Chapter 2. CPU Features & Specifications 
22 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
CPU310 
CPU315 
CPU320/ 
CRU320
4
CPE305 
CPE310 
CPE330 
Time-of-Day Clock 
Time-of-Day Clock Accuracy (@60°C) 
±2 secs/day 
±2 secs/day 
±2 secs/day 
±2 secs/day 
±2 secs/day 
±2 secs/day 
Elapsed Time Clock (internal timing) accuracy 
±0.01% max 
±0.01% max 
±0.01% max 
±0.01% max 
±0.01% max 
±0.01% max 
Simple Network Time Protocol (SNTP) accuracy 
to timestamp
16
±2 ms using 
ETM001 
±2 ms using 
ETM001 
±2 ms using 
ETM001 
±2 ms using 
ETM001 
±2 ms using 
ETM001  
±2 ms using 
ETM001 
RTC Battery Backup 
RTC Battery Life expectancy 
5 years 
5 years 
5 years 
Redundancy Features 
Model CRU320 
only 
Configurable in 
CPE330 
Memory Error Checking and Correction (ECC) 
Single bit 
correcting & 
Multiple bit 
checking 
same - pending 
Switchover Time (max)17 
1 logic scan 
same - pending 
Switchover Time (min)
17
3.133 ms 
same - pending 
Max data in redundancy transfer list18 
2 Mbytes 
same - pending 
Redundant Synchronized Links Supported 
RMX128 x2 max 
RMX228 x2 max 
same - pending 
16
SNTP is not supported by the embedded CPU Ethernet interfaces at time of publication. Use ETM001 for SNTP. 
17
Switchover time is defined as the time from failure detection until backup CPU is active in a redundancy system. 
18
Symbolic variable and Reference data can be exchanged between redundancy controllers, up to the stipulated limit. 
Adding image to pdf in preview - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
pdf insert image; add image to pdf
Adding image to pdf in preview - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
add jpg signature to pdf; add picture to pdf document
Chapter 2. CPU Features & Specifications 
GFK-2222W 
August 2015 
23 
2.2.1
CPE330 
Figure 1: CPE330 Front View & Features 
C# Word - Insert Image to Word Page in C#.NET
Preview Document. Conversion. Convert Word to PDF. Convert Word to HTML5. VB.NET How-to, VB.NET PDF, VB.NET Word It's a demo code for adding image to word page using
how to add a photo to a pdf document; add photo to pdf reader
C# PowerPoint - Insert Image to PowerPoint File Page in C#.NET
Preview Document. Conversion. Convert PowerPoint to PDF. Convert PowerPoint to Pages. Annotate PowerPoint. Text Search. Insert Image. Thumbnail Create.
adding a png to a pdf; how to add image to pdf in acrobat
Chapter 2. CPU Features & Specifications 
24 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
2.2.1.1
Serial Ports CPE330 
CPE330 is not equipped with a serial port. Use the embedded Ethernet ports for all communications 
with the CPU; use IC695CMM002 or IC695CMM004 modules for serial communications. 
2.2.1.2
Ethernet Ports CPE330 
CPE330 supports two independent 10/100/1000 Ethernet Local Area Networks (LANs).  
LAN1 connects to the uppermost RJ-45 connector (Figure 1). It is not switched.  
LAN2 connects to the two lower RJ-45 connectors. They are switched internally.  
Space is provided beside each connector (Figure 1) to record the IP address used on each LAN. 
Each of the embedded Ethernet interfaces automatically senses the data rate (10 Mbps or 100 Mbps 
or 1 Gbps), communications mode (half-duplex or full-duplex), and cabling arrangement (straight-
through or crossover) of the attached link. 
Any of the embedded Ethernet ports may be used to communicate with the Proficy Machine Edition 
(PME) programming and configuration software using the Service Request Transport Protocol (SRTP, a 
proprietary GE protocol, used primarily for communication with the programmer).  
For default IP Address and other details, refer to Establishing Initial Ethernet Communications, Section 
3.4.1. 
Ethernet Network Configuration CPE330 
The user must be careful when assigning IP Addresses and Subnet Masks for CPE330: 
Each LAN supports a unique IP Address 
LAN1 and LAN2 interfaces should not be configured for the same network unless they are 
both physically connected to the same network. 
By default, PME prohibits configuring both LAN interfaces on an overlapping IP subnet. 
Care must also be taken when assigning IP Addresses and subnet masks to each LAN so that each 
network does not overlap any remote subnets in the network infrastructure: 
Subnets overlap with one another when the subnet portions of the IP Addresses are not 
completely unique 
Overlapping subnets may result in intermittent Ethernet communications, or none at all. This 
would be due to packets being routed to the wrong LAN.  
Duplicate IP Addresses may also result in intermittent Ethernet communications, or none at 
all. This is due to collisions on the LAN induced by two devices with the same IP Addresses 
communicating at the same time. 
Ethernet Gateway Operation CPE330 
The CPE330 allows configuration of an Ethernet gateway on both LAN1 and LAN2. Since the CPE330 
contains two LAN interfaces, each one supporting a unique IP Address, only one gateway is active at 
a time. 
Whenever a gateway is configured on only one of the two LAN interfaces and the other is not 
configured (0.0.0.0), the single gateway is shared by both interfaces; 
Whenever a gateway is configured on both LAN interfaces, the LAN1 gateway is given priority 
over the LAN2 gateway as long as LAN1 is functional. For example, in the event the LAN1 
cable is disconnected, the CPE330 will use the LAN2 gateway as a backup. 
C# PDF Page Insert Library: insert pages into PDF file in C#.net
applications. Support adding and inserting one or multiple pages to existing PDF document. Forms. Ability to add PDF page number in preview. Offer
add jpeg to pdf; adding a jpg to a pdf
C# PDF insert text Library: insert text into PDF content in C#.net
Supports adding text to PDF in preview without adobe reader installed in ASP.NET. Powerful .NET PDF edit control allows modify existing scanned PDF text.
how to add an image to a pdf in reader; how to add image to pdf reader
Chapter 2. CPU Features & Specifications 
GFK-2222W 
August 2015 
25 
2.2.1.3
Switches CPE330 
Figure 2: CPE330 RUN/STOP Switch and 
RDSD Switches 
The RDSD and RUN/STOP Switches are located behind 
the protective door, as shown in Figure 2.  
Refer to RUN/STOP Switch Operation in Chapter 4.  
The Reset pushbutton, located just above these 
switches, is currently not used. 
RDSD Switch Operation CPE330 
RDSD Pushbuttons 
Function 
RDSD UPLD 
Loads user program or data from CPU to RDSD. 
RDSD DNLD 
Stores user program or data from RDSD to CPU. 
Refer to Removable Data Storage Devices (RDSDs) for full description of RDSD functionality. 
VB.NET PDF insert text library: insert text into PDF content in vb
Multifunctional Visual Studio .NET PDF SDK library supports adding text content to adobe PDF document in VB.NET Add text to PDF in preview without adobe
add image to pdf acrobat; adding an image to a pdf in acrobat
C# Create PDF Library SDK to convert PDF from other file formats
Load PDF from existing documents and image in SQL server. Besides, using this PDF document metadata adding control, you can add some additional
add photo to pdf in preview; add image to pdf preview
Chapter 2. CPU Features & Specifications 
26 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
2.2.1.4
Indicators CPE330  
CPU Status Indicators 
On
Blinking
Off
CPE330 LED 
LED State 
Operating State 
CPU OK 
On Green 
CPU has passed its power-up diagnostics and is functioning 
properly. (After initialization sequence is complete.) 
Off 
Power is not applied or CPU has a problem, which may be 
indicated by blink pattern. 
Blinking 
Other LEDs off 
CPU in STOP-Halt state; possible watchdog timer fault. If PME 
cannot connect, cycle power with charged Energy Pack 
attached and refer to fault tables. 
RUN 
Blinking in unison 
CPU is updating an internal programmable hardware device. 
OUT EN 
RUN 
On Green 
CPU is in RUN Mode. 
Off 
CPU is in STOP Mode. 
OUT EN 
On Green 
Output scan is enabled. 
Off 
Output scan is disabled. 
FORCE 
On Amber 
Override is active on a bit reference. 
Off 
No Overrides active in I/O Reference Tables. 
RDSD 
On Green 
USB or Cfast Device detected (No Activity) 
Blinking Green 
Port activity detected on USB or Cfast Interface 
Off 
No port activity detected on USB or Cfast Interface 
On Red 
RDSD Failure 
Blinking Red 
Target name mismatch: Press same RDSD pushbutton again to 
dismiss. 
SYS FLT 
On Red 
CPU is in Stop/Faulted mode: a fatal fault has occurred. 
Off 
No fatal faults detected. 
Ethernet Indicators CPE330 (part of RJ-45 connectors) 
On
Blinking
Off
LED 
LED State 
Operating State 
LINK (upper) 
On Green 
The corresponding link is physically connected. 
Blinking Green 
Traffic is detected at the corresponding port. 
Off 
No connection detected at the corresponding port. 
1Gbps (lower) 
On Amber (LAN1) or   Corresponding network data speed is 1 Gbps. 
On Green (LAN2) 
Off 
Corresponding network data speed is 100 Mbps or 10 Mbps. 
C# TIFF: TIFF Editor SDK to Read & Manipulate TIFF File Using C#.
Easy to generate image thumbnail or preview for Tiff to Tiff, like Word, Excel, PowerPoint, PDF, and images. assemblies into your C# project by adding reference
add image pdf acrobat; add an image to a pdf acrobat
C# PowerPoint - Insert Blank PowerPoint Page in C#.NET
This C# .NET PowerPoint document page inserting & adding component from RasterEdge is written in managed C# code and designed particularly for .NET class
add jpg to pdf; add photo pdf
Chapter 2. CPU Features & Specifications 
GFK-2222W 
August 2015 
27 
2.2.1.5
Replacement of Real-Time Clock Battery on CPE330 
The CPE330 is shipped with a real time clock (RTC) battery installed 
(see Figure 3). There is no isolation barrier between the battery and 
the circuit. This battery will need to be replaced periodically. 
Typically, no action is required during initial installation. 
Should the RTC battery fail, the CPU date and time will be reset to 
12:00 AM, 01-10-2000 at start-up. The CPU operates normally with 
a failed or missing RTC battery; however, the initial CPU time-of-
day (TOD) clock information will be incorrect. 
There are no diagnostics or indicators to monitor RTC battery 
status. The RTC battery has an estimated life of 5 years and must 
be replaced every 5 years on a preventative maintenance 
schedule.  
To replace a depleted battery,  
1.
Power down the RX3i rack.  
2.
Disconnect cables attached to the CPE330 module, labeling 
each for later reconnection. 
3.
Remove the CPE330 module.  
4.
Take the CPE330 module to a clean environment.  
5.
Place the module on a workbench with the heat-sink side 
down. 
6.
With ESD protection in place, remove the four screws holding 
the upper side sheet metal in place.  
7.
Remove the sheet metal. This exposes the circuit board, 
connectors and coin battery shown in Figure 3.  
8.
Using a non-conductive pliers, grip the battery and 
simultaneously hold back the retaining clip so it is clear of the 
battery.  
9.
Remove the depleted battery and dispose of it by an approved 
method.  
Figure 3: Location and 
Orientation of Real-Time Clock 
Battery in CPE330 
10.
Install the replacement battery so that the inscribed positive face is towards the green 
connector (i.e. downwards as shown in Figure 3).  
11.
Check that the retaining clip has engaged the edge of the newly installed battery.  
12.
Replace the sheet metal cover. 
13.
Tighten all four retaining screws to 0.9Nm (8 in-lbs).  
14.
Restore the CPE330 module to its original location and secure it in place. 
15.
Reconnect all cables to their original connectors. 
16.
Turn power on to the RX3i rack.  
17.
If needed, set the current date and time via PME or using SVC_REQ 7 (refer to PACSystems RX7i 
and RX3i CPU Programmer’s Reference Manual, GFK-2950 Chapter 6). 
Note: Battery replacement on CPE305 & CPE310 is different: see Figure 8. 
Replacement Real-Time Clock Battery 
The replacement battery must be IC690ACC001 from GE Intelligent Platforms, or equivalent, such as 
Rayovac Lithium BR2032 Coin Cell 3V 190mAh -40°C to +85°C. 
Chapter 2. CPU Features & Specifications 
28 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
Warning 
Use of a different type of battery than that specified here may 
present a risk of fire or explosion. 
Battery may explode if mistreated. Do not recharge, 
disassemble, heat above 100°C (212°F), or incinerate. 
Caution 
To avoid damage from electrostatic discharge, use proper precautions 
when performing these procedures: 
Wear a properly functioning antistatic strap and be sure that you are 
fully grounded. Never touch the printed circuit board, or components 
on the board, unless you are wearing an antistatic strap. 
Any surface upon which you place the unprotected circuit board 
should be static-safe, facilitated by antistatic mats if possible. 
Extra caution should be taken in cold, dry weather, when static charges can 
easily build up. 
Chapter 2. CPU Features & Specifications 
GFK-2222W 
August 2015 
29 
2.2.2
CPE305 and CPE310 
Figure 4: IC695CPE305 Front View 
Figure 5: IC695CPE310 Front View 
2.2.2.1
Serial Ports 
These ports provide serial interfaces to external devices and can be used for firmware upgrades. For 
serial port pin assignments, electrical isolation, and details on serial communications, refer to 
Chapter 5. 
CPE305: 
one RS-232 port (using RJ-25 connector). 
CPE310: 
one RS-232 port (COM1) and one RS-485 port (COM2). 
The RS-232 port does not supply the 5Vdc power offered by other RX3i and Series 90-30 CPUs.  
Use cable IC693CBL316 to connect to the serial RJ-25 port on the CPE305. This 3m shielded cable 
provides a 9-pin D-connector on the other end. 
Chapter 2. CPU Features & Specifications 
30 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
2.2.2.2
Ethernet Port 
The embedded Ethernet interface connects via one RJ-45 Ethernet port that automatically senses 
the data rate (10 Mbps or 100 Mbps), communication mode (half-duplex or full-duplex), and cabling 
arrangement (straight-through or crossover) of the attached link.  
The embedded Ethernet interface supports communications with the Proficy Machine Edition (PME) 
programming and configuration software using the proprietary SRTP protocol. The CPE305/CPE310 
CPUs provide two SRTP-server connections.  
Refer to Establishing Initial Ethernet Communications, Section 3.4.1. 
Chapter 2. CPU Features & Specifications 
GFK-2222W 
August 2015 
31 
2.2.2.3
Switches CPE305 & CPE310 
The RDSD and RUN/STOP Switches are located behind the protective door, as shown in Figure 6 and 
Figure 7. Refer to RUN/STOP Switch Operation in Chapter 4. The Reset pushbutton is not used. 
Figure 6: External Features of CPE305 
Figure 7: External Features of CPE310 
RDSD Switch Operation CPE305 & CPE310 
RDSD Switches 
Function 
Start pushbutton 
Pressing this switch initiates RDSD data transfer. (The three-position switch must 
have previously been set to Upload or Download.)  
See 
Removable Data Storage Devices (RDSDs)
for full description of RDSD 
functionality. 
Three-position switch 
Enables/disables RDSD data transfer and selects the direction of data transfer. 
Upload 
Loads application from CPU to RDSD. 
Off 
Disables RDSD data transfer. 
Download 
Stores application from RDSD to CPU. 
Documents you may be interested