SKM Power*Tools for Windows 
Export to 
This selection allows users to export the result 
into excel, *.htm, or *.ss3 file formats. 
User defined Arc Flash Table 
This option selection displays the user “User 
defined Arc Flash Table” where the user can 
enter any user-defined bus voltage, fault 
current, and arcing duration and it will 
calculate the incident energy and flash 
boundary results.  You can also click on the 
“Custom Label” button it will produce arc 
flash label based on those results. 
Include non 3-phase system 
Includes non 3-phase system buses to the Arc 
Flash display and report 
Study Options 
This option selection will display Option 
menu for Arc Flash Study 
Study Options Report 
This option selection will display a window 
where the user can print the options that have 
been selected in the Option menu for Arc 
Flash Study 
Font, Page Margin  
This option selection will display a window 
where the user can select the type of font to 
use for the arc flash report  
Print/Export Option 
This option selection will display a window 
where the user can change page margin, and 
page number display for printing.   
The same menu items are available by clicking the Right Mouse button. 
Notes Section  
(*N1) - Out of IEEE 1584 or NFPA 70E Ranges. LEE equation is used in this case and 
applicable for Open Air only.   
(*N2) - Percentage of fault current cleared is less than the Cleared Fault Threshold 
specified in the study options 
(*N3) - Arcing Fault Current Low Tolerances Used.  
(*N4) - Equipment Specific Incident Energy and Flash Boundary Equations Used. 
(*N5) - Mis-coordinated, Upstream Device Tripped.   
(*N6) - Special Instantaneous Protection in Use.  Refer to Bus Equipment & Arc Flash 
subview.  
(*N7) - Trip Time Unlinked with TCC. 
(*N8) - Fault Current Unlinked with Fault Study results. 
(*N9) - Max. Arcing Duration Reached.  The time taken for the protective device to clear 
the fault is longer than the Max. Arcing Duration is specified in the study options.   
Cut and paste pdf image - copy, paste, cut PDF images in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Detailed tutorial for copying, pasting, and cutting image in PDF page using C# class code
copy image from pdf reader; copy images from pdf file
Cut and paste pdf image - VB.NET PDF copy, paste image library: copy, paste, cut PDF images in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
VB.NET Tutorial for How to Cut or Copy an Image from One Page and Paste to Another
copy picture from pdf; how to cut an image out of a pdf
(*N10) - Fuse Cable Protector Modeled.  Fuse Cable Protector Modeled is when the fuse is 
connected to a cable with multiple conductors in parallel. The fault current and arcing fault 
through the fuse is divided by the #parallel to read the trip time. 
(*N11) - Out of IEEE 1584 Range, Lee Equation Used. Applicable for Open Air only.  
Existing Equipment type is not Open Air.  This shows only if data at the bus is out of the 
IEEE 1584 Range and the selected equipment is not an Open Air type. 
(*N12) - Out of IEEE 1584 Gap Range 
(*N13) - PPE up one Category.   
(*N14)  - Zone Selective Interlock (ZSI) in Use.  If one of the protective device directly 
connected to the bus has a ZSI function, the bus is considered having instantaneous 
protection and the trip time become user-definable in the Arc Flash main window. 
(*N15) - Bolted Fault < 10 kA or Transformer Size < 125 kVA, Report as Category 0 
(*N20) - Out of NESC Voltage Range. 
(*N21) - Out of NESC Fault Current Range. 
(*N22) - Out of NESC Max Clearing Range. 
(*N23) - Out of NESC Voltage Range. 
(*N24) - Out of NESC Altitude Range. 
(*N25) - Out of NESC Max Over Voltage Factor Range. 
(*N26) - NESC SLG Fault is Zero 
(*S0), (*S1),(*S2),..etc – Indicates which scenario  the incident energy being reported came 
from. 
C# PDF Page Extract Library: copy, paste, cut PDF pages in C#.net
C#.NET PDF Library - Copy and Paste PDF Pages in C#.NET. Easy to C#.NET Sample Code: Copy and Paste PDF Pages Using C#.NET. C# programming
paste image into pdf preview; how to copy picture from pdf to powerpoint
VB.NET PDF Page Extract Library: copy, paste, cut PDF pages in vb.
Dim page As PDFPage = doc.GetPage(3) ' Select image by the New PDFDocument(filepath) ' Copy the first page of PDF document. VB.NET: Copy and Paste PDF Pages.
how to copy pictures from pdf; cut and paste pdf image
153 
SKM Power*Tools for Windows 
Important Concepts:  
No Protective Device To Clear the Fault 
You may wonder why is there no protective device bolted fault or arcing fault current 
reported for protective “BUS-001” of the Arc Flash  Evaluation table in the Tutorial project.  
From the one-line, you can see fuse “PD-001” is con nected to this bus, why didn’t any fault 
current show up? 
Careful inspection of the fault study result from the following picture shows that for a fault 
at BUS-001, the bus fault current is 8367 Amps, but the current from the down stream 
branch through fuse PD-0001is zero.   This is because the load down stream is a non-motor 
load.  All of the contribution therefore comes from the Utility.  Since there are no protective 
devices specified between the utility and the bus, the fault can’t be cleared.  The PPE 
requirement is listed with the (*N2) indicates that the Cleared Fault Threshold percent 
specified in the Study Setup was not reached.   
Note that where a protective device is not found or where the trip time is longer than a few 
seconds that additional review may be required to account for how much energy is released 
before the worker can move to a safer distance.  For example, you may want to check the 
energy generated over the first few seconds to see if the worker would be capable of 
moving out of the way, or if most of the damage is already done.  This check can be done 
by setting the Maximum Arcing Duration to 2 seconds.  In the example above, (*N9) 
indicates that the time taken for the protective device to clear the fault is longer than the 
Max. Arcing Duration is specified in the study options.   
C# PDF remove image library: remove, delete images from PDF in C#.
document page. Able to cut and paste image into another PDF file. Export high quality image from PDF document in .NET program. Remove
cut and paste image from pdf; paste image into pdf form
C# PDF Convert to Images SDK: Convert PDF to png, gif images in C#
Converter control easy to create thumbnails from PDF pages. Selection for compressing to multiple image formats. Cut and paste any areas in PDF pages to images.
pasting image into pdf; how to copy pdf image into word
Important Concepts:  
Effects of Trip Time 
To demonstrate the effects of trip time, change the Short Time Delay (STD) setting for 
breaker PD-0003 from 0.1 to 0.32 seconds.  This can be done in the Component Editor or 
from the TCC drawing you created in Section 3 as shown: 
Note that when this change was made, the Arc Flash calculation was updated to reflect the 
new trip time for an arcing fault at Bus-0003.  The trip time changed from 0.158 seconds to 
0.494 seconds, the flash boundary increased from 25 inches to 51 inches, and the incident 
energy increased from 2.11 cal/cm2 to 6.6 cal/cm2.  The higher energy results in a clothing 
class change from 1 to 2. 
C# PDF Image Extract Library: Select, copy, paste PDF images in C#
PDF ›› C# PDF: Extract PDF Image. How to C#: Extract Image from PDF Document. Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document.
paste picture to pdf; copy pdf picture to word
VB.NET PDF Image Extract Library: Select, copy, paste PDF images
Home ›› XDoc.PDF ›› VB.NET PDF: Extract PDF Image. Support PDF Image Extraction from a Page, a Region on a Page, and PDF Document in VB.NET Project.
cut and paste pdf images; how to paste a picture into a pdf
155 
SKM Power*Tools for Windows 
According to the results above, if the fault is on “Bus-0003”, “PD-0003” will see an arcing 
fault current of 4.31 kA and will trip at 0.494 seconds.  To verify this we can go to the 
TCC.  Open or make “TCC1.TCC” active.  Select “PD-0
003” and then click on the 
Settings>Selected Device Settings.. command.  A window, similar to the one below will 
show up.  Click on the “Arcing Fault and UDF Flags” ”  and then, check on the “Show Arcing 
Fault current for Worse case Incident energy” and ” ” Show Other Arcing Fault Current 
(dash-dot)” check boxes.  Also make sure to highlig ht the “Bus-0003” bus.   
Click on the OK button. 
VB.NET PDF url edit library: insert, remove PDF links in vb.net
position, such as PDF text, image and PDF table. Delete or remove partial or all hyperlinks from PDF file in VB.NET class. Copy, cut and paste PDF link to
how to cut an image out of a pdf file; how to copy pdf image to jpg
How to C#: Basic SDK Concept of XDoc.PDF for .NET
s), and add, create, insert, delete, re-order, copy, paste, cut, rotate, and And PDF file text processing like text writing, extracting, searching Image Process.
copy pdf picture to powerpoint; copy a picture from pdf to word
A TCC window should now be similar to the one above.  The TCC will now show two 
vertical lines.  One showing the arcing fault current for worse case incident energy (dark 
line) and the other showing the non-worse case arcing fault current (dashed line).  With the 
arcing fault flags shown on the TCC, we can easily see and verify that at 4.31 kA, “PD-
0003” will trip at 0.494 seconds. 
On the TCC, you can also plot the C-lines.  Constant incident energy line (C-Line) is a 
sloped line on a TCC that describes the relationship of a finite series of time and current 
combinations for which energy remains constant.  For buses or system with single source of 
contribution, this C-Line can then be used as an aid in overcurrent device coordination to 
demonstrate visually which setting regions might be adjusted to reduce the arc flash hazard.   
At 4.31 kA, “PD-0003” 
will trip at 0.494 seconds 
157 
SKM Power*Tools for Windows 
In our example, select the “PD-0003” curve on the T CC.  Right-mouse click and then select 
“Selected Device Setting” option.  On the window th at comes up select the “Arcing Fault 
and UDF Flags” tab.    
In this window click on the checkboxes for the “Sho w User Constant Category Line or User 
Define C-line”, “Extend to Pickup”, and the “Catego
ry C-Lines.”   For the current “From” 
and “To” field, enter in 10 and 100,000.0consecutiv ely.  Click the “OK” button. 
The C-lines on the example above represents the top incident energy range of each PPE 
category per NFPA 70E standard PPE table.  With the “PD-0003” STD setting = 0.32, you 
can see from the TCC above that the worst case arcing current flag hits the trip curve 
between Category 2 and Category 1 C-line.  From here, we can visually see from the TCC 
that the resulting incident energy for this particular setting will result in a Category 2 
situation.  This matches the result of the software for “Bus-0003”. 
The worst case arcing 
current flag hits the trip 
curve between Category 
2 and Category 1 C-line. 
159 
SKM Power*Tools for Windows 
Important Concept:  Accumulated Energy from Multiple Contributions 
The concept of accumulated energy is based on conditions where parallel contributions feed 
a single fault location.   Referring to the following diagram, a fault at MCC1 Bus is fed 
from three parallel contributions (Utility, Generator, Motor).  Each contribution will trip at 
a different time and the worker will be exposed to a varying amount of energy as each 
branch trips.   
Trips in 0.5 Sec.
(6kA Arcing Fault)
Fault 
Location
Trips in 0.07 Sec
(14kA Arcing Fault)
Trips in 39 Seconds
(0.9 kA Arcing Fault)
Motor Contribution 
Decays within first 
6 cycles
MCC1 Bus
C1
U1
G1
C2
C3
M1
Utility Fuse
LVB3
Generator Fuse
LVB1
LVB2
For this example, the worker is exposed to all three contributions for the first 0.07 seconds, 
the motor and generator for the next 0.03 seconds, and the generator contribution for 
another 0.4 sec.   
The Arc Flash study reports the accumulated energy from all three contributions.  If the 
Utility had been the only significant contribution, the energy would have been accumulated 
only for the first 0.07 seconds, the time when the utility contribution was cleared.  In this 
case, the utility is 67% of the total and the generator contribution was 28% of the total.  
Therefore both the utility and generator were both determined to be significant 
contributions as defined by the 80% “Cleared Fault  Threshold” percentage specified.  Both 
the Utility and the Generator must trip before the 80% Cleared Fault Threshold is reached. 
Important Concept:   Detail View versus Summary View  
The detail view in the arc flash report lists all contributions to the location of the fault and 
the accumulated energy as each contribution is cleared. The summary view lists only one 
protective device with the final accumulated incident energy. As mentioned before, the 
selection and display of this device is based on the chosen Labels and Summary View 
Report Options. 
If the Labels and Summary View Report Option is set to “Report Last Trip Device”, the 
Summary View will list the last device to trip whereby the accumulated current tripped 
meets or exceeds the specified Cleared Fault Threshold percent (for example when at least 
80% of total fault current has cleared). 
If the Labels and Summary View Report Option is set to “Report Main Device”, the 
Summary View will list the device that carries the largest percentage of the fault 
contribution to the bus. 
In the following example, 3 branches contribute current to the bus as the location of the 
fault.  
Arcing Fault
7.76 kA 
Arcing Fault
2.24 kA 
Arcing Fault
0.67 kA 
Gen-Bus
UTIL
TX1
GEN
C1
M1
R-Util
R-Gen
R-M1