051 = 40 
Online 
.NET PDF Document Viewing, Annotation, Conversion & Processing
Convert image files to PDF. File & Page Process. Annotate & Comment. Add, insert PDF native annotations to PDF file. Support for all the print modes in Acrobat PDF
how to add an image to a pdf file in acrobat; add photo to pdf preview
C# PDF Converter Library SDK to convert PDF to other file formats
without using other external third-party dependencies like Adobe Acrobat. demo code for PDF to TIFF image conversion may directly copy and paste it into your C#
add jpg to pdf preview; add signature image to pdf
SIEMENS AG    6RX1700-0AD76 
11-127 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
Setpoint branching (output = K9234) 
The input quantity is weighted with 2 parameters: 
Parameter U297 determines the output value with an input = 0% 
Parameter U298 determines the output value with an input = +100% 
-U297 and -U298 apply in the case of negative input values. 
The hysteresis set in parameter U299 is applied for transitions from negative to positive input values and vice versa 
U296 
(2296) 
S00 
(B161) 
Source for input quantity 
FB 112 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U297 
(2297) 
S00 
(B161) 
Minimum speed 
FB 112  0.00 to 199.99 
[%] 
0.01 
Ind: None 
FS=0.00 
Type: O2 
P052 = 3 
P051 = 40 
Online 
U298 
(2298) 
S00 
(B161) 
Maximum speed 
FB 112  0.00 to 199.99 
[%] 
0.01 
Ind: None 
FS=100.00 
Type: O2 
P052 = 3 
P051 = 40 
Online 
U299 
(2299) 
S00 
(B161) 
Hysteresis 
FB 112  0.00 to 100.00 
[%] 
0.01 
Ind: None 
FS=0.00 
Type: O2 
P052 = 3 
P051 = 40 
Online 
11.65  Simple ramp-function generator 
Only active with optional technology software S00 
Please note:  The output (y) = 0 is set in response to "Set simple ramp-function generator to zero" and POWER ON 
The output (y) is frozen at the current value in response to "Stop simple ramp-function generator" 
The ramp-up and ramp-down times are set to zero in response to "Bypass simple ramp-function generator" 
Ramp-up integrator: 
The simple ramp-function generator contains a flip-flop whose output is set to log. "0" (ramp generator initial run) after POWER 
ON or when the ramp-function generator has been enabled. When the ramp-function generator output reaches a value 
corresponding to the input quantity (y=x) for the first time, the flip-flop output switches to log. "1" and remains in this state until 
the next enabling command. This output is linked to binector B9191. By parameterizing U301, index i001=919, it is possible to 
apply this binector to the "Bypass simple ramp-function generator" function and thus to implement a ramp-up integrator 
function. 
U300 
(2300) 
S00 
(B165) 
Source for input quantity 
FB 113 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U301 
(2301) 
S00 
(B165) 
Source for control signals 
FB 113 
i001  Source for "Bypass simple ramp-function generator" signal 
i002  Source for "Stop simple ramp-function generator" signal 
i003  Source for "Reset / enable simple ramp-function generator" 
signal 
(0 = reset to zero, 1 = enable) 
Settings: 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 3 
FS= 
i001: 0 
i002: 0 
i003: 1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U302 
(2302) 
S00 
(B165) 
Ramp-up time 
FB 113  0.00 to 300.00 
[s] 
0.01 
Ind: None 
FS=0.00 
Type: O2 
P052 = 3 
P051 = 40 
Online 
U303 
(2303) 
S00 
(B165) 
Ramp-down time 
FB 113  0.00 to 300.00 
[s] 
0.01 
Ind: None 
FS=0.00 
Type: O2 
P052 = 3 
P051 = 40 
Online 
C# powerpoint - PowerPoint Conversion & Rendering in C#.NET
using other external third-party dependencies like Adobe Acrobat. demo code for PowerPoint to TIFF image conversion may directly copy and paste it into your C#
add an image to a pdf with acrobat; how to add an image to a pdf file
C# Word - Word Conversion in C#.NET
using other external third-party dependencies like Adobe Acrobat. C# demo code for Word to TIFF image conversion You may directly copy and paste it into your C#
add a jpeg to a pdf; add an image to a pdf form
11-128 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
11.66  Multiplexer  
Only active with optional technology software S00 
FB86 = 1st multiplexer (output = K9450)
FB87 = 2nd multiplexer (output = K9451) 
FB88 = 3rd multiplexer (output = K9452) 
Function: 
An input quantity is connected through to the output depending on the control bits: 
B3  B2  B1 
Output y
X0 
X1 
X2 
X3 
X4 
X5 
X6 
X7 
U310 
(2310) 
S00 
(B195) 
Source for control bits for the multiplexer 
[SW 1.8 and later] 
0 = Binector B0000 
1 = Binector B0001 
etc. 
i001:  Control bit B1  
for 1st multiplexer 
i002:  Control bit B2  
i003:  Control bit B3  
i004:  Control bit B1  
for 2nd multiplexer 
i005:  Control bit B2  
i006:  Control bit B3  
i007:  Control bit B1  
for 3rd multiplexer 
i008:  Control bit B2  
i009:  Control bit B3  
All binector numbers 
Ind: 9 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
off-line 
U311 
(2311) 
S00 
(B195) 
Source for input quantities for 1st multiplexer  
[SW 1.8 and later] 
0 = Connector K0000 
1 = Connector K0001 
etc. 
i001  Input quantity X0 
i002  Input quantity X1 
i003  Input quantity X2 
i004  Input quantity X3 
i005  Input quantity X4 
i006  Input quantity X5 
i007  Input quantity X6 
i008  Input quantity X7 
All connector 
numbers 
Ind: 8 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
off-line 
U312 
(2312) 
S00 
(B195) 
Source for input quantities for 2nd multiplexer  
[SW 1.8 and later] 
0 = Connector K0000 
1 = Connector K0001 
etc. 
i001  Input quantity X0 
i002  Input quantity X1 
i003  Input quantity X2 
i004  Input quantity X3 
i005  Input quantity X4 
i006  Input quantity X5 
i007  Input quantity X6 
i008  Input quantity X7 
All connector 
numbers 
Ind: 8 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
off-line 
C# Windows Viewer - Image and Document Conversion & Rendering in
without using other external third-party dependencies like Adobe Acrobat. Image and Document Conversion Supported by Windows Viewer. Convert to PDF.
adding an image to a pdf file; add picture to pdf file
VB.NET PDF: How to Create Watermark on PDF Document within
PDF Watermark Creator, users need no external application plugin, like Adobe Acrobat. to PDF. Besides text, users also can insert a target image, like company
add image to pdf preview; adding a jpg to a pdf
SIEMENS AG    6RX1700-0AD76 
11-129 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
U313 
(2313) 
S00 
(B195) 
Source for input quantities for 3rd multiplexer  
[SW 1.8 and later] 
0 = Connector K0000 
1 = Connector K0001 
etc. 
i001  Input quantity X0 
i002  Input quantity X1 
i003  Input quantity X2 
i004  Input quantity X3 
i005  Input quantity X4 
i006  Input quantity X5 
i007  Input quantity X6 
i008  Input quantity X7 
All connector 
numbers 
Ind: 8 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
off-line 
11.67  Counters  
Only active with optional technology software S00 
Software counter  
FB 89 
n314 
(2314) 
S00 
(B196) 
Display of output of software counter 
FB 89
[SW 1.9 and later] 
0 to 65535 
Ind: None 
Type: O2 
P052 = 3 
U315 
(2315) 
S00 
(B196) 
Fixed values for setting/limiting inputs of software counter 
FB 89
[SW 1.9 and later] 
i001:  Minimum value 
i002:  Maximum value 
i003:  Setting value 
i004:  Start value 
0 to 65535 
Ind: 4 
FS=  
i001: 0 
i002: 65535 
i003: 0 
i004: 0 
Type: O2 
P052 = 3 
P051 = 40 
off-line 
U316 
(2316) 
S00 
(B196) 
Source for setting/limiting inputs of software counter 
FB 89
[SW 1.9 and later] 
i001:  Minimum value 
i002:  Maximum value 
i003:  Setting value 
i004:  Start value 
Settings: 
0 = connector K0000 
1 = connector K0001 
etc. 
All connector 
numbers 
Ind: 4 
FS=  
i001: 9441 
i002: 9442 
i003: 9443 
i004: 9444 
Type: L2 
P052 = 3 
P051 = 40 
off-line 
U317 
(2317) 
S00 
(B196) 
Source for control signals of software counter 
FB 89
[SW 1.9 and later] 
i001:  Positive edge: Count up 
i002:  Positive edge: Count down 
i003:  Stop counter  
i004:  Set counter  
i005:  Enable counter 
Settings: 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 5 
FS=  
i001: 0 
i002: 0 
i003: 0 
i004: 0 
i005: 1 
Type: L2 
P052 = 3 
P051 = 40 
off-line 
C# Excel - Excel Conversion & Rendering in C#.NET
using other external third-party dependencies like Adobe Acrobat. of C# demo code for Excel to TIFF image conversion may directly copy and paste it into your C#
add a picture to a pdf file; adding images to a pdf document
VB.NET PowerPoint: VB Code to Draw and Create Annotation on PPT
with no more plug-ins needed like Acrobat or Adobe VB.NET PPT: VB Code to Add Embedded Image Object to VB.NET PPT: Insert and Customize Text Annotation on PPT
add photo to pdf online; add photo to pdf file
11-130 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
11.68  Logic functions 
Only active with optional technology software S00 
Decoders/demultiplexers, binary to 1 of 8 
U318 
(2318) 
S00 
(B200) 
Source for input signals for decoder/demultiplexer 1 
FB 118 
i001  Source for input signal, bit 0 
i002  Source for input signal, bit 1 
i003  Source for input signal, bit 2 
Settings: 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U319 
(2319) 
S00 
(B200) 
Source for input signals for decoder/demultiplexer 2 
FB 119 
i001  Source for input signal, bit 0 
i002  Source for input signal, bit 1 
i003  Source for input signal, bit 2 
Settings: 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
AND elements with 3 inputs each 
The input signals selected via the 3 indices of the parameter are ANDed and the result of the logic operation applied to the specified 
binector. 
U320 
(2320) 
S00 
(B205) 
Source for input signals, AND element 1 (output = B9350) 
FB 120 
i001  Source for input 1 
i002  Source for input 2 
i003  Source for input 3 
Settings: 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 3 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U321 
(2321) 
S00 
(B205) 
Source for input signals, AND element 2 (output = B9351) 
FB 121 
As for U320 
All binector numbers 
Ind: 3 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U322 
(2322) 
S00 
(B205) 
Source for input signals, AND element 3 (output = B9352) 
FB 122 
As for U320 
All binector numbers 
Ind: 3 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U323 
(2323) 
S00 
(B205) 
Source for input signals, AND element 4 (output = B9353) 
FB 123 
As for U320 
All binector numbers 
Ind: 3 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U324 
(2324) 
S00 
(B205) 
Source for input signals, AND element 5 (output = B9354) 
FB 124 
As for U320 
All binector numbers 
Ind: 3 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U325 
(2325) 
S00 
(B205) 
Source for input signals, AND element 6 (output = B9355) 
FB 125 
As for U320 
All binector numbers 
Ind: 3 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U326 
(2326) 
S00 
(B205) 
Source for input signals, AND element 7 (output = B9356) 
FB 126 
As for U320 
All binector numbers 
Ind: 3 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
SIEMENS AG    6RX1700-0AD76 
11-131 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
U327 
(2327) 
S00 
(B205) 
Source for input signals, AND element 8 (output = B9357) 
FB 127 
As for U320 
All binector numbers 
Ind: 3 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U328 
(2328) 
S00 
(B205) 
Source for input signals, AND element 9 (output = B9358) 
FB 128 
As for U320 
All binector numbers 
Ind: 3 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U329 
(2329) 
S00 
(B205) 
Source for input signals, AND element 10 (output = B9359) 
FB 129 
As for U320 
All binector numbers 
Ind: 3 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U330 
(2330) 
S00 
(B205) 
Source for input signals, AND element 11 (output = B9360) 
FB 130 
As for U320 
All binector numbers 
Ind: 3 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U331 
(2331) 
S00 
(B205) 
Source for input signals, AND element 12 (output = B9361) 
FB 131 
As for U320 
All binector numbers 
Ind: 3 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U332 
(2332) 
S00 
(B205) 
Source for input signals, AND element 13 (output = B9362) 
FB 132 
As for U320 
All binector numbers 
Ind: 3 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U333 
(2333) 
S00 
(B205) 
Source for input signals, AND element 14 (output = B9363) 
FB 133 
As for U320 
All binector numbers 
Ind: 3 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U334 
(2334) 
S00 
(B205) 
Source for input signals, AND element 15 (output = B9364) 
FB 134 
As for U320 
All binector numbers 
Ind: 3 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U335 
(2335) 
S00 
(B205) 
Source for input signals, AND element 16 (output = B9365) 
FB 135 
As for U320 
All binector numbers 
Ind: 3 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U336 
(2336) 
S00 
(B205) 
Source for input signals, AND element 17 (output = B9366) 
FB 136 
As for U320 
All binector numbers 
Ind: 3 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U337 
(2337) 
S00 
(B205) 
Source for input signals, AND element 18 (output = B9367) 
FB 137 
As for U320 
All binector numbers 
Ind: 3 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U338 
(2338) 
S00 
(B205) 
Source for input signals, AND element 19 (output = B9368) 
FB 138 
As for U320 
All binector numbers 
Ind: 3 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U339 
(2339) 
S00 
(B205) 
Source for input signals, AND element 20 (output = B9369) 
FB 139 
As for U320 
All binector numbers 
Ind: 3 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U340 
(2340) 
S00 
(B205) 
Source for input signals, AND element 21 (output = B9370) 
FB 140 
As for U320 
All binector numbers 
Ind: 3 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
11-132 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
U341 
(2341) 
S00 
(B205) 
Source for input signals, AND element 22 (output = B9371) 
FB 141 
As for U320 
All binector numbers 
Ind: 3 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U342 
(2342) 
S00 
(B205) 
Source for input signals, AND element 23 (output = B9372) 
FB 142 
As for U320 
All binector numbers 
Ind: 3 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U343 
(2343) 
S00 
(B205) 
Source for input signals, AND element 24 (output = B9373) 
FB 143 
As for U320 
All binector numbers 
Ind: 3 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U344 
(2344) 
S00 
(B205) 
Source for input signals, AND element 25 (output = B9374) 
FB 144 
As for U320 
All binector numbers 
Ind: 3 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U345 
(2345) 
S00 
(B205) 
Source for input signals, AND element 26 (output = B9375) 
FB 145 
As for U320 
All binector numbers 
Ind: 3 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U346 
(2346) 
S00 
(B205) 
Source for input signals, AND element 27 (output = B9376) 
FB 146 
As for U320 
All binector numbers 
Ind: 3 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U347 
(2347) 
S00 
(B205) 
Source for input signals, AND element 28 (output = B9377) 
FB 147 
As for U320 
All binector numbers 
Ind: 3 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
OR elements with 3 inputs each 
The input signals selected via the 3 indices of the parameter are ORed and the result of the logic operation applied to the specified 
binector. 
U350 
(2350) 
S00 
(B206) 
Source for input signals, OR element 1 (output = B9380) 
FB 150 
i001  Source for input 1 
i002  Source for input 2 
i003  Source for input 3 
Settings: 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U351 
(2351) 
S00 
(B206) 
Source for input signals, OR element 2 (output = B9381) 
FB 151 
As for U350 
All binector numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U352 
(2352) 
S00 
(B206) 
Source for input signals, OR element 3 (output = B9382) 
FB 152 
As for U350 
All binector numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U353 
(2353) 
S00 
(B206) 
Source for input signals, OR element 4 (output = B9383) 
FB 153 
As for U350 
All binector numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U354 
(2354) 
S00 
(B206) 
Source for input signals, OR element 5 (output = B9384) 
FB 154 
As for U350 
All binector numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
SIEMENS AG    6RX1700-0AD76 
11-133 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
U355 
(2355) 
S00 
(B206) 
Source for input signals, OR element 6 (output = B9385) 
FB 155 
As for U350 
All binector numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U356 
(2356) 
S00 
(B206) 
Source for input signals, OR element 7 (output = B9386) 
FB 156 
As for U350 
All binector numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U357 
(2357) 
S00 
(B206) 
Source for input signals, OR element 8 (output = B9387) 
FB 157 
As for U350 
All binector numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U358 
(2358) 
S00 
(B206) 
Source for input signals, OR element 9 (output = B9388) 
FB 158 
As for U350 
All binector numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U359 
(2359) 
S00 
(B206) 
Source for input signals, OR element 10 (output = B9389) 
FB 159 
As for U350 
All binector numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U360 
(2360) 
S00 
(B206) 
Source for input signals, OR element 11 (output = B9390) 
FB 160 
As for U350 
All binector numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U361 
(2361) 
S00 
(B206) 
Source for input signals, OR element 12 (output = B9391) 
FB 161 
As for U350 
All binector numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U362 
(2362) 
S00 
(B206) 
Source for input signals, OR element 13 (output = B9392) 
FB 162 
As for U350 
All binector numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U363 
(2363) 
S00 
(B206) 
Source for input signals, OR element 14 (output = B9393) 
FB 163 
As for U350 
All binector numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U364 
(2364) 
S00 
(B206) 
Source for input signals, OR element 15 (output = B9394) 
FB 164 
As for U350 
All binector numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U365 
(2365) 
S00 
(B206) 
Source for input signals, OR element 16 (output = B9395) 
FB 165 
As for U350 
All binector numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U366 
(2366) 
S00 
(B206) 
Source for input signals, OR element 17 (output = B9396) 
FB 166 
As for U350 
All binector numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U367 
(2367) 
S00 
(B206) 
Source for input signals, OR element 18 (output = B9397) 
FB 167 
As for U350 
All binector numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U368 
(2368) 
S00 
(B206) 
Source for input signals, OR element 19 (output = B9398) 
FB 168 
As for U350 
All binector numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
11-134 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
U369 
(2369) 
S00 
(B206) 
Source for input signals, OR element 20 (output = B9399) 
FB 169 
As for U350 
All binector numbers 
Ind: 3 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
EXCLUSIVE OR elements with 2 inputs each 
The input signals selected via the 2 indices of the parameter are combined in an EXCLUSIVE OR (XOR) operation and the result applied 
to the specified binector.. 
U370 
(2370) 
S00 
(B206) 
Source for input signals, XOR element 1 (output = B9195) 
FB 170 
i001  Source for input 1 
i002  Source for input 2 
Settings: 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U371 
(2371) 
S00 
(B206) 
Source for input signals, XOR element 2 (output = B9196) 
FB 171 
As for U370 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U372 
(2372) 
S00 
(B206) 
Source for input signals, XOR element 3 (output = B9197) 
FB 172 
As for U370 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U373 
(2373) 
S00 
(B206) 
Source for input signals, XOR element 4 (output = B9198) 
FB 173 
As for U370 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
Inverters 
The input signal is inverted and the result applied to the specified binector. 
U380 
(2380) 
S00 
(B207) 
Source for input signal, inverter 1 (output = B9450) 
FB 180 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U381 
(2381) 
S00 
(B207) 
Source for input signal, inverter 2 (output = B9451) 
FB 181 
As for U380 
All binector numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U382 
(2382) 
S00 
(B207) 
Source for input signal, inverter 3 (output = B9452) 
FB 182 
As for U380 
All binector numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U383 
(2383) 
S00 
(B207) 
Source for input signal, inverter 4 (output = B9453) 
FB 183 
As for U380 
All binector numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U384 
(2384) 
S00 
(B207) 
Source for input signal, inverter 5 (output = B9454) 
FB 184 
As for U380 
All binector numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U385 
(2385) 
S00 
(B207) 
Source for input signal, inverter 6 (output = B9455) 
FB 185 
As for U380 
All binector numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U386 
(2386) 
S00 
(B207) 
Source for input signal, inverter 7 (output = B9456) 
FB 186 
As for U380 
All binector numbers 
Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 