11.92  Simulation operation 
Simulation operation 
Simulation operation is used to test the power section (measurement of the firing pulses with a current probe). Firing pulses are output to 
a single thyristor (pulse distance = 20 ms, pulse duration = approx. 1 ms, firing pulse chopping as in normal operation). The thyristor is 
selected with parameter U840. The line voltage does not have to be applied during simulation operation. 
Simulation operation is activated by setting a  value > 0 in Parameter U840. 
Simulation operation is then actually started when the SIMOREG DC-MASTER is in an operating state  o7. 
As soon as the SIMOREG DC-MASTER is in simulation operation, it goes into operating state o8.1 (simulation operation). 
Simulation operation is exited by resetting parameter U840 to zero. 
U840 
(2840) 
Control parameters for simulation operation 
[SW 1.7 and later] 
No simulation operation 
11 
Firing cable 11 
... 
16  
Firing cable 16 
21  
Firing cable 21 
... 
26 
Firing cable 26 
0, 
11 to 16, 
21 to 26 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
off-line 
11.93  Parameter for DriveMonitor 
U845 
to 
n909 
(2845 to 
2909) 
These parameters are used by DriveMonitor 
11.94  Slot deactivation 
U910 
(2910) 
(G101) 
Slot deactivation parameter 
[SW 1.9 and later] 
Parameter for deactivating supplementary boards, e.g. during start-up or 
troubleshooting (for details of slot identification codes, see diagram under 
parameter r063) 
i001:  - 
i002:  Slot D 
i003:  Slot E 
i004:  Slot F 
i005:  Slot G 
Board in slot active 
Board in slot not active 
The deactivated slot is ignored during the search for installed 
supplementary boards when the supply voltage is next switched on.  
Likewise, activation of a slot does not take effect until the supply voltage 
has been switched off and on again. 
Note:  
Slot E can simply be deactivated to conceal a technology board (large 
format).  
If a communications board is installed in addition to the technology board, 
and the technology board is concealed, then the communications board will 
not be processed either. 
0 and 1 
Ind: 5 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
off-line 
11.95  Parameter for DriveMonitor 
U911 
to 
n949 
(2911 to 
2949) 
These parameters are used by DriveMonitor 
Adding an image to a pdf in preview - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
add a picture to a pdf document; add a jpeg to a pdf
Adding an image to a pdf in preview - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
how to add image to pdf form; add a picture to a pdf file
11-176 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
11.96  Technology software in the basic converter, Option S00: Sampling times 
Only active with optional technology software S00 
Sampling times 
For each function block of the technology software S00, it is necessary to define in which "time slice" (i.e. with which sampling time) it is 
processed.  
5 time slices are available: 
Time slice 
Sampling time                                            .
1 * T0 (firing-pulse-synchronous time slice) 
2 * T0 (firing-pulse-synchronous time slice) 
4 * T0 (firing-pulse-synchronous time slice) 
10 
20 ms (not
firing-pulse-synchronous ) 
20 
Block is not calculated 
T0 = Mean distance between 2 firing pulses 
T0 = 3.33 ms at 50 Hz line frequency 
T0 = 2.78 ms at 60 Hz line frequency 
Selection of time slices for function blocks FB1 to  FB100 
Index 
Function 
block 
Time  
slice 
(FS) 
Index 
Function
block 
Time  
slice 
(FS) 
U950 
(2950) 
S00 
i001 
i002 
i003 
i004 
i005 
i006 
i007 
i008 
i009 
i010 
i011 
i012 
i013 
i014 
i015 
i016 
i017 
i018 
i019 
i020 
i021 
i022 
i023 
i024 
i025 
i026 
i027 
i028 
i029 
i030 
i031 
i032 
i033 
i034 
i035 
i036 
i037 
i038 
i039 
i040 
i041 
i042 
i043 
i044 
i045 
i046 
i047 
i048 
i049 
i050 
FB1 
FB2 
FB3 
FB4 
FB5 
FB6 
FB7 
FB8 
FB9 
FB10 
FB11 
FB12 
FB13 
FB14 
FB15 
FB16 
FB17 
FB18 
FB19 
FB20 
FB21 
FB22 
FB23 
FB24 
FB25 
FB26 
FB27 
FB28 
FB29 
FB30 
FB31 
FB32 
FB33 
FB34 
FB35 
FB36 
FB37 
FB38 
FB39 
FB40 
FB41 
FB42 
FB43 
FB44 
FB45 
FB46 
FB47 
FB48 
FB49 
FB50 
20 
20 
10 
10 
10 
10 
20 
20 
20 
i051 
i052 
i053 
i054 
i055 
i056 
i057 
i058 
i059 
i060 
i061 
i062 
i063 
i064 
i065 
i066 
i067 
i068 
i069 
i070 
i071 
i072 
i073 
i074 
i075 
i076 
i077 
i078 
i079 
i080 
i081 
i082 
i083 
i084 
i085 
i086 
i087 
i088 
i089 
i090 
i091 
i092 
i093 
i094 
i095 
i096 
i097 
i098 
i099 
i100 
FB51 
FB52 
FB53 
FB54 
FB55 
FB56 
FB57 
FB58 
FB59 
FB60 
FB61 
FB62 
FB63 
FB64 
FB65 
FB66 
FB67 
FB68 
FB69 
FB70 
FB71 
FB72 
FB73 
FB74 
FB75 
FB76 
FB77 
FB78 
FB79 
FB80 
FB81 
FB82 
FB83 
FB84 
FB85 
FB86 
FB87 
FB88 
FB89 
FB90 
FB91 
FB92 
FB93 
FB94 
FB95 
FB96 
FB97 
FB98 
FB99 
FB100 
10 
10 
20 
20 
20 
20 
20 
1, 2, 4, 10, 20 
Ind: 100 
FS=  
see column 
on left 
Type: O2 
P052 = 3 
P051 = 40 
off-line 
C# PDF Page Insert Library: insert pages into PDF file in C#.net
applications. Support adding and inserting one or multiple pages to existing PDF document. Forms. Ability to add PDF page number in preview. Offer
how to add a jpeg to a pdf file; add image field to pdf form
C# PDF insert text Library: insert text into PDF content in C#.net
Supports adding text to PDF in preview without adobe reader installed in ASP.NET. Powerful .NET PDF edit control allows modify existing scanned PDF text.
add an image to a pdf with acrobat; add photo to pdf
SIEMENS AG    6RX1700-0AD76 
11-177 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
Selection of time slices for function blocks FB101 to  FB200 
Index 
Function
block 
Time  
slice 
(FS) 
Index 
Function
block 
Time  
slice 
(FS) 
U951 
(2951) 
S00 
i001 
i002 
i003 
i004 
i005 
i006 
i007 
i008 
i009 
i010 
i011 
i012 
i013 
i014 
i015 
i016 
i017 
i018 
i019 
i020 
i021 
i022 
i023 
i024 
i025 
i026 
i027 
i028 
i029 
i030 
i031 
i032 
i033 
i034 
i035 
i036 
i037 
i038 
i039 
i040 
i041 
i042 
i043 
i044 
i045 
i046 
i047 
i048 
i049 
i050 
FB101 
FB102 
FB103 
FB104 
FB105 
FB106 
FB107 
FB108 
FB109 
FB110 
FB111 
FB112 
FB113 
FB114 
FB115 
FB116 
FB117 
FB118 
FB119 
FB120 
FB121 
FB122 
FB123 
FB124 
FB125 
FB126 
FB127 
FB128 
FB129 
FB130 
FB131 
FB132 
FB133 
FB134 
FB135 
FB136 
FB137 
FB138 
FB139 
FB140 
FB141 
FB142 
FB143 
FB144 
FB145 
FB146 
FB147 
FB148 
FB149 
FB150 
20 
20 
20 
i051 
i052 
i053 
i054 
i055 
i056 
i057 
i058 
i059 
i060 
i061 
i062 
i063 
i064 
i065 
i066 
i067 
i068 
i069 
i070 
i071 
i072 
i073 
i074 
i075 
i076 
i077 
i078 
i079 
i080 
i081 
i082 
i083 
i084 
i085 
i086 
i087 
i088 
i089 
i090 
i091 
i092 
i093 
i094 
i095 
i096 
i097 
i098 
i099 
i100 
FB151 
FB152 
FB153 
FB154 
FB155 
FB156 
FB157 
FB158 
FB159 
FB160 
FB161 
FB162 
FB163 
FB164 
FB165 
FB166 
FB167 
FB168 
FB169 
FB170 
FB171 
FB172 
FB173 
FB174 
FB175 
FB176 
FB177 
FB178 
FB179 
FB180 
FB181 
FB182 
FB183 
FB184 
FB185 
FB186 
FB187 
FB188 
FB189 
FB190 
FB191 
FB192 
FB193 
FB194 
FB195 
FB196 
FB197 
FB198 
FB199 
FB200 
10 
10 
10 
10 
1, 2, 4, 10, 20 
Ind: 100 
FS=  
see column 
on left 
Type: O2 
P052 = 3 
P051 = 40 
off-line 
VB.NET PDF insert text library: insert text into PDF content in vb
Multifunctional Visual Studio .NET PDF SDK library supports adding text content to adobe PDF document in VB.NET Add text to PDF in preview without adobe
add jpg to pdf; how to add image to pdf in acrobat
C# Create PDF Library SDK to convert PDF from other file formats
Load PDF from existing documents and image in SQL server. Besides, using this PDF document metadata adding control, you can add some additional
acrobat add image to pdf; add a picture to a pdf
11-178 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
Selection of time slices for function blocks FB201 to  FB300 
Index 
Function 
block 
Time  
slice 
(FS) 
Index 
Function
block 
Time  
slice 
(FS) 
U952 
(2952) 
S00 
i001 
i002 
i003 
i004 
i005 
i006 
i007 
i008 
i009 
i010 
i011 
i012 
i013 
i014 
i015 
i016 
i017 
i018 
i019 
i020 
i021 
i022 
i023 
i024 
i025 
i026 
i027 
i028 
i029 
i030 
i031 
i032 
i033 
i034 
i035 
i036 
i037 
i038 
i039 
i040 
i041 
i042 
i043 
i044 
i045 
i046 
i047 
i048 
i049 
i050 
FB201 
FB202 
FB203 
FB204 
FB205 
FB206 
FB207 
FB208 
FB209 
FB210 
FB211 
FB212 
FB213 
FB214 
FB215 
FB216 
FB217 
FB218 
FB219 
FB220 
FB221 
FB222 
FB223 
FB224 
FB225 
FB226 
FB227 
FB228 
FB229 
FB230 
FB231 
FB232 
FB233 
FB234 
FB235 
FB236 
FB237 
FB238 
FB239 
FB240 
FB241 
FB242 
FB243 
FB244 
FB245 
FB246 
FB247 
FB248 
FB249 
FB250 
10 
10 
10 
10 
20 
20 
20 
20 
20 
20 
10 
10 
10 
10 
i051 
i052 
i053 
i054 
i055 
i056 
i057 
i058 
i059 
i060 
i061 
i062 
i063 
i064 
i065 
i066 
i067 
i068 
i069 
i070 
i071 
i072 
i073 
i074 
i075 
i076 
i077 
i078 
i079 
i080 
i081 
i082 
i083 
i084 
i085 
i086 
i087 
i088 
i089 
i090 
i091 
i092 
i093 
i094 
i095 
i096 
i097 
i098 
i099 
i100 
FB251 
FB252 
FB253 
FB254 
FB255 
FB256 
FB257 
FB258 
FB259 
FB260 
FB261 
FB262 
FB263 
FB264 
FB265 
FB266 
FB267 
FB268 
FB269 
FB270 
FB271 
FB272 
FB273 
FB274 
FB275 
FB276 
FB277 
FB278 
FB279 
FB280 
FB281 
FB282 
FB283 
FB284 
FB285 
FB286 
FB287 
FB288 
FB289 
FB290 
FB291 
FB292 
FB293 
FB294 
FB295 
FB296 
FB297 
FB298 
FB299 
FB300 
20 
10 
10 
10 
10 
10 
10 
10 
10 
10 
10 
10  
10 
10 
10 
10 
10 
10 
10 
10 
10 
10 
10 
10 
10 
10 
10 
10 
10 
10 
10 
10 
10 
10 
10 
10 
10 
10 
10 
10 
20 
20 
1, 2, 4, 10, 20 
Ind: 100 
FS=  
see column 
on left 
Type: O2 
P052 = 3 
P051 = 40 
off-line 
11.97  Parameter for DriveMonitor 
n953 
to 
n959 
(2953 to 
2959) 
These parameters are used by DriveMonitor 
C# Word - Insert Image to Word Page in C#.NET
Preview Document. Conversion. Convert Word to PDF. Convert Word to HTML5. VB.NET How-to, VB.NET PDF, VB.NET Word It's a demo code for adding image to word page using
add signature image to pdf; add image to pdf online
C# PowerPoint - Insert Image to PowerPoint File Page in C#.NET
Preview Document. Conversion. Convert PowerPoint to PDF. Convert PowerPoint to Pages. Annotate PowerPoint. Text Search. Insert Image. Thumbnail Create.
how to add image to pdf acrobat; add image pdf
SIEMENS AG    6RX1700-0AD76 
11-179 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
11.98  Technology software in basic unit, S00 option:  
Altering the processing sequence of function blocks 
Only active with optional technology software S00 
Processing sequence of function blocks 
The function blocks of the S00 technology software are processed within the computational cycle in the sequence defined in parameters 
U960 to U962: 
1. 
Function block with number set in U960 index.001 
... 
100.  Function block with number set in U960 index.100 
101.  Function block with number set in U961 index.001 
... 
200.  Function block with number set in U961 index.100 
201.  Function block with number set in U962 index.001 
etc. 
The numbers are parameterized in ascending sequence (1, 2, 3, …) in the factory setting (standard sequence). 
Altering the processing sequence:
If a new function block number is entered (i.e. moved from another location) in a certain index of parameter U960, U961 or U962, then the 
new processing sequence is defined such that the function block previously entered in this index will be processed after
the newly entered 
block. The gap which may be left at the old location of the moved (newly entered) function block is closed by shifting the function block 
numbers behind the space forward by one position. 
Example 1:
Starting with the standard sequence setting, the processing sequence must be altered such that function block 90 (analog signal selector 
switch) will be processed immediately after function block 83 (tracking/storage element): 
Function block no. 90 must be entered in the index in which the number of the function block previously processed after
block 83 (84 in 
U960.9065) is currently stored. Function block numbers (84 and 85) in the following indices of U960 will be shifted up to the next index 
automatically. 
83
82
81
84
85
90
91
83
82
81
90
84
85
91
U960.Index 062
U960.Index 063
U960.Index 064
U960.Index 065
U960.Index 066
U960.Index 067
U960.Index 068
Function
block
Processing
sequence
U960.Index 062
U960.Index 063
U960.Index 064
U960.Index 065
U960.Index 066
U960.Index 067
U960.Index 068
Function
block
Processing
sequence
Example 2:
Starting with the standard sequence setting, the processing sequence must be altered such that function block 38 (sign inverter) will be 
processed immediately after function block 45 (divider): 
Function block number 38 must be entered in the index in which the number of the function block previously processed after
function block 
45 (46 in U960.i035) is currently stored. The function block numbers stored in the indices immediately above this position shift up by one 
index, then all numbers immediately above the gap left shift down automatically by one index. 
40
38
37
41
45
46
47
40
38
37
41
45
46
47
40
38
37
41
45
46
47
U960.Index 030
U960.Index 031
U960.Index 032
U960.Index 033
U960.Index 034
U960.Index 035
U960.Index 036
U960.Index 030
U960.Index 031
U960.Index 032
U960.Index 033
U960.Index 034
U960.Index 035
U960.Index 036
U960.Index 030
U960.Index 031
U960.Index 032
U960.Index 033
U960.Index 034
U960.Index 035
U960.Index 036
Function
block
Processing
sequence
Function
block
Processing
sequence
Function
block
Processing
sequence
U960 
(2960) 
S00 
Processing sequence of function blocks of S00 technology  
software (1) 
i001:  Number of function block for 1
st
place in processing  
sequence 
i002:  Number of function block for 2
nd
place in processing  
sequence 
etc. 
Numbers of all 
function blocks 
Ind: 100 
FS= 
Standard 
sequence 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
C# TIFF: TIFF Editor SDK to Read & Manipulate TIFF File Using C#.
Easy to generate image thumbnail or preview for Tiff to Tiff, like Word, Excel, PowerPoint, PDF, and images. assemblies into your C# project by adding reference
how to add image to pdf in preview; add picture to pdf preview
VB.NET PDF copy, paste image library: copy, paste, cut PDF images
Free Visual Studio .NET PDF library, easy to be integrated in .NET WinForms and ASP.NET. Besides image extracting, adding, and removing, RasterEdge
adding an image to a pdf in preview; add a picture to a pdf
11-180 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
U961 
(2961) 
S00 
Processing sequence of function blocks of S00 technology  
software (2) 
i001:  Number of function block for 101
st
place in processing sequence 
i002:  Number of function block for 102
nd
place in processing 
sequence 
etc. 
Numbers of all 
function blocks 
Ind: 100 
FS= 
Standard 
sequence 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
U962 
(2962) 
S00 
Processing sequence of function blocks of S00 technology  
software (3) 
i001:  Number of function block for 201
st
place in processing sequence 
i002:  Number of function block for 202
nd
place in processing 
sequence 
etc. 
Numbers of all 
function blocks 
Ind: 100 
FS= 
Standard 
sequence 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
U969 
(2969) 
S00 
Automatic setting and activation of the execution sequence 
Return 
Set standard sequence: 
The numbers of the function blocks are entered in ascending 
order in Parameters U960, U961 and U962. The parameter is 
then automatically set to value 0. 
Set optimum sequence: 
U960, U961, and U962 are set in such a way that as few 
deadtimes as possible occur. After that, the parameter is 
automatically set to value 0 again. 
Set standard setting of the sampling times. 
U950, U951, and U952 are set to the factory setting. 
Automatic activation / deactivation: 
U950, U951 and U952 are set in such a way that the unwired 
function blocks are deselected and the wired function blocks are 
selected (activated), if they are not yet selected. 
The time slice 10 (sampling time 20 ms) is set for all function 
blocks not previously activated, the time slice is left unchanged 
for all previously activated function blocks. 
In order to ensure that this function also functions correctly for 
function blocks FB261 to FB269 (PI controllers 2 to 10), the 
value 0 is to be set for PI controllers 2 to 10 which are not used 
and this must be done at the corresponding indices U544.i002 
to i010 before this function is used. 
0 to 4 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
off-line 
SIEMENS AG    6RX1700-0AD76 
11-181 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
11.99  Enabling of technology software in basic unit, S00 option 
("freely assignable function blocks") 
The S00 technology option can only be utilized on SIMOREG DC-MASTER converters on which this option has been enabled by a proper 
PIN number. The software remains enabled after software updates, i.e. it need not be enabled again after new software has been 
installed. 
Permanent enabling of S00 technology option (subject to charge):
Please proceed as follows if you wish to enable the S00 technology option: 
1.  Find out the serial number of your SIMOREG DC-MASTER unit  (e.g. "Q6K31253320005"): 
 The serial number is specified on the delivery note 
 The serial number is printed on the rating plate of the SIMOREG DC-MASTER 
 The serial number can be displayed in parameter r069 on the OP1S 
2.  Find out the PIN number (a number between 2001 and 65535) which matches the converter serial number: 
 If you have ordered the SIMOREG DC-MASTER with S00 option, you will find the PIN number printed on a sticker on the unit 
and specified on the delivery note. 
 If not, please contact your local Siemens sales office to obtain the correct PIN number. 
3.  Enter the PIN number in parameter U977 and complete your entry by pressing button <P>. This parameter is automatically reset to 
0 after the entry is made. Enter the PIN number with care as you only have five attempts. 
4.  Technology option S00 is now enabled, which can be verified in n978 = 2000. 
Technology option S00 can be disabled by entering U997 = PIN - 1 (e.g. for test purposes). Parameter n978 then displays 500. The option 
is enabled again by entering U977 = PIN. 
Temporary enabling of S00 technology option (free of charge):
The S00 technology option can be enabled once, free of charge, on all converters for 500 hours of use by means of a special PIN 
number. This 500-hour period can be used for test purposes or for the operation of replacement units which have been ordered without 
the S00 option (i.e. to cover the period until a PIN number for permanent enabling is obtained). 
The 500 hours are counted by the hours run counter (r048) , i.e. only the time that the drive is actually switched on is counted. When the 
500-hour period has expired, the S00 option is disabled automatically if the PIN number for permanent enabling has not been entered in 
the meantime. 
The special PIN number is: U977 = 1500 (identical number for all units) 
Temporary enabling of the option can be interrupted with PIN U977 = 500. The remaining time credit remains valid for the next period of 
use with the temporarily enabling PIN number. 
Alarm A059 is output if the time credit is less than 50 hours and the S00 technology option is temporarily enabled. 
Fault message F059 is displayed if the time credit of 500 hours has run out and the S00 option is still temporarily enabled. 
System response when S00 technology option is not enabled: 
The connectors and binectors associated with freely assignable function blocks are not updated (they are set to 0 when the electronics 
voltage is connected; when the time credit for temporary enabling has run out, they remain frozen at the last recorded values until the 
electronics voltage is disconnected again). 
U977 
(2977) 
S00 
PIN number for S00 option 
This parameter is automatically reset to "0" after entry of the PIN number. 
Take care to enter the PIN number correctly. You are only allowed up to 5 
attempts! 
0 to 65535 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
Offline 
n978 
(2978) 
S00 
"S00 enabled" display 
The optional S00 technology software is disabled 
The time credit for temporary enabling has run out 
xxx 
The optional S00 technology software is not enabled. 
xxx = number of credit hours which are still available for use 
under temporary enabling PIN number 
1xxx  The optional SOO technology software is temporarily enabled. 
xxx = number of credit hours still available 
2000  The optional S00 technology software is permanently enabled. 
see column on left 
Ind: None 
Type: O2 
P052 = 3 
11-182 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
11.100  Parameter access for experts 
U979 
(2979) 
Parameter access for experts 
[SW 1.9 and later] 
999 
Parameter access for experts is activated. 
This means that even offline parameters can be modified in 
operation. 
Notes: 
The value of this parameter is lost when the electronics power supply is 
switched off. 
Parameters can be modified only if both P051 and P052 as well as P927  
are set to the correct values. 
0 to 2000 
Ind: None 
FS=0 
Type: O2 
P052 = 3 
P051 = 40 
on-line 
11.101  List of existing and modified U and n parameters 
n980 
(2980) 
List of existing parameter numbers, continuation 
Viewing parameter for displaying the first 100 parameter numbers in the U 
or n parameter range (numbers 2000 to 2999). 
The parameters are arranged in ascending sequence. 
The list is continued in the parameter whose number is displayed in index 
101. This means, for example, 
2981  =  n981 
The first 0 to be displayed signals that no further parameter numbers are 
stored. 
Ind: 101 
Type: O2 
P052 = 3 
n981 
(2981) 
List of existing parameter numbers, continuation 
See n980. 
Ind: 101 
Type: O2 
P052 = 3 
n982 
(2982) 
List of existing parameter numbers, continuation 
See n980. 
Ind: 101 
Type: O2 
P052 = 3 
n983 
(2983) 
List of existing parameter numbers, continuation 
See n980. 
Ind: 101 
Type: O2 
P052 = 3 
n984 
(2984) 
List of existing parameter numbers, continuation 
See n980. 
Ind: 101 
Type: O2 
P052 = 3 
n985 
(2985) 
List of existing parameter numbers, continuation 
See n980. 
Ind: 101 
Type: O2 
P052 = 3 
n986 
(2986) 
List of existing parameter numbers, continuation 
See n980. 
Ind: 101 
Type: O2 
P052 = 3 
n987 
(2987) 
List of existing parameter numbers, continuation 
See n980. 
Ind: 101 
Type: O2 
P052 = 3 
n988 
(2988) 
List of existing parameter numbers, continuation 
See n980. 
Ind: 101 
Type: O2 
P052 = 3 
n989 
(2989) 
List of existing parameter numbers, continuation 
See n980. 
Ind: 101 
Type: O2 
P052 = 3 
n990 
(2990) 
List of modified parameters, continuation  
Viewing parameter for displaying the first 100 modified parameters in the U 
or n parameter range (numbers 2000 to 2999). 
The parameters are arranged in ascending sequence. 
The list is continued in the parameter whose number is displayed in index 
101. This means, for example, 
2991  =  n991 
The first 0 to be displayed signals that there are no further modified 
parameters. 
Ind: 101 
Type: O2 
P052 = 3 
n991 
(2991) 
List of modified parameters, continuation 
See n990. 
Ind: 101 
Type: O2 
P052 = 3 
n992 
(2992) 
List of modified parameters, continuation 
See n990. 
Ind: 101 
Type: O2 
P052 = 3 
SIEMENS AG    6RX1700-0AD76 
11-183 
SIMOREG DC-MASTER    Operating Instructions 
PNU 
Description 
Value range 
[Unit] 
Steps 
No. indices 
Factory 
setting 
Type 
See 
Change 
(Access / 
Status) 
n993 
(2993) 
List of modified parameters, continuation 
See n990. 
Ind: 101 
Type: O2 
P052 = 3 
n994 
(2994) 
List of modified parameters, continuation 
See n990. 
Ind: 101 
Type: O2 
P052 = 3 
n995 
(2995) 
List of modified parameters, continuation 
See n990. 
Ind: 101 
Type: O2 
P052 = 3 
n996 
(2996) 
List of modified parameters, continuation 
See n990. 
Ind: 101 
Type: O2 
P052 = 3 
n997 
(2997) 
List of modified parameters, continuation 
See n990. 
Ind: 101 
Type: O2 
P052 = 3 
n998 
(2998) 
List of modified parameters, continuation 
See n990. 
Ind: 101 
Type: O2 
P052 = 3 
n999 
(2999) 
List of modified parameters, continuation 
See n990. 
Ind: 101 
Type: O2 
P052 = 3 
11-184 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Documents you may be interested
Documents you may be interested