Setting up communications                  Chapter 9 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
181 
A FactoryTalk View SE network application can contain more than one 
RSLinx data server, and you can create multiple data servers in a single area. 
A local application can contain only one RSLinx Enterprise data server, 
which must be located on the same computer as the application. 
To add an RSLinx Enterprise data server: 
1.  In FactoryTalk View Studio, in the Explorer window, right-click the 
application root or an area name, select Add New Server > Rockwell 
Automation Device Server (RSLinx Enterprise)
2.  In the RSLinx Enterprise Properties dialog box, select options and 
provide information in each tab, as described in the sections that 
follow. 
3.  When you are finished, click OK
Setting up general properties 
In the General tab of the RSLinx Enterprise server’s Properties dialog box, 
type a name and description for the data server, and specify the name of the 
computer that will host the data server. 
Name 
Type a name for the data server. This name will be shown in the Explorer 
window. The name cannot include dashes or hyphens ( 
). 
Adding RSLinx 
Enterprise data 
servers to an 
application 
Add hyperlinks pdf file - insert, remove PDF links in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Free C# example code is offered for users to edit PDF document hyperlink (url), like inserting and deleting
add links to pdf acrobat; add page number to pdf hyperlink
Add hyperlinks pdf file - VB.NET PDF url edit library: insert, remove PDF links in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Help to Insert a Hyperlink to Specified PDF Document Page
add hyperlink to pdf; add a link to a pdf
Chapter 9                  Setting up communications 
182 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
Description 
Type a description for the data server. For example, the description can 
consist of the server’s location, the name of a contact person or number to 
contact in case of failure, or version information. 
Computer hosting the RSLinx Enterprise server 
Type the name of the computer where the RSLinx Enterprise data server is 
running. To find and select a computer, click the Browse button. 
You can change the name of the computer hosting the data server, only in a 
network application. In a local application, you can only add one RSLinx 
Enterprise data server, which must be located on the same computer as the 
application. 
Setting up RSLinx Enterprise data server 
redundancy 
To minimize disruptions to clients in the event that the RSLinx Enterprise 
server becomes unavailable or fails, set up redundancy for the data server. 
This option is only available for network applications. 
In the Redundancy tab of the RSLinx Enterprise server’s Properties dial
og 
box, specify the name of the secondary (or backup) data server, and whether 
FactoryTalk View should switch back to the primary data server when it 
becomes available again. 
C# PDF Convert to HTML SDK: Convert PDF to html files in C#.net
Export PDF images to HTML images. Embed PDF hyperlinks to HTML links. Add necessary references: RasterEdge.Imaging.Basic.dll. using RasterEdge.XDoc.PDF;
adding links to pdf; add hyperlink to pdf in
VB.NET PDF Convert to HTML SDK: Convert PDF to html files in vb.
Embed PDF hyperlinks to HTML links in VB.NET. Add necessary references: This professional .NET solution that is designed to convert PDF file to HTML web page
pdf links; pdf link open in new window
Setting up communications                  Chapter 9 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
183 
Tip: 
In a local application, there is no Redundancy tab in the 
RSLinx Enterprise Server Properties dialog box. Local 
applications do not support data server redundancy. 
When changing the redundancy setting (from 
non-redundant to redundant or vice-versa), for the 
he 
changes to take effect, you must restart the computers 
hosting the redundant pair, and restart the computer 
hosting the FactoryTalk Network Directory Server. 
Provide redundancy using a secondary server 
Select or clear this check box, depending on whether you want to set up 
redundancy for the data server. 
Computer running the secondary server 
Type the name of the computer where the secondary data server is running. 
To find and select a computer, click the Browse button. 
Switch back options 
To prevent FactoryTalk View SE from switching back to the primary data 
server when it becomes available, select the option, Continue using the 
secondary server even when the primary becomes available again
To make FactoryTalk View SE switch back to the primary data server when 
it becomes available, select the option, Switch over to the primary server 
when it becomes available again
Setting up support for FactoryTalk Alarms and 
Events 
To enable an RSLinx Enterprise server to use FactoryTalk Alarms and 
Events services to receive and send alarms detected in Logix5000 controllers, 
in the Alarms and Events tab in RSLinx Enterprise Server Properties dialog 
box, select the check box, Enable alarm and event support. 
For more information, see Setting up FactoryTalk alarms on page 261
Deleting an RSLinx Enterprise data server 
If an RSLinx Enterprise data server is no longer required, you can delete it 
from the application. 
To delete an RSLinx Enterprise data server: 
In FactoryTalk View Studio, in the Explorer window, right-click the RSLinx 
Enterprise data server you want to delete, and then click Delete
VB.NET PDF Page Replace Library: replace PDF pages in C#.net, ASP.
all PDF page contents in VB.NET, including text, image, hyperlinks, etc. Add necessary references to replace a PDF page with PDF page from other PDF file using VB
accessible links in pdf; add hyperlink to pdf online
VB.NET PDF Thumbnail Create SDK: Draw thumbnail images for PDF in
PDF document is an easy work and gives quick access to PDF page and file, or even hyperlinks. How to VB.NET: Create Thumbnail for PDF. Add necessary references:
pdf reader link; add links to pdf in preview
Chapter 9                  Setting up communications 
184 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
Use the RSLinx Communication Setup editor to add or remove drivers and 
devices, set up driver and device properties, create device shortcuts, enable 
shortcuts to support FactoryTalk Alarms and Events services, or browse for 
tags in an offline tag file. 
To open the Communication Setup editor: 
1.  In FactoryTalk View Studio, in the Explorer window, click the + 
symbol beside the RSLinx Enterprise data server icon. 
2.  Double-click the Communication Setup icon. 
For details about options in the Communication Setup editor, click Help
About the Primary and Secondary tabs 
If you have not set up redundancy for an RSLinx Enterprise data server, the 
Communication Setup editor will contain only a Primary tab. 
In a network application, if you set up both a primary and a secondary 
RSLinx Enterprise data server, the Communication Setup editor has a 
Primary and a Secondary tab. 
You can use these tabs to point RSLinx Enterprise at different networks or 
different hardware in case of failure. 
Note: 
When specifying device shortcuts for a redundant server pair, 
be sure to use exactly the same shortcut names for the 
primary and secondary servers. If the names are not the 
same, tag references that use these shortcuts will not be able 
to obtain data reliably. 
Setting up 
communications for 
RSLinx Enterprise 
PDF Image Viewer| What is PDF
with advanced capabilities, such as text extraction, hyperlinks, bookmarks and NET Imaging SDK, you may add it on you to quickly convert your PDF images into
pdf link to attached file; adding hyperlinks to pdf files
.NET PDF SDK | Read & Processing PDF files
by this .NET Imaging PDF Reader Add-on. Include extraction of text, hyperlinks, bookmarks and metadata; Annotate and redact in PDF documents; Fully support all
adding links to pdf document; add url to pdf
Setting up communications                  Chapter 9 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
185 
Add an OPC data server for use with RSLinx Classic or KEPServer 
Enterprise for use with third-party devices such as Modicon or Siemens. 
You can add more than one OPC data server to a local or a network 
application. In a network application, an area can contain multiple OPC data 
servers. 
For details about adding RSLinx Enterprise data servers, see Using multiple 
data servers in an application on page 178
To add an OPC data server: 
1.  In FactoryTalk View Studio, in the Explorer window, right-click the 
application root or an area name, select Add New Server > OPC Data 
Server
2.  In the OPC Data Server Properties dialog box, select options and 
provide information in each tab. 
3.  When you are finished, click OK
Setting up general properties 
In the General tab of the OPC Data Server Properties dialog box, type a name 
and description for the data server, and specify a computer and an OPC 
server name. 
Name 
Type a name for the data server. This name will be shown in the Explorer 
window. The name cannot include dashes or hyphens ( 
). 
Description 
Type a description for the data server. For example, it can describe the 
server’s location, the name of a con
tact person or number to contact in case 
of failure, or version information. 
Computer that will run the OPC server 
Type the name of the computer where the OPC server is running. To find and 
select a computer, click the Browse button. 
Adding OPC data 
servers to an 
application 
Chapter 9                  Setting up communications 
186 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
Tip: 
The Browse button is available only if you select the 
option, Server will be hosted on remote computer. 
OPC server name (Prog ID) 
Type the programmatic ID of theOPC server. To browse for the 
programmatic ID, click the Browse button. 
To use RSLinx Classic as the OPC server, click the Browse button, and then 
click RSLinx Remote OPC Server. 
Tip: In a network application, always select RSLinx Remote 
OPC Server, instead of RSLinx OPC Server. 
Setting up OPC data server redundancy 
To minimize disruptions to clients in the event that the OPC server becomes 
unavailable or fails, set up redundancy for the data server. This option is only 
available for network applications. 
In the Redundancy tab of the OPC server’s Properties dialog box, specify the 
name of the secondary (or backup) data server, and whether FactoryTalk 
View should switch back to the primary data server when it becomes 
available again. 
Tip: 
For a local application, there is no Redundancy tab in the 
OPC Data Server Properties dialog box. Local 
applications do not support data server redundancy. 
Provide redundancy using a secondary server 
Select or clear this check box, depending on whether you want to set up 
redundancy for the data server. 
Setting up communications                  Chapter 9 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
187 
Computer running secondary server 
Type the name of the computer where the secondary data server is running. 
To find and select a computer, click the Browse button. 
Switch back options 
To prevent FactoryTalk View SE from switching back to the primary data 
server when it becomes available, select the option, Continue using the 
secondary server even when the primary becomes available again
To make FactoryTalk View SE switch back to the primary data server when 
it becomes available, select the option, Switchback to the primary server 
when it becomes available
Setting up advanced properties 
In the Advanced tab, set up a cache for tags on the data server. A cache lets 
you view tag names when you are not connected to the data server. 
Include extended information in the server cache file 
Select this check box to make available additional information about tags, for 
example, their data types, when you are not connected to the data server. 
To create a data server cache: 
1.  To provide the list of tags, ensure that the OPC data server is running, 
and that the devices are connected. 
2.  In the Advanced tab of the OPC Data Server Properties dialog box, 
select the check box, Include extended information in the server 
cache file
3.  Click Create Cache, and then click OK
Chapter 9                  Setting up communications 
188 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
Synchronizing a data server’s cache
If tags are added, modified, or deleted on the data server, you must 
synchronize the cache manually. You can synchronize a data server’s cache 
only after you have created one. 
To synchronize a data server’s cache:
1.  To provide the list of tags, ensure that the OPC data server is running, 
and that the devices are connected. 
2.  In FactoryTalk View Studio, in the Explorer window, right-click the 
data server, and then click Properties
3.  In the Advanced tab of the OPC Data Server Properties dialog box, 
click Synchronize, and then click OK. 
Deleting an OPC data server 
If an OPC data server is no longer required, you can delete it from the 
application. When you delete a data server, its cache files are also deleted. 
To delete an OPC data server: 
In FactoryTalk View Studio, in the Explorer window, right-click the OPC 
data server you want to delete, and then click Delete
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
189 
Chapter 10 
Working with tags 
This chapter describes: 
Data server tags, HMI tags, and their attributes. 
Using tag data in a FactoryTalk View Site Edition application. 
How tag references work. 
Parts of the Tag Browser. 
Searching for and selecting tags. 
Browsing for offline tags. 
What HMI tags are. 
How to organize HMI tags. 
Parts of the HMI Tags editor. 
Creating, modifying, and deleting HMI tags. 
Selecting a data source for HMI tags. 
Creating HMI tags without using the Tags editor. 
Defining alarm conditions for HMI tags. 
FactoryTalk View Site Edition conforms to the OPC-DA 2.05a specification 
for exchanging data among automation or control applications, field systems 
or devices, and business or office applications. 
A tag is a logical name that represents a variable in a network device or in a 
computer’s memory (RAM). In FactoryTalk View Site Edition , you can use 
two types of tags: 
Data server tags (also called direct reference tags, or data items in the 
OPC-DA specification) provide direct access to the basic attributes of 
all OPC-DA-compliant tags, through data servers you add to an 
application. 
HMI tags provide additional properties for run-time security and data 
manipulation. HMI tags are created in the Tags editor and stored in an 
HMI server’s tag database. For information about HMI tags, see 
sections in this chapter starting on Working with HMI tags on page 
204
About data server 
tags and HMI tags 
Chapter 10                  Working with tags 
190 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
Using direct referencing to eliminate duplication 
For some uses in an application, using direct references to tags in devices, or 
to tags located in an OPC server’s database, offers advantages over using 
HMI tags. 
For example, use data server tags to add, modify, or delete tags in a device 
without having to duplicate the changes in the HMI server’s tag database.
Providing access to complex data types 
Some devices (Logix5000 controllers, for example) support data types such 
as arrays and structures, which can contain hundreds of member elements. 
Use data server tags to reference the tag values directly, and eliminate the 
need to create an HMI tag for each member element. 
Using the extended capabilities of HMI tags 
To take advantage of extended capabilities, such as run-time security, scaling 
or offsetting of tag values, or more flexible addressing, you can create HMI 
tags in FactoryTalk View Studio, in the Tags editor. 
Securing tag or device values 
HMI tags let you secure tag or device values at run time. 
For example, to prevent users from changing a value in a device, create an 
HMI tag for the device’s address, and then assign a security code to the HMI 
tag. For details, see Assigning security codes to HMI tags on page 104
Scaling and offsetting values 
HMI tags provide scale and offset capabilities, which are not supported by 
some data servers. 
Use scale and offset to modify the raw data that comes from the network 
device before it is saved in the computer’s memory, or to modify a value 
specified in FactoryTalk View before it is written to a device or data server. 
Scale is a multiplication factor 
the value from the device is multiplied by 
the scale. Offset is a fixed value 
after the value from the device is 
multiplied by the scale, the offset amount is added. 
Specifying minimum and maximum values 
With HMI tags, you can specify the minimum and maximum values that can 
be written to the network device or data server. 
Documents you may be interested
Documents you may be interested