Rockwell Automation Publication VIEWSE-UM006K-EN-E 
261 
Chapter 12 
Setting up FactoryTalk alarms 
This chapter describes: 
What FactoryTalk Alarms and Events is. 
Key FactoryTalk alarm concepts. 
The basic steps involved in setting up FactoryTalk alarms. 
Setting up system-wide alarm and event policies. 
Working with Rockwell Automation Device Servers. 
Working with Tag Alarm and Event Servers. 
Setting up FactoryTalk tag-based alarms. 
Setting up alarm and event history logging. 
Setting up alarm and event displays. 
Using an alarm and event summary to monitor and respond to alarms. 
Working with alarm sources in the Alarm Status Explorer. 
Viewing alarm and event history logs. 
Using tags to interact with alarms or to obtain alarm status. 
Using FactoryTalk alarm functions in expressions. 
Importing and exporting alarms. 
Alarms are an important part of most plant control applications because they 
alert operators when something goes wrong. 
An alarm can signal that a device or process has ceased operating within 
acceptable, predefined limits, or it can indicate breakdown, wear, or a 
process malfunction. Often, it is also important to have a record of alarms 
and whether they were acknowledged. 
In FactoryTalk View Site Edition, you can set up a traditional alarm system, 
using HMI tags. 
You can also use FactoryTalk Alarms and Events services, to centralize the 
distribution of device-based and tag-based alarm data to run-time clients, 
through FactoryTalk alarm servers that you add to a FactoryTalk View SE 
application. 
About FactoryTalk 
Alarms and Events 
Pdf link - insert, remove PDF links in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Free C# example code is offered for users to edit PDF document hyperlink (url), like inserting and deleting
add hyperlink to pdf acrobat; add hyperlink pdf document
Pdf link - VB.NET PDF url edit library: insert, remove PDF links in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Help to Insert a Hyperlink to Specified PDF Document Page
add link to pdf file; convert a word document to pdf with hyperlinks
Chapter 12                  Setting up FactoryTalk alarms 
262 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
The choices you make will depend on factors such as the design of your 
application, the processes you need to monitor for alarms, the types of 
devices used in the application, and whether you want to build alarm 
detection into those devices. 
Advantages in using FactoryTalk Alarms and 
Events services 
There are advantages in using FactoryTalk Alarms and Events services for 
alarm monitoring and control, when compared with using traditional, HMI 
tag alarms. 
FactoryTalk Alarms and Events offers a single, integrated set of alarm 
information, distributed through supporting alarm servers. This means that all 
clients in a FactoryTalk system can receive a consistent view of device-based 
and tag-based alarm activity. 
FactoryTalk Alarms and Events services are also integrated with FactoryTalk 
Security services. This means you can set up FactoryTalk system users and 
computers with different levels of access to alarm sources and data. 
Choosing FactoryTalk device-based alarms 
FactoryTalk device-based alarms are set up by programming alarm 
instructions directly into Logix5000 controllers that support built-in alarm 
detection. 
Following are some reasons why you might choose device-based alarms, 
when compared with using HMI tag alarms. 
Using device-based alarms 
Using HMI tag alarms 
Alarm detection instructions are programmed once, in 
the controller. 
Alarm detection is programmed in the controller, and in FactoryTalk 
View SE. 
To set up HMI tag alarms, first you must create the HMI tags, which 
are mapped to tags in the controller. Then, in a separate step, you 
must add alarm conditions to the HMI tags you want to monitor. 
This duplication of programming effort can lead to errors. 
Alarms are processed once, in the controller. Data 
polling is eliminated. 
This reduces network overhead and speeds up alarm 
detection. 
Alarms are processed in the controller, and in FactoryTalk View SE. 
To monitor alarms, the HMI software polls tags in the controller. If 
alarms are detected, the HMI software notifies clients. 
Alarm states are managed, processed, and 
preserved in the controller. 
Alarm states are stored on the HMI server computer. If the computer 
is disconnected from the network, or if the HMI server fails or is 
restarted, alarm states might be lost. 
RasterEdge .NET Document Imaging Trial Package Download Link.
View & Process. XImage.Raster. Adobe PDF. XDoc.PDF. Scanning. XImage.OCR. Microsoft Office. View & Process. XImage.Raster. Adobe PDF. XDoc.PDF. Scanning. XImage.
c# read pdf from url; pdf link to attached file
C# PDF Library SDK to view, edit, convert, process PDF file for C#
RasterEdge PDF SDK for .NET package offers robust APIs for editing PDF document hyperlink (url) and quick navigation link in PDF bookmark.
accessible links in pdf; pdf link
Setting up FactoryTalk alarms                  Chapter 12 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
263 
Time stamps are applied in the controller. 
This makes time stamps more accurate. Also, the 
same time stamp is delivered to multiple servers and 
clients. 
Tip: If multiple controllers are used in an application, 
to ensure accurate time stamps, synchronize the 
controller clocks. 
Time stamps are applied on the HMI server computer. 
To ensure that time stamps are accurate and consistent, clocks at 
server and client computers must always be synchronized. 
The following illustration shows how device-based alarm information flows, 
from a Logix5000 controller, to operators running FactoryTalk View SE 
clients. 
FactoryTalk View SE Clients receive device-based alarm data by way of 
Rockwell Automation Device Servers (RSLinx Enterprise) that you add to a 
FactoryTalk View SE application. 
For more information, see Working with Rockwell Automation Device 
Servers on page 279
Tip: 
RSLogix 5000 version 16 or later, is required to program 
alarm instructions into a Logix5000 controller. For a 
complete list of controllers in the Logix5000 family, that 
support FactoryTalk Alarms and Events services, see the 
FactoryTalk Alarms and Events Help. 
How to C#: Basic SDK Concept of XDoc.PDF for .NET
XDoc.PDF for .NET allows C# developers to edit hyperlink of PDF document, including editing PDF url links and quick navigation link in bookmark/outline.
adding hyperlinks to pdf; pdf hyperlink
VB.NET PDF: Basic SDK Concept of XDoc.PDF
XDoc.PDF for .NET allows VB.NET developers to edit hyperlink of PDF document, including editing PDF url links and quick navigation link in bookmark/outline.
add hyperlink in pdf; adding an email link to a pdf
Chapter 12                  Setting up FactoryTalk alarms 
264 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
Choosing FactoryTalk tag-based alarms 
FactoryTalk tag-based alarms are set up by specifying alarm conditions for 
tags in devices that do not have built-in alarm detection. 
Use tag-based alarms to include these devices in an integrated FactoryTalk 
Alarms and Events system. 
You can set up tag-based alarms for tags in older programmable controllers 
(PLC-5 or SLC 500), for tags in third-party devices communicating through 
OPC da
ta servers, or for HMI tags in an HMI server’s tag database.
If you prefer not to set up built-in alarm detection, you can also set up 
tag-based alarms for Logix5000 controllers that do support device-based 
alarms. 
FactoryTalk View SE Clients receive tag-based alarm data by way of Tag 
Alarm and Event Servers that you add to a FactoryTalk View SE application. 
For more information, see Working with Tag Alarm and Event Servers on 
page 281
About traditional HMI tag alarms 
HMI tag alarms are set up by specifying alarm conditions for HMI tags in a 
FactoryTalk View SE 
Server’s tag database.
If your application uses HMI tags for other purposes, and you want to 
monitor these tags for alarms, use a traditional HMI tag alarm system. 
FactoryTalk View SE Clients receive HMI tag alarm information by way of 
the FactoryTalk View SE Servers (also called HMI servers) that contain the 
HMI tags. 
HMI tag alarm data is not managed by FactoryTalk Alarms and Events 
services. To monitor and respond to HMI tag alarms, you must use the HMI 
tag alarm displays and logs available in FactoryTalk View SE. 
For details, see Setting up HMI tag alarms. on page 217 
Finding more information 
This section provides an overview of key FactoryTalk Alarms and Events 
concepts, and describes some of the basic tasks involved in setting up 
FactoryTalk alarms in a FactoryTalk View SE application. 
For example, this manual contains basic information about: 
VB.NET Word: How to Process MS Word in VB.NET Library in .NET
Besides, here is the quick link for how to process Word document within We are dedicated to provide powerful & profession imaging controls, PDF document, image
pdf email link; add links to pdf in acrobat
Setting up FactoryTalk alarms                  Chapter 12 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
265 
Setting up Rockwell Automation Device Servers (RSLinx Enterprise), 
so that FactoryTalk View SE Clients can receive FactoryTalk 
device-based alarm information. 
Setting up Tag Alarm and Event Servers, so that FactoryTalk View 
SE Clients can receive FactoryTalk tag-based alarm information. 
Setting up run-time alarm monitoring and control, using the 
FactoryTalk objects available in FactoryTalk View Studio, in the 
Graphics editor. 
Setting up FactoryTalk alarm and event history logs, and viewing 
alarm history information. 
For information about creating FactoryTalk View SE applications and 
components, see other chapters in this manual, or see the FactoryTalk View 
Site Edition Help. 
Tip: This manual does not contain information about using 
RSLogix 5000 to program alarm instructions into 
Logix5000 controllers. For details, see the RSLogix 5000 
documentation, or see the FactoryTalk Alarms and 
Events System Configuration Guide. 
Opening the FactoryTalk Alarms and Events Help 
For comprehensive information about FactoryTalk Alarms and Events, 
including detailed setup instructions, see the FactoryTalk Alarms and Events 
Help. 
To open the Help, use one of these methods: 
Select Start > All Programs > Rockwell Software > FactoryTalk 
Tools > FactoryTalk Help
In the FactoryTalk Help file, open the book FactoryTalk Alarms and 
Events Help. 
Click Help in editors and dialog boxes for help with a specific object. 
Opening the FactoryTalk Alarms and Events System 
Configuration Guide 
For step-by-step instructions about setting up FactoryTalk Alarms and Events 
quickly, from a FactoryTalk system perspective, see the FactoryTalk Alarms 
and Events System Configuration Guide. 
To open the System Configuration Guide, in FactoryTalk View Studio, from 
the Help menu, select Online Books > FactoryTalk Alarms and Events 
System Configuration Guide. 
VB.NET PDF: Create PDF Document Viewer in C#.NET for Document
reading PDF document in ASP.NET web, .NET Windows Forms and mobile developing applications respectively. For more information on them, just click the link and
adding hyperlinks to pdf documents; add url link to pdf
VB.NET Word: VB Code to Create Word Mobile Viewer with .NET Doc
For the respective tutorials of these Document or Image Mobile Viewer in VB.NET prorgam, please link to see: PDF Document Mobile Viewer within VB.NET
add links to pdf; pdf reader link
Chapter 12                  Setting up FactoryTalk alarms 
266 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
This section presents some of the common terms and concepts used to 
describe FactoryTalk Alarms and Events services, components, and data. 
Alarms and events 
A FactoryTalk Alarms and Events system produces two types of events: 
Condition-related events 
are associated with changes in an alarm’s 
state. For example, a condition-related event is generated when an 
alarm changes to In Alarm, Acknowledged, Return to Normal or 
Disabled. 
Also known as alarms, alarm conditions, or alarm activity, 
condition-related events are recorded in FactoryTalk alarm and event 
displays and logs. 
Tracking-related events are associated with monitoring or auditing 
changes to the FactoryTalk system. For example, a tracking-related 
event is generated when an operator acknowledges an alarm. 
Tracking-related events associated with alarm activity are recorded in 
FactoryTalk alarm and event logs only. 
For details about these types of events, see the FactoryTalk Alarms and 
Events Help. 
Alarm servers 
FactoryTalk Alarms and Events services make alarm information available to 
subscribing FactoryTalk View SE Clients through two types of alarm 
servers: 
Rockwell Automation Device Servers (RSLinx Enterprise) provide 
access to alarms detected in Logix5000 controllers that support built-in 
alarm detection. 
Tag Alarm and Event Servers provide access to alarms set up for 
tags in: 
Key FactoryTalk 
Alarms and Events 
concepts 
Setting up FactoryTalk alarms                  Chapter 12 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
267 
Older devices (PLC-
5 or SLC 500) that don’t support built
-in 
alarm detection. 
Third-party devices communicating through OPC data servers. 
An HMI server’s tag database (HMI tags).
Tip: You can also set up tag-based alarms for Logix5000 
controllers that do support device-based alarms, if you 
prefer not to set up built-in alarm detection. 
For information about setting up alarm servers in a FactoryTalk View SE 
application, see: 
Working with Rockwell Automation Device Servers on page 279
Working with Tag Alarm and Event Servers on page 281
Level alarms 
A level alarm compares an analog value against predefined limits (also called 
thresholds) and triggers an alarm when a limit is exceeded. For information 
about setting up tag-based level alarms, see Creating tag-based level alarms 
on page 284. 
Level alarm limits 
When defining a level alarm, you can assign any of the following limits, with 
different levels of severity: 
High High 
High 
Low 
Low Low 
The High and High High alarm conditions monitor for a rising value, and the 
Low and Low Low conditions monitor for a decreasing value. 
Chapter 12                  Setting up FactoryTalk alarms 
268 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
Example: Alarm limits 
In this example, a tag’s value changes as it monitors a motor’s revolutions 
per minute (rpm). An X in the illustration shows when the alarm condition 
goes into alarm, and an O shows when the alarm condition returns to normal. 
With the given limit settings, the motor must run between 3000 rpm and 
4000 rpm (the safe zone), otherwise, an alarm will be triggered. 
If the motor speed 
It triggers an alarm of this severity 
Exceeds 4000 rpm 
750 (High limit) 
Exceeds 6000 rpm 
1000 (High High limit) 
Falls below 3000 rpm 
500 (Low limit) 
Falls below 1000 rpm 
250 (Low Low limit) 
Variable limits and alarm faults 
Limits can be constant or variable. Variable limits are derived from the value 
of another tag. As the value of the specified tag changes, the limit changes. 
A variable limit must not become higher than the limit above it, or lower than 
the limit below it. If this happens, an alarm fault is generated for the tag 
being monitored. 
To correct an alarm fault, you must change the variable limit so it does not 
overlap either of its neighbors. This can become complex when the 
neighboring limits are also variable, because these boundaries are determined 
dynamically at run time. 
When the faulty limits return to their normal operating range, the alarm fault 
is cleared, the out-of-alarm-fault status is generated and logged, and normal 
alarm monitoring for the alarm condition resumes. 
Setting up FactoryTalk alarms                  Chapter 12 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
269 
Deadband 
With some types of measured values, such as line pressure, tag values can 
fluctuate rapidly above and below a critical limit. 
Where such conditions exist, you can create a deadband as a buffer zone to 
prevent the fluctuations from re-triggering unnecessary alarms. 
For the High and High High alarm conditions, the tag value must drop below 
the alarm limit minus the deadband, before the alarm condition goes Normal 
(Out of Alarm). For the Low and Low Low alarm conditions, the tag value 
must go above the alarm limit plus the deadband, before the alarm condition 
goes Normal. 
In the following illustration, an increasing limit of 4000 rpm, with a 
deadband value of 500 rpm, means that the rpm has to fall to 3500 and then 
rise above 4000, before the rpm value will trigger an alarm again. 
A deadband range can only be an absolute (constant) value. If a buffer is not 
required, the deadband must be set up as zero. 
With a deadband of zero, alarms will be triggered as soon as the tag value 
crosses any of its limits. 
For information about how deadbands work with deviation alarms, see the 
FactoryTalk Alarms and Events Help. 
Note: 
Use the deadband carefully in safety-critical applications. In 
the preceding illustration, for example, the variable has to 
fluctuate by more than 500 rpm before an alarm is triggered 
again. 
Chapter 12                  Setting up FactoryTalk alarms 
270 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
Deviation alarms 
A deviation alarm compares the value of an input tag to the value of a target 
for a deviation value. 
The target can be either a constant or a tag, but the deviation value can only 
be an absolute value (a constant, not a tag value). 
If the target differs from the input tag by greater or less than the deviation 
value, an alarm occurs. 
In the following illustration, an X shows when the tag goes into alarm, and 
an O shows when the tag returns to normal. 
For information about setting up tag-based deviation alarms, see Creating 
tag-based deviation alarms on page 285
Digital alarms 
A digital alarm monitors the value of a tag or input for either of these alarm 
conditions: the value is equal to zero, or the value is not equal to zero. 
FactoryTalk Alarms and Events does not support tag-based, digital 
change-of-state alarms. Change-of-state alarms are triggered by any change 
in the digital tag being monitored, or when the tag’s value changes to either 0 
or 1. 
Tip: 
If you want to set up digital change-of-state alarms, use 
HMI digital tags. For more information, see Setting up 
HMI tag alarms on page 217. 
Digital alarms can be latched. This means that the digital alarm will remain 
In Alarm, even if its alarm condition returns to normal, until an operator 
resets the alarm. 
For information about setting up tag-based digital alarms, see Creating 
tag-based digital alarms on page 283