Setting up FactoryTalk alarms                  Chapter 12 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
291 
FactoryTalk Alarms and Events generates messages to record the alarm 
activity that occurs at tag-based and device-based alarm servers in an 
application. 
The Alarm and Event Historian software, which is installed with FactoryTalk 
Alarms and Events, logs alarm information to the databases set up to store 
logged data. It also manages connections and data buffering between alarm 
servers and their databases. 
Tip: 
FactoryTalk Alarms and Events also generates audit and 
diagnostic messages. For information about logging and 
viewing these messages, see the FactoryTalk Alarms 
and Events Help. 
Following are the tasks involved in setting up FactoryTalk alarm logging: 
Install Microsoft SQL Server and supporting components, on 
computers that will host alarm and event log databases. For details, see 
the FactoryTalk Alarms and Events Help. 
Create database definitions at the FactoryTalk Directory. For more 
information, "Defining an alarm and event log database," next. 
Set up support for alarm and event history logging, for each alarm 
server in an application. For more information, see Enabling alarm and 
event history logging on page 292
Set up alarm and event log viewers to display logged data at run time. 
For more information, see Viewing alarm and event history logs on 
page 310
Defining an alarm and event log database 
The FactoryTalk Alarm and Event Historian routes FactoryTalk 
alarm-related data from alarm servers to Microsoft SQL Server databases. 
Information is logged when: 
A tag goes into alarm or returns to normal. 
An alarm is acknowledged. 
An alarm is suppressed or unsuppressed. 
An alarm is enabled or disabled. 
An alarm fault is generated or cleared. 
An alarm is reset. 
An alarm is shelved or unshelved. 
Database definitions are stored in the FactoryTalk Directory, and can be 
shared by multiple alarm servers in an application. 
Setting up alarm 
and event history 
logging 
Add hyperlink in pdf - insert, remove PDF links in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Free C# example code is offered for users to edit PDF document hyperlink (url), like inserting and deleting
pdf hyperlink; add email link to pdf
Add hyperlink in pdf - VB.NET PDF url edit library: insert, remove PDF links in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Help to Insert a Hyperlink to Specified PDF Document Page
clickable pdf links; add links to pdf in acrobat
Chapter 12                  Setting up FactoryTalk alarms 
292 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
You specify the database definition an alarm server will use, in the server’s 
Properties dialog box. For more information, "Enabling alarm and event 
history logging," next. 
To create an alarm and event log database definition: 
1.  In FactoryTalk View Studio, in the Explorer window, expand the 
System and Connections folders. 
2.  Right-click the Databases folder, and then select New Database
For details about options in the Alarm and Event Historian Database 
Properties dialog box, click Help
Enabling alarm and event history logging 
To set up an alarm server to log alarm activity, for each Rockwell 
Automation Device Server (RSLinx Enterprise), and Tag Alarm and Event 
Server in an application, you must enable alarm and event history logging, 
and then select a database for storing the data. 
You do this in the 
alarm server’s Properties dialog box, in the Alarm and 
Event History section. For an illustration, see Setting up alarm priorities and 
history logging on page 282
Tip: 
For an RSLinx Enterprise server, Alarm and Event 
History settings are in the Alarms and Events tab. For a 
Tag Alarm and Event server, the settings are in the 
Priorities and History tab. 
To view the alarm servers using a database definition: 
1.  In FactoryTalk View Studio, in the Explorer window, expand the 
System, Connections, and Databases folders. 
2.  Right-click the database definition you want to check, and then select 
Properties
3.  In the Alarm and Event Historian Database Properties dialog box, click 
Show Usage
To monitor and respond to FactoryTalk alarms at run time, use FactoryTalk 
alarm and event objects hosted in FactoryTalk View SE graphic displays. 
In FactoryTalk View Studio, in the Graphics editor, you can create the 
following objects: 
Use the alarm and event summary to view, acknowledge, suppress, 
and disable alarms from multiple FactoryTalk alarm sources. For 
Setting up alarm 
and event displays 
VB.NET Create PDF from Word Library to convert docx, doc to PDF in
Change Word hyperlink to PDF hyperlink and bookmark. VB.NET Demo Code for Converting Word to PDF. Add necessary references: RasterEdge.Imaging.Basic.dll.
add link to pdf acrobat; adding links to pdf
VB.NET Create PDF from Excel Library to convert xlsx, xls to PDF
Change Excel hyperlink to PDF hyperlink and bookmark. VB.NET Demo Code for Converting Excel to PDF. Add necessary references: RasterEdge.Imaging.Basic.dll.
add links in pdf; adding a link to a pdf in preview
Setting up FactoryTalk alarms                  Chapter 12 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
293 
information about setting up an alarm and event summary, see "Setting 
up an alarm and event summary," next. 
Use the alarm and event banner to monitor and acknowledge the 
most serious FactoryTalk alarms in the system. For information about 
setting up an alarm and event banner, see Setting up an alarm and event 
banner on page 296
Use the alarm and event log viewer to view, sort, filter, and print 
historical alarm information. For information about the alarm and event 
log viewer, see Viewing alarm and event history logs on page 310. 
Use the alarm status explorer to view alarm sources, suppress or 
unsuppress, and enable or disable alarms. For information about the 
alarm status explorer, see Working with alarm sources in the Alarm 
Status Explorer on page 306
For detailed setup instructions, see the FactoryTalk Alarms and Events Help. 
About the Alarm and Event graphic library 
The Alarm and Event graphic library contains a pre-configured FactoryTalk 
alarm and event summary, and buttons you can use to acknowledge 
FactoryTalk alarms. 
Use the objects in the library as they are, or drag them into a graphic display, 
and then modify them to suit the needs of your application. 
To open the Alarm and Event library: 
In FactoryTalk View Studio, open the Graphics folder, double-click the 
Libraries icon, and then double-click Alarm and Event. You can also drag 
the Alarm and Event library into the FactoryTalk View Studio workspace. 
Setting up an alarm and event summary 
When setting up an alarm and event summary, you specify which alarm 
information will be shown at run time, and how the information will appear 
in the summary. 
For example, you can specify a different color for each priority
blue for 
low, yellow for medium, orange for high, and red for urgent
so that 
operators can identify the priority of alarms at a glance. 
A FactoryTalk alarm and event summary can occupy part of a FactoryTalk 
View SE graphic display, or it can fill the entire display. 
How to C#: Basic SDK Concept of XDoc.PDF for .NET
You may add PDF document protection functionality into your C# program. Hyperlink Edit. XDoc.PDF for .NET allows C# developers to edit hyperlink of PDF document
add a link to a pdf in acrobat; convert doc to pdf with hyperlinks
VB.NET PDF: Basic SDK Concept of XDoc.PDF
You may add PDF document protection functionality into your VB.NET program. Hyperlink Edit. XDoc.PDF for .NET allows VB.NET developers to edit hyperlink of PDF
pdf link open in new window; pdf email link
Chapter 12                  Setting up FactoryTalk alarms 
294 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
To create an alarm and event summary object: 
1.  In FactoryTalk View Studio, in the Explorer window, expand the 
application, area, and HMI server icons, where you want to create the 
alarm and event summary display. 
2.  To create a new graphic display, expand the Graphics folder, 
right-click Displays, and then click New
3.  In the Graphics editor, select Objects > Alarm and Event > 
Summary. You can also click 
on the Graphic editor’s toolbar.
4.  Drag the alarm and event summary tool on the graphic display, to the 
desired size and shape, and then release the mouse. 
You can move and resize the Alarm and Event Summary Design View 
object, as needed. To set up properties, double-click the object (or 
right-click, and then click Properties). 
Following is an overview of alarm and event summary properties. For 
details about options in the Alarm and Event Summary Properties 
dialog box, click Help
Setting up the overall appearance of the summary display 
In the Appearance tab, set up which parts of the alarm and event summary to 
show at run time. For example, you can determine whether the summary will 
include a vertical scroll bar, the details pane, or a toolbar. 
You can also set up fonts, text color, and background color, for various parts 
of the summary display. For example, you can set up a font, text color, and 
icon size for the toolbar. 
Choosing the columns and toolbar buttons to show 
In the Columns tab, set up which columns to show in the alarm and event 
summary, and in what order. You can also set up the heading text, and the 
alignment and format of information shown in each column. Use the Sample 
column to preview your selections. 
In the Toolbar tab, you can set up which buttons will show in the alarm and 
event summary’s toolbar. You can also set up the caption, tooltip, and format 
of each button. 
Choosing the status bar contents 
In the Status Bar tab, set up which information to display in the status bar, 
and in what order. You can also set up tooltips for the status bar. 
C# Create PDF from Word Library to convert docx, doc to PDF in C#.
Change Word hyperlink to PDF hyperlink and bookmark. C#.NET Sample Code: Convert Word to PDF in C#.NET Project. Add necessary references:
add a link to a pdf file; add url link to pdf
.NET PDF Document Viewing, Annotation, Conversion & Processing
Extract hyperlink inside PDF. PDF Write. Insert text, text box into PDF. Edit, delete text from PDF. Insert images into PDF. Edit, remove images from PDF. Add,
chrome pdf from link; adding hyperlinks to pdf documents
Setting up FactoryTalk alarms                  Chapter 12 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
295 
Setting up event subscriptions 
In the Event Subscription tab, specify the areas and alarm sources from 
which the alarm and event banner will obtain data. 
You can subscribe to events from any area or alarm source in an application, 
as long as the source is set up to support FactoryTalk Alarms and Events.You 
can also filter event subscriptions by priority (Urgent, High, Medium, or 
Low). 
Once you determine where the alarm information will come from, you can 
decide how to filter and sort the information, to control what appears in the 
alarm and event summary. By default, all information generated at the alarm 
source is shown. 
Tip: When subscribing to events for an alarm banner, keep in 
mind that the purpose of the alarm and event banner is 
to make operators aware of the most serious alarms in a 
process or area. 
Setting up filter and sort criteria 
In the Display Filter tab, set up filters for the alarm and event summary, that 
the operator can apply at run time. 
You can build filter criteria using the event fields provided. You can also 
select an initial display filter for the alarm and event summary. 
Tip: Create filters based on what you want to include in the 
alarm and event summary, not what you want to exclude. 
Anything you don’t specify in the filter will 
not be shown 
at run time. 
In the Sort tab, specify which criteria will be used to sort information in the 
alarm and event summary, and in what order (ascending or descending). 
For information about filtering and sorting information in an alarm an event 
summary at run time, see Using an alarm summary to monitor and respond to 
alarms on page 299
Choosing colors and blink styles for the alarm states 
In the States tab, set up text and background colors for the different alarm 
states (In Alarm Unacknowledged, In Alarm Acknowledged, and Normal 
Unacknowledged), and the priorities (Urgent, High, Medium, and Low) for 
each state. 
VB.NET Create PDF from PowerPoint Library to convert pptx, ppt to
Export PowerPoint hyperlink to PDF. VB.NET Demo Code for Converting PowerPoint to PDF. Add necessary references: RasterEdge.Imaging.Basic.dll.
adding links to pdf document; clickable links in pdf
C# Create PDF from PowerPoint Library to convert pptx, ppt to PDF
Export PowerPoint hyperlink to PDF in .NET console application. C#.NET Demo Code: Convert PowerPoint to PDF in C#.NET Application. Add necessary references:
add links to pdf; change link in pdf file
Chapter 12                  Setting up FactoryTalk alarms 
296 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
You can also select whether alarm messages blink in the alarm and event 
summary, and at what rate (slow, medium, or fast). Use the Sample column 
to preview your selections. To test the blink rate, click Test Rates. 
Determining run-time behavior and appearance 
In the Behavior tab, determine to what extent the operator can interact with 
the alarm and event summary at run time. For example, determine whether 
the operator can resize columns, or sort information by clicking on column 
headings. 
In the Common tab, set up the size and position of the alarm and event 
summary, and give the object a name. You can also determine whether the 
summary will present a tooltip, or show a highlight when it has focus in the 
graphic display. 
Setting up an alarm and event banner 
When setting up an alarm and event banner, you specify which alarm 
information will be shown at run time, and how the information will appear 
in the banner. 
For example, to notify operators when the most severe alarms occur, set up 
these alarms to blink and sound an alarm bell. To further indicate severity, 
adjust the alarm bell beep rate. 
A FactoryTalk alarm and event banner can be docked to the inside of the 
FactoryTalk View SE Client window. For more information, see Docking a 
banner display to the run-time client window on page 299
To create an alarm and event banner: 
1.  In FactoryTalk View Studio, in the Explorer window, expand the 
application, area, and HMI server icons, where you want to create the 
alarm and event banner display. 
2.  To create a new graphic display, expand the Graphics folder, 
right-click Displays, and then select New
3.  In the Graphics editor, select Objects > Alarm and Event > Banner. 
You can also click 
on the Graphic editor’s toolbar.
4.  Drag the alarm and event banner tool on the graphic display, to the 
desired size and shape, and then release the mouse. 
You can move and resize the Alarm and Event Banner Design View 
object, as needed. To set up properties, double-click the object (or 
right-click, and then click Properties). 
Setting up FactoryTalk alarms                  Chapter 12 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
297 
Following is an overview of alarm and event banner properties. For 
details about options in the Alarm and Event Banner Properties dialog 
box, click Help
Setting up the appearance of the banner display 
In the General tab, set up the appearance of the alarm list and the status bar. 
For example, you can set up the font, text color, and number of rows in the 
alarm list. 
You can also determine the behavior, when an operator interacts with the 
banner, such as whether double-clicking a row causes an action. 
Choosing the columns and toolbar buttons to show 
In the Columns tab, set up which columns to show in the alarm and event 
banner, and in what order. You can also set up the column width, and the 
alignment and format of information shown in each column. Use the Sample 
column to preview your selections. 
Choosing the status bar contents 
In the Status Bar tab, set up which information to display in the status bar, 
and in what order. You can also set up tooltips for the status bar. 
Setting up event subscriptions 
In the Event Subscription tab, specify the areas and alarm sources from 
which the alarm and event banner will obtain data. 
You can subscribe to events from any area or alarm source in an application, 
as long as the source is set up to support FactoryTalk Alarms and Events.You 
can also filter event subscriptions by priority (Urgent, High, Medium, or 
Low). 
Once you determine where the alarm information will come from, you can 
decide how to filter and sort the information, to control what appears in the 
alarm and event summary. By default, all information generated at the alarm 
source is shown. 
Tip: When subscribing to events for an alarm banner, keep in 
mind that the purpose of the alarm and event banner is 
to make operators aware of the most serious alarms in a 
process or area. 
Chapter 12                  Setting up FactoryTalk alarms 
298 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
Choosing colors, sound, and blink styles for the alarm 
states 
In the States tab, set up text and background colors for the different alarm 
states (In Alarm Unacknowledged, In Alarm Acknowledged, and Normal 
Unacknowledged), and the priorities (Urgent, High, Medium, and Low) for 
each state. 
You can also select whether alarm messages blink in the alarm and event 
banner, or sound an alarm bell, and at what rate. 
Use the Sample column to preview your selections. To test blink and audible 
notification rates, click Test Rates. 
Determining run-time behavior and appearance 
In the Common tab, set up the size and position of the alarm and event 
banner, and give the object a name. You can also determine whether the 
banner will present a tooltip, or show a highlight when it has focus in the 
graphic display. 
About the alarm and event banner at run time 
The alarm and event banner shows only the most serious alarms and events 
in the system. If you want operators to focus on alarms that need immediate 
attention, provide this object. 
You can set up the appearance and behavior of the alarm banner, but it can 
only show up to five of the most recent, most severe alarms. An operator can 
use the alarm banner to: 
Acknowledge the selected alarm (and enter an optional comment). 
Silence alarms. 
Enable or disable the alarm bell. 
Tip: 
The alarm bell is a feature of the alarm and event banner 
only. In an alarm and event summary, alarms cannot be 
set up to sound a bell when they occur. 
Run the command associated with an alarm. 
Refresh the alarm list. 
Open an alarm and event summary. 
For more information, see the FactoryTalk Alarms and Events Help. 
Setting up FactoryTalk alarms                  Chapter 12 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
299 
Docking a banner display to the run-time client window 
At run time, graphic displays can be docked to an edge of the FactoryTalk 
View SE Client window, so that they are available to operators at all times. 
For example, to let an operator continuously monitor the most serious alarms 
in an application, dock an alarm banner display to the top or bottom of the 
client window. 
Example: Docking an alarm banner when the FactoryTalk View 
SE Client starts up 
To dock an alarm banner display to the bottom edge of the FactoryTalk View 
SE Client window when the client starts up, follow these steps: 
1.  In FactoryTalk View Studio, create a macro that contains the command 
Display <Alarm Banner> /DB
where Alarm Banner is the name of the graphic display that contains 
the alarm banner. 
Tip: /DB is the Display command parameter for docking a 
display at the bottom of the FactoryTalk View SE Client 
window. For a full list of docking parameters, see Display 
command parameters for docking displays on page 442. 
2.  In the FactoryTalk View SE Client Wizard, in the Components 
window, select the macro that contains the Display command for 
docking the banner. 
3.  Save the client configuration file. 
When you start the client, the alarm banner will be attached to the 
bottom edge of the client window. 
Opening and closing other graphic displays will not interfere with the 
position or appearance of the docked banner display. 
The alarm and event summary is a table that displays active alarm 
notifications received from the FactoryTalk alarm servers in a FactoryTalk 
View SE application. 
Alarm and event summaries are hosted in graphic displays created in 
FactoryTalk View Studio, and run in the FactoryTalk View SE Client. 
A single alarm and event summary can subscribe to alarm notifications from 
multiple alarm servers in an application. 
At run time, an operator can use an alarm and event summary to monitor 
alarm activity, and to acknowledge, suppress, disable, or reset active alarms. 
Using an alarm 
summary to monitor 
and respond to 
alarms 
Chapter 12                  Setting up FactoryTalk alarms 
300 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
For more information about these actions, see subsequent sections in this 
chapter. 
Tip: You can also use alarm tags to suppress, unsuppress, 
enable, and disable alarms. For more information, see 
Using tags to interact with alarms or obtain their status 
on page 312
The parts of an alarm and event summary 
The following illustration shows an alarm and event summary at run time. 
An alarm and event summary is composed of: 
An alarm list, that shows alarms that need the operator’s attention.
An optional status bar, that provides information about the contents of 
the alarm and event summary, such as the name of the filter applied to 
the list view. 
An optional details pane, that shows the attributes of the currently 
selected alarm. 
A shortcut menu, and an optional toolbar, for alarm-related operations. 
The following sections describe some of the ways you can use an alarm and 
event summary at run time. For details, see the FactoryTalk Alarms and 
Events Help. 