Working with tags                  Chapter 10 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
201 
Selecting folders instead of individual tags 
You can also select folders in the Tag Browser, for example, to select 
structure tags for faceplate objects. 
When you select a folder, you select all the member elements in the folder. 
Instead of a tag name, the folder name is shown under Selected Tag, as 
shown in the next illustration 
S
howing a tag’s properties
To show the properties of a tag in the Tag Browser, right-click the tag, and 
then click Properties. The Tag Properties dialog box shows information 
about the tag. 
The properties are a snapshot, and do not update in real time. You cannot 
show the properties of multiple tags at the same time. 
Adding an email link to a pdf - insert, remove PDF links in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Free C# example code is offered for users to edit PDF document hyperlink (url), like inserting and deleting
pdf link to email; add hyperlink to pdf in preview
Adding an email link to a pdf - VB.NET PDF url edit library: insert, remove PDF links in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Help to Insert a Hyperlink to Specified PDF Document Page
c# read pdf from url; add link to pdf
Chapter 10                  Working with tags 
202 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
Tip: 
By default, the Tag Browser does not show tag 
descriptions. To show or hide tag descriptions, right-click 
a blank area of the right pane, and then select Show 
Description. 
Filtering tags 
To show only tags whose names match a pattern, type the pattern in the Tag 
Filter list box, and then press Enter. 
The Tag Filter list contains the last 10 filters you applied. You can create 
filters using wildcard characters:  
This wildcard character 
Does this 
Matches any single character. 
Matches any number of characters, including the 
backslash ( \ ) character. 
To remove a tag filter: 
In the Tag Browser, in the Tag Filter list, click <None>
VB.NET PDF Convert to Word SDK: Convert PDF to Word library in vb.
Create editable Word file online without email. In order to convert PDF document to Word file using VB your VB.NET class application by adding reference directly
adding links to pdf document; change link in pdf
Working with tags                  Chapter 10 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
203 
Creating    modifying, and importing HMI tags 
In the Tag Browser, you can also create new folders for HMI tags, create and 
modify the HMI tags, or import tags from a PLC or SLC database. 
To perform these actions, right-
click in the Tag Browser’s right pane, and 
select: 
New HMI Tag to create a new HMI tag 
Edit HMI Tag to modify an existing HMI tag 
Import PLC Tags to import a tag from another database 
For information about creating HMI tags and modifying their properties, see 
Creating, modifying, and deleting HMI tags on page 209
In the Tag Browser, tags that are available when the application is connected 
to a device are located in the Online folder. Tags that are available from an 
offline file, such as a PLC program file, are located in the Offline folder. 
Browsing for offline tags from RSLinx Enterprise 
For each RSLinx Enterprise shortcut in an application, an Offline and Online 
folder is shown in the Tag Browser. 
Use the Offline folder to browse for tags in a PLC or Logix5000 program 
stored on disk. If the shortcut in RSLinx Enterprise has access to symbols, 
you can also browse for them in the Offline folder. 
For details about browsing offline for tags or adding symbols to a shortcut in 
RSLinx Enterprise, see the RSLinx Enterprise Help. 
To browse an offline file in the Communication Setup dialog box: 
1.  In FactoryTalk View Studio, in the Explorer window, double-click the 
RSLinx Enterprise icon. 
Browsing for offline 
tags 
Chapter 10                  Working with tags 
204 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
2.  Double-click Communication Setup to open the RSLinx Enterprise 
Communication Setup dialog box. 
3.  Click the Browse button beside Offline Tag File. 
Browsing from RSLinx Classic 
For each RSLinx Classic topic in an application, an Offline and an Online 
folder is shown in the Tag Browser. 
Use the Offline folder to browse for tags in a PLC or Logix5000 program 
stored on disk. If the RSLinx topic can gain access to symbols, you can also 
browse for the symbols in the Offline folder. 
For details about adding symbols to a topic in RSLinx, see the RSLinx 
Classic Help. 
Browsing from other OPC servers 
To browse for offline tags from OPC servers other than RSLinx Classic, set 
up a data server cache. 
When you are not connected to the device, you will find the offline tags in 
the same Tag Browser folder that contains the online tags. (In RSLinx, the 
offline tags are located in a separate folder.) 
For details about setting up and managing an OPC data server’s cache files, 
see Setting up advanced properties on page 187
In FactoryTalk View SE, HMI servers have tag databases that can store HMI 
tags. 
You can use HMI tags in an application, to take advantage of extended 
properties for securing tag or device values, manipulating data, or triggering 
alarms. 
You can create HMI tags, or modify the properties of existing tags, in 
FactoryTalk View Studio, in the Tags editor. For more information, see 
Creating, modifying, and deleting HMI tags on page 209.In a network 
distributed application, you can create or modify HMI tags locally (on the 
same computer) or remotely (in FactoryTalk View Studio on a different 
computer). 
HMI tag types 
An HMI server’s tag database
can contain the following types of tags. 
Working with HMI 
tags 
Working with tags                  Chapter 10 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
205 
Tag 
Type of data stored 
Analog 
Range of values. 
HMI analog tags can represent variable states such as temperature or the position of rotary controls. 
Digital 
0 or 1. 
HMI digital tags can represent devices that can only be on or off, such as switches, contacts, and relays. 
String 
ASCII string, series of characters, or whole words (maximum of 82 characters). 
HMI string tags can represent devices that use text, such as a bar code scanner that uses an 
alphanumeric product code. 
System 
Information generated while the system is running, including HMI tag alarm information, system time and 
date, and so on. 
FactoryTalk View creates system tags when it creates an HMI project. The system tags are stored in the 
tag database, in the folder called System. You can use system tags anywhere you would use any other 
type of tag. You cannot modify system tag properties. 
Data sources for HMI tags 
When creating an HMI analog, digital, or string tag, you specify the source 
of the tag
’s values. This is called the data source.
You can specify two types of data source for an HMI tag: 
An HMI tag with device as its data source receives data externally, 
from a source other than FactoryTalk View SE. 
The data can come from a programmable controller or other device via 
RSLinx, or from another OPC or DDE data server. 
An HMI tag with memory as its data source receives data internally, 
from FactoryTalk View SE. 
A memory tag can be used to store values internally. 
About retentive memory tags 
By default, the value of an HMI memory tag reverts to the initial value 
specified for the tag, whenever the HMI server containing the tag is shut 
down and restarted. 
To set up a memory tag to retain the last value it was set to, even after the 
HMI server is shut down, in the Tags editor, select the Retentive check box 
for the tag. 
A retentive memory tag will always have the last value it had prior to the 
HMI server shutting down. In other words, the tag’s value will not revert to 
the initial value specified for the tag. 
To make HMI tags easier to work with, especially if the tag database is large, 
organize related tags by establishing naming conventions for them, or by 
Organizing HMI tags 
Chapter 10                  Working with tags 
206 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
grouping them in folders. 
Naming HMI tags 
Establishing naming conventions for HMI tags makes using wildcard 
characters more effective, when searching for and displaying tags during 
development and at run time. 
Tag names can use up to 255 characters of the following types: 
A to Z (upper and lower case) 
0 to 9 
Underscore ( _ ) and dash ( 
For HMI tags stored in folders, the folder name becomes part of the tag 
name, and the backslash that separates folder names counts as one character. 
Tag names can be mixed case. Tag names preserve upper and lower case for 
readability but they are not case sensitive. For example, the tag name 
MixerValve1 is the same as mixervalve1. 
Enclosing tag names in brackets 
In an expression, tag names that start with a number or contain a dash must 
be enclosed in brackets, for example, {N33-0}. 
Also use brackets with wildcard characters to represent multiple tags in an 
expression, for example, {alarm*}. 
For more information about using tags in expressions, see Adding logic and 
control on page 631
Grouping HMI tags in folders 
To organize tags, create folders in the Tags editor, for tags that are related to 
one another. 
When naming tags stored in a folder, to separate the folder name from the 
rest of the tag name, use a backslash ( \ ). For example, the names of tags in a 
folder called Pump would start with Pump\. 
To further organize tags, you can also nest folders. For example, if a plant is 
divided into zones, you can organize the tag database first by zone, then by 
machines in the zone, and finally by devices in each machine. In this case, 
the names of tags in the nested folder might start with 
Area1\Machine1\Pump
Working with tags                  Chapter 10 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
207 
Tip: 
Do not place all HMI tags in the root folder of the 
database. HMI tags contained in nested folders do not 
contribute to the total number of tags in the root folder. It 
is recommended that you limit the number of tags in any 
folder to less than 2000. 
For details about creating, duplicating and deleting folders in the Tags editor, 
see the FactoryTalk View Site Edition Help. 
Viewing tag statistics 
The Tag Statistics dialog box shows the number of tags that an HMI server 
contains, and provides information about the tags, such as the date the tag 
database was last modified. 
To view tag statistics: 
1.  In FactoryTalk View Studio, in the Explorer window, open the Tags 
editor. 
2.  From the View menu, select Tag Statistics
In FactoryTalk View Studio, use the Tags editor to: 
Create HMI tags and modify their properties. 
Duplicate and delete HMI tags. 
Create folders to group related tags. 
Duplicate, nest, and delete folders. 
While the Tags editor is open, use items on the View menu and the toolbar, 
to control the editor’s appearance.
To open the Tags editor: 
1.  In FactoryTalk View Studio, in the Explorer window, open the HMI 
tags folder. 
2.  Right-click the Tags icon, and then select Open. 
You can also double-click the Tags icon, or drag the icon into the 
FactoryTalk View Studio workspace. 
Parts of the Tags 
editor 
Chapter 10                  Working with tags 
208 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
The main parts of the Tags editor are the form, the query box, the 
folder hierarchy, and the spreadsheet, as shown in the following 
illustration. 
Accept and Discard buttons 
When you enter information in the Tags editor, the Prev and Next buttons 
change to Accept and Discard buttons. 
Click Accept to save tag and alarm information. Click Discard to cancel 
changes to a tag’s properties.
Form and spreadsheet 
In the upper part of the form, define the basic characteristics of the tag, such 
as tag name, type, security, and specifics related to the tag type. 
In the lower part of the form, specify the data source (where the tag’s values 
will come from). 
To define alarm conditions for an analog or a digital tag, select the Alarm 
check box. To modify alarms once they have been defined, click the Alarm 
button. 
Query box 
Use the query box to select the tags you want to show in the spreadsheet. 
Working with tags                  Chapter 10 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
209 
This means that you can modify tags in different folders without browsing 
the folder hierarchy. You can select a single tag by typing the tag name, or 
select multiple tags by typing wildcard characters. 
This wildcard character 
Does this 
Matches any single character. 
Matches any number of characters, including the backslash ( \ ) character. 
Use this wildcard character by itself, to display all the tags in the tag database. 
Folder hierarchy 
The hierarchy and spreadsheet work together. The hierarchy shows the tag 
folders, and the spreadsheet shows the tags within the folders. 
A folder icon called root is always present in the hierarchy window, at the 
top of the folder hierarchy. This folder contains all the tag folders you and 
FactoryTalk View create. 
If a folder icon has a plus ( + ) sign on it, the folder contains one or more 
nested folders. If the folder’s icon is blank, it does not contain any other 
folders. 
When you nest folders, remember that the backslash in a folder name counts 
as one character in the tag name. 
Use the Tags editor to create, modify, duplicate, and delete HMI tags. 
For details about these operations, see the FactoryTalk View Site Edition 
Help. 
To create an HMI tag: 
1.  In FactoryTalk View Studio, in the Explorer window, open the HMI 
Tags folder, and then double-click the Tags icon. 
2.  In the Tags editor, if you want to add the new tag to a folder, 
double-click the folder in the folder hierarchy window (under the 
Search For field). 
3.  To clear the form and position the cursor in the Name box, click New 
in the form section of the editor. 
If 
you have opened a folder, the folder’s name is inserted in the Name 
box automatically, and the cursor is positioned to the right of the folder 
name. 
Creating, modifying, 
and deleting HMI 
tags 
Chapter 10                  Working with tags 
210 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
4.  Type a name for the tag, and then select its type. 
5.  In the Tag section, specify any additional information required for the 
type of tag you are creating. 
6.  Select a data source and specify the required information. 
7.  Select the Alarm box if the tag is to have an alarm set up for it. 
For more information, see Defining alarm conditions for HMI tags on 
page 215
8.  Click Accept to save the tag to the database. 
To modify a tag: 
1.  In the Tags editor, find and select the tag you want to modify. 
Tag attributes are shown in the form section of the editor. 
2.  Modify selected attributes. 
You can modify all parts of an existing tag, except the tag name and 
tag type. 
3.  Click Accept to save changes. 
To duplicate a tag: 
1.  In the Tags editor, find and select the tag you want to duplicate. 
2.  From the Edit menu, select Duplicate 
You can also click the Duplicate 
button on the editor’s toolbar.
A new row is inserted under the highlighted row. The new row 
contains all the same information except the tag name. 
3.  In the Tag Name field, type a name for the new tag. 
4.  Click Accept
To delete a tag: 
1.  In the Tags editor, find and select the tag you want to delete. 
2.  From the Edit menu, select Delete. 
You can also click the Delete button on the editor’s toolbar.