pdf renderer c# : How to add a jpeg to a pdf control Library system web page asp.net winforms console OPI_simoreg_DC_0707_en63-part1919

SIEMENS AG    6RX1700-0AD76 
11-165 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
11.86  Configuring the EB1 expansion board 
U755 
(2755) 
(Z112) 
(Z115) 
Signal type of analog inputs on EB1  
[SW 1.5 and later] 
0 =  Voltage input 0 to ± 10 V 
1 =  Current input 0 to ± 20 mA 
i001:  AI1 of the first EB1  
i002: AI1 of the second EB1  
0 to 1 
Ind: 2 
WE=0 
Typ: O2 
P052 = 3 
P051 = 40 
on-line 
U756 
(2756) 
(Z112) 
(Z115) 
Normalization of analog inputs on EB1  
[SW 1.5 and later] 
This parameter specifies the percentage value which is generated for an 
input voltage of 10V (or an input current of 20mA) at the analog input. 
The following general rule applies: 
With a voltage input: 
U
V
Y
X
756
10
[%] =
X .. input voltage in volts 
Y .. % value which is generated for input 
voltage X 
With a current input: 
U
mA
Y
X
756
20
[%] =
X .. input current in mA 
Y .. % value which is generated for input 
current X 
i001:  AI1 of the first EB1 
i002:  AI2 of the first EB1 
i003:  AI3 of the first EB1 
i004:  AI1 of the second EB1 
i005:  AI2 of the second EB1 
i006:  AI3 of the second EB1 
-1000.0 to 1000.0 
[%] 
0.1% 
Ind: 6 
WE=100,0 
Typ: I2 
P052 = 3 
P051 = 40 
on-line 
U757 
(2757) 
(Z112) 
(Z115) 
Offset for analog inputs on EB1 
[SW 1.5 and later] 
i001:  AI1 of the first EB1 
i002:  AI2 of the first EB1 
i003:  AI3 of the first EB1 
i004:  AI1 of the second EB1 
i005:  AI2 of the second EB1 
i006:  AI3 of the second EB1 
-100.00 to 100.00 
[%] 
0.01% 
Ind: 6 
WE=0,00 
Typ: I2 
P052 = 3 
P051 = 40 
on-line 
U758 
(2758) 
(Z112) 
(Z115) 
Mode of signal injection at analog inputs on EB1  [SW 1.5 and later] 
0 =  Injection of signal with sign 
1 =  Injection of absolute value of signal 
2 =  Injection of signal with sign, inverted 
3 =  Injection of absolute value of signal, inverted 
i001:  AI1 of the first EB1 
i002:  AI2 of the first EB1 
i003:  AI3 of the first EB1 
i004:  AI1 of the second EB1 
i005:  AI2 of the second EB1 
i006:  AI3 of the second EB1 
0 to 3 
Ind: 6 
WE=0 
Typ: O2 
P052 = 3 
P051 = 40 
off-line 
U759 
(2759) 
(Z112) 
(Z115) 
Source for selection of sign reversal at 
[SW 1.5 and later] 
analog inputs on EB1 
Selection of binector to control sign reversal at the analog input ("1" state 
= reverse sign) 
0 = binector B0000 
1 = binector B0001 
etc. 
i001:  AI1 of the first EB1 
i002:  AI2 of the first EB1 
i003:  AI3 of the first EB1 
i004:  AI1 of the second EB1 
i005:  AI2 of the second EB1 
i006:  AI3 of the second EB1 
All binector numbers 
Ind: 6 
WE=0 
Typ: L2 
P052 = 3 
P051 = 40 
off-line 
How to add a jpeg to a pdf - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
add image to pdf preview; adding an image to a pdf file
How to add a jpeg to a pdf - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
add jpg to pdf document; add photo to pdf preview
11-166 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
U760 
(2760) 
(Z112) 
(Z115) 
Filtering time for analog inputs on EB1 
[SW 1.5 and later] 
Note: Hardware filtering of approximately 0.2 ms is applied as standard 
i001:  AI1 of the first EB1 
i002:  AI2 of the first EB1 
i003:  AI3 of the first EB1 
i004:  AI1 of the second EB1 
i005:  AI2 of the second EB1 
i006:  AI3 of the second EB1 
0 to 10000 
[ms] 
1ms 
Ind: 6 
WE=0 
Typ: O2 
P052 = 3 
P051 = 40 
on-line 
U761 
(2761) 
(Z112) 
(Z115) 
Source for enabling of analog inputs on EB1 
[SW 1.5 and later] 
Selection of binector to control enabling of the analog input ("1" state = 
enabled) 
0 = binector B0000 
1 = binector B0001 
etc. 
i001:  AI1 of the first EB1 
i002:  AI2 of the first EB1 
i003:  AI3 of the first EB1 
i004:  AI1 of the second EB1 
i005:  AI2 of the second EB1 
i006:  AI3 of the second EB1 
All binector numbers 
Ind: 6 
WE=1 
Typ: L2 
P052 = 3 
P051 = 40 
off-line 
n762 
(2762) 
(Z112) 
(Z115) 
Display of analog inputs on EB1 
[SW 1.5 and later] 
i001:  AI1 of the first EB1 
i002:  AI2 of the first EB1 
i003:  AI3 of the first EB1 
i004:  AI1 of the second EB1 
i005:  AI2 of the second EB1 
i006:  AI3 of the second EB1 
-200.00 to 199.99 
[%] 
0.01% 
Ind: 6 
Typ: I2 
P052 = 3 
U763 
(2763) 
(Z113) 
(Z116) 
Source for output value at analog outputs on EB1  [SW 1.5 and later] 
Selection of connector whose value must be output at the analog output 
0 = connector K0000 
1 = connector K0001 
etc. 
i001:  AO1 of the first EB1 
i002:  AO2 of the first EB1 
i003:  AO1 of the second EB1 
i004:  AO2 of the second EB1 
All connector 
numbers 
Ind: 4 
WE=0 
Typ: L2 
P052 = 3 
P051 = 40 
on-line 
U764 
(2764) 
(Z113) 
(Z116) 
Mode of signal injection at analog outputs on EB1  [SW 1.5 and later] 
0 =  Injection of signal with sign 
1 =  Injection of absolute value of signal 
2 =  Injection of signal with sign, inverted 
3 =  Injection of absolute value of signal, inverted 
i001:  AO1 of the first EB1 
i002:  AO2 of the first EB1 
i003:  AO1 of the second EB1 
i004:  AO2 of the second EB1 
0 to 3 
Ind: 4 
WE=0 
Typ: O2 
P052 = 3 
P051 = 40 
on-line 
U765 
(2765) 
(Z113) 
(Z116) 
Filtering time for analog outputs on EB1 
[SW 1.5 and later] 
i001:  AO1 of the first EB1 
i002:  AO2 of the first EB1 
i003:  AO1 of the second EB1 
i004:  AO2 of the second EB1 
0 to 10000 
[ms] 
1ms 
Ind: 4 
WE=0 
Typ: O2 
P052 = 3 
P051 = 40 
on-line 
VB.NET PDF Convert to Jpeg SDK: Convert PDF to JPEG images in vb.
Convert PDF to JPEG Using VB.NET. Add necessary references: RasterEdge.Imaging.Basic. dll. RasterEdge.Imaging.Basic.Codec.dll. RasterEdge.Imaging.Drawing.dll.
how to add an image to a pdf file in acrobat; add photo to pdf in preview
C# PDF Convert to Jpeg SDK: Convert PDF to JPEG images in C#.net
Convert PDF to JPEG Using C#.NET. Add necessary references: RasterEdge.Imaging.Basic. dll. RasterEdge.Imaging.Basic.Codec.dll. RasterEdge.Imaging.Drawing.dll.
adding image to pdf file; adding a jpeg to a pdf
SIEMENS AG    6RX1700-0AD76 
11-167 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
U766 
(2766) 
(Z113) 
(Z116) 
Normalization of analog outputs on EB1 
[SW 1.5 and later] 
100%
766
U
y[V] x
= ∗
x = normalization input (corresponds to filtering output) 
y = normalization output (corresponds to output voltage at analog output 
with an offset of 0) 
i001:  AO1 of the first EB1 
i002:  AO2 of the first EB1 
i003:  AO1 of the second EB1 
i004:  AO2 of the second EB1 
-200.00 to 199.99 
[V] 
0.01V 
Ind: 4 
WE=10,00 
Typ: I2 
P052 = 3 
P051 = 40 
on-line 
U767 
(2767) 
(Z113) 
(Z116) 
Offset for analog outputs on EB1 
[SW 1.5 and later] 
i001:  AO1 of the first EB1 
i002:  AO2 of the first EB1 
i003:  AO1 of the second EB1 
i004:  AO2 of the second EB1 
-10.00 to 10.00 
[V] 
0.01V 
Ind: 4 
WE=0,00 
Typ: I2 
P052 = 3 
P051 = 40 
on-line 
n768 
(2768)  
(Z113) 
(Z116) 
Display of analog outputs on EB1 
[SW 1.5 and later] 
i001:  AO1 of the first EB1 
i002:  AO2 of the first EB1 
i003:  AO1 of the second EB1 
i004:  AO2 of the second EB1 
-200.0 to 199.99 
[%] 
0.01% 
Ind: 4 
Typ: I2 
P052 = 3 
U769 
(2769) 
(Z114)  
(Z117) 
Source for output values at binary outputs on EB1  [SW 1.5 and later] 
Selection of binectors to be applied to binary outputs at terminals 43 - 46. 
0 = Binector B0000 
1 = Binector B0001 
etc. 
i001:  BO1 of the first EB1 
i002:  BO2 of the first EB1 
i003:  BO3 of the first EB1 
i004:  BO4 of the first EB1 
i005:  BO1 of the second EB1 
i006:  BO2 of the second EB1 
i007:  BO3 of the second EB1 
i008:  BO4 of the second EB1 
All binector numbers 
Ind: 8 
WE=0 
Typ: L2 
P052 = 3 
P051 = 40 
off-line 
n770 
(2770) 
(Z114)  
(Z117) 
Display of status of binary inputs and outputs on EB1 
[SW 1.5 and later] 
Representation on operator panel (PMU): 
3
2
1
0
4
5
6
Segment ON: 
Corresponding terminal is activated 
(HIGH level is applied) 
Segment OFF: 
Corresponding terminal is not activated 
(LOW level is applied) 
Segment or bit 
 ....... Terminal 40 
 ....... Terminal 41 
 ....... Terminal 42 
 ....... Terminal 43 
 ....... Terminal 44 
 ....... Terminal 45 
 ....... Terminal 46 
i001:  Terminal states of first EB1 
i002:   Terminal states of second EB1 
Ind: 2 
Typ: V2 
P052 = 3 
VB.NET PDF Password Library: add, remove, edit PDF file password
VB: Add Password to PDF with Permission Settings Applied. This VB.NET example shows how to add PDF file password with access permission setting.
add picture to pdf file; how to add a picture to a pdf file
C# PDF Password Library: add, remove, edit PDF file password in C#
C# Sample Code: Add Password to PDF with Permission Settings Applied in C#.NET. This example shows how to add PDF file password with access permission setting.
add image to pdf java; add png to pdf preview
11-168 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
11.87  Configuring the EB2 expansion board 
n773 
(2773) 
(Z118)  
(Z119) 
Display of status of binary inputs and outputs on EB2 
[SW 1.5 and later] 
Representation on operator panel (PMU): 
3
2
1
0
4
5
Segment ON: 
Corresponding terminal is activated 
(HIGH level is applied) 
Segment OFF: 
Corresponding terminal is not activated 
(LOW level is applied) 
Segment or bit 
0 ........ Terminal 53 
1 ........ Terminal 54 
2 ........ Terminal 39 
3 ........ Terminal 41 
4 ........ Terminal 43 
5 ........ Terminal 45 
i001:  Terminal states of first EB2 
i002:   Terminal states of second EB2 
Ind: 2 
Type: V2 
P052 = 3 
U774 
(2774) 
(Z118)  
(Z119) 
Source for output values at binary outputs on EB2  [SW 1.5 and later] 
Selection of binectors to be applied to binary outputs at terminals 39 - 46. 
0 = binector B0000 
1 = binector B0001 
etc. 
i001:  BO1 of the first EB2 
i002:  BO2 of the first EB2 
i003:  BO3 of the first EB2 
i004:  BO4 of the first EB2 
i005:  BO1 of the second EB2 
i006:  BO2 of the second EB2 
i007:  BO3 of the second EB2 
i008:  BO4 of the second EB2 
All binector numbers 
Ind: 8 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Online 
U775 
(2775) 
(Z118)  
(Z119) 
Signal type of analog input on EB2 
[SW 1.5 and later] 
0 =  voltage input 0 to ± 10 V 
1 =  current input 0 to ± 20 mA 
i001:  AI1 of the first EB2 
i002:  AI1 of the second EB2 
0 to 1 
Ind: 2 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
U776 
(2776) 
(Z118)  
(Z119) 
Normalization of analog input on EB2  
[SW 1.5 and later] 
This parameter specifies the percentage value which is generated for an 
input voltage of 10V (or an input current of 20mA) at the analog input. 
The following general rule applies: 
With a voltage input: 
U
V
Y
X
776
10
[%] =
X .. input voltage in volts 
Y .. % value which is generated for input 
voltage X 
With a current input: 
U
mA
Y
X
776
20
[%] =
X .. input current in mA 
Y .. % value which is generated for input 
current X 
i001:  AI of the first EB2 
i002:  AI of the second EB2 
-1000.0 to 1000.0 
[%] 
0.1% 
Ind: 2 
FS=100.0 
Type: I2 
P052 = 3 
P051 = 40 
Online 
C# PDF Sticky Note Library: add, delete, update PDF note in C#.net
C#.NET PDF SDK - Add Sticky Note to PDF Page in C#.NET. Able to add notes to PDF using C# source code in Visual Studio .NET framework.
add image to pdf form; add image pdf acrobat
C# Create PDF from images Library to convert Jpeg, png images to
Load 3 image files (BMP, JPEG and PNG Bitmap(Program.RootPath + "\\" 1.jpg")); images.Add(new Bitmap RootPath + "\\" 1.png")); / Build a PDF document with
adding jpg to pdf; add photo pdf
SIEMENS AG    6RX1700-0AD76 
11-169 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
U777 
(2777)  
(Z118)  
(Z119) 
Offset for analog input on EB2 
[SW 1.5 and later] 
i001:  AI of the first EB2 
i002:  AI of the second EB2 
-100.00 to 100.00 
[%] 
0.01% 
Ind: 2 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
U778 
(2778) 
(Z118)  
(Z119) 
Mode of signal injection at analog input on EB2 
[SW 1.5 and later] 
0 =  Injection of signal with sign 
1 =  Injection of absolute value of signal 
2 =  Injection of signal with sign, inverted 
3 =  Injection of absolute value of signal, inverted 
i001:  AI of the first EB2 
i002:  AI of the second EB2 
0 to 3 
Ind: 2 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
U779 
(2779) 
(Z118)  
(Z119) 
Source for selection of sign reversal at 
[SW 1.5 and later] 
analog input on EB2 
Selection of binector to control sign reversal at the analog input ("1" state 
= reverse sign) 
0 = binector B0000 
1 = binector B0001 
etc. 
i001:  AI of the first EB2 
i002:  AI of the second EB2 
All binector numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
U780 
(2780)  
(Z118)  
(Z119) 
Filtering time for analog input on EB2 
[SW 1.5 and later] 
Note: Hardware filtering of approximately 0.2 ms is applied as standard 
i001:  AI of the first EB2 
i002:  AI of the second EB2 
0 to 10000 
[ms] 
1ms 
Ind: 2 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
U781 
(2781) 
(Z118)  
(Z119) 
Source for enabling of analog inputs on EB2 
[SW 1.5 and later] 
Selection of binector to control enabling of the analog input ("1" state = 
enabled) 
0 = binector B0000 
1 = binector B0001 
etc. 
i001:  AI of the first EB2 
i002:  AI of the second EB2 
All binector numbers 
Ind: 2 
FS=1 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
n782 
(2782)  
(Z118)  
(Z119) 
Display of analog input on EB2 
[SW 1.5 and later] 
i001:  AI of the first EB2 
i002:  AI of the second EB2 
-200.0 to 199.99 
[%] 
0.01% 
Ind: 2 
Type: I2 
P052 = 3 
U783 
(2783) 
(Z118)  
(Z119) 
Source for output value at analog output on EB2 
[SW 1.5 and later] 
Selection of connector whose value must be output at the analog output 
0 = connector K0000 
1 = connector K0001 
etc. 
i001:  AO of the first EB2 
i002:  AO of the second EB2 
All connector 
numbers 
Ind: 2 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Online 
U784 
(2784) 
(Z118)  
(Z119) 
Mode of signal injection at analog output on EB2  [SW 1.5 and later] 
0 =  Injection of signal with sign 
1 =  Injection of absolute value of signal 
2 =  Injection of signal with sign, inverted 
3 =  Injection of absolute value of signal, inverted 
i001:  AO of the first EB2 
i002:  AO of the second EB2 
0 to 3 
Ind: 2 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
C# PDF File & Page Process Library SDK for C#.net, ASP.NET, MVC
C#: Convert PDF to HTML; C#: Convert PDF to Jpeg; C# File: Compress PDF; C# C# Read: PDF Image Extract; C# Write: Insert text into PDF; C# Write: Add Image to
add jpeg to pdf; add an image to a pdf acrobat
C# PDF Digital Signature Library: add, remove, update PDF digital
C#: Convert PDF to HTML; C#: Convert PDF to Jpeg; C# File: Compress PDF; C# C# Read: PDF Image Extract; C# Write: Insert text into PDF; C# Write: Add Image to
add picture to pdf document; acrobat insert image into pdf
11-170 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
U785 
(2785)  
(Z118)  
(Z119) 
Filtering time for analog outputs on EB2 
[SW 1.5 and later] 
i001:  AO of the first EB2 
i002:  AO of the second EB2 
0 to 10000 
[ms] 
1ms 
Ind: 2 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
U786 
(2786) 
(Z118)  
(Z119) 
Normalization of analog outputs on EB2 
[SW 1.5 and later] 
100%
786
U
y[V] x
= ∗
x = normalization input (corresponds to filtering output) 
y = normalization output (corresponds to output voltage at analog output 
with an offset of 0) 
i001:  AO of the first EB2 
i002:  AO of the second EB2 
-200.00 to 199.99 
[V] 
0.01V 
Ind: 2 
FS=10.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
U787 
(2787)  
(Z118)  
(Z119) 
Offset for analog output on EB2 
[SW 1.5 and later] 
i001:  AO of the first EB2 
i002:  AO of the second EB2 
-10.00 to 10.00 
[V] 
0.01V 
Ind: 2 
FS=0.00 
Type: I2 
P052 = 3 
P051 = 40 
Online 
n788 
(2788)  
(Z118)  
(Z119) 
Display of analog outputs on EB2 
[SW 1.5 and later] 
i001:  AO of the first EB2 
i002:  AO of the second EB2 
-200.00 to 199.99 
[%] 
0.01% 
Ind: 2 
Type: I2 
P052 = 3 
11.88  Configuring the SBP pulse encoder board 
U790 
(2790) 
(Z120) 
Configuration of input level of A/B and CRTL tracks and Zero pulse 
[SW 1.5 and later]
i001:  A/B and CRTL track 
i002:  Zero pulse  
0: 
HTL unipolar 
1: 
TTL unipolar 
2: 
HTL differential input 
3: 
TTL/RS422 differential input 
0 to 3 
Ind: 2 
FS=1 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
U791 
(2791) 
(Z120) 
Configuration of encoder supply voltage  
[SW 1.5 and later] 
The supply is subject to a current limit of 250mA 
Caution: Setting the parameter incorrectly can damage the encoder (i.e. 15 
V voltage for an encoder which requires a 5 V supply). 
0: 
5V   voltage supply 
1: 
15V voltage supply 
0 to 1 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
U792 
(2792) 
(Z120) 
Number of pulses per revolution  
[SW 1.5 and later] 
Number of lines on one track around circumference of disk 
100 to 20000 
Ind: None 
FS=1024 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
U793 
(2793) 
(Z120) 
Encoder type  
[SW 1.5 and later] 
0: 
Encoder with A/B track (two tracks displaced by 90 degrees) 
1: 
Encoder with separate forward and reverse tracks 
0 to 1 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
U794 
(2794)  
(Z120) 
Reference speed  
[SW 1.5 and later] 
When actual speed = reference speed a value of 100% is output in the 
appropriate diagnostic parameter (n795) and connector 
50.0 to 6500.0 
[rev/min] 
0.1 
Ind: None 
FS=500.0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
n795 
(2795)  
(Z120) 
Display of actual speed in % of reference speed  
[SW 1.5 and later] 
-200.00 to 199.99 
[%] 
Ind: None 
Type: I2 
P052 = 3 
U796 
(2796) 
S00 
(Z120) 
Resetting the position counter 
[SW 2.0 and later] 
Setting the type of resetting for position acquisition 
0 = free-running (no reset) 
1 = see function diagram Z120 
2 = see function diagram Z120 
0 to 2 
Ind: none 
FS=0 
Type: O2 
P052 = 2 
P051 = 40 
online 
SIEMENS AG    6RX1700-0AD76 
11-171 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
11.89  Configuration of paralleling interface 
Notes about parameterization of the paralleling interface see Chapter 6.3.2 
U800 
(2800) 
(G195) 
Control word for paralleling interface 
0: 
Paralleling interface not active 
1: 
Paralleling interface active  
The gating pulses are generated by this
SIMOREG converter 
2: 
Paralleling interface active  
The gating pulses of the master are used 
Must also be set if a SIMOREG CCP is used 
0 to 2 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
U803 
(2803) 
(G195) 
Operating mode for the parallel connection  
[SW 1.7 and later] 
Standard mode 
All parallel-connected SIMOREG devices must be in continuous 
operation. Failure (fault message, fuse blown) of one
of the 
parallel-connected SIMOREG devices causes immediate pulse 
disabling for all
SIMOREG devices. 
"N+1 mode" (redundancy mode) 
On failure (fault message, fuse blown) of one of the parallel-
connected SIMOREG devices, operation is maintained with the 
remaining SIMOREG devices. 
0 to 1 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
off-line 
U804 
(2804) 
(G195) 
Transmit data on paralleling interface 
Selection of connectors whose contents must be injected as transmit data 
(master to slaves or slave to master) for the paralleling interface. 
0 = connector K0000 
1 = connector K0001 
etc. 
This parameter not only defines the transmit data, but also their position in 
the transmit telegram. 
i001:  Word 1 of telegram 
... 
i005:  Word 5 of telegram 
i006:  word 1 of the telegram, if "standby master"   [SW 1.7 and later] 
... 
i010:  word 5 of the telegram, if "standby master"   [SW 1.7 and later] 
Indices .06 to .10 of U804 are activated on the master and the standby 
master when the “master” function is transferred to the standby master 
All connector 
numbers 
Ind: 10 
FS=0 
Type: L2 
P052 = 3 
P051 = 40 
Online 
U805 
(2805)  
(G195) 
Control word for bus terminator of paralleling interface 
0: 
No bus terminator 
1: 
Bus terminator active 
0 to 1 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Online 
U806 
(2806) 
(G195) 
Address for the parallel connection of SIMOREG devices 
i001:  Address of the masters or of the slaves 
i002:  Address of the "standby master" or slaves 
[SW 1.7 and later] 
2: 
Slave device with address 2 
3: 
Slave device with address 3 
4: 
Slave device with address 4 
5: 
Slave device with address 5 
6: 
Slave device with address 6 
12: 
Master device for 1 slave device with address 2 
13: 
Master device for 2 slave devices with addresses 2 and 3 
14: 
Master device for 3 slave devices with addresses 2, 3 and 4 
15: 
Master device for 4 slave devices with addresses 2, 3, 4 and 5 
16: 
Master device for 5 slave devices with addresses 2, 3, 4, 5 and 
In "Standard" mode (U803 = 0), i001 and i002 must be set to the same 
value. 
In "N+1 mode" (U803 = 1), a SIMOREG device has the "master" function, a 
SIMOREG device has the "standby Master" function and all other devices 
are slaves. In the slaves, i001 and i002 must be set to the same value. 
On the master,  a value of 12 to 16 must be set in i001, in i002 a value of 2 
to 6.  
In the "standby master", a value of 2 to 6 must be set in i001, in i002 a value 
of 12 to 16. 
see column on left 
Ind: 2 
FS=2 
Type: O2 
P052 = 3 
P051 = 40 
off-line 
11-172 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
U807 
(2807)  
(G195) 
Telegram failure time on paralleling interface 
No time monitoring 
0.001...65.000  Permissible time interval between two data exchange 
operations before a fault message is output. 
Fault message F014 is displayed if no data are exchanged with the parallel-
connected converter within this delay period. 
The monitoring function is implemented within a 20 ms cycle. For this 
reason, only setting values which constitute a multiple of 20 ms are 
meaningful. 
Note: 
The telegram monitoring function is active  
 from the receipt of the first error-free telegram after connection of the 
electronics power supply 
 from the receipt of the first error-free telegram after the telegram monitor 
has responded (i.e. monitoring timeout). 
0.000 to 65.000 
[s] 
0.001s 
Ind: None 
FS=0.100 
Type: O2 
P052 = 3 
P051 = 40 
Online 
U808 
(2808) 
(G195) 
Source for triggering of message F014 
Selection of binector which must trigger message F014 when it switches to 
log. "1" 
6040 = binector B6040 
6041 = binector B6041 
6040, 6041 
Ind: None 
FS=6040 
Type: L2 
P052 = 3 
P051 = 40 
Offline 
n809 
(2809)  
(G195) 
Diagnostic information for paralleling interface 
i001 to i009 = Free-running counter, overflow at 65535 
i001:  Number of error-free telegrams 
i002:  Number of errored telegrams 
i003:  Transmit Error Counter 
i004:  Receive Error Counter 
i005:  Phase Error Counter 
i006:  Baud rate Error Counter 
i007:  Bad BCC Counter 
i008:  Timeout Counter 
i009:   Number of telegrams with unknown identifier 
0 to 65535 
Ind: 9 
Type: O2 
P052  0 
SIEMENS AG    6RX1700-0AD76 
11-173 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
n810 
(2810)  
(G195) 
Diagnostic information for the paralleling interface 
3
2
1
0
4
5
6
7
8
9
10
11
12
13
14
15
Unit with active “master” function
Segment 
 .......  
 .......  
 ....... ON: Slave with address 2 responding 
 ....... ON: Slave with address 3 responding 
 ....... ON: Slave with address 4 responding 
 ....... ON: Slave with address 5 responding 
 ....... ON: Slave with address 6 responding 
 .......  
 ....... OFF 
 ....... OFF 
10  .......  
11  .......  
12  .......  
13  .......  
14  .......  
15  ....... ON: Master function active 
Unit with “slave” function
Segment 
 .......  
 .......  
 ....... ON: Data for slave with address 2 are ok 
 ....... ON: Data for slave with address 3 are ok 
 ....... ON: Data for slave with address 4 are ok 
 ....... ON: Data for slave with address 5 are ok 
 ....... ON: Data for slave with address 6 are ok 
 .......  
 ....... ON: Slave function active 
 ....... ON: Firing pulses of master are used 
10  .......  
11  .......  
12  .......  
13  .......  
14  .......  
15  ....... OFF 
Ind: None 
Type: V2 
P052 = 3 
11-174 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
n812 
(2812)  
(G195) 
Receive data on paralleling interface 
When U806=1 (master) is selected
i001  Receive data from slave with address 2, word 1 
... 
i005  Receive data from slave with address 2, word 5 
i006  Receive data from slave with address 3, word 1 
... 
i010  Receive data from slave with address 3, word 5 
i011  Receive data from slave with address 4, word 1 
... 
i015  Receive data from slave with address 4, word 5 
i016  Receive data from slave with address 5, word 1 
... 
i020  Receive data from slave with address 5, word 5 
i021  Receive data from slave with address 6, word 1 
... 
i025  Receive data from slave with address 6, word 5 
When U806=2 to 6 (slave) is selected
i001  Receive data from master, word 1 
... 
i005  Receive data from master, word 5 
i006  Not in use 
... 
i025  Not in use 
0000 to FFFFH 
Ind: 25 
Type: L2 
P052  0 
n813 
(2813)  
(G195) 
Transmit data on paralleling interface 
When U806=1 (master) is selected
i001  Transmit data to slaves, word 1 
... 
i005  Transmit data to slaves, word 5 
When U806=2 to 6 (slave) is selected:
i001  Transmit data to master, word 1 
... 
i005  Transmit data to master, word 5 
0 to FFFFH 
Ind: 5 
Type: L2 
P052  0 
11.90  Parameters for SIMOREG DC-MASTER Control Module (SIMOREG CM) 
U819 
to 
U835 
(2819 to 
2835) 
These parameters have no meaning for SIMOREG DC-MASTER! 
The SIMOREG CM (Control Module, control section for converting or 
upgrading systems) requires these parameters.  
(for details see operating instructions for SIMOREG CM, order No. 
6RX1700-0BD76) 
11.91  Rated DC current of external field device 
U838 
(2838) 
Rated DC current of external field device 
[SW 1.9 and later] 
0.00  Parameter not yet set 
Note: 
This parameter is operative only if P082 >= 21. 
0.00 to 600.00 
[A] 
0.01A 
Ind: None 
FS=0.00 
Type: O2 
P052 = 3 
P051 = 40 
on-line 
Documents you may be interested