Chapter 3. CPU Configuration 
72 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
Port Parameters 
Turn 
Around 
Delay Time 
(ms) 
(Available only when STOP Mode is set to SNP Slave.) The Turn Around Delay Time is the minimum 
time interval required between the reception of a message and the next transmission. In 2-wire 
mode, this interval is required for switching the direction of data transmission on the 
communication line. 
Valid range: 0 through 2550ms, in increments of 10 ms. 
Default: 
When the STOP Mode is different from the Port Mode: 0ms. 
When the STOP Mode is the same as the Port Mode: the value is read-only and is set 
to the same value as the Turn-Around Delay Time for the Port Mode.  
Timeout (s) 
(Available only when STOP Mode is set to SNP Slave.) The maximum time that the slave will wait 
to receive a message from the master. If a message is not received within this timeout interval, 
the slave will assume that communications have been disrupted, and then it will wait for a new 
attach message from the master. 
Valid range: 0 through 60 seconds. 
Default: 
When the STOP Mode is different from the Port Mode: 10 seconds. 
When the STOP Mode is the same as the Port Mode: the value is read-only and is set 
to the same value as the Timeout for the Port Mode. 
SNP ID 
(Available only when STOP Mode is set to SNP Slave.) The port ID to be used for SNP 
communications. In SNP multi-drop communications, this ID is used to identify the intended 
receiver of a message. This parameter can be left blank if communication is point to point. To 
change the SNP ID, click the values field and enter the new ID. The SNP ID is up to seven 
characters long and can contain the alphanumeric characters (A through Z, 0 through 9) or the 
underline (_).  
Default: 
When the STOP Mode is different from the Port Mode: the default is blank.  
When the STOP Mode is the same as the Port Mode: the value is read-only and is set 
to the same value as the SNP ID for the Port Mode. 
Station 
Address 
(Available only when STOP Mode is set to RTU slave.) ID for the RTU Slave.  
Valid range: 1 through 247. 
Default: 
When the STOP Mode is different from the Port Mode: 1.  
When the STOP Mode is the same as the Port Mode: the value is read-only and is set 
to the same value as the Station Address for the Port Mode. 
Attach image to pdf form - insert images into PDF in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Sample C# code to add image, picture, logo or digital photo into PDF document page using PDF page editor control
adding jpg to pdf; add picture to pdf document
Attach image to pdf form - VB.NET PDF insert image library: insert images into PDF in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Guide VB.NET Programmers How to Add Images in PDF Document
add picture to pdf preview; add image to pdf file acrobat
Chapter 3. CPU Configuration 
GFK-2222W 
August 2015 
73 
3.2.9
Scan Sets Parameters 
You can create multiple sets of asynchronous I/O scans, with a unique scan rate assigned to each 
scan set. You can assign up to 31 scan sets for a total of 32. Scan set 1 is the standard scan set 
where I/O is scanned once per sweep. Each module is assigned to a scan set during the 
configuration of that module. Scan Set 1 is the default scan set.  
Scan Set Parameters 
Number  
A sequential number from 1 to 32 is automatically assigned to each scan set. Scan set 1 is 
reserved for the standard scan set.  
Scan Type  
Determines whether the scan set is enabled (as a fixed scan) or is disabled. 
Choices: Disabled, Fixed Scan. 
Default: Disabled. 
Number of 
Sweeps  
(Editable only when the Scan Type is set to Fixed Scan.) The scan rate of the scan set. Double-
click the field, then select a value. A value of 0 prevents the I/O from being scanned.  
Valid range: 0 through 64. 
Default: 1. 
Output 
Delay  
(Editable only when the Number of Sweeps is non-zero.) The number of sweeps that the output 
scan is delayed after the input scan has occurred. Double-click on field, then select a value.  
Valid range: 0 to (number of Sweeps - 1) 
Default: 0. 
Description   (Editable only when the Scan Type is set to Fixed Scan.) Brief description of the scan set (32 
characters maximum).  
3.2.10
Power Consumption Parameters 
The programming software displays the power consumed by the CPU (in Amps) for each voltage 
provided by the power supply.  
VB.NET Image: Image Drawing SDK, Draw Text & Graphics on Image
text writing function and graphics drawing function, we attach links to provide powerful & profession imaging controls, PDF document, image to pdf files and
acrobat insert image into pdf; add jpg to pdf document
VB.NET Image: VB.NET Rectangle Annotation Imaging Control
Able to attach a user-defined shadow to created rectangle annotation to provide powerful & profession imaging controls, PDF document, image to pdf files and
how to add a photo to a pdf document; add photo to pdf form
Chapter 3. CPU Configuration 
74 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
3.2.11
Access Control 
The Access Control List allows you to specify the reference address ranges that can be accessed by 
non-local devices such as HMIs and other controllers. To use this feature, Enhanced Security must be 
enabled in the properties of the target. 
When Enhanced Security mode is enabled, any reference address range not defined cannot be 
accessed by other devices. External reads and writes that do not exist in the table are rejected by the 
firmware. 
If overlapping memory ranges are defined, they must have the same Access level. 
For symbolic variables, access control is specified by the Publish property of the variable, which 
includes a Read Only and Read/Write setting.  
Note:  When requesting data from an external device, some drivers packetize data to optimize 
communication. If a request attempts to read a value that is not published, the entire packet 
will fail. A fault has been added to the fault table to help you understand a failed read/write. 
After addressing the fault, you must clear the fault in order to try again. 
3.2.11.1
Access Control List Settings 
Memory 
Area 
The memory area in which the reference address range is defined. 
Default: Select an Area 
Choices: %AI Analog Input, %AQ Analog Output, %I Discrete Input, %G Genius Global, 
%M Internal Discrete, %Q Discrete Output, %R Register Memory, %S System,  %SA 
System, %SB System, %SC System, %T Temporary Status,   %W Bulk Memory. 
Start 
The starting offset of the reference address range. 
Default: 0 (not valid) 
Valid range: 
For %S, %SA, %SB and %SC, must be 1. 
All other memory types: 1 through the upper limit of the reference address range. Must be less 
than the End value. 
End 
The ending offset of the reference address range.  
Default: 0 (not valid) 
Valid range: 
For %S, %SA, %SB and %SC, must be 128. 
All other memory types: Any value greater than Start, through the upper limit of the reference 
address range.  
For word memory types (%AI, %R and %W) the highest address available is configured on the 
Memory tab. 
Access  
Selects the type of external access allowed for the defined address range. 
Choices: Read-Only, Read/Write 
Default: Read-Only 
VB.NET Word: VB Tutorial to Convert Word to Other Formats in .NET
rendered REImage into desired document image format 2007 or later versions into PDF, tiff, bmp NET Word converting functions but also attach detailed programming
adding a png to a pdf; add image to pdf preview
VB.NET Image: VB.NET Sample Code to Draw EAN-13 Barcode on Image
How to Attach EAN-13 Barcode Image to Word in VB.NET. NET EAN-13 barcode generation tutorial page on how to add & insert EAN-13 barcode into image, PDF or Word
add png to pdf preview; how to add picture to pdf
Chapter 3. CPU Configuration 
GFK-2222W 
August 2015 
75 
3.3
Storing (Downloading) Hardware Configuration 
A PACSystems control system is configured by creating a configuration file using the PME 
programming and configuration software, then transferring (downloading) the file from the 
programmer to the CPU via serial port COM1, serial port COM2, or via an Ethernet port. If you use a 
serial port, it must be configured as RTU Slave (default) or SNP Slave.  
The CPU stores the configuration file in its non-volatile RAM memory. After the configuration is stored, 
I/O scanning is enabled or disabled according to the newly stored configuration parameters. 
Before you can use an Ethernet Interface to store the hardware configuration to the PACSystems, 
you must first set the IP Address in the Ethernet Interface either by using the Set Temporary IP 
Address utility (refer to Setting a Temporary IP Address) or by downloading a hardware configuration 
through a serial connection. 
1.
In the programmer software, go to the 
Project tab of the Navigator, right click the 
Target, and choose Go Online. 
2.
Right click the Target and choose Online 
Commands, Set Programmer Mode. Make 
sure the CPU is in STOP Mode.  
3.
Right click the Target node, and choose 
Download to Controller.  
4.
In the Download to Controller dialog box, 
select the items to download and click OK. 
Notes:  If you download to a PACSystems target that already has a project on it, the existing project 
is overwritten. 
If I/O variables are configured, hardware configuration and logic cannot be stored 
independently. They must be stored at the same time. 
If passwords have been set, when you go online, you will be taken to the highest unprotected 
level. If no passwords have been set, you will go online with Privilege Level 4. 
Figure 15: Downloading Hardware Config 
to CPU
VB.NET TIFF: VB.NET Code to Scan Document into TIFF Image File
generate those scanned documents in TIFF or PDF file format. you are also allowed to determine the image type, TIFF Here we attach a link which can lead you to
add image to pdf; add image to pdf in preview
Chapter 3. CPU Configuration 
76 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
3.4
Configuring the Embedded Ethernet Interface 
Before you can use the embedded Ethernet Interface, you must configure it using the programming 
software. To configure the embedded Ethernet interface: 
1.
In the Project tab of the Navigator, expand 
your PACSystems Target, the hardware 
configuration, and the main rack (Rack 0). 
2.
Expand the CPU slot (Slot 1). The Ethernet 
Interface daughterboard is displayed as 
Ethernet. 
3.
Right click the daughterboard slot and 
choose Configure. The Parameter Editor 
window displays the Ethernet Interface 
parameters. 
Figure 16: Selecting Embedded Ethernet for 
Configuration 
Ethernet interface configuration includes the following additional procedures. For details on 
completing these steps, refer to the PACSystems RX7i & RX3i TCP/IP Ethernet Communications User 
Manual, GFK-2224. 
Assigning an IP Address for initial network operation, such as connecting the programmer to 
download the hardware configuration, using the Set Temporary IP Address utility (refer to Setting 
a Temporary IP Address) or by downloading a hardware configuration through a serial 
connection. 
Configuring the characteristics of the Ethernet interface.  
Configuring Ethernet Global Data, if used. 
(Optional, not required for most systems). Setting up the RS-232 port for Local Station Manager 
Operation. This is part of the basic Ethernet Interface configuration.  
(Optional, not required for most systems). Configuring advanced user parameters. This requires 
creating a separate ASCII parameter file that is stored to the Controller with the hardware 
configuration. The Ethernet Interface has a set of default Advanced User Parameter values that 
should be changed only in exceptional circumstances by experienced users.  
(Optional) Setting up the Controller for Modbus/TCP Server operation. 
Note:  Whenever a CPE310 is configured as a CPU310, Ethernet properties cannot be configured.  
The embedded Ethernet interface is not supported when CPE310 is configured as a CPU310 
and the Ethernet port should not be connected to any network because it may have adverse 
effects on the network and/or operation of the CPU. 
Note:  Whenever a CPE330 is configured as a CPU320, Ethernet properties cannot be configured. 
However, the embedded Ethernet ports may be used with their default IP Addresses. 
Chapter 3. CPU Configuration 
GFK-2222W 
August 2015 
77 
3.4.1
Establishing Initial Ethernet Communications 
To establish Ethernet communications between the PME programming and configuration software 
and the CPU, you first need to set an IP address. Use one of the following methods: 
Default IP Addresses for 
CPE305/CPE310/CPE330 
Embedded Ethernet 
Initial Ethernet communication with the CPU may be established using the default 
IP addresses programmed at the factory: 
CPE305/CPE310 and CPE330 LAN1 
CPE330 LAN2 
IP Address: 
192.168.0.100 
10.10.0.100 
Subnet Mask: 
255.255.255.0 
255.255.255.0 
Gateway: 
0.0.0.0 
0.0.0.0 
Connecting to 
CPE305/CPE310 
Embedded Ethernet 
when IP Addresses are 
not Known 
If the IP address of the CPE305/CPE310 embedded Ethernet interface is not known, 
communication may be established using one of these methods to set a 
permanent IP addresses: 
Connect to the CPE305/CPE310 via its serial port and assign an IP Address to 
the embedded Ethernet interface by downloading a hardware configuration. 
Connect to the CPE305/CPE310 with PME using an IC695ETM001 module with 
a known IP address and located in the same rack. Download a new hardware 
configuration with the desired IP address for the embedded Ethernet interface. 
Connecting to CPE330 
Embedded Ethernet 
when IP Addresses are 
not Known 
If the IP addresses of the CPE330 embedded LAN 1 and LAN 2 Ethernet interfaces 
are not known, communication may be established using one of these methods to 
set new IP addresses: 
Setting a Temporary IP Address using the Set Temporary IP Address tool in 
Proficy Machine Edition (PME). After setting the temporary address, connect to 
the selected CPE330 LAN using PME and download a new hardware 
configuration with the desired permanent IP addresses. 
Connect to the CPE330 with PME using an IC695ETM001 module with a known 
IP address and located in the same rack. Download a new hardware 
configuration with the desired permanent IP addresses for the CPE330 
embedded Ethernet interfaces. 
Chapter 3. CPU Configuration 
78 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
3.4.2
Setting a Temporary IP Address 
If supported by the host CPU, use the Set Temporary IP Address utility to specify an IP address in 
place of one that has been lost or forgotten. 
The following restrictions apply when using the Set Temporary IP Address utility: 
To use the Set Temporary IP Address utility, the PLC CPU must not be in RUN Mode. IP address 
assignment over the network will not be processed until the CPU is stopped and is not scanning 
outputs. 
The Set Temporary IP Address utility does not function if communications with the networked 
PACSystems target travel through a router. The Set Temporary IP Address utility can be used if 
communications with the networked PACSystems target travel across network switches and 
hubs. 
The current user logged on the computer running the Set Temporary IP Address utility must have 
full administrator privileges. 
The target PACSystems must be located on the same local sub-network as the computer running 
the Set Temporary IP Address utility. The sub-network is specified by the computer's subnet mask 
and the IP addresses of the computer and the PACSystems Ethernet Interface. 
Note:  To set the IP address, you will need the MAC 
address of the Ethernet Interface to which PME 
will be connected.  
1.
Connect the PACSystems CPU LAN to the Ethernet 
network on which PME is communicating. 
2.
In the Project tab of the Navigator, right click the 
PACSystems target, choose Offline Commands, and 
then choose Set Temporary IP Address. The Set 
Temporary IP Address dialog box (Figure 17) appears. 
3.
In the Set Temporary IP Address dialog box, do the 
following: 
Key in the 12-digit hexadecimal MAC address (two 
digits per field). 
In the IP Address to Set box, specify the temporary 
IP address you want to set for the PACSystems 
LAN. 
If necessary, select the Enable Network Interface 
Selections check box and specify the IP address of 
the network interface on which the PACSystems is 
located. 
4.
When the fields are properly configured, click the 
Set IP button. 
5.
The IP Address of the specified PACSystems LAN will 
be set to the specified temporary address. This may 
take up to a minute. 
After the programmer connects over Ethernet, the permanent IP address for the Ethernet interface, 
which is set in the hardware configuration, will have been downloaded to the CPU.  
The temporary IP address remains in effect until the Ethernet interface is restarted, power-cycled or 
until the hardware configuration is downloaded or cleared. 
Figure 17: Set Temporary IP Address 
Chapter 3. CPU Configuration 
GFK-2222W 
August 2015 
79 
Caution 
The temporary IP Address set by the Set Temporary IP Address 
utility is not retained through a power cycle. To set a 
permanent IP Address, you must set the IP Address property of 
the target and download (store) HWC to the PACSystems. 
The Set Temporary IP Address utility can assign a temporary 
IP Address even if the target Ethernet Interface has previously 
been configured to a non-default IP Address. (This includes 
overriding an IP Address previously configured by the 
programmer.) 
Use this IP Address assignment mechanism with care. 
Chapter 3. CPU Configuration 
80 
PACSystems* RX7i & RX3i CPU Reference Manual 
GFK-2222W 
GFK-2222W 
August 2015 
81 
Chapter 4
CPU Operation 
This chapter describes the operating modes of a PACSystems CPU and describes the tasks the CPU 
carries out during these modes. The following topics are discussed: 
CPU Sweep
Program Scheduling Modes