SIEMENS AG    6RX1700-0AD76 
12-61 
SIMOREG DC-MASTER    Operating Instructions 
Binector 
Name, description 
Function 
diag., Sheet 
B9913 
USS3 receive data, word 9, bit 13 
G172 
B9914 
USS3 receive data, word 9, bit 14 
G172 
B9915 
USS3 receive data, word 9, bit 15 
G172 
Trace function 
B9999 
Trigger condition of trace function is fulfilled 
[SW 1.8 and later] 
Acrobat insert image in pdf - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
add image to pdf java; adding images to pdf files
Acrobat insert image in pdf - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
how to add a jpeg to a pdf file; adding an image to a pdf file
12-62 
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
.NET PDF Document Viewing, Annotation, Conversion & Processing
Convert image files to PDF. File & Page Process. Annotate & Comment. Add, insert PDF native annotations to PDF file. Support for all the print modes in Acrobat PDF
add a picture to a pdf file; add picture to pdf form
C# PDF Converter Library SDK to convert PDF to other file formats
without using other external third-party dependencies like Adobe Acrobat. you can easily perform file conversion from PDF document to image or document
how to add a photo to a pdf document; adding a jpeg to a pdf
SIEMENS AG    6RX1700-0AD76 
13-1 
SIMOREG DC-MASTER    Operating Instructions 
13  Maintenance 
WARNING
Hazardous voltage are present in this electrical equipment during operation. 
A hazardous voltage may be present at the signaling relays in the customer installation. 
Non-observance of the safety instructions can result in death, severe personal injury or 
substantial property damage. 
When carrying out maintenance work on this converter, please read all safety instructions 
included in this section and attached to the product itself. 
•  Maintenance work on the converter may be carried out only by qualified personnel who are  
thoroughly familiar with all safety notices in this manual and with the installation, operating 
and maintenance instructions. 
•  Before carrying out visual checks and maintenance work, ensure that the AC power supply 
is disconnected and locked out and that the converter is grounded. Before the AC supply is 
disconnected, both converters and motors are at hazardous voltage levels. Even when the 
converter contactor is open, hazardous voltages are still present. 
•  The snubber capacitors might still be carrying hazardous voltage after isolation from the 
supply. For this reason, the converter must not be opened for at least two minutes after 
switch-off. 
Only spare parts authorized by the manufacturer may be used. 
The converter must be thoroughly protected against the ingress of dirt so as to prevent voltage 
flashovers and this irreparable damage. Dust and foreign bodies, and especially contamination 
drawn in through the cooling air flow, must be carefully removed at regular intervals depending on 
the degree of pollution, but at least once every 12 months. The converter must be cleaned with dry, 
compressed air, max. 1 bar, or with a vacuum cleaner. 
Please note the following with respect to converters with forced air cooling: 
The fan bearings are designed for a service lifetime of 30000 hours. The fans should be replaced 
in plenty of time in order to maintain the availability of the thyristor sets. 
13.1  Procedure for updating software 
CAUTION 
Before updating your software, find out the product state of your SIMOREG device. You will find this on the 
rating plate (field on the bottom left-hand side "Prod. State"). 
Prod. State = A1,A2 (devices with the CUD1 electronics board, version C98043-A7001-L1
-xx):  
It is only permissible to load software versions 1.xx and 2.xx. 
Prod. State = A3 (devices with the CUD1 electronics board, version C98043-A7001-L2
-xx):  
It is only permissible to load software versions 3.xx. 
In the Internet at http://support.automation.siemens.com/WW/view/de/10804957/133100
a WINDOWS-based version of the loading program is available (HEXLOAD_WIN.EXE). This 
program is started by double clicking on it in step 5 of the procedure described below for updating 
software.      
USB-RS232 interface converters are supported. 
C# powerpoint - PowerPoint Conversion & Rendering in C#.NET
using other external third-party dependencies like Adobe Acrobat. file conversion from PowerPoint document to image or document PowerPoint to PDF Conversion.
add image to pdf form; add jpg to pdf form
C# Word - Word Conversion in C#.NET
without using other external third-party dependencies like Adobe Acrobat. perform file conversion from Word document to image or document Word to PDF Conversion.
add picture to pdf online; how to add an image to a pdf in preview
13-2
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
1
Read out and write down all parameter 
contents. 
(also note software version in r060.001 and 
r065.001!) 
Note: 
The parameter set can be transferred to a PC or 
programming device by means of DriveMonitor 
(see also Section 15). 
2
Switch off electronics power supply 
3
Connect one COM port on the PC to 
connector X300 on the converter 
Cable order number:  9AK1012-1AA00 
(see also Section 15.3) 
4
Switch on electronics power supply AND 
press down the UP key on the PMU of the 
SIMOREG converter at the same time 
⇒  The SIMOREG converter switches to 
operating state o13.0 
Note: 
A software update can be started only from the 
PMU panel and not
via an OP1S or the 
DriveMonitor system 
5
Open a DOS window on the PC and enter 
program call: 
HEXLOAD 7001Axxx.H86 7001Bxxx.H86 COMx
Start the program by pressing Return 
⇒  The software update is performed 
automatically 
Note: 
HEXLOAD.EXE:  Loading program 
7001Axxx.H86 and 7001Bxxx.H86: 
Data files which contain the SIMOREG software 
xxx is the SW release 
COMx: COM1 or COM2 
6
⇒  When the software has been updated 
successfully, the SIMOREG switches to 
operating state o13.2 for approx. 1 s 
⇒  The SIMOREG converter then switches to 
operating state o12.9 in many cases 
(depending on which SW version was 
previously installed in the converter) for 
approximately 15s. 
Note: 
The currently programmed addressed is displayed 
on the PMU while the update is in progress 
The current status of the update routine is 
displayed on the PC 
7
Check the checksum: 
Comparison of the value of parameter r062.001 with the checksum in the Internet under menu item 
"Info" (see the inside page of the cover sheet of the operation instructions). 
8
Was the electronics supply disconnected 
while Step 6 was in progress? 
yes 
9b
Acknowledge any fault message that may 
appear on the SIMOREG device 
10b
Restore default setting 
(see Section 7.4) 
11b
Start up the converter again 
(see Section 7.5) 
Note: 
The parameter set stored in Step 1 above can 
be loaded from a PC or programming device 
by means of DriveMonitor. 
12
End 
C# Windows Viewer - Image and Document Conversion & Rendering in
without using other external third-party dependencies like Adobe Acrobat. Image and Document Conversion Supported by Windows Viewer. Convert to PDF.
add an image to a pdf form; add jpeg to pdf
VB.NET PDF: How to Create Watermark on PDF Document within
PDF Watermark Creator, users need no external application plugin, like Adobe Acrobat. to PDF. Besides text, users also can insert a target image, like company
how to add jpg to pdf file; adding an image to a pdf in preview
SIEMENS AG    6RX1700-0AD76 
13-3 
SIMOREG DC-MASTER    Operating Instructions 
13.2  Replacement of components 
13.2.1  Replacement of fan 
WARNING
The converter fan may be replaced only by properly qualified personnel. 
The snubber capacitors might still be carrying hazardous voltage after isolation from the 
supply. For this reason, the converter must not be opened for at least two minutes after switch-
off. 
Non-observance of the safety instructions can result in death, severe personal injury or 
substantial property damage. 
Replacement of fan on 210A to 280A converters 
2
1
4
3
The two fans are mounted on the underside of the converter. 
•  Remove connector 
a
•  Release the two retaining clips 
s
on the fan and swing fan out downwards. 
Installation: 
•  When mounting the fan make sure it is in the correct mounting position (blowing direction 
upward, see arrow 
on the fan housing). 
•  Insert the fan into lugs 
f
and push upwards until it engages in retaining clips 
s
•  Insert connector 
a
again. 
C# Excel - Excel Conversion & Rendering in C#.NET
without using other external third-party dependencies like Adobe Acrobat. file conversion from Excel document to image or document, or Excel to PDF Conversion.
adding images to a pdf document; add photo to pdf in preview
VB.NET PowerPoint: VB Code to Draw and Create Annotation on PPT
with no more plug-ins needed like Acrobat or Adobe VB.NET PPT: VB Code to Add Embedded Image Object to VB.NET PPT: Insert and Customize Text Annotation on PPT
adding images to pdf forms; how to add picture to pdf
13-4
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Replacement of fan on 400A to 850A converters 
4U1
4V1
4W1
PE
1
2
The fan is mounted on the underside of the converter. 
•  Remove connector 
a
•  Use a T20 screwdriver to undo the two Torx screws 
s
•  Lift the fan using the fixing straps and pull out downwards. 
Installation: 
•  Push fan box up along the rear panel right up over the fixing clips. 
•  Tighten the two Torx screws 
s
with 2.5 Nm. 
•  Insert connector 
a
SIEMENS AG    6RX1700-0AD76 
13-5 
SIMOREG DC-MASTER    Operating Instructions 
Replacement of fan on 900A to 1200A converters 
3
1
2
The fan is mounted on top of the converter. 
•  Remove connector 
a
•  Use a T20 screwdriver to undo the two Torx screws 
s.
•  Undo the M6 hexagonal nut 
d
•  Pull fan upwards out of its guideway and then forwards to remove. Take care to protect the field 
module mounted on the left (risk of mechanical damage!). 
Installation: 
•  Insert fan into guideway from above. 
•  Tighten the two Torx screws 
s
with 10 Nm. 
•  Tighten hexagonal nut M6 
d
with 10 Nm. 
•  Insert connector 
a
13-6
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Replacement of fan on 1500A to 3000A converters 
WARNING
When dismantling the fan-mounting box, please remember that it weighs 12 kg. 
Non-observance of this warning can result in  severe personal injury or substantial property 
damage. 
2
1
The fan is mounted on top of the converter. 
•  Remove connector 
a
•  Undo the M6 hexagonal nut 
s
•  Swing fan upwards and pull it out towards you, taking care to protect the field module mounted 
on the left against any mechanical damage! 
Installation: 
•  Tilting the fan from the front and upward (see Fig.), slot it into the two rear guide tabs and then 
tilt it downward as far as it will go. 
•  Tighten hexagonal nut M6 
s
with 10 Nm. 
•  Insert connector 
a
SIEMENS AG    6RX1700-0AD76 
13-7 
SIMOREG DC-MASTER    Operating Instructions 
13.2.2  Replacement of PCBs 
WARNING
PCBs may be replaced only by properly qualified personnel. 
PCBs must not be removed or inserted when the power supply is connected. 
Non-observance of the safety instructions can result in death, severe personal injury or 
substantial property damage. 
CAUTION
PCBs contains electrostatically sensitive devices. Before touching a PCB, the person carrying 
out the work must himself be electrostatically discharged. The simplest way of doing this is to 
touch an electrically conductive earthed object, e.g. socket outlet earth contact. 
CAUTION 
If one of the following boards is replaced 
•  C98043-A7004 
(field board for units with disk-type thyristors) 
•  C98043-A7010 
(power section for 15A and 30A units) 
•  C98043-A7014 
•  C98043-A7015 
(field boards for 60A to 1200A units)   
the "internal offset adjustments" (P051 = 22) must be repeated ! 
13-8
SIEMENS AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
13.2.3   Replacement of diodes and thyristor modules for devices up to 1200A 
The diodes and thyristor modules are mounted by means of self-tapping screws. When a module is 
replaced, the support surfaces on the heatsink must be cleaned and a new layer of thermo-
lubricant applied to the thyristor module. To fix the modules always used screws with a metric 
thread of the same length as the original screws and fixing elements (washer and spring lock 
washer). When screwing the modules to the busbars and boards, also use screws with a metric 
thread and the same length as the original screws and fixing elements (washer and spring lock 
washer). 
NOTICE 
The layer of thermo-lubricant (silicone-free, type H-T-C made by Electrolube) applied to the modules must 
be so thin and even that the baseplate is still clearly visible underneath! 
No auxiliary cathodes must be contacted on the standby modules! 
Module design 
Tightening torque on module: 3,5 Nm 
Tightening torque of current terminals: 3 Nm 
Tightening torque on module: 3,5 Nm 
Tightening torque of current terminals: 5 Nm 
Tightening torque on module: 6 Nm 
Tightening torque of current terminals: 12 Nm 
Tightening torque on module: 6 Nm 
Tightening torque of current terminals: 15 Nm 