Chapter 6. Serial I/O, SNP & RTU Protocols 
182 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
6.3.3.13
Message (23): Read Write 4x Memory 
Performs a combination of one read and one write operation in a single Modbus transaction. The 
function can write new contents to a group of 4x registers, and then return the contents of another 
group of 4x registers. Broadcast is not supported.  
Query:  
The query specifies the starting address and quantity of registers of the group to be read. It also 
specifies the starting address, quantity of registers, and data for the group to be written. The Byte 
Count field specifies the quantity of bytes to follow in the Write Data field.  
Here is an example of a query to read six registers starting at register 5, and to write three registers 
starting at register 16, in slave device 17:  
Field Name 
Example (Hex) 
Slave address 
11 
Function 
17 
Read Reference Address Hi 
00 
Read Reference Address Lo  04 
Quantity to Read Hi 
00 
Quantity to Read Lo 
06 
Write Reference Address Hi  00 
Write Reference Address Lo  0F 
Quantity to Write Hi 
00 
Quantity to Write Lo 
03 
Byte Count 
06 
Write Data 1 Hi 
00 
Write Data 1 Lo 
FF 
Write Data 2 Hi 
00 
Write Data 2 Lo 
FF 
Write Data 3 Hi 
00 
Write Data 3 Lo 
FF 
Error Check (LRC or CRC) 
-- 
Add signature image to pdf - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
how to add image to pdf form; adding an image to a pdf in preview
Add signature image to pdf - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
adding image to pdf; adding images to pdf forms
Chapter 6. Serial I/O, SNP & RTU Protocols 
GFK-2222W 
August 2015 
183 
Response:  
The normal response contains the data from the group of registers that were read. The Byte Count 
field specifies the quantity of bytes to follow in the Read Data field.  
Here is an example of a response to the query:  
Field Name 
Example (Hex) 
Slave Address 
11 
Function 
17 
Byte Count 
0C 
Read Data 1 Hi 
00 
Read Data 1 Lo 
FE 
Read Data 2 Hi 
0A 
Read Data 2 Lo 
CD 
Read Data 3 Hi 
00 
Read Data 3 Lo 
01 
Read Data 4 Hi 
00 
Read Data 4 Lo 
03 
Read Data 5 Hi 
00 
Read Data 5 Lo 
0D 
Read Data 6 Hi 
00 
Read Data 6 Lo 
FF 
Error Check (LRC or CRC)  -- 
C# PDF Digital Signature Library: add, remove, update PDF digital
Verify the validity of PDF signature. Add necessary references CHINA SHANGHAI"; cert.Reason = "Reason"; cert.APMode = APMode.Text; // APMode.Text | APMode.Image.
adding image to pdf in preview; how to add image to pdf reader
VB.NET PDF Digital Signature Library: add, remove, update PDF
Verify the validity of PDF signature. Add necessary references: CHINA SHANGHAI" cert.Reason = "Reason" cert.APMode = APMode.Text ' APMode.Text | APMode.Image.
add picture to pdf in preview; add jpg to pdf file
Chapter 6. Serial I/O, SNP & RTU Protocols 
184 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
6.3.3.14
Message (67): Read Scratch Pad Memory 
Format: 
Address
Starting
Byte No.
Number of
Bytes
Error
Check
Func
67
Query
Address
Data
Error
Check
Func
67
Normal Response
Byte
Count
Figure 40: RTU Read Scratch Pad Memory Message Format 
Query: 
An Address of 0 is not allowed as this cannot be a broadcast request. 
The Function Code is equal to 67. 
The Starting Byte Number is two bytes in length and may be any value less than or equal to the 
highest scratch pad memory address available in the attached CPU as indicated in the table 
below. The Starting Byte Number is equal to the address of the first scratch pad memory byte 
returned in the normal response to this request. 
The Number of Bytes value is two bytes in length. It specifies the number of scratch pad memory 
locations (bytes) returned in the normal response. The sum of the Starting Byte Number and the 
Number of Bytes values must be less than two plus the highest scratch pad memory address 
available in the attached CPU. The high order byte of the Starting Byte Number and Number of 
Bytes fields is sent as the first byte in each of these fields. The low order byte is the second byte in 
each of the fields. 
Response: 
The Byte Count is a binary number from 1 to 256 (0 = 256). It is the number of bytes in the Data 
field of the normal response. 
The Data field contains the contents of the scratch pad memory requested by the query. The 
scratch pad memory bytes are sent in order of address. The contents of the scratch pad memory 
byte whose address is equal to the Starting Byte Number is sent in the first byte of the Data field. 
The contents of the scratch pad memory byte whose address is equal to one less than the sum of 
the starting byte number and number of bytes values is sent in the last byte of the Data field. 
C# HTML5 Viewer: Load, View, Convert, Annotate and Edit PDF
convert PDF to multi-page Tiff image files and to PDF, including freehand signature, text and date signature. If you need to add your own signatures such as
add picture to pdf reader; add jpg to pdf online
C# HTML5 Viewer: Load, View, Convert, Annotate and Edit Tiff
For examples, add text signature to Tiff image, insert date signature to Tiff or create freehand signature to Tiff.
add signature image to pdf acrobat; add jpg to pdf
Chapter 6. Serial I/O, SNP & RTU Protocols 
GFK-2222W 
August 2015 
185 
6.3.4
RTU Scratch Pad 
The entire scratch pad is updated every time an external READ request is received by the 
PACSystems RTU slave. All scratch pad locations are read only. The scratch pad is a byte-oriented 
memory type. 
6.3.4.1
RTU Scratch Pad Memory Allocation 
SP Address  Field Identifier 
Bits 
00 
CPU Run Status 
See note.43 
01 
CPU Command Status 
Bit pattern same as SP(00) 
02 
03 
CPU Type 
Major
44
(in hexadecimal) 
Minor
45
(in hexadecimal) 
04 – 0B 
CPU SNP ID 
7 ASCII characters + termination character (00h) 
0C 
0D 
CPU Firmware Revision No. 
Major (in BCD) 
Minor (in BCD) 
0E 
0F 
Communications Management Module 
(CMM) Firmware Revision No. 
Major 
Minor 
10—11 
Reserved 
00h 
12 
Node Type Identifier 
PACSystems 43 (hexadecimal) 
13—15 
Reserved 
00h 
16 
RTU Station Address 
1—247 (decimal) 
17 
Reserved 
00h 
18—33
46
Sizes of Memory Types 
18—1B 
Register Memory 
%R size (words) 
1C—1F 
Analog Input Table 
%AI size (words) 
20—23 
Analog Output Table 
%AO size (words) 
24—27 
Input Table 
%I size (bits) 
28—2B 
Output Table 
%O size (bits) 
2C—2F 
Internal Discrete Memory 
%M size (bits) 
30—33 
User Program Code 
The amount of program memory occupied by the logic 
program. 
34—FF 
Reserved 
00h 
43  
0000 = Run_Enabled 
0100 = Halted 
0001 = Run_Disabled 
0101 = Suspended  
0010 = Stopped   
0110 = Stopped_IO_Enabled 
44 CPU Major Type Codes: PACSystems 0x43 
45 PACSystems Minor Types for CPU: refer to Message (17): Report Device Type 
46 Four bytes hold the hexadecimal length of each memory type with the most significant word reserved for future 
expansion. For example, the default register memory size of 1024 words (0400h) would be returned in the following 
format: 
Word  
Least   Significant   Most   Significant  
SP Byte  
18  
19  
1A  
1B  
Contains   00  
04  
00  
00  
C# WPF Viewer: Load, View, Convert, Annotate and Edit Tiff
users can perform Tiff viewing and multiple Tiff image manipulation functionalities. convert Tiff file to PDF, add annotations to Tiff, Create signature on tiff
add an image to a pdf with acrobat; how to add an image to a pdf in reader
C# WinForms Viewer: Load, View, Convert, Annotate and Edit Tiff
load Tiff to WinForms Viewer easily and view Tiff image on it in preview, such as convert Tiff file to PDF, add annotations to Tiff, Create signature on tiff
how to add a jpg to a pdf; adding images to pdf files
Chapter 6. Serial I/O, SNP & RTU Protocols 
186 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
6.3.5
Communication Errors 
Serial link communication errors are divided into three groups: 
Invalid Query Message 
Serial Link Time Outs 
Invalid Transaction 
6.3.5.1
Invalid Query Message 
When the communications module receives a query addressed to itself, but cannot process the 
query, it sends one of the following error responses: 
Subcode 
Invalid Function Code 
Invalid Address Field  
Invalid Data Field  
Query Processing Failure   4 
The format for an error response to a query is as follows: 
Address 
Exception 
Func 
Error 
Subcode 
Error 
Check 
Figure 41: RTU Error Response Format 
The address reflects the address provided on the original request. The exception function code is 
equal to the sum of the function code of the query plus 128. The error subcode is equal to 1, 2, 3, or 4. 
The value of the subcode indicates the reason the query could not be processed. 
Invalid Function Code Error Response (1) 
An error response with a subcode of 1 is called an invalid function code error response. This response 
is sent by a slave if it receives a query whose function code is not equal to 1- 8, 15, 16, 17, or 67. 
Note:  Starting with Release 6.70 for the RX3i, the invalid function code error response is not used. 
Instead, undefined and unsupported function codes are ignored, and no response is 
generated. 
.NET PDF SDK - Description of All PDF Processing Control Feastures
Create signatures in existing PDF signature fields; Create signatures in new fields which hold the signature; Add signature image to PDF file. PDF Hyperlink Edit
how to add an image to a pdf file in acrobat; add image pdf
How to C#: Basic SDK Concept of XDoc.PDF for .NET
In general, image extraction, editing, drawing, and You may add PDF document protection functionality into your C# PDF password and digital signature, and set
acrobat add image to pdf; add picture to pdf file
Chapter 6. Serial I/O, SNP & RTU Protocols 
GFK-2222W 
August 2015 
187 
Invalid Address Error Response (2) 
An error response with a subcode of 2 is called an invalid address error response. This error response 
is sent in the following cases: 
1.
The Starting Point Number and Number of Points fields specify output points or input points that 
are not available in the attached CPU (returned for function codes 1, 2, 15). 
2.
The Starting Register Number and Number of Registers fields specify registers that are not 
available in the attached CPU (returned for function codes 4, 16). 
3.
The Starting Analog Input Number and Analog Input Number fields specify analog inputs that are 
not available in the attached CPU (returned for function code 3). 
4.
The Point Number field specifies an output point not available in the attached CPU (returned for 
function code 5). 
5.
The Register Number field specifies a register not available in the attached CPU (returned for 
function code 6). 
6.
The Analog Input Number field specifies an analog input number not available in the at-attached 
CPU (returned for function code 3). 
7.
The Diagnostic Code is not equal to 0, 1, or 4 (returned for function code 8). 
8.
The starting Byte Number and Number of Bytes fields specify a scratch pad memory address that 
is not available in the attached CPU (returned for function code 67). 
Invalid Data Value Error Response (3) 
An error response with a subcode of 3 is called an invalid data value error response. This response is 
sent in the following cases: 
The first byte of the Data field is not equal to 0 or 255 (FFh) or the second byte of the Data field is not 
equal to 0 for the Force Single Output Request (Function Code 5) or the initiate communication 
restart request (function code 8, diagnostic code 1). The two bytes of the Data field are not both 
equal to 0 for the Force Listen-Only request (Function Code 8, Diagnostic Code 4). This response is 
also sent when the data length specified by the Memory Address field is longer than the data 
received. 
Query Processing Failure Error Response (4) 
An error response with a subcode of 4 is called a query processing failure response. This error 
response is sent by a RTU device if it properly receives a query but communication between the 
associated CPU and the CMM fails. 
Chapter 6. Serial I/O, SNP & RTU Protocols 
188 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
6.3.5.2
Serial Link Timeout 
The only cause for a RTU device to timeout is if an interruption to a data stream of 4 character times 
occurs while a message is being received. If this occurs the message is considered to have 
terminated and no response will be sent to the master. There are certain timing considerations due 
to the characteristics of the slave that should be taken into account by the master. After sending a 
query message, the master should wait an appropriate amount of time for slave turnaround before 
assuming that the slave did not respond to the request. Slave turnaround time is affected by the 
Controller Communications Window time and the CPU sweep time, as described in RTU Slave 
Turnaround Time. 
6.3.5.3
Invalid Transactions 
If an error occurs during transmission that does not fall into the category of an invalid query 
message or a serial link time-out, it is known as an invalid transaction. Types of errors causing an 
invalid transaction include: 
Bad CRC. 
The data length specified by the Memory Address field is longer than the data received. 
Framing or overrun errors. 
Parity errors. 
If an error in this category occurs when a message is received by the slave serial port, the slave does 
not return an error message; rather the slave ignores the incoming message, treating the message 
as though it was not intended for it. 
Chapter 6. Serial I/O, SNP & RTU Protocols 
GFK-2222W 
August 2015 
189 
6.3.6
RTU Slave/SNP Slave Operation with Programmer Attached 
A port that has been configured for RTU Slave protocol can switch to SNP protocol if an SNP master 
such as a programmer begins communicating to the port. The programmer must use the same serial 
communications parameters (baud rate, parity, stop bits, etc.) as the currently active RTU Slave 
protocol for it to be recognized. When the CPU recognizes the SNP master, the CPU removes the RTU 
Slave protocol from the port and installs SNP Slave as the active protocol. 
The SNP protocol that is installed in this case has the following fixed characteristics:  
The SNP ID is set to blank. Therefore the SNP master must use a blank ID in the SNP attach 
message. This also means that this capability is only useful for point-to-point connections. 
The turnaround time is set to 0ms. 
The idle timeout is set to 10 seconds.  
After the programmer is removed, there is a slight delay (equal to the idle timeout) before the CPU 
recognizes its absence. During this time, no messages are processed on the port. The CPU detects 
removal of the programmer as an SNP Slave protocol timeout. Therefore, it is important to be careful 
when disabling timeouts used by the SNP Slave protocol.  
When the CPU recognizes the programmer disconnect, it reinstalls RTU Slave protocol unless a new 
protocol has been configured in the meantime. In that case, the CPU installs the new protocol 
instead.  
Example 
1.
COM1 is running RTU Slave protocol at 9600 baud. 
2.
A programmer is attached to COM1. The programmer is using 9600 baud. 
3.
The CPU installs SNP Slave on COM1 and the programmer communicates normally. 
4.
The programmer stores a new configuration to COM1. The new configuration sets the port for 
SNP Slave at 4800 baud (it will not take effect until the port loses communications with the 
programmer).  
5.
When the CPU loses communications with the programmer, the new configuration takes effect. 
Chapter 6. Serial I/O, SNP & RTU Protocols 
190 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
6.4
SNP Slave Protocol 
PACSystems CPUs can communicate with Machine Edition software through either COM1 or COM2 
using SNP slave protocol. 
CPU COM1 is wired as an RS-232 Data Communications Equipment (DCE) port, and can be connected 
directly using straight-through cable to one of the serial ports of a PC running Machine Edition or 
other SNP master software. 
CPU COM2 is wired for RS-485. If the SNP master does not have an RS-485 port, an RS-485/RS-232 
converter is required. The RX3i can use converter IC690ACC901, which uses +5Vdc from the serial 
port. The RX7i CPU COM2 does not support IC690ACC901 and requires an externally powered 
converter. 
PACSystems provides the break free version of SNP, so that the SNP master does not need to issue a 
break signal as part of the SNP attach sequence. However, the CPU responds appropriately if a break 
signal is detected, by resetting the protocol to wait for another attach sequence from the master. 
PACSystems supports both point-to-point connections (single master/single slave) and multi-drop 
connections (single master/multiple slaves). 
For details on SNP protocol, refer to the Series 90 PLC Serial Communications User’s Manual, 
GFK-0582. 
6.4.1
Permanent Datagrams 
Permanent datagrams survive after the SNP session that created them has been terminated. This 
allows an SNP master device to periodically retrieve datagram data from a number of different 
controllers on a multi-drop link, without the master having to establish and write the datagram each 
time it reconnects to the controller. 
The maximum number of permanent datagrams that can be established is 32. When this limit is 
reached, additional requests to establish datagrams are denied. One or more of the permanent 
datagrams will need to be cancelled before others can be established. Since the permanent 
datagrams are not automatically deleted when the SNP session is terminated, this limit prevents an 
inordinate amount of these datagrams from being established. 
Permanent datagrams do not survive a power-cycle. 
6.4.2
Communication Requests (COMMREQs) for SNP 
The PACSystems serial ports COM1 and COM2 currently do not provide SNP Master service, nor do 
they support COMMREQ functions for SNP commands. However, those COMMREQ functions can be 
used with PCM/CMM modules that are configured to provide SNP service. For more information, refer 
to the Series 90 PLC Serial Communications User’s Manual, GFK-0582. 
GFK-2222W 
August 2015 
191 
Appendix A
Performance Data 
This appendix contains instruction and overhead timing collected for each PACSystems CPU module. 
This timing information can be used to predict CPU sweep times. The information in this appendix is 
organized as follows: 
 Boolean Execution Times
 Instruction Timing
 Overhead Sweep Impact Times