Chapter 6. Serial I/O, SNP & RTU Protocols 
172 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
6.3.3.4
Message (04): Read Analog Inputs 
Format: 
Address
Starting
Analog Input 
No.
Number of
Analog 
Inputs 
Error
Check
Func
04 
Query
Hi
Hi
Lo
Lo
Address
Data
Error
Check
Func
04
Normal Response
Byte
Count
First 
Analog 
Input
No. 
Hi
Hi
Lo
Lo
Figure 32: RTU Read Analog Inputs Message Format 
Query: 
An Address of 0 is not allowed as this request cannot be a broadcast request. 
The function code is equal to 4. 
The Starting Analog Input Number is two bytes in length. The Starting Analog Input Number may 
be any value less than the highest analog input number available in the attached CPU. It is equal 
to one less than the number of the first analog input returned in the normal response to this 
request. 
The Number Of Analog Inputs value is two bytes in length. It must contain a value from 1 to 125 
inclusive. The sum of the Starting Analog Input value and the Number Of Analog Inputs value 
must be less than or equal to the highest analog input number available in the at-attached CPU. 
The high order byte of the Starting Analog Input Number and Number of Analog Inputs fields is 
sent as the first byte in each of these fields. The low order byte is the second byte in each of these 
fields. 
Response: 
The Byte Count is a binary number from 2 to 250 inclusive. It is the number of bytes in the normal 
response following the byte count and preceding the error check. Note that the Byte Count is 
equal to two times the number of analog inputs returned in the response. A maximum of 250 
bytes (125) analog inputs is set so that the entire response can fit into one 256 byte data block. 
The analog inputs are returned in the Data field in order of number with the lowest number 
analog input in the first two bytes and the highest number analog input in the last two bytes of 
the Data field. The number of the First Analog Input in the Data field is equal to the Starting 
analog input number plus one. The high order byte is sent before the low order byte of each 
analog input. 
Add image to pdf java - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
add jpeg signature to pdf; adding an image to a pdf
Add image to pdf java - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
add image to pdf reader; adding a png to a pdf
Chapter 6. Serial I/O, SNP & RTU Protocols 
GFK-2222W 
August 2015 
173 
6.3.3.5
Message (05): Force Single Output 
Format: 
Address
Point
Number
Data
Error Check
Func
05
Query
Hi
Hi
Lo
Lo
Normal Response
00H 
Address
Point
Number
Data
Error Check
Func
05
00H 
Hi
Hi
Lo
Lo
Figure 33: RTU Force Single Output Message Format 
Query: 
An Address of 0 indicates a broadcast request. All slave stations process a broadcast re-quest 
and no response is sent. 
The function code is equal to 05. 
The Point Number field is two bytes in length. It may be any value less than the highest output 
point number available in the attached CPU. It is equal to one less than the number of the output 
point to be forced on or off. 
The first byte of the Data field is equal to either 0 or 255 (FFH). The output point specified in the 
Point Number field is to be forced off if the first Data field byte is equal to 0. It is to be forced on if 
the first Data field byte is equal to 255 (FFH). The second byte of the Data field is always equal to 
zero. 
Response: 
The normal response to a force single output query is identical to the query. 
Note:  The force single output request is not an output override command. The output specified in 
this request is ensured to be forced to the value specified only at the beginning of one sweep 
of the user logic. 
Java Imaging SDK Library: Document Image Scan, Process, PDF
imaging solutions, allowing developers to add document and Using RasterEdge Java Image SDK, developers can easily open Tiff, Jpeg2000, DICOM, JBIG2, PDF, MS Word
add an image to a pdf form; add image to pdf in preview
Zero Footprint AJAX Document Image Viewer| ASP.NET Imaging SDK
Image Annotating Draw and add various text or graphics annotations on Converting Transform, convert and save web document or image file to PDF or TIFF
adding images to a pdf document; how to add photo to pdf in preview
Chapter 6. Serial I/O, SNP & RTU Protocols 
174 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
6.3.3.6
Message (06): Preset Single Register 
Format: 
Address
Register
Number
Data
Error Check
Func
06
Query
Hi
Hi
Lo
Lo
Normal Response
Address
Register
Number
Data
Error Check
Func
06
Hi
Hi
Lo
Lo
Figure 34: RTU Preset Single Register Message Format 
Query: 
An Address 0 indicates a broadcast request. All slave stations process a broadcast request and 
no response is sent. 
The function code is equal to 06. 
The Register Number field is two bytes in length. It may be any value less than the highest 
register available in the attached CPU. It is equal to one less than the number of the register to be 
preset. 
The Data field is two bytes in length and contains the value that the register specified by the 
Register Number Field is to be preset to. The first byte in the Data field contains the high order 
byte of the preset value. The second byte in the Data field contains the low order byte. 
Response: 
The normal response to a preset single register query is identical to the query. 
DocImage SDK for .NET: HTML Viewer, View, Annotate, Convert, Print
in .NET, including Microsoft Word, Excel, PPT, PDF, Tiff, Dicom OCR .NET OCR Add-on provides you with powerful and of years before I found this .NET Image SDK.
add photo to pdf in preview; how to add a picture to a pdf file
.NET PDF SDK | Read & Processing PDF files
by this .NET Imaging PDF Reader Add-on. and metadata; Advanced document cleanup and image processing options provides royalty-free .NET Imaging PDF Reader SDK
add picture pdf; add photo to pdf reader
Chapter 6. Serial I/O, SNP & RTU Protocols 
GFK-2222W 
August 2015 
175 
6.3.3.7
Message (07): Read Exception Status 
Format: 
Address
Error Check
Func
07
Query
Normal Response
Address
Data
Error Check
Func
07
Figure 35: RTU Read Exception Status Message Format 
Query: 
This query is a short form of request for the purpose of reading the first eight output points. 
An Address of zero is not allowed as this cannot be a broadcast request. 
The function code is equal to 07. 
Response: 
The Data field of the normal response is one byte in length and contains the states of output 
points one through eight. The output states are packed in order of number with output point 
one’s state in the least significant bit and output point eight’s state in the most significant bit. 
.NET PDF Generator | Generate & Manipulate PDF files
RasterEdge .NET Image SDK - PDF Generator. swap and delete any pages in PDFs; Add metadata of a RasterEdge provides royalty-free .NET Imaging PDF Generator of
add image field to pdf form; how to add image to pdf file
Image Converter | Convert Image, Document Formats
Can be used as an add-on for .NET Imaging SDK; support, like ASCII, PDF, HTML, MS- Word, PDF/A Most Find image converters to suit your needs in this following
add picture to pdf; how to add an image to a pdf file
Chapter 6. Serial I/O, SNP & RTU Protocols 
176 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
6.3.3.8
Message (08): Loopback/Maintenance (General) 
Format: 
Address
Diagnostic
c
Code
Data
Error Check
Func
08
Query
0, 1, or 4 
DATA 1  DATA 1 
Address
Diagnostic
c
Code
Data
Error Check
Func
08
Normal Response
0, 1, or 4 
DATA 1  DATA 1 
Figure 36: RTU Loopback/Maintenance Message Format 
Query: 
The Function code is equal to 8. 
The Diagnostic Code is two bytes in length. The high order byte of the Diagnostic Code is the first 
byte sent in the Diagnostic Code field. The low order byte is the second byte sent. The 
loopback/maintenance command is defined only for Diagnostic Codes equal to 0, 1, or 4. All 
other Diagnostic Codes are reserved. 
The Data field is two bytes in length. The contents of the two Data bytes are defined by the value 
of the Diagnostic Code. 
.NET Annotation SDK| Annotate, Redact Images
object or group of annotation objects add-on; Save annotation into image files, separate annotation files NET Document Imaging SDK and Java Document Imaging
add photo to pdf; how to add image to pdf acrobat
.NET Barcode Generate SDK| Generate Barcodes
Support QR Code, Data Matrix, PDF-417; Seamless integrate into any Automatically add check digit for barcodes; High-usability image options provided to
add image to pdf preview; add image to pdf file acrobat
Chapter 6. Serial I/O, SNP & RTU Protocols 
GFK-2222W 
August 2015 
177 
Response: 
See descriptions for individual Diagnostic Codes. 
Diagnostic Return Query Data Request (Loopback/Maintenance Code 00): 
An address of 0 is not allowed for the return query data request. 
The values of the two Data field bytes in the query are arbitrary. 
The normal response is identical to the query. 
The values of the Data bytes in the response are equal to the values sent in the query. 
Diagnostic Initiate Communication Restart Request (Loopback/Maintenance Code 01): 
An Address of 0 indicates a broadcast request. All slave stations process a broadcast request and 
no response is sent. 
This request disables the listen-only mode (enables responses to be sent when queries are 
received so that communications can be restarted). 
The value of the first byte of the Data field (DATA1) must be 0 or FF. Any other value will cause an 
error response to be sent. The value of the second byte of the Data field (DATA2) is always equal 
to 0. 
The normal response to an Initiate Communication Restart query is identical to the query. 
Diagnostic Force Listen-Only Mode Request (Loopback/Maintenance code 04): 
An Address of 0 indicates a broadcast request. All slave stations process a broadcast request. 
After receiving a Force Listen-Only mode request, the RTU device will go into the listen-only 
mode, will not perform a requested function, and will not send either normal or error responses 
to any queries. The listen-only mode is disabled when the RTU device receives an Initiate 
Communication Restart request or when the RTU device is powered up. 
Both bytes in the Data field of a Force Listen-Only Mode request are equal to 0. The RTU device 
never sends a response to a Force Listen-Only Mode request. 
Note:  Upon power up, the RTU device disables the listen-only mode and is enabled to continue 
sending responses to queries. 
.NET Excel Document Add-on | Manipulate Excel File in .NET
to convert Excel to PNG, JPEG, BMP, and GIF image formats, and to TIFF, PDF and SVG functions of this DLL, .NET programmers also need to add .NET Basic DLL
add a jpeg to a pdf; adding an image to a pdf file
.NET Word Document Add-on DLL of RasterEdge DocImage SDK for .NET
any page of Word document to raster image file (PNG and convert Word to other documents, like PDF, TIFF and be ordered for using .NET Word Document Add-on for
add png to pdf acrobat; pdf insert image
Chapter 6. Serial I/O, SNP & RTU Protocols 
178 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
6.3.3.9
Message (15): Force Multiple Outputs 
Format: 
Address
Number  
of Points
Error Check
Func
15
Query
Normal Response
Address
Error Check
Func
15
Byte 
Count
Data
Starting
Point 
Point No.
Number  
of Points
Starting
Point 
Point No.
Figure 37: RTU Force Multiple Outputs Message Format 
Query: 
An Address of 0 indicates a broadcast request. All slave stations process a broadcast request and 
no response is sent. 
The value of the Function code is 15. 
The Starting Point Number is two bytes in length and may be any value less than the highest 
output point number available in the attached CPU. The Starting Point Number is equal to one 
less than the number of the first output point forced by this request. 
The Number of Points value is two bytes in length. The sum of the Starting Point Number and the 
Number of Points value must be less than or equal to the highest output point number available 
in the attached CPU. The high order byte of the Starting Point Number and Number of Bytes fields 
is sent as the first byte in each of these fields. The low order byte is the second byte in each of 
these fields. 
The Byte Count is a binary number from 1 to 256 (0 = 256). It is the number of bytes in the Data 
field of the force multiple outputs request. 
The Data field is packed data containing the values that the outputs specified by the Starting 
Point Number and the Number of Points fields are to be forced to. Each byte in the Data field 
contains the values that eight output points are to be forced to. The least significant bit (LSB) of 
the first byte contains the value that the output point whose number is equal to the starting point 
number plus one is to be forced to. The values for the output points are ordered by number 
starting with the LSB of the first byte of the Data field and ending with the most significant bit 
(MSB) of the last byte of the Data field. If the number of points is not a multiple of 8, then the last 
data byte contains zeroes in one to seven of its highest order bits. 
Response: 
The descriptions of the fields in the response are covered in the query description. 
Note:  The force multiple outputs request is not an output override command. The outputs specified 
in this request are ensured to be forced to the values specified only at the beginning of one 
sweep of the user logic. 
Chapter 6. Serial I/O, SNP & RTU Protocols 
GFK-2222W 
August 2015 
179 
6.3.3.10
Message (16): Preset Multiple Registers 
Format: 
Address
Number of
Registers
Error Check
Func
16
Query
Normal Response
Address
Error Check
Func
16
Byte
Count
Data
Starting
Register No.
Number of
Registers
Starting
Point
Figure 38: RTU Preset Multiple Registers Message Format 
Query: 
An Address of 0 indicates a broadcast request. All slave stations process a broadcast re-quest 
and no response is sent. 
The value of the Function code is 16. 
The Starting Register Number is two bytes in length. The Starting Register Number may be any 
value less than the highest register number available in the attached CPU. It is equal to one less 
than the number of the first register preset by this request. 
The Number of Registers value is two bytes in length. It must contain a value from 1 to 125 
inclusive. The sum of the Starting Register Number and the Number of Registers value must be 
less than or equal to the highest register number available in the attached CPU. The high order 
byte of the Starting Register Number and Number of Registers fields is sent as the first byte in 
each of these fields. The low order byte is the second byte in each of these fields. 
The Byte Count field is one byte in length. It is a binary number from 2 to 250 inclusive. It is equal 
to the number of bytes in the data field of the preset multiple registers request. Note that the 
Byte Count is equal to twice the value of the Number of Registers. 
The registers are returned in the Data field in order of number with the lowest number register in 
the first two bytes and the highest number register in the last two bytes of the Data field. The 
number of the first register in the Data field is equal to the starting register number plus one. The 
high order byte is sent before the low order byte of each register. 
Response: 
The descriptions of the fields in the response are covered in the query description. 
Chapter 6. Serial I/O, SNP & RTU Protocols 
180 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
6.3.3.11
Message (17): Report Device Type 
Format: 
Address
Error Check
Func 17
Query
Normal Response
Address
Device
Type 43
Error Check
Func 17
Slave Run
Light
Data
Byte
Count
Figure 39: RTU Report Device Type Message Format 
Query: 
The Report Device Type query is sent by the master to a slave in order to learn what type of 
programmable control or other computer it is. 
An Address of zero is not allowed as this cannot be a broadcast request. 
The Function code is 17. 
Response: 
The Byte Count field is one byte in length and is equal to 5. 
The Device Type field is one byte in length and is equal to 43 (hexadecimal) for PACSystems 
The Slave Run Light field is one byte in length. The Slave Run Light byte is equal to OFFH if the 
CPU is in RUN Mode. It is equal to 0 if the CPU is not in RUN Mode. 
The Data field contains three bytes. For PACSystems CPUs, the first byte is the Minor Type, and 
the remaining bytes are zeroes. The following table lists minor types. 
Response Data 
(Minor Type) 
CPU Model42 
02 hex 
IC698CPE010 
04 hex 
IC698CPE020 
05 hex 
IC698CRE020 
06 hex 
IC698CPE030 
08 hex 
IC698CPE040 
0A hex 
IC695CPE305 
IC695CPU310 
0C hex 
IC695NIU001 
10 hex 
IC695CPU320 
11 hex 
IC695CRU320 
12 hex 
IC695CPE305 
18 hex 
IC695CPU315 
42
Does not apply to CPE330, which has no serial ports. 
Chapter 6. Serial I/O, SNP & RTU Protocols 
GFK-2222W 
August 2015 
181 
6.3.3.12
Message (22): Mask Write 4x Memory 
Modifies the contents of a specified 4x register using a combination of an AND mask, an OR mask, 
and the register's current contents. The function can be used to set or clear individual bits in the 
register. Broadcast is not supported.  
Query:  
The query specifies the 4x reference to be written, the data to be used as the AND mask, and the 
data to be used as the OR mask.  
The function's algorithm is:  
Result = (Current Contents AND And_Mask) OR (Or_Mask AND And_Mask)  
For example:  
Hex 
Binary 
Current Contents  12 
0001 
0010 
And_Mask 
F2 
1111 
0010 
Or_Mask 
25 
0010 
0101 
And_Mask 
0D 
0000 
1101 
Result 
17 
0001 
0111 
Note:  If the Or_Mask value is zero, the result is simply the logical ANDing of the current contents 
and And_Mask. If the And_Mask value is zero, the result is equal to the Or_Mask value.  
Note:  The contents of the register can be read with the Read Holding Registers function (function 
code 03). They could, however, be changed subsequently as the controller scans its user logic 
program.  
Example of a Mask Write to register 5 in slave device 17, using the above mask values: 
Field Name 
Example (Hex) 
Slave Address 
11 
Function 
16 
Reference Address Hi 
00 
Reference Address Lo 
04 
And_Mask Hi 
00 
And_Mask Lo 
F2 
Or_Mask Hi 
00 
Or_Mask Lo 
25 
Error Check (LRC or CRC)  -- 
Response:  
The normal response is an echo of the query. The response is returned after the register has been 
written.  