pdf viewer c# : How to add image to pdf document Library software component asp.net winforms web page mvc OPI_simoreg_DC_0707_en9-part1931

Siemens AG    6RX1700-0AD76 
6-5 
SIMOREG DC-MASTER    Operating Instructions 
Rule 9 
The shields of digital signal cables must be connected to ground at both ends (source and 
destination). If there is poor potential bonding between the shield connections, an additional 
potential bonding cable of at least 10 mm² must be connected in parallel to the shield to reduce the 
shield current. Generally speaking, the shields can be connected to the cabinet housing (ground 
2)
at several points. The shields may also be connected at several locations outside the cabinet. 
Foil-type shields should be avoided. Their shielding effect is poorer by a factor of 5 as compared to 
braided shields. 
Rule 10 
The shields of analog signal cables may be connected to ground at both ends (conductively over a 
large area) if potential bonding is good. Potential bonding can be assumed to be good if all metal 
parts are well connected and all the electronic components involved are supplied from the same 
source. 
The single-ended shield connection prevents low-frequency, capacitive noise from being coupled 
in (e.g. 50 Hz hum). The shield connection should then be made in the cabinet. In this case, the 
shield may be connected by means of a sheath wire. 
The cable to the temperature sensor on the motor (X174:22 and X174:23) must be shielded and 
connected to ground at both ends.    
Rule 11 
The RI suppression filter must always be mounted close to the suspected noise source. The filter 
must be mounted over the largest possible area with the cabinet housing, mounting plate, etc. 
Incoming and outgoing cables must be routed separately. 
Rule 12 
To ensure adherence to limit value class A1, the use of RI suppression filters is obligatory. 
Additional loads must be connected on the line side of the filter. 
The control system used and the other wiring in the cubicle determines whether an additional line 
filter needs to be installed. 
Rule 13 
A commutating reactor must be installed in the field circuit for controlled field supplies. 
Rule 14 
A commutating reactor must be installed in the converter armature circuit. 
Rule 15 
Unshielded motor cables may be used in SIMOREG drive systems. 
The line supply cable must be routed at a distance of at least 20 cm from the motor cables (field, 
armature). Use a metal partition if necessary. 
Footnotes: 
1)   Signal cables are defined as:  
Digital signal cable: 
Analog signal cable.: 
Pulse encoder cables 
e.g. +
10 V setpoint cable 
Serial interfaces, e.g. PROFIBUS-DP 
2)  The term "Ground" generally refers to all metallic, conductive components which can be 
connected to a protective conductor, e.g. cabinet housing, motor housing, foundation grounder, 
etc. 
How to add image to pdf document - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
add png to pdf preview; add photo to pdf
How to add image to pdf document - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
acrobat add image to pdf; how to add a jpg to a pdf
6-6
Siemens AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Cabinet design and shielding: 
The cabinet design illustrated in Figure 1 is intended to make the user aware of EMC-critical 
components. The example does not claim to include all possible cabinet components and their 
respective mounting possibilities. 
Details which influence the noise immunity/radiation of the cabinet and are not absolutely clear in 
the overview diagram are described in Figures 1a - 1d. 
Figures 2a -2d  show details of different shield connection techniques with ordering source 
information. 
Arrangement of RI suppression filters and commutating reactors: 
Section 6.1.2.3 shows how RI suppression filters and commutating reactors are arranged in the 
SIMOREG DC-MASTER system. The specified sequence for mounting reactors and filters must be 
observed. The line-side and load-side filter cables must be physically separated. Fuses for 
semiconductor protection are selected according to Section 6.6.2. 
C# PDF Password Library: add, remove, edit PDF file password in C#
in C#.NET framework. Support to add password to PDF document online or in C#.NET WinForms for PDF file protection. Able to create a
add image to pdf file acrobat; add an image to a pdf in preview
C# PDF Image Extract Library: Select, copy, paste PDF images in C#
Get image information, such as its location, zonal information, metadata, and so on. Able to edit, add, delete, move, and output PDF document image.
add an image to a pdf with acrobat; add jpg to pdf acrobat
Siemens AG    6RX1700-0AD76 
6-7 
SIMOREG DC-MASTER    Operating Instructions 
SIMOREG DC Master
Main contactor
Cable clamping bar
Shield rail
Connecting terminals
Commutating reactor
Cable duct
Line filter
Shield rail
Connecting terminals
Main switch
Circuit-breakers
Circuit breaker
Commutating 
reactor for field
Fuse-links/miniature
circuit-breakers
Converter filter
3AC
Fuse-links
Control trans-
former for fan
PE conductor
(position is not critical)
Customer terminal DC
Customer terminal 3AC
Customer terminal of field winding
Pulse encoder
Fig. 1b
Fig. 1c or 1d
Shield connection
Fig. 1a
Fig. 1e
Shield rail
s
Fuse-links
Fig. 1:  Example of a cabinet design with a SIMOREG DC-MASTER 15 A to 850 A 
VB.NET PDF Image Extract Library: Select, copy, paste PDF images
More detailed functions are listed below. DLLs for PDF Image Extraction in VB.NET. Add necessary references: VB.NET: Extract All Images from PDF Document.
add png to pdf acrobat; add photo to pdf online
VB.NET PDF Password Library: add, remove, edit PDF file password
allowed. passwordSetting.IsCopy = True ' Allow to assemble document. passwordSetting.IsAssemble = True ' Add password to PDF file.
add image to pdf file; attach image to pdf form
6-8
Siemens AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Cable clamping bar
Shield connection according to the
following variants 1,2,3 and 4.
Connect to cabinet housing at
both ends in conductive,
large-surface connection!
Shield at plant end as well
(e.q. on pulse encoder)
Cable duct
Do not use shield
rail as strain relief
⇒ Cable clamping bar
Fig. 1a:  Shield at cable entry point to cabinet 
Connect to cabinet housing 
at both ends in a conductive,
large-area connection!
Terminals
Analog signal line
Data line
(e.g. PROFIBUS-DP)
Data line
(e.g. pulse encoder)
Shield at the plant end as well
(e.g. on pulse encoder)
Fig. 1b:  Shielding in the cabinet 
C# Create PDF from images Library to convert Jpeg, png images to
List<Bitmap> images = new List<Bitmap>(); images.Add(new Bitmap(Program.RootPath + "\\" 1.gif")); / Build a PDF document with GIF image.
add multiple jpg to pdf; how to add image to pdf form
C# PDF: How to Create PDF Document Viewer in C#.NET with
The PDF document manipulating add-on from RasterEdge DocImage SDK Support thumbnail image and outline preview for quick PDF document page navigation;
add photo to pdf in preview; how to add an image to a pdf in reader
Siemens AG    6RX1700-0AD76 
6-9 
SIMOREG DC-MASTER    Operating Instructions 
X172
X173
X174
X175
XR
XS
XT
XP
XF1
XF2
X163
X164
X161
X171
X162
The customer connections must be routed above the electronics box. 
Fig. 1c:  Connecting shields on SIMOREG DC-MASTER converters up to 850A 
X171
X172
X173
X174
X175
XP
XR
XS
XT
Fig. 1d:  Connecting shields on SIMOREG DC-MASTER >850A 
C# PDF Sticky Note Library: add, delete, update PDF note in C#.net
PDF document processing tool, which can perform various PDF annotation works in easy ways. Using this .NET PDF annotation control, C# developers can add a
add an image to a pdf form; add picture to pdf file
DocImage SDK for .NET: Web Document Image Viewer Online Demo
on the client side without additional add-ins and Microsoft PowerPoint: PPTX, PPS, PPSX; PDF: Portable Document Format; TIFF: Tagged Image File Format;
add image in pdf using java; add image to pdf preview
6-10
Siemens AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
L1
L2
L3
L1
L2
L3
NETZ/LINE
LAST/LOAD
Connect line filter over large
surface to cabinet housing!
Electronics supply and mains
connection for field supply
Mains connection
Connect the
PE conduct
Separate filtered and
unfiltered cables
Fig. 1e:  Line filter for SIMOREG DC-MASTER 6RA70 electronics power supply 
Siemens AG    6RX1700-0AD76 
6-11 
SIMOREG DC-MASTER    Operating Instructions 
Shield connections: 
Variant 1: 
Variant 2: 
Fig. 2a:  Terminal on a copper busbar, max. 
cable diameter 15 mm 
Fig. 2b:  Terminal on copper busbar, max. cable 
diameter 10 mm 
Caution! 
The conductor might be damaged if the terminal 
screw is over-tightened. 
Note: 
Terminals: 
5 mm busbar thickness 
Order No. 8US1921-2AC00 
10 mm busbar thickness 
Order No. 8US1921-2BC00 
Note: 
Terminals: 
Order No. 8HS7104, 
8HS7104, 8HS7174, 8HS7164 
6-12
Siemens AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
Variant 3: 
Variant 4: 
Fig. 2c:  Metallized tubing or cable ties on a bare 
metal comb-type/serrated rail 
Fig. 2d:  Clamp and metallic mating piece on a 
cable clamping rail 
Note: 
Comb-type rail: 
Item No. J48028 
Note: 
Siemens 5VC55... cable clamps; 
Clamping rails in various sizes: 
Item No. K48001 to 48005 
Siemens AG    6RX1700-0AD76 
6-13 
SIMOREG DC-MASTER    Operating Instructions 
6.1.2.3  Arrangement of components for converters 
Arrangement of reactors and RI suppression filter 
1U1
1V1 1W1
3U1 3W1
5U1 5W1
1C1 1D1
M
3C 3D
1)
2)
3)
4)
5N1
NC
400V
230V
5U1 5W1
5N1
5)
Line voltage
Field
Armature
Power supply input
either 230V or 400V
SIMOREG-converter
1)  The commutating reactor in the field circuit is dimensioned for the rated motor field current. 
2)  The commutating reactor in the armature circuit is dimensioned for the motor rated current in 
the armature. 
The line current equals DC times 0.82. 
3)  The RI suppression filter for the armature circuit is dimensioned for the motor rated current in 
the armature. 
The line current equals DC times 0.82 
4)  The RI suppression filter for the electronics power supply alone with 400 V is dimensioned 
for ≥1A. 
The RI suppression filter for the field circuit and electronics power supply with 400 V is 
dimensioned for the rated current of the motor field plus 1A. 
5)  The RI suppression filter for the electronics power supply with 230 V is dimensioned for ≥2A. 
CAUTION 
When RI suppression filters are installed, commutating reactors must always be inserted 
between the filter and device input to decouple the surge suppression circuits and protect the X 
capacitors. 
The commutating reactors must be selected from Catalog LV60. The RI suppression filters must 
be selected from Catalog LV60 or according to the table of EPCOS filters below. 
6-14
Siemens AG    6RX1700-0AD76
SIMOREG DC-MASTER    Operating Instructions 
6.1.2.4  List of recommended RI suppression filters made by EPCOS: 
Rated current 
RI suppression 
filter (A) 
RI suppression filter 
Order number 
Terminal  
cross-section 
(mm²) 
Holes for M . .  
Weight 
(kg) 
Dimensions 
HxWxD 
(mm) 
B84143-G8-R11* 
4 mm² 
1,3 
80 x 230 x 50 
20 
B84143-G20-R11* 
4 mm² 
1,3 
80 x 230 x 50 
36 
B84143-G36-R11* 
6 mm² 
2,8 
150 x 280 x 60 
50 
B84143-G50-R11* 
16 mm² 
3,3 
150 x 60 x 330 
66 
B84143-G66-R11* 
25 mm² 
4,4 
150 x 330 x 80 
90 
B84143-G90-R11* 
25 mm² 
4,9 
150 x 330 x 80 
120 
B84143-G120-R11* 
50 mm² 
7,5 
200 x 380 x 90 
150 
B84143-G150-R11* 
50 mm² 
8,0 
200 x 380 x 90 
220 
B84143-G220-R11* 
95 mm² 
11,5 
220 x 430 x 110 
150 
B84143-B150-S** 
M10 
13 
140 x 310 x 170 
180 
B84143-B180-S** 
M10 
13 
140 x 310 x 170 
250 
B84143-B250-S** 
M10 
15 
115 x 360 x 190 
320 
B84143-B320-S** 
M10 
21 
115 x 360 x 260 
400 
B84143-B400-S** 
M10 
21 
115 x 360 x 260 
600 
B84143-B600-S** 
M10 
22 
115 x 410 x 260 
1000 
B84143-B1000-S** 
M12 
28 
165 x 420 x 300 
1600 
B84143-B1600-S** 
2 x M12 
34 
165 x 550 x 300 
2500 
B84143-B2500-S** 
4 x M12 
105 
200 x 810 x 385 
*)  The code for the construction type must be inserted instead of *: 
0 = 480 V      2 = 530 V 
**) The code for the construction type must be inserted instead of **: 
20 = 500 V      21 = 760 V       24 = 690 V 
*) RI suppression filters produce discharge currents. VDE 0160 stipulates a 10 mm² PE 
connection. To ensure an optimum filtering effect, it is absolutely essential to mount the filters and 
converter on a single metal plate. 
In the case of converters with a 3-phase connection, the minimum rated current of the filter  
equals the output DC of the converter times 0.82. 
With a two-phase connection (field supply and electronics supply), only two phases are connected 
to the three-phase RI suppression filter. In this case, the line current equals the field DC (plus 1A 
for the electronics supply). 
Important technical data of Siemens RI suppression filters: 
Rated supply voltage 
3AC 380-460 V (± 15%) 
Rated frequency 
50/60 Hz (± 6%) 
Operating temperature 
0° C to +40° C 
Degree of protection 
IP20 (EN60529)   IP00 with 500 A and above 
For further technical data about RI suppression filters, please refer to the Operating Instructions:  
SIMOVERT Master Drives  RI Suppression Filters  EMC Filters, Order number:  
6SE7087-6CX87-0FB0. 