Chapter 4. CPU Operation 
112 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
4.11
Power-Up and Power-Down Sequences 
4.11.1
Power-Up Sequence 
System power-up consists of the following parts:  
Power-up self-test 
CPU memory validation  
System configuration 
Intelligent option module self-test completion 
Intelligent option module dual port interface tests 
I/O system initialization 
4.11.1.1
Power-Up Self-Test  
On system power-up, many modules in the system perform a power-up diagnostic self-test. The CPU 
module executes hardware checks and software validity checks. Intelligent option modules perform 
setup and verification of on-board microprocessors, software checksum verification, local hardware 
verification, and notification to the CPU of self-check completion. Any failed tests are queued for 
reporting to the CPU during the system configuration portion of the cycle.  
If a low or failed battery (or Energy Pack fault) indication is present, a fault is logged in the CPU fault 
table. 
4.11.1.2
CPU Memory Validation   
The next phase of system power-up is the validation of the CPU memory. First, if the system verifies 
that user memory areas are still valid. A known area of user memory is checked to determine if data 
was preserved. Next, if a ladder diagram program exists, a checksum is calculated across the _MAIN 
ladder block. If no ladder diagram program exists, a checksum is calculated across the smallest 
standalone C program. 
When the system is sure that the user memory is preserved, a known area of the bit cache area is 
checked to determine if the bit cache data was preserved. If this test passes, the Bit Cache memory is 
left containing its power-up values. (Non-retentive outputs are cleared on a transition from STOP 
Mode to RUN Mode.) If the checksum is not valid or the retentive test on the user memory fails, the bit 
cache memory is assumed to be in error and all areas are cleared. The CPU is now in a cleared state, 
the same as if a new CPU module were installed. All logic and configuration files must be stored from 
the programmer to the CPU.  
4.11.1.3
System Configuration 
After completing its self-test, the CPU performs the system configuration. It first clears all system 
diagnostic bits in the bit cache memory. This prevents faults that were present before power-down 
but are no longer present from accidentally remaining as faulted. Then it polls each module in the 
system for completion of the corresponding self-test.  
The CPU reads information from each module, comparing it with the stored (downloaded) rack/slot 
configuration information. Any differences between actual configuration and the stored 
configuration are logged in the fault tables.  
Adding an image to a pdf - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
adding image to pdf file; add picture to pdf preview
Adding an image to a pdf - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
how to add image to pdf acrobat; acrobat add image to pdf
Chapter 4. CPU Operation 
GFK-2222W 
August 2015 
113 
4.11.1.4
Intelligent Option Module Self-Test Completion   
Intelligent option modules may take a longer time to complete their self-tests than the CPU due to 
the time required to test communications media or other interface devices. As an intelligent option 
module completes its initial self-tests, it tells the CPU the time required to complete the remainder of 
these self-tests. During this time, the CPU provides whatever additional information the module 
needs to complete its self-configuration, and the module continues self-tests and configuration. If the 
module does not report back in the time it specified, the CPU marks the module as faulted and makes 
an entry in one of the fault tables. When all self-tests are complete, the CPU obtains reports from the 
module as generated during that particular module’s power-up self-test and places fault information 
(if any) in the fault tables.  
4.11.1.5
Intelligent Option Module Dual Port Interface Tests  
After completion of the intelligent option module self-test and results reporting, integrity tests are 
jointly performed on the dual-port interface used by the CPU and intelligent option module for 
communications. These tests validate that the two modules are able to pass information back and 
forth, as well as verify the interrupt and semaphore capabilities needed by the communications 
protocol. After dual port interface tests are complete, the communications messaging system is 
initialized.  
4.11.1.6
I/O System Initialization 
If the module is an input module, no further configuration is required. If the module is an output 
module, the module is commanded to go to its default state. The output modules default to all 
outputs off at power-up and in failure mode, unless configured otherwise. 
A bus transmitter module is interrogated about what expansion racks are present in the system. 
Based on the bus transmitter module’s response, the CPU adds those racks and their associated slots 
into the list of slots to be configured.  
Finally, the I/O Scanner performs its initialization. The I/O Scanner initializes all the I/O controllers in 
the system by establishing the I/O connections to each I/O bus on the I/O controller and obtaining all 
I/O configuration data from that I/O controller. This configuration data is compared with the stored 
I/O configuration and any differences reported in the I/O Fault Table. The I/O Scanner then sends 
each I/O controller a list of the I/O modules to be configured on the I/O bus. After the I/O controllers 
have been initialized, the I/O Scanner replaces the factory default settings in all I/O modules with any 
application-specified settings. 
VB.NET PDF Page Insert Library: insert pages into PDF file in vb.
Support adding PDF page number. Offer PDF page break inserting function. DLLs for Adding Page into PDF Document in VB.NET Class. Add necessary references:
add an image to a pdf form; how to add a jpeg to a pdf
VB.NET PDF Library SDK to view, edit, convert, process PDF file
PDF document to/from supported document and image forms. to define text or images on PDF document and Capable of adding PDF file navigation features to your VB
add jpg to pdf file; add image pdf acrobat
Chapter 4. CPU Operation 
114 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
4.11.2
Power-Down Sequence   
System power-down occurs when the power supply detects that incoming power has dropped for 
more than 15ms.  
4.11.3
Power Cycle Operation with an Energy Pack 
Energy Packs offer distinct advantages over batteries: 
a)
significantly longer life cycles 
b)
they are more reliable 
c)
flammability during shipment is not an issue 
d)
in their end-of-life phase, their decline is a lot more gradual. 
The system design includes the ability of the CPU and the Energy Pack to monitor each other in real 
time. This permits the user to monitor alarms and thereby determine when to replace a capacitor 
pack. The capacitor pack is normally replaced while the CPU is powered on, giving it time to charge 
up before any subsequent loss of power. Users should target periods which are expected to be free 
from electrical events, such as thunderstorms, to carry out such work. Capacitor packs may also be 
replaced while power is off. 
When power is lost, the Energy Pack supplies current and maintains voltage levels for a period of 
time sufficient to permit the connected CPU to save all dynamic memory to non-volatile memory. 
When power is restored, the CPU will not start running its application until the Energy Pack signals 
that it is fully charged. The CPU will then resume operation using the contents of memory retained at 
the previous loss of power event. The Energy Pack charges continuously during normal operation. 
The RX3i and RX7i product lines encompass a number of different Energy Packs, so it is important to 
use compatible products: 
CPU 
IC695CPE330  IC695CPE305  
IC695CPE310 
ICRXICTL000 
Energy Pack 
IC695ACC402  IC695ACC400  ICRXIACCEPK01 
Capacitor Pack 
IC695ACC412  IC695ACC400  ICRXIACCCPK01 
Connecting Cable 
IC695CBL002  IC695CBL001  ICRXIACCCBL01 
Documentation 
GFK-2939 
GFK-2724 
GFK-2741 
User memory is preserved only if the compatible Energy Pack is connected (and charged) at 
power-down. 
If the Energy Pack is connected at power-up, the CPU waits for it to charge up before beginning 
normal operations. For CPE330, this typically takes up to 90 seconds.  
In the event the Energy Pack fails to charge up in a reasonable amount of time, or is absent, the CPU 
will time out the wait period and will then commence operations without the Energy Pack. When this 
occurs, the CPU is vulnerable to loss of memory, should another power failure occur. It is critical to 
monitor the status bits shown in Energy Pack Status Bit Operation so that human intervention can be 
summoned. 
Removing or reconnecting the Energy Pack while the connected CPU is powered off has no effect on 
the preservation of user memory. 
Note:  Because the Time of Day (TOD) clock is powered by a separate Real Time Clock battery in 
CPE305/CPE310/CPE330, the Energy Pack has no effect on the CPU TOD value.  
C# PDF Page Insert Library: insert pages into PDF file in C#.net
By using reliable APIs, C# programmers are capable of adding and inserting (empty) PDF page or pages from various file formats, such as PDF, Tiff, Word, Excel
how to add image to pdf in preview; adding jpg to pdf
C# PDF insert text Library: insert text into PDF content in C#.net
Supports adding text to PDF in preview without adobe reader installed in ASP.NET. Powerful .NET PDF edit control allows modify existing scanned PDF text.
add image pdf; add an image to a pdf acrobat
Chapter 4. CPU Operation 
GFK-2222W 
August 2015 
115 
4.11.3.1
Energy Pack Status Bit Operation 
As shown in the table below, the CPU application program can monitor the status of the attached 
Energy Pack via %S0014 (PLC_BAT) and %SA0011 (LOW_BAT). For more details, refer to the chapter 
on Diagnostics in PACSystems RX7i and RX3i CPU Programmer’s Reference Manual, GFK-2950.  
PLC_BAT (%S0014)   LOW_BAT (%SA0011)   Energy Pack Status  
Energy Pack connected and operational (may be charging)  
Energy Pack not connected or has failed  
Energy Pack is nearing its end-of-life and should be replaced.  
The LEDs on the Energy Pack also indicate its status. Refer to the documentation for each product for 
corresponding LED status. 
4.11.3.2
Energy Pack Replacement 
If an Energy Pack fails, you can replace it while the CPU is in operation. Use a compatible new unit or 
a compatible replacement Cap Pack. Whenever an Energy Pack is replaced, the newly installed Cap 
Pack must build up its charge.  
In the case of ACC402 attached to CPE330, the Energy Pack, when hot-swapped, draws minimal 
current in order to recharge: it may therefore take up to 10 minutes for ACC402 to charge 
completely. This is normal operation. 
If a loss of power occurs while the Energy Pack is disconnected, or before the capacitors are fully 
charged, memory loss may occur. 
4.11.3.3
CPE330/ACC402 Status Detection & Fault Reporting 
Both the CPE330 and ACC402 contain intelligence, allowing each to determine the status of the 
other. This permits the CPU to report various conditions to the user via the status bits discussed in 
Energy Pack Status Bit Operation.  
Whenever the CPE330 detects any kind of issue with the ACC402 Energy Pack, it resumes normal 
operation and issues warnings or faults to the user. The table below details the various permutations 
possible at power-up. If the Cap Pack is removed during normal operation, this fault will be reported 
as a failed battery fault. 
Energy Pack Base  Cap Pack 
CPE330 power up response 
Not present 
(removed or failed) 
Not present 
(removed or failed) 
Detects missing ACC402 and boots up immediately but does not use 
any stored memory when resuming operations. Issues fail battery 
fault. 
Not present  
(bad base) 
Present  
(good cap pack) 
Detects missing ACC402 and boots up immediately but does not use 
any stored memory when resuming operations. Issues fail battery 
fault. 
Present  
(good base) 
Not present 
(removed or failed) 
When the CPU does not see a fully charged status within 90 
seconds, it does not use any stored memory when resuming 
operations. Issues fail battery fault. 
Present 
(good base) 
Present 
(good cap pack) 
The CPU will wait for fully charged status within timeout period and 
then resume operation using the contents of memory retained at 
the previous loss of power event 
Present 
(suspicious) 
Present 
(suspicious) 
If the CPU does not see a fully charged status within 90 seconds, it 
does not use any stored memory when resuming operations. Issues 
fail battery fault. 
VB.NET Image: How to Draw Annotation on Doc Images with Image SDK
multi-page TIFF, Microsoft Office Word and PDF file programmer, you might need some other image annotating tutorials besides adding annotation using VB
add image to pdf reader; add photo to pdf reader
VB.NET TIFF: Add New Image to TIFF File in Visual Basic .NET
NET TIFF image processing SDK and its TIFF image adding function at this section, the following parts will describe the sample method for adding image to TIFF
how to add image to pdf in acrobat; add photo to pdf for
Chapter 4. CPU Operation 
116 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
4.11.4
Retention of Data Memory Across Power Failure   
The following types of data are preserved across a power cycle with an operational battery (or for 
CPE305, CPE310, or CPE330, with an operational and attached Energy Pack):  
Application program  
Fault tables and other diagnostic data  
Checksums on programs and blocks 
Override data 
Data in register (%R), local register (%L), and program register (%P) memory  
Data in analog memory (%AI and %AQ) 
State of discrete inputs (%I) 
State of retentive discrete outputs (%Q)  
State of retentive discrete internals (%M)  
The following types of data are not preserved across a power cycle:  
State of discrete temporary memory (%T)  
%M and %Q memories used on non-retentive -()- coils 
State of discrete system internals (system bits, fault bits, reserved bits). 
VB.NET Image: Adding Line Annotation to Images with VB.NET Doc
Codes for Line Annotation on Image. Displayed below are the complete Visual Basic .NET sample codes for adding a line annotation on your image (supporting png
add a jpeg to a pdf; add an image to a pdf in preview
VB.NET Word: Word Image Adding Guide in VB.NET
Developed in .NET Framework, this Word image adding toolkit also allows provide powerful & profession imaging controls, PDF document, image to pdf files and
add image to pdf form; how to add an image to a pdf in acrobat
GFK-2222W 
August 2015 
117 
Chapter 5
Communications 
This chapter describes the Ethernet and Serial communications features of the PACSystems CPU. 
Ethernet communications may be handled by the embedded CPU Ethernet port(s) or by an 
IC695ETM001 module installed in an RX3i rack. Refer to PACSystems RX7i & RX3i TCP/IP Ethernet 
Communications User Manual, GFK-2224. 
Serial communications may be handled by the embedded CPU Serial port(s)  or by an IC695CMM002 
or IC695CMM004 module installed in an RX3i rack. Refer to PACSystems RX3i Serial Communications 
Modules User’s Manual, GFK-2460. 
This chapter contains the following information with respect to the embedded CPU ports: 
Ethernet Communications
Serial Communications
Series 90-70 Communications and Intelligent Option Modules
VB.NET PDF insert text library: insert text into PDF content in vb
VB.NET PDF - Insert Text to PDF Document in VB.NET. Providing Demo Code for Adding and Inserting Text to PDF File Page in VB.NET Program.
how to add an image to a pdf in reader; add picture to pdf document
Chapter 5. Communications 
118 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
5.1
Ethernet Communications 
For details on Ethernet communications for PACSystems, please refer to the following manuals: 
PACSystems RX7i & RX3i TCP/IP Ethernet Communications User Manual, GFK-2224 
PACSystems TCP/IP Ethernet Communications Station Manager User Manual, GFK-2225. 
5.1.1
Embedded Ethernet Interface 
5.1.1.1
RX3i 
RX3i CPE305, CPE310 and CPE330 CPUs provide one or more embedded Ethernet interfaces. If used, 
each interface connects to a Local Area Network (LAN). 
The corresponding RJ-45 Ethernet port(s) automatically sense the data rate on the attached LAN 
(1 Gbps, 100 Mbps or 10 Mbps), as well as the corresponding communication mode (half-duplex or 
full-duplex), and the corresponding cabling arrangement (straight through or crossover). Automatic 
detection greatly simplifies installation procedures. 
See RX3i CPU Features and Specifications or RX7i CPU Features and Specifications to determine the 
complete list of Internet protocols supported by each CPU.  
Some important protocols supported by all RX3i CPUs are: 
TCP/IP, which provides basic Internet capabilities; 
SRTP, which is proprietary and which provides the interface with the PME programming and 
configuration software and supports communications with certain control systems and 
supervisory computer layers in the factory; 
Modbus/TCP, which supports the Modbus messaging structure over the Internet. 
On the CPE305/CPE310 models, the same shared processor performs both Ethernet port processing 
and Controller logic processing.  
On the CPE330, the dual core CPU enables communication to be handled by one core while CPU logic 
and I/O scanning is handled by the second core. Furthermore, each LAN interface is controlled by a 
dedicated Network Interface Controller (NIC). As a result of these hardware advances, a higher level 
of processing power is provided in support of each LAN. This is especially important at higher data 
rates. It also offloads the handling of Ethernet-level activity from the processor core tasked with 
performing CPU logic and I/O scanning, permitting that core to run more efficiently. 
Each interface on a LAN must have a unique IP Address and also a non-overlapping IP subnet. This is 
configured in PME. Care must be taken to survey the entire connected network architecture in order 
to tabulate the IP addresses and IP subnets already in use, both on the local networks and on any of 
its routed subnets connected with a gateway. Never assign a conflicting IP Address or configure 
duplicate IP subnets.  
Chapter 5. Communications 
GFK-2222W 
August 2015 
119 
The following examples would be problematic: 
Problem example #1: 
Figure 23: CPE330 Overlapping Local IP Subnet Example 
The issue demonstrated in Figure 23 is that requests entering one CPE330 interface can be routed 
out the other interface since both CPE330 Ethernet ports have been configured to be on the same 
network (255.255.0.0) but are physically connected to separate networks. Avoid this by assigning 
non-overlapping Subnets. 
Problem example #2:  
A user wishes to communicate through a routed network to an RX3i CPU with multiple network 
interfaces (CPE330, in this example). This remote IP device is configured with the following IP 
parameters: 
IP  
192.168.0.5 
Subnet Mask  255.255.255.0 
Gateway  
192.168.0.250 
LAN1 and LAN2 on the CPE330 are initially configured with following problematic IP parameters: 
LAN1 
LAN2 
IP  
10.10.0.1 
192.168.0.1 
Subnet Mask   255.255.255.0  255.255.255.0 
Gateway  
10.10.0.249 
0.0.0.0 
The user intends to communicate between the remote device and CPE330 LAN1 (Figure 24). 
IP Address routing allows the CPE330 to receive the remote IP requests through the respective 
gateways (192.168.0.250 for the remote node and 10.10.0.249 for CPE330 LAN1). However, since 
CPE330 LAN2 shares the same IP subnet as the remote network (192.168.0.x), responses may be 
routed to the local 192.168.0.x network rather than to the remote network (Figure 25). 
The duplicate IP subnet in the example must be eliminated. One way to do this is simply change the 
IP Address assigned to CPE330 LAN2 from 192.168.0.1 to 192.168.1.1 thereby creating a non-
overlapping 192.168.1.x network. In short, consider the totality of the network when assigning 
IP subnets and IP Addresses. 
Chapter 5. Communications 
120 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
Figure 24: Expected Response Path 
Figure 25: Actual Response Path 
Chapter 5. Communications 
GFK-2222W 
August 2015 
121 
5.1.1.2
RX7i 
RX7i CPUs have an embedded Ethernet interface that provides TCP/IP communications with 
programming software and other control systems. These communications use the proprietary SRTP 
protocol and the standard Modbus/TCP protocol over a four-layer TCP/IP (Internet) stack. The 
Ethernet interface also supports Ethernet Global Data protocol using UDP (User Datagram Protocol).  
The embedded Ethernet interface has two RJ-45 Ethernet ports. Either or both of these ports may be 
attached to other Ethernet devices. Each port automatically senses the data rate (10 Mbps or 
100 Mbps), communication mode (half-duplex or full-duplex), and cabling arrangement (straight 
through or crossover) of the attached link. 
Caution 
The two ports on the Ethernet Interface must not be 
connected, directly or indirectly to the same device. The hub or 
switch connections in an Ethernet network must form a tree; 
otherwise duplication of packets may result.  