Chapter 6. Serial I/O, SNP & RTU Protocols 
152 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
6.2.12
Autodial Function (4400) 
This feature allows the CPU to automatically dial a modem and send a specified byte string.  
To implement this feature, the port must be configured for Serial I/O. After the autodial function is 
executed and the modem has established a connection, other serial I/O functions (Write bytes, Set 
Up Input Buffer, Flush Input buffer, Read port status, Write port control, Read bytes, Read String, and 
Cancel Operation) can be used. 
Example 
Pager enunciation can be implemented by three commands, requiring three COMMREQ command 
blocks: 
Autodial: 
04400 (1130h) 
Dials the modem.  
Write Bytes: 
04401 (1131h) 
Specifies an ASCII string, from 1 to 250 bytes in length, to send from the serial port. 
Autodial: 
04400 (1130h) 
It is the responsibility of the application program to hang up the phone connection. 
This is accomplished by reissuing the autodial command and sending the hang up 
command string. 
6.2.12.2
Autodial Command Block 
The Autodial command automatically transmits an Escape sequence that follows the Hayes 
convention. If you are using a modem that does not support the Hayes convention, you may be able 
to use the Write Bytes command to dial the modem. 
Examples of commonly used command strings for Hayes-compatible modems are listed below:  
Command String 
Length 
Function 
ATDP15035559999<CR>  16 (10h) 
Pulse dial the number 1-503-555-9999 
ATDT15035559999<CR>  16 (10h) 
Tone dial the number 1-503-555-9999 
ATDT9,15035559999<CR>  18 (12h) 
Tone dial using outside line with pause 
ATH0<CR> 
5 (05h) 
Hang up the phone 
ATZ <CR> 
4 (04h) 
Restore modem configuration to internally saved values 
Add image to pdf preview - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
adding an image to a pdf form; add image in pdf using java
Add image to pdf preview - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
adding images to pdf forms; how to add image to pdf file
Chapter 6. Serial I/O, SNP & RTU Protocols 
GFK-2222W 
August 2015 
153 
Sample Autodial Command Block 
This COMMREQ command block dials the number 234-5678 using a Hayes-compatible modem. 
Word  Definition 
Values 
0009h 
CUSTOM data block length (includes command string) 
0000h 
NOWAIT mode 
0008h 
Status word memory type (%R) 
0000h 
Status word address minus 1 (Register 1) 
0000h 
not used 
0000h 
not used 
04400 (1130h)  Autodial command number 
00030 (001Eh)  Modem response timeout (30 seconds) 
0012 (000Ch)  Number of bytes in command string 
10 
5441h 
A (41h), T (54h) 
11 
5444h 
D (44h), T (54h) 
12 
3332h 
Phone number: 2 (32h), 3 (33h) 
13 
3534h 
4 (34h), 5 (35h) 
14 
3736h 
6 (36h), 7 (37h) 
15 
0D38h 
8 (38h) <CR> (0Dh) 
C# WinForms Viewer: Load, View, Convert, Annotate and Edit PDF
Convert PDF to Tiff image (.tif, .tiff). • Convert PDF to HTML (.htm, .html). PDF Annotation. • Add sticky notes to PDF document in preview.
how to add an image to a pdf; how to add image to pdf document
C# WPF Viewer: Load, View, Convert, Annotate and Edit PDF
PDF to Tiff image (.tif, .tiff). • Convert PDF to HTML (.htm, .html). PDF Annotation. • Add sticky notes to PDF document. • Highlight PDF text in preview.
add jpg to pdf; add image pdf document
Chapter 6. Serial I/O, SNP & RTU Protocols 
154 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
6.2.13
Write Bytes Function (4401) 
This operation can be used to transmit one or more characters to the remote device through the 
specified serial port. The character(s) to be transmitted must be in a word reference memory. They 
should not be changed until the operation is complete.  
Up to 250 characters can be transmitted with a single invocation of this operation. The status of the 
operation is not complete until all of the characters have been transmitted or until a timeout occurs 
(for example, if hardware flow control is being used and the remote device never enables the 
transmission). 
Example Command Block for the Write Bytes Function 
Value 
(decimal) 
Value 
(hexadecimal) 
Meaning 
Address 
0006 
0006 
Data block length (includes characters to send) 
Address +1  0000 
0000 
NOWAIT mode 
Address +2  0008 
0008 
Status word memory type (%R) 
Address +3  0000 
0000 
Status word address minus 1 (%R0001) 
Address +4 
0000 
0000 
Not used 
Address +5 
0000 
0000 
Not used 
Address +6 
4401 
1131 
Write bytes command 
Address +7  0030 
001E 
Transmit time-out (30 seconds). See note below. 
Address +8  0005 
0005 
Number of bytes to write 
Address +9  25960 
6568 
‘h’ (68h), ‘e’ (65h) 
Address +10  27756 
6C6C 
‘l’ (6Ch), ‘l’ (6Ch) 
Address +11 
0111 
006F 
‘o’ (6Fh) 
Although printable ASCII characters are used in this example, there is no restriction on the values of 
the characters that can be transmitted. 
6.2.13.2
Operating Notes 
Specifying zero as the Transmit time-out sets the time-out value to the amount of time actually 
needed to transmit the data, plus 4 seconds. 
Caution 
If an Initialize Port (4300) COMMEQ is sent or a Cancel 
Operation (4399) COMMREQ is sent in either Cancel All or 
Cancel Write mode while this COMMREQ is transmitting a 
string from a serial port, transmission is halted. The position 
within the string where the transmission is halted is 
indeterminate. In addition, the final character received by the 
device the CPU is sending to is also indeterminate. 
How to C#: Preview Document Content Using XDoc.Word
C# DLLs for Word File Preview. Add references: Get Preview From File. You may get document preview image from an existing Word file in C#.net.
add picture to pdf reader; acrobat insert image into pdf
How to C#: Preview Document Content Using XDoc.PowerPoint
Add necessary XDoc.PowerPoint DLL libraries into your created C# application as You may get document preview image from an existing PowerPoint file in C#.net.
add image to pdf file acrobat; adding image to pdf in preview
Chapter 6. Serial I/O, SNP & RTU Protocols 
GFK-2222W 
August 2015 
155 
6.2.14
Read Bytes Function (4402)  
This function causes one or more characters to be read from the specified port. The characters are 
read from the internal input buffer and placed in the specified input data area. The function returns 
both the number of characters retrieved and the number of unprocessed characters still in the input 
buffer. If zero characters of input are requested, only the number of unprocessed characters in the 
input buffer is returned.  
If insufficient characters are available to satisfy the request and a non-zero value is specified for the 
number of characters to read, the status of the operation is not complete until either sufficient 
characters have been received or the time-out interval expires. In either of those conditions, the port 
status indicates the reason for completion of the read operation. The status word is not updated until 
the read operation is complete (either due to timeout or when all the data has been received). 
If the time-out interval is set to zero, the COMMREQ remains pending until it has received the 
requested amount of data, or until it is cancelled. 
If this COMMREQ fails for any reason, no data is returned to the input data area. Any data that has 
not been read from the internal input buffer remains and it can be retrieved with a subsequent read 
request. 
Example Command Block for the Read Bytes Function 
Value 
(decimal) 
Value 
(hexadecimal) 
Meaning 
Address 
0005 
0005 
Data block length 
Address +1  0000 
0000 
NOWAIT mode 
Address +2  0008 
0008 
Status word memory type (%R) 
Address +3 
0000 
0000 
Status word address minus 1 (%R0001) 
Address +4 
0000 
0000 
Not used 
Address +5 
0000 
0000 
Not used 
Address +6  4402 
1132 
Read bytes command 
Address +7  0030 
001E 
Read time-out (30 seconds) 
Address +8  0005 
0005 
Number of bytes to read 
Address +9  0008 
0008 
Input data memory type (%R).  
Address +10 
0100 
0064 
Input data memory address (%R0100) 
VB.NET PDF File Compress Library: Compress reduce PDF size in vb.
enables compressing and decompressing in preview in ASP.NET to reduce or minimize original PDF document size Reduce image resources: Since images are usually or
add image to pdf preview; add image to pdf in preview
How to C#: Preview Document Content Using XDoc.excel
Add necessary references: RasterEdge.Imaging.Basic.dll. Get Preview From File. You may get document preview image from an existing Excel file in C#.net.
add signature image to pdf; how to add image to pdf
Chapter 6. Serial I/O, SNP & RTU Protocols 
156 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
6.2.14.2
Return Data Format for the Read Bytes Function 
The return data consists of the number of characters actually read, the number of characters still 
available in the input buffer after the read is complete (if any), and the actual input characters.  
Address 
Number of characters actually read 
Address + 1  Number of characters still available in the input buffer, if any 
Address + 2  first two characters (first character is in the low byte) 
Address + 3  third and fourth characters (third character is in the low byte) 
Address + n 
subsequent characters 
6.2.14.3
Operating Notes for Read Bytes 
If the input data memory type parameter is specified to be a word memory type, and if an odd 
number of bytes is actually received, then the high byte of the last word to be written with the 
received data is left unchanged. 
As data is received from the serial port it is placed in the internal input buffer. If the buffer becomes 
full, then any additional data received from the serial port is discarded and the Overflow Error bit in 
the Port Status word (See Read Port Status Function) is set. 
How to C#: Set Image Thumbnail in C#.NET
VB.NET How-to, VB.NET PDF, VB.NET Word following steps below, you can create an image viewer WinForm Open or create a new WinForms application, add necessary dll
acrobat insert image in pdf; add image to pdf
C# PDF remove image library: remove, delete images from PDF in C#.
Generally speaking, using well-designed APIs, C# developers can do following things. Remove Image from PDF Page Using C#. Add necessary references:
add picture to pdf form; adding jpg to pdf
Chapter 6. Serial I/O, SNP & RTU Protocols 
GFK-2222W 
August 2015 
157 
6.2.15
Read String Function (4403) 
This function causes characters to be read from the specified port until a specified terminating 
character is received. The characters are read from the internal input buffer and placed in the 
specified input data area. 
The function returns both the number of characters retrieved and the number of unprocessed 
characters still in the input buffer. If zero characters of input are requested, only the number of 
unprocessed characters in the input buffer is returned.  
If the terminating character is not in the input buffer, the status of the operation is not complete until 
either the terminating character has been received or the time-out interval expires. In either of those 
conditions, the port status indicates the reason for completion of the read operation. 
If the time-out interval is set to zero, the COMMREQ remains pending until it has received the 
requested string, terminated by the specified end character. 
If this COMMREQ fails for any reason, no data is returned to the input data area. Any data that has 
not been read from the internal input buffer remains, and it can be retrieved with a subsequent read 
request. 
Example Command Block for the Read String Function 
Value 
(decimal) 
Value 
(hexadecimal) 
Meaning 
Address 
0005 
0005 
Data block length 
Address +1 
0000 
0000 
NOWAIT mode 
Address +2 
0008 
0008 
Status word memory type (%R) 
Address +3 
0000 
0000 
Status word address minus 1 (%R0001) 
Address +4 
0000 
0000 
Not used 
Address +5 
0000 
0000 
Not used 
Address +6 
4403 
1133 
Read string command 
Address +7 
0030 
001E 
Read time-out (30 seconds) 
Address +8 
0013 
000D 
Terminating character (carriage return):  must be 
between 0 and 255 (0xFF), inclusive 
Address +9 
0008 
0008 
Input data memory type (%R) 
Address +10 
0100 
0064 
Input data memory address (%R0100) 
Chapter 6. Serial I/O, SNP & RTU Protocols 
158 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
6.2.15.2
Return Data Format for the Read String Function 
The return data consists of the number of characters actually read, the number of characters still 
available in the input buffer after the read is complete (if any), and the actual input characters: 
Address 
Number of characters actually read 
Address + 1  Number of characters still available in the input buffer, if any 
Address + 2  first two characters (first character is in the low byte) 
Address + 3  third and fourth characters (third character is in the low byte) 
Address + n 
subsequent characters 
6.2.15.3
Operating Notes for Read String 
If the input data memory type parameter is specified to be a word memory type, and if an odd 
number of bytes is actually received, then the high byte of the last word to be written with the 
received data is left unchanged. 
As data is received from the serial port it is placed in the internal input buffer. If the buffer becomes 
full, then any additional data received from the serial port is discarded and the Overflow Error bit in 
the Port Status word (See Read Port Status Function) is set. 
Chapter 6. Serial I/O, SNP & RTU Protocols 
GFK-2222W 
August 2015 
159 
6.3
RTU Slave Protocol 
RTU protocol is a query-response protocol used for communication between the RTU device and a 
host computer, which is capable of communicating using RTU protocol. The host computer is the 
master device and it transmits a query to a RTU slave, which responds to the master. The RTU slave 
device cannot query; it can only respond to the master. A PACSystems CPU can only function as an 
RTU slave. 
The RTU data transferred consists of 8-bit binary characters with an optional parity bit. No control 
characters are added to the data block; however, an error check (Cyclic Redundancy Check) is 
included as the final field of each query and response to ensure accurate transmission of data. 
Note:  You should avoid using station address 1 for any other Modbus slave in a PACSystems control 
system because the default station address for the PACSystems CPU is 1. The CPU uses the 
default address in two situations: 
1.
If you power up without a configuration, the default station address of 1 is used. 
2.
When the Port Mode parameter is set to Message Mode, and Modbus becomes the 
protocol in STOP Mode, the station address defaults to 1, unless you specify a STOP Mode 
for the serial port in the CPU configuration, and then change the station address to be 
used for STOP Mode. 
In either of these situations, if you have a slave configured with a station address of 1, 
confusion may result when the PACSystems CPU responds to requests intended for that 
slave. 
Chapter 6. Serial I/O, SNP & RTU Protocols 
160 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
6.3.1
Message Format 
The general formats for RTU message transfers are shown below: 
6.3.1.1
RTU Message Transfers 
Query Message
Master
Slave
Master
Slave
Broadcast Message
Response
(No Response)
Slave Turn-around Time
Query Transaction
Broadcast Transaction
Figure 26: RTU Message Transactions 
The master device begins a data transfer by sending a query or broadcast request message. A slave 
completes that data transfer by sending a response message if the master sent a query message 
addressed to it. No response message is sent when the master sends a broadcast request. 
6.3.1.2
RTU Slave Turnaround Time 
The time between the end of a query and the beginning of the response to that query is called the 
slave turnaround time. The turnaround time of a PACSystems slave depends on the Controller 
Communications Window time and the sweep time of the PACSystems. RTU requests are processed 
only in the Controller Communications Window. In Normal sweep mode, the Controller 
Communications Window occurs once per sweep. Because the sweep time on PACSystems can be 
up to 2.5 seconds, the time to process an RTU request could be up to 2.5 seconds. Another factor is 
the Controller Communications Window time allowed in Hardware Configuration. If you configure a 
very small Controller Communications Window, the RTU request may not be completed in one sweep, 
causing RTU processing to require multiple sweeps. For details on CPU window modes, refer to 
Window Modes in Chapter 4. 
6.3.1.3
Receive-to-Transmit Delay 
Part of the RTU Slave Turnaround time is the receive-to-transmit delay. The RTU driver inserts this 
delay after a request from the master has been received, and before the response to the master is 
sent. Starting with Release 6.70 for the RX3i, the receive-to-transmit delay can be configured with the 
Serial Port Setup COMMREQ function 65520. The timeout is specified in units of 10 ms, with a range of 
0–255 units (maximum delay is 2.55 seconds). If the specified time is less than 3.5 character times, 
then the delay is set to 3.5 character times. 
Chapter 6. Serial I/O, SNP & RTU Protocols 
GFK-2222W 
August 2015 
161 
6.3.1.4
Message Types 
The RTU protocol has four message types: query, normal response, error response, and broadcast. 
Query 
The master sends a message addressed to a single slave. 
Normal Response 
After the slave performs the function requested by the query, it sends back a normal response for 
that function. This indicates that the request was successful. 
Error Response 
The slave receives the query, but cannot perform the requested function. The slave sends back an 
error response that indicates the reason the request could not be processed. (No error message will 
be sent for certain types of errors. For more information refer to Communication Errors below.) 
Broadcast 
The master sends a message addressed to all of the slaves by using address 0. All slaves that receive 
the broadcast message perform the requested function. This transaction is ended by a time-out 
within the master. 