Chapter 5. Communications 
132 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
5.3.2
Programmable Coprocessor Module (PCM) 
PACSystems RX7i CPUs with versions 1.50 and higher support IC697PCM711modules with firmware 
versions 4.05 and higher. You must ensure that you are using a valid version of the PCM firmware 
because the CPU cannot check the PCM’s firmware version. (The module’s firmware version can be 
found on a label attached to the EEPROM.) 
PACSystems does not support the following with an IC697PCM711: 
Connecting the programming software to the CPU through the serial ports on the PCM711. 
Access to Symbolic variables. 
WAIT mode COMMREQs. 
The following C functions are not supported: 
chk_genius_bus 
chk_genius_device 
get_cpu_type_rev 
get_memtype_sizes 
get_one_rackfault 
get_rack_slot_faults 
The C function write_dev will not write to read only references (%S references, transition bits, and 
override bits). If this is attempted, the call will fail at run time and return an error code.  
The following restrictions apply when using the IC697PCM711 with PACSystems: 
Access to %W references is partially supported. Only offsets 0—65535 of %W can be accessed 
via the PCM. 
The Program Name is currently always LDPROG1 for PACSystems. 
In case of ERROR NACK, the Control Program number, privilege level and other piggyback status 
data will be set to 0. 
If an application program running on the PCM accesses the VME bus, the VME addresses being 
used by that program must be in agreement with the PACSystems RX7i VME address 
assignments. The PACSystems RX7i VME address assignments are described in the PACSystems 
RX7i User’s Guide to Integration of VME Modules, GFK-2235. 
PACSystems CPUs return the major/minor type of the Series 90-70 CPX935 (major type 12, minor 
type 35) to the PCM scratch pad memory when communicating with a PCM. 
If your RX7i application program needs to access the PCM’s dual port memory, use the BUS READ 
and WRITE functions. When accessing the PCM, set the Region parameter on the function block 
to 1. (For the PCM, region 1 is predefined to be the module's entire dual port memory.) 
Note:  For details on operation of the IC697PCM711, refer to Series 90 Programmable Coprocessor 
Module and Support Software, GFK-0255. 
How to add image to pdf document - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
how to add a picture to a pdf document; adding an image to a pdf file
How to add image to pdf document - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
add image to pdf acrobat reader; add a jpg to a pdf
Chapter 5. Communications 
GFK-2222W 
August 2015 
133 
5.3.3
DLAN/DLAN+ (Drives Local Area Network) Interface 
PACSystems RX7i CPUs with versions 1.50 and higher support IC697BEM763 modules with firmware 
versions 3.00 and higher. You must ensure that you are using a valid version of the PCM firmware 
because the CPU cannot check the DLAN’s firmware version. (The module’s firmware version can be 
found on a label attached to the EEPROM.)  
If your RX7i application program needs to access the DLAN’s dual port memory, use the BUS READ 
and WRITE functions. When accessing a DLAN module, set the Region parameter on the function 
block to 1. (For the DLAN module, region 1 is predefined to be the module's entire dual port memory.) 
Note:  The DLAN Interface module is a specialty module with limited availability. If you have a DLAN 
system, refer to the Series 90-70 DLAN/DLAN+ Interface Module User’s Manual, GFK-0729, for 
details. 
C# PDF Password Library: add, remove, edit PDF file password in C#
in C#.NET framework. Support to add password to PDF document online or in C#.NET WinForms for PDF file protection. Able to create a
add photo to pdf file; pdf insert image
C# PDF Image Extract Library: Select, copy, paste PDF images in C#
Get image information, such as its location, zonal information, metadata, and so on. Able to edit, add, delete, move, and output PDF document image.
adding image to pdf form; add jpg to pdf preview
Chapter 5. Communications 
134 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
VB.NET PDF Image Extract Library: Select, copy, paste PDF images
More detailed functions are listed below. DLLs for PDF Image Extraction in VB.NET. Add necessary references: VB.NET: Extract All Images from PDF Document.
adding a jpg to a pdf; adding a jpeg to a pdf
VB.NET PDF Password Library: add, remove, edit PDF file password
allowed. passwordSetting.IsCopy = True ' Allow to assemble document. passwordSetting.IsAssemble = True ' Add password to PDF file.
adding images to pdf; attach image to pdf form
GFK-2222W 
August 2015 
135 
Chapter 6
Serial I/O, SNP & RTU Protocols 
This chapter discusses the following topics related to communications on CPU serial ports COM1 and 
COM2: 
 Configuring Serial Ports Using COMMREQ Function 65520
 Serial I/O Protocol
 RTU Slave Protocol
 SNP Slave Protocol
Details of the RTU and SNP protocol are described in the Series 90 PLC Serial Communications User’s 
Manual, GFK-0582. 
C# Create PDF from images Library to convert Jpeg, png images to
List<Bitmap> images = new List<Bitmap>(); images.Add(new Bitmap(Program.RootPath + "\\" 1.gif")); / Build a PDF document with GIF image.
how to add image to pdf form; add a picture to a pdf file
C# PDF: How to Create PDF Document Viewer in C#.NET with
The PDF document manipulating add-on from RasterEdge DocImage SDK Support thumbnail image and outline preview for quick PDF document page navigation;
add image field to pdf form; how to add an image to a pdf file
Chapter 6. Serial I/O, SNP & RTU Protocols 
136 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
6.1
Configuring Serial Ports Using COMMREQ Function 65520 
The Serial Port Setup COMMREQ function 65520 (FFF0 hex) may be used to activate a serial 
communication protocol for a serial port, overriding the protocol that was specified in the port 
settings of the CPU configuration. The COMMREQ installed protocol remains active as long as the CPU 
is in RUN Mode. When the CPU is STOPped, the COMMREQ installed protocol is removed, and the 
protocol settings from the CPU configuration are reactivated. 
The COMMREQ requires that all its command data be placed in the correct order (in a command 
block) in the CPU memory before it is executed. The COMMREQ should be executed by a contact of a 
one-shot coil to prevent sending the data multiple times. For details on the operands and command 
block format used by the COMMREQ function, refer to PACSystems RX7i and RX3i CPU Programmer’s 
Reference Manual, GFK-2950 Chapter 4. 
The COMMREQ uses the following TASKs to specify the port for which the operation is intended: 
task 19 for COM1  
task 20 for COM2 
Note:  Because address offsets are stored in a 16-bit word field, the full range of %W memory type 
cannot be used with COMMREQs. 
6.1.1
COMMREQ Function Example 
In the example, when %M0021 is ON, a Command Block located starting at %R0032 is sent to COM2 
(communications task 20) of the CPU (rack 0, slot 0). If an error occurs processing the COMMREQ, 
%Q0110 is set.  
6.1.2
Timing  
If a port configuration COMMREQ is sent to a serial port that currently has an SNP master (for 
example, the programmer) connected to it, the COMMREQ function returns an error code to the 
COMMREQ status word. 
6.1.3
Sending Another COMMREQ to the Same Port 
After sending a COMMREQ to configure a serial port, the application program should monitor the 
COMMREQ status word to determine when it can begin sending protocol specific COMMREQs to that 
port. It is recommended that the application clear the COMMREQ status word prior to issuing the 
configuration change. The status word will be set to a nonzero value when the request has been 
processed. 
C# PDF Sticky Note Library: add, delete, update PDF note in C#.net
PDF document processing tool, which can perform various PDF annotation works in easy ways. Using this .NET PDF annotation control, C# developers can add a
how to add a photo to a pdf document; add image to pdf file
DocImage SDK for .NET: Web Document Image Viewer Online Demo
on the client side without additional add-ins and Microsoft PowerPoint: PPTX, PPS, PPSX; PDF: Portable Document Format; TIFF: Tagged Image File Format;
how to add image to pdf reader; add jpg to pdf online
Chapter 6. Serial I/O, SNP & RTU Protocols 
GFK-2222W 
August 2015 
137 
6.1.4
Invalid Port Configuration Combinations 
The Machine Edition programming software safeguards against the download of some hardware 
configurations that would prevent the programmer from communicating serially with the CPU. In a 
system that does not have an embedded Ethernet module, if a rack-based Ethernet is not present, a 
serial connection is required for programmer communications. 
For CPE305/CPE310 CPUs, which have an embedded Ethernet port that, when configured, is available 
for programmer communications, the safeguards on serial port configurations are still enforced. 
6.1.5
COMMREQ Command Block Parameter Values 
The following table lists common parameter values that are used within the COMMREQ command 
blocks for configuring a serial port. All values are in decimal. 
Parameter 
Values 
Protocol Selector 
1 = SNP 
3 = RTU 
5 = Serial I/O 
7 = Message Mode 
Data Rate 
0 = 300 
1 = 600 
2 = 1200 
3 = 2400 
4 = 4800 
5 = 9600 
6 = 19200 
7 = 38400 
8 = 57600 
9 = 115200 
Parity 
0 = None 
1 = Odd 
2 = Even 
Flow Control 
0 = Hardware [RTS / CTS] 
1 = None 
2 = Software [XON / XOFF]  (Serial I/O only) 
Bits Per Character 
0 = 7 bits 
1 = 8 bits 
Stop Bits 
0 = 1 stop bit 
1 = 2 stop bits 
Duplex Mode 
0 = 2-wire 
1 = 4-wire 
2 = 4-wire transmitter always on 
Turnaround Delay (SNP only) 
0 = none 
1 = 10ms 
2 = 100ms 
3 = 500ms 
Timeout (SNP only) 
0 = Long  (8 sec) 
1 = Medium  (2 sec) 
2 = Short  (500ms) 
3 = None (200ms) 
Chapter 6. Serial I/O, SNP & RTU Protocols 
138 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
6.1.6
Example COMMREQ Command Blocks for Serial Port Setup function 
The following COMMREQ command blocks provide examples for configuring the various protocols. All 
values are in decimal unless followed by an H indicating hexadecimal. 
Note that an example is not provided for Message Mode, but it can be setup with a command block 
similar to the one for Serial I/O, with a value of 7 for the protocol selector. 
Example COMMREQ Command Block for Configuring SNP Protocol 
Values 
Meaning 
Address 
16 
Data Block Length 
Address + 1 
0 = No Wait (WAIT mode not supported) 
WAIT/NOWAIT Flag 
Address + 2 
0008 = %R, register memory 
Status Word Pointer Memory 
Type 
Address + 3 
Zero-based number that gives the address of the COMMREQ 
status word (for example, a value of 99 gives an address of 
100 for the status word) 
Status Word Pointer Offset 
Address + 4 
not used 
Idle Timeout Value 
Address + 5 
not used 
Maximum Communication 
Time 
Address + 6 
FFF0H 
Command Word (serial port 
setup) 
Address + 7 
1 = SNP 
Protocol  
Address + 8 
0 = Slave 
Port Mode 
Address + 9 
See COMMREQ Command Block Parameter Values. 
Data Rate 
Address + 10  0 = None, 1 = Odd, 2 = Even 
Parity 
Address + 11  not used  (SNP always chooses NONE by default) 
Flow Control 
Address + 12  0 = None, 1 = 10ms, 2 = 100ms, 3 = 500ms 
Turnaround Delay  
Address + 13  0 = Long, 1 = Medium, 2 = Short, 3 = None 
Timeout  
Address + 14  not used  (SNP always chooses 8 bits by default)  
Bits Per Character 
Address + 15  0 = 1 Stop Bit, 1 = 2 Stop bits 
Stop Bits   
Address + 16 
not used 
Interface 
Address + 17 
not used  (SNP always chooses 4-wire mode by default) 
Duplex Mode 
Address + 18 
user-provided 37 
Device identifier bytes 1 and 2 
Address + 19 
user-provided 37 
Device identifier bytes 3 and 4 
Address + 20  user-provided 
37
Device identifier bytes 5 and 6 
Address + 21 
user-provided 37 
Device identifier bytes 7 and 8 
37
The device identifier for SNP Slave ports is packed into words with the least significant character in the least significant 
byte of the word. For example, if the first two characters are “A” and “B,” the Address + 18 will contain the hex value 4241. 
Chapter 6. Serial I/O, SNP & RTU Protocols 
GFK-2222W 
August 2015 
139 
Example COMMREQ Data Block for Configuring RTU Protocol 
Values 
Meaning 
Address 
13, or 17 
Data Block Length 
Address + 1 
0 = No Wait (WAIT mode not supported) 
WAIT/NOWAIT Flag 
Address + 2 
0008 = %R, register memory 
Status Word Pointer Memory Type 
Address + 3 
Zero-based number that gives the address of the COMMREQ 
status word (for example, a value of 99 gives an address of 
100 for the status word) 
Status Word Pointer Offset 
Address + 4 
not used 
Idle Timeout Value 
Address + 5 
not used 
Maximum Communication Time 
Address + 6  FFF0H 
Command Word (serial port setup) 
Address + 7  3 = RTU 
Protocol  
Address + 8  0 = Slave 
Port Mode 
Address + 9  See COMMREQ Command Block Parameter Values. 
Data Rate  
Address + 10  0 = None, 1 = Odd, 2 = Even 
Parity 
Address + 11  0 = Hardware, 1 = None 
Flow Control 
Address + 12  not used 
Turnaround delay 
Address + 13  not used 
Timeout 
Address + 14  not used  (RTU always chooses 8 bits by default) 
Bits per Character 
Address + 15  not used  (RTU always chooses 1 stop bit by default) 
Stop Bits 
Address + 16 
not used 
Interface 
Address + 17 
0 = 2-wire, 1 = 4-wire, 2 = 4-wire transmitter always on 
Duplex Mode 
Address + 18 
Station Address (1-247) 
Device Identifier 
Address + 19 
Count of 100 µs units  (0 = 3.5 character times) 
End-of-frame timeout 38 
Address + 20  not used 
Address + 21  not used 
Address + 22  Count of 10 ms units  (range 0-255) 
Receive-to-transmit delay 
38
38
The End-of-frame timeout and Receive-to-transmit delay values were added in Release 6.70 for the RX3i. They are 
discussed in the RTU Slave Protocol section. 
Chapter 6. Serial I/O, SNP & RTU Protocols 
140 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
Example COMMREQ Data Block for Configuring Serial I/O Protocol 
Values 
Meaning 
Address 
12 
Data Block Length 
Address + 1 
0 = No Wait (WAIT mode not supported) 
WAIT/NOWAIT Flag 
Address + 2 
0008 = %R, register memory 
Status Word Pointer Memory 
Type 
Address + 3  Zero-based number that gives the address of the COMMREQ 
status word (for example, a value of 99 gives an address of 
100 for the status word) 
Status Word Pointer Offset 
Address + 4  not used 
Idle Timeout Value 
Address + 5  not used 
Maximum Communication Time 
Address + 6  FFF0H 
Command Word (serial port 
setup) 
Address + 7 
5 = Serial I/O 
Protocol 
Address + 8 
not used 
Port Mode 
Address + 9 
See COMMREQ Command Block Parameter Values. 
Data Rate  
Address + 10  0 = None, 1 = Odd, 2 = Even 
Parity 
Address + 11  0 = Hardware, 1 = None, 2 = Software 
Flow Control 
Address + 12  not used 
Turnaround Delay  
Address + 13  not used 
Timeout  
Address + 14  0=7 bits, 1=8 bits 
Bits per Character 
Address + 15  0 = 1 stop bit, 1 = 2 stop bits 
Stop Bits 
Address + 16  not used 
Interface 
Address + 17 
0 = 2-wire, 1 = 4-wire, 2 = 4-wire transmitter always on 
Duplex Mode 
Chapter 6. Serial I/O, SNP & RTU Protocols 
GFK-2222W 
August 2015 
141 
6.2
Serial I/O Protocol 
Serial I/O protocol is a communication protocol that is driven entirely by the application program. 
Serial I/O protocol is active only when the CPU is in RUN Mode, since it is driven completely by 
COMMREQ functions in the application program. Those COMMREQ functions are described in detail 
within this section. 
When the CPU is stopped, a port configured for Serial I/O protocol will revert to a STOP Mode protocol 
as specified in the port settings of the CPU configuration. If a STOP Mode protocol was not specified, 
RTU slave protocol is used by default. 
6.2.1
Calling Serial I/O COMMREQs from the CPU Sweep 
Implementing a serial protocol using Serial I/O COMMREQs may be restricted by the sweep time. For 
example, if the protocol requires that a reply to a certain message from the remote device be 
initiated within 5ms of receiving the message, this method may not be successful if the sweep time is 
5ms or longer, since timely response is not guaranteed. 
6.2.2
Compatibility 
The COMMREQ function blocks supported by Serial I/O are not supported by other currently existing 
protocols (such as SNP slave and RTU slave). Errors are returned if they are attempted for a port 
configured for one of those protocols. 
6.2.3
Status Word for Serial I/O COMMREQs 
A value of 1 is returned in the COMMREQ status word upon successful completion of the COMMREQ. 
Any other value returned is an error code where the low byte is a major error code and the high byte 
is a minor error code.  
Major Error Code  Description 
01 (01h) 
Successful Completion 
(this is the expected completion value in the COMMREQ status word). 
12 (0Ch) 
Local error —Error processing a local command. 
The minor error code identifies the specific error. 
02 (02h) 
COMMREQ command is not supported. 
06 (06h)  Invalid CPU memory type specified. 
07 (07h) 
Invalid CPU memory offset specified. 
08 (08h)  Unable to access CPU memory. 
12 (0Ch)  COMMREQ data block length too small. 
14 (0Eh)  COMMREQ data is invalid. 
15 (0Fh) 
Could not allocate system resources to complete COMMREQ. 