reportviewer c# windows forms pdf : How to copy images from pdf to word Library software class asp.net windows web page ajax PTW_V6.5_Tutorial12-part400

121 
SKM Power*Tools for Windows 
Alternatively, you can use a short-cut Icon to start the Arc Flash Evaluation module. 
The Run>Arc Flash Evaluation option will produce a table as shown below: 
Arc Flash Evaluation Table  
Reading from left to right, the columns have the following definitions: 
Bus Name 
Fault location for bus report.  For line side and load side report options the bus refers to the 
equipment where the line side and load side protective devices are connected. 
Protective Device Name  
Refers to the protective device that clears the arcing fault or portion of the total arcing fault 
current. 
Bus kV 
Bus voltage at the fault location. 
Bus Bolted Fault Current (kA) 
The current flowing to a bus fault that occurs between two or more conductors or bus bars, 
where the impedance between the conductors is zero. 
Bus Arcing Fault 
The calculated arcing current on the faulted bus 
Protective Device Bolted Fault Current (kA) 
The portion of the total bolted fault current, that flows through a given protective device. 
Protective Device Arcing Fault Current (kA) 
The arc current flowing through each protective device feeding the electric arc fault.   Note 
that the total arc fault current may flow through several parallel sources to the arc location. 
Trip / Delay Time 
The time required for the protective device to operate for the given fault condition.  In the 
case of a relay, the breaker opening time is entered separately from the relay trip time.  For 
low voltage breakers and fuses, the trip time is assumed to be the total clearing curve or 
high tolerance of the published trip curve. 
Breaker Opening Time 
The time required for a breaker to open after receiving a signal from the trip unit to operate.  
How to copy images from pdf to word - copy, paste, cut PDF images in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Detailed tutorial for copying, pasting, and cutting image in PDF page using C# class code
paste image into pdf form; how to copy pictures from pdf to word
How to copy images from pdf to word - VB.NET PDF copy, paste image library: copy, paste, cut PDF images in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
VB.NET Tutorial for How to Cut or Copy an Image from One Page and Paste to Another
copy picture from pdf to powerpoint; how to copy pdf image to powerpoint
The combination of the Trip/Delay time and the Breaker Opening time determines the total 
time required to clear the fault.  For low voltage circuit breakers, the total clearing time 
displayed on the Manufacturer’s drawing is assumed  to include the breaker opening time. 
Ground 
Indicates whether the fault location includes a path to ground.  Systems with high-resistance 
grounds are assumed to be ungrounded in the Arc Flash calculations. (Available for IEEE 
1584 only) 
Equip Type 
Used only in the IEEE 1584 method to indicate whether the equipment is Switchgear, 
Panel, Cable or Open Air.  The equipment type provides a default Gap value and a distance 
exponent used in the IEEE incident energy equations. The equipment type provides a 
default Gap value and a distance exponent used in the IEEE incident energy equations. 
Gap 
Used only in the IEEE 1584 method to define the spacing between bus bars or conductors 
at the arc location.  
Duration of Arc 
The summation of Trip/Delay Time and Breaker Opening Time.  
Arc Type 
Identifies whether the fault location is in an enclosure or in open air.  In open air the arc 
energy will radiate in all directions whereas an enclosure will focus the energy toward the 
enclosure opening.  The In Box / Air selection is available when the NFPA 70E study 
option is selected.  For the IEEE 1584 study selection the In Box or In Air is determined 
automatically from the Equipment Type specification. 
Arc Flash Boundary 
The distance from exposed live parts within which a person could receive a 2nd degree 
burn. 
Working Distance 
The distance between the arc source and the worker’s face or chest. 
Incident Energy 
The amount of energy on a surface at a specific distance from a flash. 
Required Protective FR Clothing Category (PPE) 
Indicates the Personal Protective Equipment (PPE) required to prevent an incurable burn at 
the working distance during an arcing fault. 
Label # 
This allows the user to specify the prefix character that will go on the "Label #" column in 
the Arc Flash spreadsheet report.  This field can help in sorting out (organizing) the label 
when they printed out. 
Cable Length From Trip Device 
Reports the total cable length from the protective device that trips to clear the fault to the 
faulted bus. If there is no cable in between, nothing will be reported. 
C# PDF Image Extract Library: Select, copy, paste PDF images in C#
Able to extract vector images from PDF. Extract all images from whole PDF or a specified PDF page. C#: Extract All Images from PDF Document.
how to copy image from pdf file; paste jpg into pdf
VB.NET PDF Image Extract Library: Select, copy, paste PDF images
Able to extract images from PDF in both .NET WinForms and ASP.NET project. using RasterEdge.XDoc.PDF; VB.NET: Extract All Images from PDF Document.
how to copy picture from pdf and paste in word; copy image from pdf to powerpoint
123 
SKM Power*Tools for Windows 
Incident Energy at Low Marginal 
This will report an incident energy value of the bus, if the incident energy on the bus meets 
the low marginal criteria value entered in the PPE. 
Incident Energy at High Marginal 
This will report an incident energy value of the bus, if the incident energy on the bus meets 
the high marginal criteria value entered in the PPE. 
If NESC 2007 method is selected, the following column headers also 
appear: 
SLG Bolted Fault 
Initial Symmetrical RMS single-line-to-ground fault current. (Reported by Comprehensive 
Short Circuit Study.) 
Duration of Arc (sec.) 
The sum of the Trip/Delay Time and the Breaker Opening Time. 
Altitude (feet or meter) 
Altitude of the worksite where the arcing fault could potentially occur.  The unit is in feet or 
meter depending on the unit selection (English or Metric) in the arc flash study option 
window.  This will affect the minimum approach distance. 
Max Over Voltage Factor (T) 
The maximum anticipated per-unit over voltage factor (T) at the worksite determined by an 
engineering analysis. 
3-Phase Multiplier 
Specify here the 3-phase multiplier.  This will affect the calculated incident energy.  The 
calculated incident energy from Table 410-1 and Table 410-2 of NESC 2007 is based 
single-phase system. 
Gap 
Distance of the arc gap 
Type of Work 
Specify here the type of work:  Com (for communications) or Sup (for supply).  This will 
affect the minimum approach distance. 
LL/LG 
Specify here whether the work being done is on a line to line (phase-to-phase) or line to 
ground (phase-to-ground) system.  This will affect the minimum approach distance for 
supply type of work 
Separation Distance 
The distance at which the calculated incident energy from Table 410-1 and Table 410-2 of 
NESC 2007 is based on. 
Minimum Approach Distance 
The distance from any exposed energized part within which an employee could approach. 
VB.NET PDF Page Extract Library: copy, paste, cut PDF pages in vb.
Please refer to below listed demo codes. VB.NET DLLs: Extract, Copy and Paste PDF Page. VB.NET: Extract All Images from PDF Document.
cut and paste pdf image; how to copy pictures from a pdf to word
C# PDF Page Extract Library: copy, paste, cut PDF pages in C#.net
Ability to copy selected PDF pages and paste into The portable document format, known as PDF document, is a they are using different types of word processors.
how to copy picture from pdf; how to copy an image from a pdf in
Rubber Insulating Equipment Class  
The class of rubber insulating sleeves the employee shall wear, in addition to the rubber 
insulating gloves. 
Detail View or Summary View:  
The detail view in the arc flash report lists all parallel contributions and the accumulated 
energy as each contribution is cleared.  The summary view lists only the last branch that 
clears the significant contribution as defined by the "Cleared Fault Threshold" percentage 
specified. 
In the Detail View, the program traces each connected branches to find the protective 
device that trips first in the branch and lists it under the faulted bus.  If the directly 
connected branch doesn’t have a protective device,  the program walks the branch until it 
finds one.   
If standard NFPA is followed, the incident energy is calculated using the bolted bus fault 
current for all protective devices listed under the bus without consider the reduction of fault 
current after some of the devices have been tripped.  If IEEE 1584 is followed, the incident 
energy is calculated by using the arcing bus fault current left at the bus which consider the 
fact that some devices have tripped already and the one that trips later doesn’t see as much 
current. 
In the Summary View, only one device under each bus is listed, and that is the one after it’s 
tripping a user defined percentage (ie… 80%) of the  total fault current would have been 
cleared.  The user can define the percentage in the Arc Flash Study Options dialog (see 
section 1.5.2). 
The data associated with the device listed in the summary view will be used in the Bus 
Detail report and Arc Flash Label. 
VB.NET PDF Convert to Word SDK: Convert PDF to Word library in vb.
is much easier for content editing. Therefore, people usually reuse PDF content by outputting its texts and images to Word file.
how to copy pictures from pdf file; copy image from pdf
C# PDF Convert to Word SDK: Convert PDF to Word library in C#.net
converted by RasterEdge PDF to Word converter toolkit, preserves the structure & layout of target PDF document, keeps the elements (like images, tables and
how to copy a picture from a pdf; copy picture to pdf
125 
SKM Power*Tools for Windows 
Scenarios…  
This button brings up a window where the user can specify to report Arc Flash results based 
on the current scenario opened; or if the project has multiple scenarios, the user can select 
Arc Flash results to report the worst case (the one with the highest incident energy) out all 
of all the selected scenarios.  Furthermore, the user can also select Arc Flash result to report 
the "Best Case Scenario".  The "Best Case Scenario" is the one with the lowest incident 
energy out of all the selected scenarios.   
For instance, if a project has four scenarios, in this window the user can select all of the 
scenarios and select the "Worse Scenario" option button.  When the user clicks on the 
"OK" button, what will be reported by Arc Flash spreadsheet report for each bus is the 
incident energy from the scenario with the highest value. 
Similarly, if a project has four scenarios, in this window the user can select all of the 
scenarios and select the "Best Scenario" option button.  When the user clicks on the "OK" 
button, what will be reported by Arc Flash spreadsheet report for each bus is the incident 
energy from the scenario with the lowest value. 
Selecting worst case will greatly help in printing out the arc flash label for the worst case 
situation for those scenarios selected. 
In the Arc Flash Report, the scenario where the incident energy being reported came from is 
indicated by (*S0), (*S1), (*S3), etc. depending on the scenario number. 
C# Create PDF from Word Library to convert docx, doc to PDF in C#.
Create PDF from Word. |. Home ›› XDoc.PDF ›› C# PDF: Create PDF from Word. C#.NET PDF - .NET XDoc.PDF SDK for Creating PDF from Word in C#.
copy image from pdf to ppt; paste image into pdf acrobat
C# Create PDF from images Library to convert Jpeg, png images to
C#.NET Project DLLs for Conversion from Images to PDF in C#.NET Program. C# Example: Convert More than Two Type Images to PDF in C#.NET Application.
how to copy an image from a pdf to word; how to copy and paste a pdf image
Custom Label.. 
This button will bring up the custom label window where the user can specify the Page 
Size, Label Size, Page Margins, Orientation, Rows and Columns of the labels and Spacing 
between labels  
Work Permit  
This button brings up the window to generates a work permit required for working on 
energized equipment per NFPA 70E 2004 
Re-Run Study  
This button refreshes the Arc Flash display to reflect updated short circuit values caused by 
system changes made since the last arc flash study was run. 
Options… 
This button will display Option menu for Arc Flash Study 
The Arc Flash Options dialog box lets you select options for running the Study. The Arc 
Flash Options dialog box is divided into 3 options tabs: Standard and Units, Fault Current, 
and Report Options. 
The descriptions of the options of each tab follows: 
Standard and Unit 
127 
SKM Power*Tools for Windows 
Standard allows the choice of NFPA 70E, IEEE 1584, or NESC 2007 methods.  If NFPA 
70E method is selected, the equations published in NFPA 70E – 2004 Annex D.6 will be 
used to calculate the incident energy and flash boundary. If the IEEE 1584 method is 
selected, the equations published in the IEEE 1584 2002 and NFPA 70E – 2004 Annex D.8 
will be used to calculate the arcing fault current, incident energy, and flash boundary.  The 
IEEE 1584 method is based on more recent and expanded test data, and is the preferred 
method. Since IEEE 1584 method is also part of the NFPA 70E 2004, using the IEEE 1584 
method could be considered as comply with NFPA 70E as well.  If NESC 2007 method is 
selected, the tables from NESC 2007 are used to calculate the incident energy and 
minimum approach distance. 
Flash Boundary Calculation Adjustments - The Flash Boundary is normally calculated 
by setting the incident energy to 1.2 cal/cm^2 and use the incident energy equation to 
reverse calculate the flash boundary.   An option to use 1.5 cal/cm^2 for equipments above 
1 kV and trip time < 0.1 seconds is provided here.  This is recommended by NFPA 70E – 
2004 (section 130.3 (a) page 70E-25). 
Equipment Below 240 Volts Options
Two separate list boxes are provided due to the difference in applicable voltage criteria to 
the location of the arcing fault in addition to Bolted Fault magnitude or upstream 
Transformer Size presented in IEEE 1584 and NFPA 70E standards.  
 The first list box represents the Equipment Voltage range and the choices are "<= 
240 V" (equal to 240 V or below) referred to NFPA 70E Std Table 
130.7.(C)(9)(a), or "< 240 V" ( less than 240 V) referred to IEEE 1584-2002 Std. 
 The second list box provides the following options: 
- Option1: Report as Category 0 if Bolted Fault < 10 kA. Referred to Note 3 
in Table 130.7.(C)(9)(a) of NFPA 70E-2004 Std. 
- Option2: Report as Category 0 if Transformer Size < 125 kVA. Referred to 
IEEE 1584-2002 Std. 
 Option3: Report as Category 0 if Bolted Fault < 10 kA or Transformer Size < 125 
kVA. 
 Option4: Report as Category 0 if Bolted Fault < 10 kA and Transformer Size < 
125 kVA. 
 Option5: Report Calculated Values From Equations. Use normal incident energy 
calculation methodology. 
If option 1, 2, 3, or 4 is selected, and the calculated incident energy is smaller than 1.2 
cal/cm^2, the calculated value will be reported and used to calculate the flash 
boundary. If the calculated incident energy is greater than 1.2 cal/cm^2, it will be 
reported as 1.2 cal/cm^2. 
English or Metric Units – For NFPA 70E – 2004, IEEE 1584 - 2002 standards,  or 
NESC 2007, we allow the choice of English or Metric units.   
If the English units option is selected, the incident energy is in Calories/cm
2
. The 
working distance and flash boundary can then be in inches or feet.   
If the Metric units option is selected the incident energy can then be in Joules/cm
or 
Calories/cm
2.
The working distances and flash boundary can then be in mm, cm, or m. 
Fault Current 
Maximum Arcing Time Duration allows you to specify a maximum (Trip Time + Breaker 
Time) for the incident energy and flash boundary calculations.   IEEE 1584 Annex B.1.2 
stated that “If the time is longer than two seconds, consider h h ow long a person is likely to 
remain in the location of the arc flash.  It is likely that the person exposed to arc flash will 
move away quickly if it is physically possible and two seconds is a reasonable maximum 
time for calculations.  A person in a bucket truck or a person who has crawled into 
equipment will need more time to move away.” ”  
The default for the Maximum Arcing Duration in PTW is set to 2 seconds, if the Trip Time 
read from the TCC plus the Breaker Time is bigger than the Maximum Arcing Duration, the 
Trip Time will be set to the Maximum Arcing Duration – Breaker Time.   
Sound engineering judgment is always required when making reasonable arc flash energy 
estimates. 
129 
SKM Power*Tools for Windows 
Use Global Max Arcing Time:  Allow user to enter different maximum arcing 
during for system voltage > 240 Volts and system voltage <= 240 Volts.  
Enter for each bus:  When this option is selected, the user can click on the “Max 
Arcing Time for Each Bus” button, and “Maximum Arci ng Duration for Each 
Bus” window will come up.   See picture below. 
In this window, the user can specify the maximum arcing duration for each buses in the 
system modeled.  For convenience, the user can also sort the window by bus name, bus 
voltage, or maximum arcing duration by selection one of the available options button. 
Furthermore, user can change the maximum arcing duration of all the buses globally by 
clicking on the “Global Change” button.  This helps  in modeling your system accurately for 
arc flash study, since each bus location you are analyzing may have different maximum 
arcing duration depending on the situation. 
Arcing Fault Tolerances… …  
- For the IEEE 1584 standard, specify a low and high tolerance for arcing fault current 
calculations.  For example, enter a –15% low and +1 0% high tolerances means the program 
will calculate two incident energies one at 0.85* arcing fault current, and another at 1.1* 
arcing fault current.  For the NFPA 70E standard, specify the percentage of bolted fault 
current used to calculate the second incident energy.  For example, enter a 38% bolted fault 
current means the program will calculate two incident energies one at 100% of the bolted 
fault current and another at 38% of the bolted fault current. 
The arcing fault current magnitude is a function of the voltage and arc impedance.  Since a 
small change in arcing fault current can produce substantially different trip times and 
incident energy, it is prudent to account for arcing fault current variability through 
reasonable tolerances.  The IEEE 1584 standard uses a 15% low tolerance for arcing fault 
current calculations, and the NFPA 70E suggests using a 38% bolted fault current.  The 
incident energy is calculated at the low and high tolerance specified and the largest incident 
energy is reported.  For cases where both the low and high tolerance values result in the 
same trip time, the high tolerance will always produce the highest incident energy.  For 
cases where the low tolerance results in longer trip times, which is often the case, the 
incident energy is typically higher at the longer trip time.  In the arc flash table, the value is 
labeled with (*3) when the low tolerance arc fault value is used 
Pre-Fault Voltage options… 
This button allows the user to specify the pre-fault voltage options for the short circuit 
study. 
Documents you may be interested
Documents you may be interested