Setting up FactoryTalk alarms                  Chapter 12 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
271 
FactoryTalk alarm and event displays 
To monitor and respond to FactoryTalk device-based and tag-based alarms at 
run time, use the following FactoryTalk Alarm and Event objects, embedded 
in FactoryTalk View SE graphic displays. 
Tip: 
FactoryTalk Alarm and Event objects do not show HMI 
tag alarms. To monitor and respond to HMI tag alarms, 
you must use the HMI tag alarm objects available in 
FactoryTalk View SE. For details, see Setting up HMI tag 
alarms on page 217. 
Alarm and event summary 
The Alarm and Event Summary shows alarm information from Rockwell 
Automation Device Servers (RSLinx Enterprise) and Tag Alarm and Event 
Servers that support FactoryTalk Alarms and Events. 
Use the alarm and event summary to view, acknowledge, suppress, and 
disable the alarms on display. The alarm and event summary also provides a 
detail view of selected alarms. 
An alarm and event summary can display alarms from more than one area 
and alarm server in a FactoryTalk View SE application. 
For information about setting up an alarm and event summary, see Setting up 
an alarm and event summary on page 293
Alarm and event banner 
The alarm and event banner can show up to five of the highest priority, most 
severe, and most recent alarms in the FactoryTalk system. 
Use the alarm and event banner to monitor and acknowledge the critical 
system alarms. You can also open an alarm and event summary, from an 
alarm and event banner. 
For information about setting up an alarm and event banner, see Setting up 
an alarm and event banner on page 296
Alarm status explorer 
The alarm status explorer shows all of the alarm sources in an application. 
Use the alarm status explorer to view alarm sources, suppress or unsuppress, 
and enable or disable alarms. 
Add links in pdf - insert, remove PDF links in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Free C# example code is offered for users to edit PDF document hyperlink (url), like inserting and deleting
change link in pdf; adding links to pdf document
Add links in pdf - VB.NET PDF url edit library: insert, remove PDF links in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Help to Insert a Hyperlink to Specified PDF Document Page
add a link to a pdf file; add a link to a pdf in preview
Chapter 12                  Setting up FactoryTalk alarms 
272 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
For information about setting up an alarm status explorer, see Working with 
alarm sources in the Alarm Status Explorer on page 306
Alarm and event log viewer 
The alarm and event log viewer shows the information stored in the alarm 
and event logs, generated by the FactoryTalk Alarms and Events Historian. 
Use the alarm and event log viewer to view, sort, filter, and print historical 
alarm and event information. 
For information about setting up an alarm and event log viewer, see Viewing 
alarm and event history logs on page 310
Alarm priority and severity 
An individual alarm in a FactoryTalk system can have a severity value of 1 
to 1000, as well as a priority value that covers a range of severities. 
Priority values group severities into levels of urgency that an operator can 
easily identify. 
Alarm priorities can be defined in an alarm server (Rockwell Automation 
Device Server or Tag Alarm and Event Server), or in the FactoryTalk 
Directory. 
If priority values are not defined in an alarm server, then the following 
system-wide settings are in effect for all alarm servers in the FactoryTalk 
Directory. 
This priority value 
Includes this range of severities 
Urgent 
751 to 1000 
High 
501 to 750 
Medium 
251 to 500 
Low 
1 to 250 
You can change the range of severities associated with a given priority value. 
If you change the settings held in the FactoryTalk Directory, the changes will 
apply to all FactoryTalk alarm servers the directory manages. For more 
information, see Setting up system-wide alarm and event policies on page 
277
If priority values are defined at an alarm server, the server-defined priorities 
take precedence over the system-wide priorities. 
C# PDF Convert to HTML SDK: Convert PDF to html files in C#.net
HTML converter toolkit SDK, preserves all the original anchors, links, bookmarks and to Use C#.NET Demo Code to Convert PDF Document to Add necessary references
adding hyperlinks to pdf files; add links in pdf
.NET PDF Document Viewing, Annotation, Conversion & Processing
PDF Write. Insert text, text box into PDF. Edit, delete text from PDF. Insert images into PDF. Edit, remove images from PDF. Add, edit, delete links. Form Process
convert excel to pdf with hyperlinks; change link in pdf file
Setting up FactoryTalk alarms                  Chapter 12 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
273 
You can set up server-defined priorities in the Properties dialog box for the 
Rockwell Automation Device Server or Tag Alarm and Event Server. For 
details, see the FactoryTalk Alarms and Events Help. 
Alarm class 
Use alarm classes to further group related alarms, based on characteristics 
other than priority and severity. 
For example, you might group alarms based on their function, to make it 
easier for operators to identify alarms related to temperature, pressure, tank 
levels, equipment running, or valves that fail to open or close. 
To create an alarm class, in the Alarm and Event Setup editor, in any of the 
Digital, Level, or Deviation Properties dialog boxes, type the class name in 
the Alarm class box, or select one from the list of classes. 
Each time you create a new alarm class, it is added to the list. In the previous 
illustration, for example, Pump temperature will be listed with Equipment 
running, the next time you create an alarm. 
For more information about alarm classes, see the FactoryTalk Alarms and 
Events Help. 
Alarm states 
Alarm states indicate the current status of an alarm. 
When shown in an alarm and event summary or banner, an alarm condition 
can have one of the following states. 
This icon 
Indicates the alarm condition has this state 
In Alarm and Unacknowledged 
In Alarm and Acknowledged 
Normal and Unacknowledged 
For more information, see Using an alarm summary to monitor and respond 
to alarms on page 299
VB.NET PDF Convert to HTML SDK: Convert PDF to html files in vb.
Turn PDF images to HTML images in VB.NET. Embed PDF hyperlinks to HTML links in VB.NET. Convert PDF to HTML in VB.NET Demo Code. Add necessary references:
add hyperlink to pdf in; add hyperlink to pdf in preview
C# PDF Convert to Word SDK: Convert PDF to Word library in C#.net
the original text style (including font, size, color, links and boldness). C#.NET DLLs and Demo Code: Convert PDF to Word Document in C# Add necessary references
add link to pdf acrobat; active links in pdf
Chapter 12                  Setting up FactoryTalk alarms 
274 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
Alarm tags 
Tags that you can use to obtain and change the state of an alarm are called 
alarm tags. 
Use alarm tags to monitor and interact with alarms at run time, without the 
need for an operator to use alarm and event objects in a graphic display. 
For example, an operator can use the OperAck (or OperAckAll) alarm tag to 
acknowledge an alarm when it occurs. 
To use alarm tags for an alarm, in the Alarm Setup editor, in the alarm’s 
Properties dialog box, you must select the check box, Show Alarm as a Tag 
(shown in the next illustration). 
After you set up an alarm to show as a tag, you can select the alarm in the 
Tag Browser, and then select the alarm tags you want to use. For more 
information, see Using tags to interact with alarms or obtain their status on 
page 312
Alarm status tags 
Alarm status tags let you use handshaking to keep alarm state changes 
synchronized with a controller (PLC-5 or SLC 500). 
For example, if an Acknowledged status tag is specified for an alarm, when 
an operator acknowledges the alarm, the status tag is set to 1. 
You can use status tags to handshake changes in the In Alarm, Disabled, 
Suppressed, and Acknowledged alarm states. 
To assign status tags to tag-based alarms, in the Alarm and Event Setup 
editor, select the Status Tags tab in any of the Digital, Level, or Deviation 
Properties dialog boxes. For more information, see Setting up status tags for 
tag-based alarms on page 287
Alarm messages 
Alarm messages report information about alarms. 
How to C#: Basic SDK Concept of XDoc.PDF for .NET
You may add PDF document protection functionality into your C# program. to edit hyperlink of PDF document, including editing PDF url links and quick
clickable links in pdf; add hyperlink to pdf
C# Create PDF Library SDK to convert PDF from other file formats
PDF with a blank page, bookmarks, links, signatures, etc. PDF document in C#.NET using this PDF document creating toolkit, if you need to add some text
add a link to a pdf in acrobat; add hyperlink to pdf online
Setting up FactoryTalk alarms                  Chapter 12 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
275 
For each alarm condition, you can create a message (or specify an existing 
message) to display when the alarm condition occurs. You can also use 
placeholders and insert variables in alarm messages. 
To create and modify tag-based alarm messages, in the Alarm and Event 
Setup editor, select the Messages tab or open any of the Digital, Level, or 
Deviation Properties dialog boxes. For more information, see Setting up 
tag-based alarm messages on page 288
Alarm audit, diagnostic, and history logs 
FactoryTalk Alarms and Events generates three types of messages for 
logging: 
Audit messages are generated in response to actions performed in 
alarm and event objects, such as modifying or acknowledging an 
alarm. 
FactoryTalk Diagnostics routes audit messages to the Local Log (and 
to the FactoryTalk Audit Log, if you have the FactoryTalk AssetCentre 
software installed). You can look at audit messages logged the Local 
Log in the Diagnostics Viewer. 
Diagnostic messages inform operators of system activity, in the form 
of information, error, and warning messages. 
FactoryTalk Diagnostics routes these messages to a Diagnostics Local 
Log, the Diagnostics List, and to a central ODBC log, if one is 
available. You can look at diagnostic messages in the Diagnostics 
Viewer. 
Historical alarm and event messages record all the alarm activity that 
occurs at an alarm server at run time. 
The Alarm and Event Historian manages connections between alarm 
servers and databases, and logs data from each alarm server to an alarm 
history database. 
You can look at historical alarm information in the Alarm and Event 
Log Viewer. 
For information about FactoryTalk Diagnostics, see the FactoryTalk Help. 
For more information about historical alarm and event logging, see Setting 
up alarm and event history logging on page 291
VB.NET PDF: Basic SDK Concept of XDoc.PDF
You may add PDF document protection functionality into your VB.NET program. to edit hyperlink of PDF document, including editing PDF url links and quick
add hyperlink pdf; add a link to a pdf
C# Image: Tutorial for Document Management Using C#.NET Imaging
more detailed C# tutorials on each part by following the links respectively are dedicated to provide powerful & profession imaging controls, PDF document, image
check links in pdf; add url to pdf
Chapter 12                  Setting up FactoryTalk alarms 
276 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
Tip: 
The Alarm and Event Historian is installed with the 
FactoryTalk Alarms and Events software. To log alarm 
and event data, you must also install Microsoft SQL 
Server separately, on the computers where data will be 
stored. For details, see the FactoryTalk Alarms and 
Events Help. 
To set up FactoryTalk alarm monitoring, plan the design of the FactoryTalk 
View SE application first, and decide which processes you want to monitor 
for alarms. 
Then, in FactoryTalk View Studio, create the application and set up the 
FactoryTalk Alarms and Events components you need. Following are the 
basic tasks involved: 
1.  Set up system-wide alarm and event policies for the application. 
For information, see Setting up system-wide alarm and event policies 
on page 277
2.  If the application is to use device-based alarms, in RSLogix 5000, 
program alarm instructions into Logix5000 controllers that support 
built-in alarm detection. 
For information, see the RSLogix 5000 documentation. 
3.  To let run-time clients receive device-based alarm data, add one or 
more Rockwell Automation Device Servers (RSLinx Enterprise) to the 
application, and set up the servers to support FactoryTalk Alarms and 
Events. 
For information, see Working with Rockwell Automation Device 
Servers on page 279
4.  If the application is to use tag-based alarms, add one or more Tag 
Alarm and Event Servers. 
For information, see Working with Tag Alarm and Event Servers on 
page 281
5.  In the Alarm and Event Setup editor, create digital, level, and deviation 
alarm conditions, for the tags you want to monitor for alarms. 
For information, see Setting up FactoryTalk tag-based alarms on page 
282
Summary of basic 
steps for setting up 
FactoryTalk alarms 
Setting up FactoryTalk alarms                  Chapter 12 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
277 
6.  In FactoryTalk View Studio, in the Graphics editor, set up FactoryTalk 
alarm and event objects in graphic displays, to monitor and interact 
with device-based and tag-based alarms at run time. 
For information, see Setting up alarm and event displays on page 292
7.  Set up historical alarm and event logging. 
For information, see Setting up alarm and event history logging on 
page 291
8.  Set up FactoryTalk View SE Clients to run the graphic displays. 
For information, see the FactoryTalk View Site Edition Help. 
FactoryTalk Alarms and Events policies are stored at the FactoryTalk 
Directory and apply system-wide, to all alarm servers the directory manages. 
In FactoryTalk View Studio, you can modify system-wide alarm settings, 
such as the range of severities set up for alarm priority values, and whether 
to send audit messages to the alarm and event log. 
You can also modify the severity settings associated with system events, 
such as loss of connection to a controller, or with events that track operator 
actions, such as acknowledging an alarm. 
To modify system-wide alarm settings 
1.  In FactoryTalk View Studio, in the Explorer window, expand the 
System, Policies, System Policies, and FactoryTalk Alarms and Events 
folders. 
2.  Double-click System Settings
3.  In the System Settings Properties dialog box (shown in the following 
illustration), modify special events, event buffering, and alarm priority 
settings, as needed. 
Setting up 
system-wide alarm 
and event policies 
Chapter 12                  Setting up FactoryTalk alarms 
278 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
Tip: 
To modify the severity range for the alarm priorities, 
change the values in the Low boxes only. Priorities 
defined at an alarm server override the system-wide 
settings held at the FactoryTalk Directory. 
For details about options in the System Settings Properties dialog box, click 
Help
To modify severity settings for system events 
1.  In FactoryTalk View Studio, in the Explorer window, expand the 
System, Policies, System Policies, and FactoryTalk Alarms and Events 
folders. 
2.  Double-click Severity Settings
3.  In the Severity Settings Properties dialog box, modify the severity 
values associated with selected system events. 
For details about options in the Severity Settings Properties dialog box, 
click Help
Securing access to FactoryTalk alarm information 
For FactoryTalk products like FactoryTalk View SE, the FactoryTalk 
Directory stores information about which users are allowed access to the 
parts of a control system. 
Setting up FactoryTalk alarms                  Chapter 12 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
279 
You can secure access to alarms, and to alarm information in an application, 
by determining which users are allowed to perform alarm-related actions, or 
gain access to areas that contain alarm servers. 
About FactoryTalk Security permissions 
If FactoryTalk Security services are used to secure parts of an application, to 
perform certain tasks, users must have the necessary security permissions. 
For example, to create or modify the properties of an application, you must at 
least be allowed the Common actions Read, List Children, Write, and Create 
Children, at the FactoryTalk Directory that manages the application. 
If you receive a FactoryTalk Security message while trying to perform such a 
task, contact your system administrator about permissions you might require. 
For an overview of FactoryTalk Security services, see Setting up security on 
page 85. For details, see FactoryTalk Security Help. 
To enable FactoryTalk View SE Clients to receive and display FactoryTalk 
alarms detected in Logix5000 controllers, do the following: 
1.  Add one or more Rockwell Automation Device Servers (RSLinx 
Enterprise) to a FactoryTalk View SE network distributed application. 
In a local station application, you can only add one RSLinx Enterprise 
server, which must reside on the same computer as the application. 
2.  Set up the device server to support FactoryTalk Alarms and Events. 
3.  Create shortcuts in RSLinx Enterprise, to the Logix5000 controllers 
that are detecting alarms, and enable the device shortcuts to support 
FactoryTalk Alarms and Events. 
Tip: This manual does not contain information about how to 
use RSLogix 5000, to program alarm instructions into 
Logix5000 controllers, nor does it describe how to set up 
redundancy for these controllers. For details, see the 
product documentation. 
To add an RSLinx Enterprise server to a network distributed 
application: 
1.  In the FactoryTalk View Studio, in the Explorer window, right-click 
the application name or an area, select Add New Server Rockwell 
Automation Device Server (RSLinx Enterprise)
2.  Provide a name and an optional description, and then specify the name 
of the computer hosting RSLinx Enterprise. 
Working with 
Rockwell 
Automation Device 
Servers 
Chapter 12                  Setting up FactoryTalk alarms 
280 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
Setting up support for FactoryTalk Alarms and 
Events 
After you add an RSLinx Enterprise server to an application, you must set up 
the server to support FactoryTalk Alarms and Events. 
Tip: If you do not enable this when the RSLinx Enterprise 
server is created, you can modify the server, but the 
server will have to be restarted. 
To do this, in the server’s Properties dialog box (shown in the next 
illustration), select the check box, Enable alarm and event support. 
To enable alarm and event history logging on the computer running the 
device server, select the check box, Enable history. 
If you enable logging, you must specify a database definition for the server. 
For more information, see Setting up alarm and event history logging on 
page 291
Optionally, you can set up server-assigned priority values for the alarm 
server. To modify the severity range, change values in the Low boxes only. 
Priorities defined at an alarm server override the system-wide settings held at 
the FactoryTalk Directory. 