SIEMENS AG    6RX1700-0AD76 
11-155 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
U678 
(2678) 
S00 
(B152) 
Memory for actual position values: Initial value at POWER ON  FB 54
[SW 2.1 and later] 
Initial value = 0 
Initial value is set such that on POWER ON KK9481 or KK9482 
assumes whatever its setting value was before the electronics 
supply was disconnected. 
0 to 1 
Ind: none 
FS=0 
Type: O2 
P052 = 2 
P051 = 40 
online 
11.82  Root extractor 
Only active with optional technology software S00 
U680 
(2680) 
S00 
(B153) 
Source for the input of the root extractor 
FB 58
[SW 2.0 and later] 
Selection of the connector whose value is to be used for the root extractor 
input. 
Settings: 
0 = Connector K0000 
1 = Connector K0001 
etc. 
All connector 
numbers 
Ind: none 
FS=9483 
Type: L2 
P052 = 2 
P051 = 40 
offline 
U681 
(2681) 
S00 
(B153) 
Operating point for limit monitoring indicator of the root extractor 
FB 58  
[SW 2.0 and later] 
applied to connector KK9483 
1 to 65535 
Ind: none 
FS=1 
Type: O2 
P052 = 2 
P051 = 40 
online 
U682 
(2682) 
S00 
(B153) 
Hysteresis for limit monitoring indicator of the root extractor 
FB 58
[SW 2.0 and later] 
1 to 65535 
Ind: none 
FS=1 
Type: O2 
P052 = 2 
P051 = 40 
online 
U683 
(2683) 
S00 
(B153) 
x value for root function and gradient 
FB 58
[SW 2.0 and later] 
Definition of input values 
i001:  Distance between input value of root function and fictitious 
passage through zero for y value U684.001 
i002:  x value of gradient for y value U684.002 
1 to 65535 
Ind: 2 
FS=1000 
Type: O2 
P052 = 2 
P051 = 40 
online 
U684 
(2684) 
S00 
(B153) 
y value for root function and gradient 
FB 58
[SW 2.0 and later] 
Definition of output values 
i001:  y value of root function for distance U683.001 
i002:  y value of gradient for x value U683.002 
0.01 to 199.99 
[%] 
0.01 
Ind: 2 
FS=100.00 
Type: O2 
P052 = 2 
P051 = 40 
online 
How to add image to pdf in preview - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
adding image to pdf; add photo to pdf reader
How to add image to pdf in preview - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
how to add an image to a pdf file; add picture to pdf form
11-156 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
11.83  Configuration of SCB1 with SCI 
U690 
(2690) 
(Z150)  
(Z151) 
Configuration of analog inputs of SCI1 
[SW 1.9 and later] 
Definition of type of input signals 
Parameter value 
Terminals 
Terminals 
X428/3, 6, 9 
X428/5, 8, 11 
0: 
-10 V ... + 10 V 
- 20 mA ... + 20 mA 
1: 
0 V ... + 10 V 
0 mA ... + 20 mA 
2: 
4 mA ... + 20 mA 
Notes: 
- Only one signal can be processed per input. Voltage or current signals can 
be evaluated. 
- Voltage and current signals must be connected to different terminals. 
- Only unipolar signals are permitted with settings 1 and 2, i.e. the internal 
process quantities are also unipolar. 
- When setting 2 is selected, an input current of< 2 mA causes shutdown on 
faults (open-circuit monitoring) 
- The offset compensation for the analog inputs is set in parameter U692. 
i001:  Slave 1, analog input 1 
i002:  Slave 1, analog input 2 
i003:  Slave 1, analog input 3 
i004:  Slave 2, analog input 1 
i005:  Slave 2, analog input 2 
i006:  Slave 2, analog input 3 
0 to 2 
Ind:6 
FS= 0 
Type O2 
P052 = 3 
P051 =40 
on-line 
U691 
(2691) 
(Z150)  
(Z151) 
Smoothing time constant for analog inputs of SCI1  [SW 1.9 and later] 
Formula:  T = 2ms * 2 to the power of U691 
i001:  Slave 1, analog input 1 
i002:  Slave 1, analog input 2 
i003:  Slave 1, analog input 3 
i004:  Slave 2, analog input 1 
i005:  Slave 2, analog input 2 
i006:  Slave 2, analog input 3 
0 to 15 
Ind:6 
FS= 2 
Type O2 
P052 = 3 
P051 =40 
on-line 
U692 
(2692) 
(Z150)  
(Z151) 
Offset compensation for analog inputs of SCI1 
[SW 1.9 and later] 
Setting instructions, see Operating Instructions for SCI1 
i001:  Slave 1, analog input 1 
i002:  Slave 1, analog input 2 
i003:  Slave 1, analog input 3 
i004:  Slave 2, analog input 1 
i005:  Slave 2, analog input 2 
i006:  Slave 2, analog input 3 
-20.00 to 20.00 
[V] 
0.01V 
Ind:6 
FS= 0 
Type I2 
P052 = 3 
P051 =40 
on-line 
U693 
(2693) 
(Z155)  
(Z156) 
Actual value output via analog outputs of SCI1 
[SW 1.9 and later] 
Selection of connectors whose values are to be output (for details, see 
Operating Instructions for SCI1) 
i001:  Slave 1, analog output 1 
i002:  Slave 1, analog output 2 
i003:  Slave 1, analog output 3 
i004:  Slave 2, analog output 1 
i005:  Slave 2, analog output 2 
i006:  Slave 2, analog output 3 
All connector 
numbers 
Ind:6 
FS= 0 
Type L2 
P052 = 3 
P051 =40 
on-line 
U694 
(2694) 
(Z155)  
(Z156) 
Gain for analog outputs of SCI1 
[SW 1.9 and later] 
Setting instructions, see Operating Instructions for SCI1 
i001:  Slave 1, analog output 1 
i002:  Slave 1, analog output 2 
i003:  Slave 1, analog output 3 
i004:  Slave 2, analog output 1 
i005:  Slave 2, analog output 2 
i006:  Slave 2, analog output 3 
-320.00 to 320.00 
[V] 
0.01V 
Ind:6 
FS= 10.00 
Type I2 
P052 = 3 
P051 =40 
on-line 
C# WinForms Viewer: Load, View, Convert, Annotate and Edit PDF
Convert PDF to Tiff image (.tif, .tiff). • Convert PDF to HTML (.htm, .html). PDF Annotation. • Add sticky notes to PDF document in preview.
adding an image to a pdf form; add picture to pdf
C# WPF Viewer: Load, View, Convert, Annotate and Edit PDF
PDF to Tiff image (.tif, .tiff). • Convert PDF to HTML (.htm, .html). PDF Annotation. • Add sticky notes to PDF document. • Highlight PDF text in preview.
how to add a jpg to a pdf; add image to pdf
SIEMENS AG    6RX1700-0AD76 
11-157 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
U695 
(2695) 
(Z155)  
(Z156) 
Offset compensation for analog outputs of SCI1 
[SW 1.9 and later] 
Setting instructions, see Operating Instructions for SCI1 
i001:  Slave 1, analog output 1 
i002:  Slave 1, analog output 2 
i003:  Slave 1, analog output 3 
i004:  Slave 2, analog output 1 
i005:  Slave 2, analog output 2 
i006:  Slave 2, analog output 3 
-100.00 to 100.00 
[V] 
0.01V 
Ind:6 
FS= 0 
Type I2 
P052 = 3 
P051 =40 
on-line 
U696 
(2696) 
Telegram failure time for SCB1 
[SW 1.9 and later] 
Fault message F079 is displayed if no process data are exchanged with the 
supplementary board within this delay period. The monitoring function is 
implemented within a 20 ms cycle. For this reason, only setting values 
which constitute a multiple of 20 ms are meaningful. 
Settings: 
No time monitoring 
1...65000  Permissible time interval between two process data 
exchange operations before a fault message is output. 
Note: 
The telegram monitoring function is active  
 from the receipt of the first error-free telegram after connection of the 
electronics power supply 
 from the receipt of the first error-free telegram after the telegram monitor 
has responded (i.e. monitoring timeout). 
0 to 65000 
[ms] 
1ms 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 =40 
Online 
n697 
(2697) 
Diagnostic information of SCB1 
[SW 1.9 and later] 
Visualization parameter for displaying diagnostic info relating to SCB1. 
The displayed values overflow at "255“ (e.g. the number of telegrams begins 
at "0" again after "255"). 
i001: Number of error-free telegrams 
i002: Number of errored telegrams 
i003:  Number of voltage failures on slaves 
i004: Number of interruptions in fiber-optic connection 
i005:  Number of missing response telegrams 
i006:  Number of search telegrams for slave location 
i007: ETX error 
i008:  Number of configuration telegrams 
i009:  Highest terminal numbers needed according to PZD 
connection (parameterization of connectors or binectors) 
i010:  Analog inputs/outputs required according to PZD connection of 
setpoint channel and actual value output via SCI 
(parameterization of appropriate connectors) 
i011:  Reserved 
i012:  Reserved 
i013:  SCB1 alarm word 
i014:  Setting defining whether slave no. 1 is needed and type if 
applicable 
0: No slave required 
1: SCI1 
2: SCI2 
i015:  Setting defining whether slave no. 2 is needed and type if 
applicable 
0: No slave required 
1: SCI1 
2: SCI2 
i016:  SCI board: Initialization error 
i017: SCB1 generation: Year 
i018: SCB1 generation: Day and month 
i019:  SCI slave1: Software version 
i020:  SCI slave1: Year of generation 
i021:  SCI slave1: Day and month of generation 
i022:  SCI slave2: Software version 
i023:  SCI slave2: Year of generation 
i024:  SCI slave2: Day and month of generation 
Ind:24 
Type O2 
P052 = 3 
P051 =40 
on-line 
How to C#: Preview Document Content Using XDoc.Word
C# DLLs for Word File Preview. Add references: Get Preview From File. You may get document preview image from an existing Word file in C#.net.
add photo to pdf for; how to add photo to pdf in preview
How to C#: Preview Document Content Using XDoc.PowerPoint
Add necessary XDoc.PowerPoint DLL libraries into your created C# application as You may get document preview image from an existing PowerPoint file in C#.net.
add jpg to pdf file; how to add a photo to a pdf document
11-158 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
U698 
(2698) 
(Z135)  
(Z136)  
(Z145)  
(Z146) 
Binector selection for binary outputs of SCI 
[SW 1.9 and later] 
Selection of binectors whose states are output via the binary outputs of the 
SCIs 
i001:  Binector selection for SCI slave1, binary output 1 
i002:  Binector selection for SCI slave1, binary output 2 
i003:  Binector selection for SCI slave1, binary output 3 
i004:  Binector selection for SCI slave1, binary output 4 
i005:  Binector selection for SCI slave1, binary output 5 
i006:  Binector selection for SCI slave1, binary output 6 
i007:  Binector selection for SCI slave1, binary output 7 
i008:  Binector selection for SCI slave1, binary output 8 
i009:  Binector selection for SCI slave1, binary output 9 
i010:  Binector selection for SCI slave1, binary output 10 
i011:  Binector selection for SCI slave1, binary output 11 
i012:  Binector selection for SCI slave1, binary output12 
i013:  Binector selection for SCI slave2, binary output 1 
i014:  Binector selection for SCI slave2, binary output 2 
i015:  Binector selection for SCI slave2, binary output 3 
i016:  Binector selection for SCI slave2, binary output 4 
i017:  Binector selection for SCI slave2, binary output 5 
i018:  Binector selection for SCI slave2, binary output 6 
i019:  Binector selection for SCI slave2, binary output 7 
i020:  Binector selection for SCI slave2, binary output 8 
i021:  Binector selection for SCI slave2, binary output 9 
i022:  Binector selection for SCI slave2, binary output 10 
i023:  Binector selection for SCI slave2, binary output 11 
i024:  Binector selection for SCI slave2, binary output12 
All binector numbers 
Ind:24 
FS= 0 
Type L2 
P052 = 3 
P051 =40 
on-line 
n699 
(2699) 
(Z130)  
(Z131)  
(Z135)  
(Z136)  
(Z140)  
(Z141)  
(Z145)  
(Z146)  
(Z150)  
(Z151)  
(Z155)  
(Z156) 
Display of SCB1/SCI process data 
[SW 1.9 and later] 
All values in hexadecimal representation 
i001:  SCI slave1, binary inputs 
i002:  SCI slave1, analog input1 
i003:  SCI slave1, analog input2 
i004:  SCI slave1, analog input3 
i005:  SCI slave2, binary inputs 
i006:  SCI slave2, analog input1 
i007:  SCI slave2, analog input2 
i008:  SCI slave2, analog input3 
i009:  SCI slave1, binary outputs 
i010:  SCI slave1, analog output1 
i011:  SCI slave1, analog output2 
i012:  SCI slave1, analog output3 
i013:  SCI slave2, binary outputs 
i014:  SCI slave2, binary outputs 
i015:  SCI slave2, analog output2 
i016:  SCI slave2, analog output3 
Ind:16 
Type L2 
P052 = 3 
P051 =40 
on-line 
11.84  Configuration of supplementary boards in board locations 2 and 3 
U710 
(2710) 
(Z110) 
(Z111) 
Initialize link to supplementary boards 
i001  Initialization of 1
st
communications board (in slot with lower ID 
letter) 
i002  Initialization of 2
nd
communications board (in slot with higher ID 
letter 
Settings: 
The link to supplementary boards is re-initialized. After the 
configuration parameters for supplementary boards have been 
changed, U710 must be set to 0 so that the new settings can 
take effect. 
The parameter is then set automatically to 1. 
Note: Data transmission is interrupted while initialization is in 
progress. 
Deactivated 
0 to 1 
Ind: 2 
FS=1 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
VB.NET PDF File Compress Library: Compress reduce PDF size in vb.
enables compressing and decompressing in preview in ASP.NET to reduce or minimize original PDF document size Reduce image resources: Since images are usually or
add jpg to pdf preview; add picture to pdf online
How to C#: Preview Document Content Using XDoc.excel
Add necessary references: RasterEdge.Imaging.Basic.dll. Get Preview From File. You may get document preview image from an existing Excel file in C#.net.
how to add a jpeg to a pdf; add a jpg to a pdf
SIEMENS AG    6RX1700-0AD76 
11-159 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
U711 
(2711) 
(Z110) 
(Z111) 
Communications board parameter 1 (CB parameter 1) 
See documentation for installed COM BOARD. 
This parameter is relevant only if a communications board is installed. The 
validity of the setting is monitored by the CB. If the CB rejects the setting, 
fault message F080 is displayed with fault value 5 
Index 1 is used to parameterize the 1
st
CB (including CB behind TB) and 
index 2 to parameterize the 2
nd
CB. 
0 to 65535 
Ind: 2 
FS=0 
Type: O2 
P052 = 3 
Online 
U712 
(2712) 
(Z110) 
(Z111) 
Communications board parameter 2 (CB parameter 2) 
See  U711 
0 to 65535 
Ind: 2 
FS=0 
Type: O2 
P052 = 3 
Online 
U713 
(2713) 
(Z110) 
(Z111) 
Communications board parameter 3 (CB parameter 3) 
See  U711 
0 to 65535 
Ind: 2 
FS=0 
Type: O2 
P052 = 3 
Online 
U714 
(2714) 
(Z110) 
(Z111) 
Communications board parameter 4 (CB parameter 4) 
See  U711 
0 to 65535 
Ind: 2 
FS=0 
Type: O2 
P052 = 3 
Online 
U715 
(2715) 
(Z110) 
(Z111) 
Communications board parameter 5 (CB parameter 5) 
See  U711 
0 to 65535 
Ind: 2 
FS=0 
Type: O2 
P052 = 3 
Online 
U716 
(2716) 
(Z110) 
(Z111) 
Communications board parameter 6 (CB parameter 6) 
See  U711 
0 to 65535 
Ind: 2 
FS=0 
Type: O2 
P052 = 3 
Online 
U717 
(2717) 
(Z110) 
(Z111) 
Communications board parameter 7 (CB parameter 7) 
See  U711 
0 to 65535 
Ind: 2 
FS=0 
Type: O2 
P052 = 3 
Online 
U718 
(2718) 
(Z110) 
(Z111) 
Communication Board Parameter 8 (CB-Parameter 8) 
See  U711 
0 to 65535 
Ind: 2 
FS=0 
Type: O2 
P052 = 3 
Online 
U719 
(2719) 
(Z110) 
(Z111) 
Communications board parameter 9 (CB parameter 9) 
See  U711 
0 to 65535 
Ind: 2 
FS=0 
Type: O2 
P052 = 3 
Online 
U720 
(2720) 
(Z110) 
(Z111) 
Communications board parameter 10 (CB parameter 10) 
See  U711 
0 to 65535 
Ind: 2 
FS=0 
Type: O2 
P052 = 3 
Online 
U721 
(2721) 
(Z110) 
(Z111) 
Communications board parameter 11 (CB parameter 11) 
See  U711 
0 to 65535 
Ind: 10 
FS=0 
Type: O2 
P052 = 3 
Online 
How to C#: Set Image Thumbnail in C#.NET
VB.NET How-to, VB.NET PDF, VB.NET Word following steps below, you can create an image viewer WinForm Open or create a new WinForms application, add necessary dll
add photo to pdf online; how to add an image to a pdf in reader
C# PDF remove image library: remove, delete images from PDF in C#.
Generally speaking, using well-designed APIs, C# developers can do following things. Remove Image from PDF Page Using C#. Add necessary references:
how to add an image to a pdf in acrobat; add signature image to pdf acrobat
11-160 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
U722 
(2722) 
(Z110) 
(Z111) 
Telegram failure time for CB and TB 
i001:  Telegram failure time for board location 2 
i002:  Telegram failure time for board location 3 
i003:  Fault delay time for 1
st
CB or TB 
i004:  Fault delay time for 2
nd
CB 
Settings for telegram failure time: 
No time monitoring; must be parameterized for sporadic 
(acyclic) telegrams 
1...65500  Maximum permissible time interval between 2 data 
exchanges before fault message F082 can be output 
Settings for fault delay time: 
Instantaneous activation of F082 
1...65499  Fault delay time before F082 is activated. 
65500 
F082 is never activated 
If no process data are exchanged with the supplementary board for a period 
in excess of the telegram failure time, fault message F082 is activated as a 
function of the fault delay time. 
Monitoring takes place in a 20 ms cycle. For this reason, it is only 
meaningful to set values that are multiples of 20 ms. 
t [ms]
U722.001
or
U722.002
U722.003
or
U722.004
last
receive
telegram
B3035 = 1
or
B8035 = 1
F082 and 
B3030 = 1
B3031 = 1
or
B8030 = 1
B8031 = 1
Note: 
The telegram monitoring function is active  
 from the receipt of the first error-free telegram after connection of the 
electronics power supply 
 from the receipt of the first error-free telegram after the telegram monitor 
has responded (i.e. monitoring timeout). 
0 to 65000 
[ms] 
1ms 
Ind: 4 
FS=0 
Type: O2 
P052 = 3 
Online 
U723 
(2723)  
Timeout period for technology boards 
[SW 2.1 and later]
i001:  Timeout period until F080 fault value 1 (no heartbeat) 
i002:  Timeout period until F080 fault value 6 (delay until initialization 
is complete). 
Additional permissible period after expiry of time set in index 
001 for completion of initialization. 
Example 
U732.001 = 30, U732.002 = 20: 
When the electronics supply is switched on, F080 fault value 1 is delayed by 
30 s and F080 fault value 6 by 30s + 20s = 50s. 
20 to 60 
[s] 
1s 
Ind: 2 
FS= 20 
Type: O2 
P052 = 3 
P051 = 40 
on-line 
U728 
(2728) 
(Z110) 
Source for binector/connector converter for 1
st
CB/TB 
[SW 1.9 and later] 
Binectors to be converted to connector K3020 
i001:  1
st 
binector (bit 0) 
i002:  2
nd
binector (bit 1) 
... 
i016:  16
th
binector (bit 15) 
Settings: 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 16 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
off-line 
SIEMENS AG    6RX1700-0AD76 
11-161 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
U729 
(2729) 
(Z111) 
Source for binector/connector converter for 2
nd
CB  [SW 1.9 and later] 
Binectors to be converted to connector K8020 
i001:  1st  binector (bit 0) 
i002:  2
nd
binector (bit 1) 
... 
i016:  16
th
binector (bit 15) 
Settings: 
0 = binector B0000 
1 = binector B0001 
etc. 
All binector numbers 
Ind: 16 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
off-line 
n732 
(2732) 
(Z110) 
(Z111) 
CB/TB diagnostics 
Diagnostic information about an installed communications board (CB) or 
technology board (TB). 
i001 - i032:  1. CB/TB (lower slot ID letter) 
i033 - i064:  2. CB (higher slot ID letter) 
i065, i066:  1. CB/TB (internal diagnostic data) 
i067, i068:  2. CB (internal diagnostic data) 
For detailed information, please refer to operating instructions of relevant 
CB or TB. 
Ind: 68 
Type: O2 
P052 = 3 
n733 
(2733) 
(Z110) 
(Z111) 
CB/TB receive data 
Display of control words and setpoints (process data) that are transferred to 
the basic converter from a communications board (CB) or technology board 
(TB). 
i001:  1
st
process data word from 1
st
CB/TB 
... 
i016  16
th
process data word from 1
st
CB/TB 
i017:  1
st
process data word from 2
nd
CB 
... 
i032:  16
th
process data word from 2
nd
CB 
Ind: 32 
Type: L2 
P052 = 3 
U734 
(2734) 
(Z110) 
Transmit data for first CB/TB (lower slot ID letter) 
Selection of connectors whose contents must be injected as transmit data to 
the first communications board (CB) or technology board (TB). 
0 = connector K0000 
1 = connector K0001 
etc. 
This parameter not only defines the transmit data, but also their position in 
the transmit telegram. 
i001:  Word 1 in PZD section of telegram 
i002:  Word 2 in PZD section of telegram 
... 
i016:  Word 16 in PZD section of telegram 
Status word 1 (K0032) should be linked to word 1. 
All connector 
numbers 
Ind: 16 
FS=  
i001: 32 
i002: 167 
i003: 0 
i004: 33  
i005: 0 
to 
i016: 0 
Type: L2 
P052 = 3 
Online 
n735 
(2735) 
(Z110) 
(Z111) 
Display of transmit data to CB/TB 
i001:  1
st
process data word to 1
st
CB or TB 
... 
i016  16
th
process data word to 1
st
CB or TB 
i017:  1
st
process data word to 2
nd
CB  
... 
i032:  16
th
process data word to 2
nd
CB 
Ind: 32 
Type: L2 
P052 = 3 
11-162 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
U736 
(2736) 
(Z111) 
Transmit data for second CB (higher slot letter) 
Selection of connectors whose contents must be injected as transmit data to 
a communications board (CB) with a higher slot ID letter. 
0 = connector K0000 
1 = connector K0001 
etc. 
This parameter not only defines the transmit data, but also their position in 
the transmit telegram. 
i001:  Word 1 in PZD section of telegram 
i002:  Word 2 in PZD section of telegram 
... 
i016:  Word 16 in PZD section of telegram 
Status word 1 (K0032) should be linked to word 1. 
All connector 
numbers 
Ind: 16 
FS=0 
Type: L2 
P052 = 3 
Online 
n738 
(2738) 
(Z110) 
(Z111) 
Display of PKW job from supplementary boards  
i001:  1
st
word of PKW job from 1
st
CB 
... 
i004  4
th
word of PKW job from 1
st
CB 
i005:  1
st
word of PKW job from location 2
nd
CB 
... 
i008  4
th
word of PKW job from 2
nd
CB 
i009:  1
st
word of PKW job from TB 
... 
i012:  4
th
word of PKW job from TB 
Details refer to “Function diagrams”, Section 8 Sheets Z110 and Z111 
Ind: 12 
Type: L2 
P052 = 3 
n739 
(2739) 
(Z110) 
(Z111) 
Display of PKW response to supplementary boards  
i001:  1
st
word of PKW job from 1
st
CB 
... 
i004  4
th
word of PKW job from 1
st
CB 
i005:  1
st
word of PKW job from location 2
nd
CB 
... 
i008  4
th
word of PKW job from 2
nd
CB 
i009:  1
st
word of PKW job from TB 
... 
i012:  4
th
word of PKW job from TB 
Details refer to “Function diagrams”, Section 8 Sheets Z110 and Z111 
Ind: 12 
Type: L2 
P052 = 3 
11.85  Configuring the SIMOLINK board 
U740 
(2740) 
(Z121) 
SLB Node address  
[SW 1.5 and later] 
Node address of the SIMOLINK board (SLB) on the bus. The node address 
defines the telegrams to which the relevant board has write access. The 
node address also defines whether a node is to perform the additional 
function of dispatcher. 
0 =  
Dispatcher (generates telegram circulation) 
Not 0 =  
Transceiver 
Only one node in a SIMOLINK ring may perform the function of dispatcher. 
Node address 0 may not be assigned to any node if a higher-level PLC is 
performing the dispatcher function as the SIMOLINK master. When an SLB 
is selected to operate as dispatcher, all nodes must be assigned 
consecutive addresses, starting with address 0 for the dispatcher. 
i001:  For first SLB in unit 
i002:  Reserved 
0 to 200 
Ind: 2 
FS=0 
Type: O2 
P052 = 3 
P051 =40 
Offline 
SIEMENS AG    6RX1700-0AD76 
11-163 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
U741 
(2741) 
(Z121) 
SLB Telegram failure time  
[SW 1.5 and later] 
The telegram failure time defines the period within which a valid 
synchronizing telegram (SYNC telegram) must be received. Failure of any 
SYNC telegram to arrive within the set period indicates a communications 
error. The unit activates fault message F015 (see also U753) as a function 
of U741. 
0 = No telegram failure monitoring 
i001:  For first SLB in unit 
i002:  Reserved 
0 to 6500 
[ms] 
Ind: 2 
FS=0 
Type: O2 
P052 = 3 
P051 =40 
Online 
U742 
(2742) 
(Z121) 
SLB Transmitter power  
[SW 1.5 and later] 
Setting of power of fiber optic transmitter 
1 =   0m to 15m (length of plastic fiber optic cable) 
2 = 15m to 25m (length of plastic fiber optic cable) 
3 = 25m to 40m (length of plastic fiber optic cable) 
Operation at a lower transmitter power increases the service life of the 
transmitter and receiver modules. Reducing the transmitter power also 
allows hidden fault sources on the transmission path (e.g. poor contacts on 
fiber optics) to be detected. 
i001:  For first SLB in unit 
i002:  Reserved 
1 to 3 
Ind: 2 
FS=3 
Type: O2 
P052 = 3 
P051 =40 
Online 
U744 
(2744) 
SLB Selection of active SLB board  
[SW 1.5 and later] 
Selection of the active SIMOLINK board (SLB) when two SLBs are installed 
in one unit. 
0 = Binector B0000 
1 = Binector B0001 etc. 
A binector value of 0 means "SLB in low slot is active“. 
A binector value of 1 is reserved for "SLB in high slot is active". 
All binector numbers  Ind: None 
FS=0 
Type: L2 
P052 = 3 
P051 =40 
Online 
U745 
(2745) 
(Z121) 
SLB No. of channels 
[SW 1.5 and later] 
Number of channels which dispatcher provides for each transceiver. 
Together with U746, the number of channels determines the number of 
addressable nodes. 
This parameter is relevant only for the dispatcher. 
i001:  For first SLB in unit 
i002:  Reserved 
1 to 8 
Ind: 2 
FS=3 
Type: O2 
P052 = 3 
P051 =40 
Offline 
U746 
(2746) 
(Z121) 
SLB Cycle time  
[SW 1.5 and later] 
The cycle time is the period required for all telegrams to be passed around 
the SIMOLINK ring. Together with U745, the cycle time determines the 
number of addressable nodes.  
This parameter is relevant only for the dispatcher. 
i001:  For first SLB in unit 
i002:  Reserved 
Caution:
Settings 0.20 ms to 0.99 ms are permissible only if option S00 is not
activated. Otherwise F059 with fault value 3 is output. 
If option S00 (free function blocks) is not
activated and
if an SLB cycle time 
of < 1.00 ms is set in parameter U746, connectors K7001 to K7008 are 
updated immediately every time
a telegram is received. The other 
connectors (K7009 to K7016) and binectors B7100 to B7915 are updated 
only once in each computation cycle (= 1/6 line period). In addition, the 
connectors selected in U751.001 to U751.008 are read with every
transmit 
telegram and the relevant up-to-date value transmitted. The connectors 
selected in parameters U751.009 to U751.016 are read only once in each 
computation cycle and written to the transmit buffer of the SLB.  
[A cycle time of < 1.00 ms can be set in SW 1.9 and later] 
0.20 to 6.50 
[ms] 
0.01 
Ind:2 
FS=1.20 
Type: O2 
P052 = 3 
P051 =40 
Offline 
11-164 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
n748 
(2748) 
(Z121) 
SLB Diagnosis  
[SW 1.5 and later] 
Visualization parameter which displays diagnostic information for an 
installed SIMOLINK board (SLB) 
i001:  Number of error-free synchronizing telegrams 
i002:  Number of CRC errors 
i003:  Number of timeout errors 
i004:  Last accessible bus address 
i005:  Address of node sending the special telegram "Timeout“ 
i006:  Implemented bus cycle time 
i007:  Number of new configurations 
i008:  Reserved 
... 
i016:  Reserved 
Ind: 16 
Type: O2 
P052 = 3 
U749 
(2749) 
(Z122) 
SLB Read address  
[SW 1.5 and later] 
Definition of node addresses and channels from which the SLB must read 
data (a total of 8 channels can be read according to the index entries). The 
digits before the decimal point in the input value define the node address 
and those after the point the channel number (see also Section 7 "Starting 
up SIMOLINK boards" and Section 8, Sheet Z122). 
Example: 
2.0 = address 2 channel 0 
0.0 to 200.7 
0.1 
Ind: 8 
FS=0.0 
Type: O2 
P052 = 3 
P051 =40 
Offline 
n750 
(2750) 
(Z122) 
SLB Receive data  
[SW 1.5 and later] 
Visualization parameter for data received via the SIMOLINK board (see also 
Section 7 "Starting up SIMOLINK boards" and Section 8 , Sheet Z122) 
i001:  Word 1 in PZD section of telegram 
... 
i016:  Word 16 in PZD section of telegram 
Ind: 16 
Type: L2 
P052 = 3 
U751 
(2751) 
(Z122) 
SLB Transmit data selection  
[SW 1.5 and later] 
Selection of connectors whose contents must be transferred as transmit 
data by the SLB (see also Section 7 "Starting up SIMOLINK boards" and 
Section 8 , Sheet Z122). 
0 = connector K0000 
1 = connector K0001 
etc. 
In addition to the transmit data itself, its place in the transmit telegram is 
also defined. 
i001:  Channel0, low word 
i002:  Channel0, high word 
... 
i015:  Channel7, low word 
i016:  Channel7, high word 
All connector 
numbers 
Ind: 16 
FS=0 
Type: L2 
P052 = 3 
P051 =40 
Offline 
n752 
(2752)  
(Z122) 
SLB Display of transmit data  
[SW 1.5 and later] 
Process data transmitted by SLB via SIMOLINK in hexadecimal notation 
(see also Section 7 "Starting up SIMOLINK boards" and Section 8 , Sheet 
Z122) 
Ind: 16 
Type: L2 
P052 = 3 
U753 
(2753) 
(Z121) 
SLB Fault delay  
[SW 1.5 and later] 
Delay in activation of fault message F015 (see also U741) 
0 = fault message is activated immediately the telegram failure monitor 
responds 
0.0 to 100.0 
[s] 
0.1 
Ind: None 
FS=0.0 
Type: O2 
P052 = 3 
P051 =40 
Offline 