Setting up HMI tag alarms                  Chapter 11 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
241 
Note: 
Alarm logging must be set up separately on each computer 
running an HMI server that is monitoring tags for alarms; 
otherwise, the settings will have no effect. 
If two HMI servers are running on a computer, the alarm log 
will contain data for both HMI servers. If the hard disk space is 
used up on the computer, alarm logging will stop. 
To open the HMI Tag Alarm Log Setup tool: 
Use one of these methods: 
In FactoryTalk View Studio or the FactoryTalk View SE 
Administration Console, from the Tools menu, select HMI Tag Alarm 
Log Setup
Select Start > All Programs > Rockwell Software > FactoryTalk 
View > Tools > SE HMI Tag Alarm Log Setup
For more information about HMI tag alarm log files, see: 
Adding remarks to the alarm log file at run time on page 247. 
Viewing HMI tag alarm log files on page 245. 
Adding a link to a pdf in preview - insert, remove PDF links in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Free C# example code is offered for users to edit PDF document hyperlink (url), like inserting and deleting
active links in pdf; pdf link to email
Adding a link to a pdf in preview - VB.NET PDF url edit library: insert, remove PDF links in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Help to Insert a Hyperlink to Specified PDF Document Page
adding hyperlinks to pdf files; add hyperlink to pdf acrobat
Chapter 11                  Setting up HMI tag alarms 
242 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
Specifying where log files are stored or printed 
In the Logging tab of the HMI Tag Alarm Log Setup tool, you can specify 
where alarm log files are stored on the computer. The default location is 
C:\Users\Public\Public Documents\RSView Enterprise\SE\AlarmLog
If alarm information is being logged to a printer, you can also specify where 
the information will be printed. For details about options in the Logging tab, 
click Help. 
Specifying when log files are created and deleted 
In the File Management tab of the HMI Tag Alarm Log Setup tool, you can 
specify when alarm log files are created and deleted. 
You can set up the system to create new log files periodically, or you can 
prevent new files from being created. 
In each 24-hour period, up to 26 new files can be created. If you attempt to 
create a 27th file, FactoryTalk View continues logging data to the 26th file. 
At midnight, the sequence starts again with the first new file for the new day. 
You can set up file management to delete log files after a specified period, or 
once a specified number of files have been created. Files scheduled to be 
deleted are deleted whenever a new file is created. 
For example, if you set up logging to start a new file daily, and to delete the 
oldest files every third day, the system will save alarm log files for the 
current day and for the three previous days. The oldest file is deleted 
whenever a new file is created. 
To never delete files, clear the check boxes under Delete oldest files. 
For details about the options in the File Management tab, click Help
Note: 
If file management is set up to delete the oldest files when a 
new file is started, and you are exporting data to an ODBC 
database, make sure you export the data before the oldest file 
is deleted, or the oldest data will be lost. 
Setting up periodic logging to a central ODBC 
database 
In the Central Logging tab of the HMI Tag Alarm Log Setup tool, you can 
set up logging to a central, ODBC-compliant database. 
C# PDF insert image Library: insert images into PDF in C#.net, ASP
viewer component supports inserting image to PDF in preview without adobe this technical problem, we provide this C#.NET PDF image adding control, XDoc
add url pdf; add hyperlink pdf
C# PDF Page Insert Library: insert pages into PDF file in C#.net
applications. Support adding and inserting one or multiple pages to existing PDF document. Forms. Ability to add PDF page number in preview. Offer
add link to pdf acrobat; pdf email link
Setting up HMI tag alarms                  Chapter 11 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
243 
Central logging works by exporting the contents of the alarm log file 
periodically to an ODBC-compliant database. FactoryTalk View supports the 
following ODBC-compliant databases: Sybase SQL Server, Oracle, and 
Microsoft SQL Server. 
For details about options in the Central Logging tab, click Help. 
Setting up security to log alarms to a remote computer: 
If you are logging HMI tag alarms to an ODBC database that is not located 
on the HMI server’s computer, you must change certain DCOM security 
settings. For details, see the FactoryTalk View Site Edition Help. 
Exporting alarm log files manually to ODBC format 
You can also use the FactoryTalk View command AlarmLogSendToODBC, 
to export alarm log file contents manually to an ODBC-compliant database. 
If the specified database table is not ODBC compliant, the export will fail. If 
the table does not exist, FactoryTalk View will try to create one. 
When you export data to an ODBC table, FactoryTalk View keeps track of 
the data in a control file called Alarm.exp, which is located in the same path 
that stores the alarm log .dat files. Whenever you export data, only the 
newest data is exported. 
However, if the control file is deleted, all the alarm log data in the .dat files is 
exported when the AlarmLogSendToODBC command is run. 
Example: Exporting alarm log files to ODBC format on demand 
To export the contents of the alarm log files to an ODBC-compliant database 
on demand, create a graphic display containing a button that uses the 
AlarmLogSendToODBC command as its press action. 
When the operator presses the button at run time, the contents of the alarm 
log file will be exported to the ODBC database. 
The AlarmLogSendToODBC command exports only the records added to 
the alarm log files since the last export. 
ODBC database schemas for HMI alarm logging 
FactoryTalk View generates HMI tag alarm and data log information that can 
be stored in ODBC-compliant databases. 
C# PDF insert text Library: insert text into PDF content in C#.net
Supports adding text to PDF in preview without adobe reader installed in ASP.NET. Powerful .NET PDF edit control allows modify existing scanned PDF text.
clickable pdf links; pdf link to specific page
VB.NET PDF insert text library: insert text into PDF content in vb
Multifunctional Visual Studio .NET PDF SDK library supports adding text content to adobe PDF document in VB.NET Add text to PDF in preview without adobe
clickable links in pdf files; pdf link to attached file
Chapter 11                  Setting up HMI tag alarms 
244 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
HMI tag alarm data stored in ODBC format uses the following table. For 
information about how alarm log files are named, see Alarm log file names 
on page 246. 
This column 
Contains 
SQL data type 
Length 
TimeStmp 
The time and date data was logged, in UTC 
(Coordinated Universal Time) format. 
TIP: If the ODBC database does not support 
SQL_TIMESTAMP, the data might be truncated.  
If you are using the Oracle ODBC driver, for example, to 
avoid truncating date and time data, use SQL_DATE 
instead of SQL_TIMESTAMP. 
SQL_TIMESTAMP 
Driver dependent 
MilliTime 
Millisecond time when data was logged. 
SQL_INTEGER 
TransType 
The type of alarm that was generated. The transaction 
type is one of: 
SysAk (System Acknowledged) 
InAlm (In Alarm) 
OutAlm (Out of Alarm) 
InFlt (In Fault) 
OutFt (Out of Fault) 
Ack (Acknowledged) 
RmAck (Remote Acknowledged) 
SupOn (Suppress On) 
SupOf (Suppress Off) 
Remar (Remark) 
SQL_VARCHAR, or 
SQL_CHAR 
AlarmType 
The number FactoryTalk View assigns to the transaction 
type: 
0 for SysAk (System Acknowledged) 
1 for InAlm (In Alarm) 
2 for OutAlm (Out of Alarm) 
3 for InFlt (In Fault) 
4 for OutFt (Out of Fault) 
5 for Ack (Acknowledged) 
6 for RmAck (Remote Acknowledged) 
7 for SupOn (Suppress On) 
8 for SupOf (Suppress Off) 
9 for Remar (Remark) 
SQL_SMALLINT, or 
SQL_INTEGER 
SrcArea 
The area, in which the alarm occurred. 
SQL_VARCHAR, or 
SQL_CHAR 
80 
TagName 
The name of the tag or alarm event that caused the 
alarm. 
SQL_VARCHAR, or 
SQL_CHAR 
255 
TagValue 
The value of the tag at the time the alarm occurred. 
SQL_DOUBLE, or 
SQL_INTEGER, or 
SQL_SMALLINT 
20 (10 decimal 
places) 
TagType 
The type of the tag in alarm: 2 for Analog, 1 for Digital. 
SQL_VARCHAR, or 
SQL_CHAR 
ThreshVal 
The threshold value. 
SQL_DOUBLE, or 
SQL_FLOAT 
20 (10 decimal 
places) 
ThreshNum 
The threshold number. 
SQL_SMALLINT, or 
SQL_INTEGER 
ThreshLabl 
The threshold label. 
SQL_VARCHAR, or 
SQL_CHAR 
21 
C# Create PDF Library SDK to convert PDF from other file formats
Load PDF from stream programmatically. Preview PDF documents without other plug-ins. Besides, using this PDF document metadata adding control, you can
add hyperlink pdf file; adding links to pdf in preview
C# PowerPoint - How to Process PowerPoint
C# methods to add, insert or delete any specific PowerPoint slide, adding & burning & methods and sample codes of respective function, you may link the quick
add links to pdf; clickable links in pdf
Setting up HMI tag alarms                  Chapter 11 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
245 
Severity 
The alarm severity. 
SQL_SMALLINT, or 
SQL_INTEGER 
UserID 
The name of the user (including domain name, if there is 
one) that initiated the alarm transaction. If the transaction 
was initiated by an HMI server, the user is NT 
Authority\System. 
SQL_VARCHAR, or 
SQL_CHAR 
38 
Dscrptn 
The message that is associated with the transaction 
(alarm) type, the log message for the alarm event, or the 
alarm log remark. 
SQL_VARCHAR, or 
SQL_CHAR 
132 
SrcComputr 
The name of the computer that initiated the command or 
action that caused the alarm. 
SQL_VARCHAR, or 
SQL_CHAR 
15 
UserName 
The name of the user (including domain name, if there is 
one) that initiated the alarm transaction. If the transaction 
was initiated by an HMI server, the user is NT 
Authority\System. 
SQL_VARCHAR, or 
SQL_CHAR 
255 
The HMI Tag Alarm Log Viewer shows the contents of the alarm log file. 
The contents of the file depend on how severities are defined in the Alarm 
Setup editor. For details, see Setting up alarm severities on page 233. 
You can show alarm log files stored on the local computer or on a remote 
computer, and you can select the number of log files to be shown in the 
alarm log viewer. Each alarm log file is shown in a separate tab in the HMI 
Tag Alarm Log Viewer. 
To open the HMI Tag Alarm Log Viewer: 
Use one of these methods: 
In FactoryTalk View Studio or the FactoryTalk View SE 
Administration Console, from the Tools menu, select HMI Tag Alarm 
Log Viewer
Select Start > All Programs > Rockwell Software > FactoryTalk 
View > Tools > SE HMI Tag Alarm Log Viewer. 
To open the alarm log viewer Help: 
Select Start > All Programs > Rockwell Software > FactoryTalk 
View > Tools > SE HMI Tag Alarm Log Viewer Help
To show the alarm log viewer at run time: 
1.  In a graphic display, create a button that an operator can use to open 
the HMI Tag Alarm Log Viewer. 
2. 
For the button’s press action, type the following command:
AppStart "C:\Program Files\Rockwell Software\RSView 
Enterprise\ AlarmLogViewer.exe"
Viewing HMI tag 
alarm log files 
VB.NET PDF insert image library: insert images into PDF in vb.net
in preview without adobe PDF control installed. Access to freeware download and online VB.NET class source code. This smart and mature PDF image adding component
pdf link open in new window; add links to pdf in acrobat
VB.NET PDF copy, paste image library: copy, paste, cut PDF images
paste and cut PDF image while preview without adobe Free Visual Studio .NET PDF library, easy to Besides image extracting, adding, and removing, RasterEdge XDoc
add hyperlink to pdf in preview; adding hyperlinks to pdf
Chapter 11                  Setting up HMI tag alarms 
246 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
You must include the quotation marks, because there are spaces in the 
parameter. 
Tip: 
At run time, due to operating system rules, the alarm log 
viewer might open behind the FactoryTalk View 
SE Client window. If you are unaware of this, and try to 
open the viewer again, another instance will open. This 
could result in multiple viewers being open at the same 
time. 
To avoid this, you can bring the viewer to the front 
manually, and close it when it is no longer required. You 
can also use the programmatic solution documented in 
Answer ID 9041 in the Rockwell Automation 
Knowledgebase. 
Alarm log file names 
HMI tag alarm information is stored in file sets, in proprietary format. 
When an alarm log file is created, it is named automatically. The name is 
based on the date the file was created and the type of data it contains. 
The format for the name is YYYYMMDDnz.dat, where: 
YYYY are the four digits of the year. 
MM is the month. 
DD is the day. 
n is the sequence letter (AB, C, and so on). This letter indicates the 
sequence, in which the files were created. You can have up to 26 files 
(A to Z) per day. At midnight, the sequence starts at again. 
z is the file type: L ( uppercase L) is for alarm. 
If you are using short file names, or if the path where the log files are stored 
does not support long file names, the format for the name is 
YYMMDDnz.dat, where YY are the last two digits of the year. 
Example: HMI tag alarm log file name 
The log file named 20061015BL.dat was created in the year 2006, month 10, 
and day 15. The B indicates that this is the second file created that day. The L 
(uppercase L) indicates that this is an alarm log file. 
C# Word - Process Word Document in C#
Capable of adding and burning image on specific Word document page in C# class. You may click the link to go to each Word document processing tutorial page to
add a link to a pdf in preview; change link in pdf file
C# Excel - Excel Page Processing Overview
Support adding image of various formats (such as BMP, PNG & TIFF) to an Excel Click the link to specific C#.NET guide page and you will find detailed API(s
clickable links in pdf from word; adding links to pdf document
Setting up HMI tag alarms                  Chapter 11 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
247 
Adding remarks to the alarm log file at run time 
Use the AlarmLogRemark command to add information to the HMI tag 
alarm log file at run time. 
Parameters for the command let you add a text comment, the alarm severity, 
and the tag name to the alarm log file. Other parameters let you prompt the 
operator for the text part of the remark, and log the remark to a printer, in 
addition to the alarm log file. 
You cannot show alarm log remarks in HMI tag alarm summaries. 
At run time, only one Alarm Log Remark dialog box opens at a time, and the 
operator must respond to the dialog box before the next one is opened. For 
details about using AlarmLogRemark, see the FactoryTalk View Site Edition 
Help. 
Tip: 
Alarm logging must be turned on before you can use the 
AlarmLogRemark command. To start alarm logging, run 
the AlarmLogOn command. For details, see the 
FactoryTalk View Site Edition Help. 
You can suppress alarm monitoring for specified HMI tags. This is useful for 
testing or performing repairs or maintenance on equipment. 
To suppress alarm monitoring, use the SuppressOn command. To suppress 
all alarms for the specified tags, run the SuppressOn command before the 
AlarmOn command. For details about using these commands, see the 
FactoryTalk View Site Edition Help. 
Use the Suppressed List to see which tags are not being monitored for 
alarms, and to turn alarm monitoring back on. 
To open the Suppressed List: 
1.  In FactoryTalk View Studio or the FactoryTalk View SE 
Administration Console, in the Explorer window, open the HMI Tag 
Alarms folder. 
2.  Right-click the Suppressed List icon, and then select Open. 
Suppressing alarm 
logging 
Chapter 11                  Setting up HMI tag alarms 
248 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
You can also double-click the Suppressed List icon, or drag the icon 
into the FactoryTalk View Studio workspace. 
For more information about the Suppressed List, click Help
Tip: 
You cannot open the Suppressed List at run time, from a 
FactoryTalk View SE Client. 
Suppressing alarm printing 
To suppress alarm printing for all HMI tags, use the AlarmPrintOff 
command. To reset alarm printing, use the AlarmPrintOn command. 
Using AlarmOn and AlarmPrintOff in the correct order 
When the AlarmOn command is run, and HMI tag alarm monitoring is 
started, if an alarm log file and a printer are set up, alarms are logged to 
destinations. To stop logging to the printer, you can run the AlarmPrintOff 
command. 
The order, in which AlarmOn and AlarmPrintOff run affects what happens at 
run time: 
If AlarmOn runs first, alarms are logged to the alarm log file and the 
printer until AlarmPrintOff is run. 
If AlarmPrintOff runs first, followed by AlarmOn, alarms are logged to 
the alarm log file, but not to the printer. To restart logging to the 
printer, you would have to run AlarmPrintOn. 
Setting up HMI tag alarms                  Chapter 11 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
249 
The AlarmPrintOff and AlarmPrintOn commands are not retained across 
FactoryTalk View sessions. If you run AlarmPrintOff before AlarmOn in the 
current session, alarms will not print to the printer. 
However, if you shut down FactoryTalk View SE, restart it, and run the 
AlarmOn command, alarms will be logged to both the alarm log file and the 
printer, until you run AlarmPrintOff. 
The HMI tag alarm summary is a table that shows the active alarms recorded 
in an HMI server (or servers). At run time, operators can use alarm 
summaries in FactoryTalk View graphic displays to view and interact with 
alarms. 
You can create a new alarm summary object in a display, or use the pre-built 
alarm summary available in the HMI Tag Alarm Information graphic library. 
To create a new HMI tag alarm summary object: 
1.  In FactoryTalk View Studio, in the Explorer window, right-click the 
Displays icon, and then select Open
2.  Select Objects > Advanced > HMI Tag Alarm Summary. 
3.  Drag the mouse diagonally on the display, to describe the approximate 
size of the alarm summary, and then release the mouse button. 
The object can be part of the display, or it can fill the entire graphic 
display. 
For details about creating an HMI tag alarm summary, see the FactoryTalk 
View Site Edition Help. 
Creating an HMI tag 
alarm summary 
Chapter 11                  Setting up HMI tag alarms 
250 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
The parts of an HMI tag alarm summary 
A new HMI tag alarm summary object in a graphic display looks like this: 
When setting up an alarm summary, you determine how many columns the 
table will have, how wide the columns will be, and what information the 
columns will contain. 
You can also specify the HMI tags and areas (in a network distributed 
application) that will provide information to the alarm summary. 
Inserting headings 
Use headings from the Insert menu (shown in the next illustration) to define 
what information is shown in the HMI tag alarm summary at run time. 
To add a heading, click an item on the menu, and then click on the header 
area in the alarm summary. You can add any number of headings, and place 
them in any order. 