c# pdf manipulation : Add url pdf SDK Library service wpf .net winforms dnn viewse-um006_-en-e5-part741

Exploring FactoryTalk View Studio                  Chapter 2 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
51 
Opening component editors 
Use the editors in FactoryTalk View Studio to create or modify application 
components. Editors are represented by icons in the Explorer window, or by 
items in menus. 
To open an editor, use one of these methods: 
Double-click on one of the components in an application (for example, 
a display). 
Drag the editor’s icon from the E
xplorer to the workspace. 
Right-
click the editor’s icon, and then click New or Open.
Tip: If the editor can create multiple components, the shortcut 
menu contains New. If the editor can only open a single 
component, the menu contains Open. 
From the Tools or Settings menu, select the editor you want to open. 
Following is a list of FactoryTalk View SE editors and their functions. If you 
can open an editor from the FactoryTalk View Studio menu bar, the name of 
the menu is noted. 
To do this 
Use this editor 
Set up runtime security accounts for FactoryTalk View, assign 
security codes to users and groups, and assign login and logout 
macros. 
Runtime Security (Settings menu) 
Assign security codes to FactoryTalk View commands and macros.  Runtime Secured Commands (Settings menu) 
Specify the type of system activity to be logged and where, when, 
and how it will be logged. 
TIP: The settings you specify in this editor apply only to the 
he 
computer you are using. 
Diagnostics Setup (Tools menu) 
For HMI tag alarms only, specify what, where, when, and how 
alarm activity is to be logged. 
TIP: The settings you specify in this editor apply only to the 
he 
computer you are using, and only if the computer contains an HMI 
server. 
HMI Tag Alarm Log Setup (Tools menu) 
Add languages to an application, set up a default language, and 
export and import text strings. 
Languages (Tools menu) 
Open a command line to run FactoryTalk View commands and 
macros. 
Command Line 
Create HMI tags and set up HMI tag alarms. 
Tags 
Create graphic displays and global object displays, or open the 
graphic libraries to use the library objects. 
Graphics (Displays, Global Objects, or Libraries icon) 
Add images to an application that are to be used repeatedly in 
graphic displays. 
Images 
Create parameter files, to specify tags whose values will replace 
tag placeholders in graphic displays at run time. 
Parameters 
Create recipe files to specify values for input and display objects in 
graphic displays. 
Recipes 
Add url pdf - insert, remove PDF links in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Free C# example code is offered for users to edit PDF document hyperlink (url), like inserting and deleting
add link to pdf file; add hyperlink pdf file
Add url pdf - VB.NET PDF url edit library: insert, remove PDF links in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Help to Insert a Hyperlink to Specified PDF Document Page
pdf link; add links to pdf in preview
Chapter 2                  Exploring FactoryTalk View Studio 
52 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
Create local message files containing trigger values, and the 
corresponding messages. 
Local Messages 
For HMI tag alarms only, set up general features such as alarm 
severities and user messages. 
Alarm Setup 
For HMI tag alarms only, display a list of tags that have alarm 
notification suppressed. 
Suppressed List 
Create tags whose values are derived from other tags, or from 
functions. 
Derived Tags 
Create events, which are expressions that trigger FactoryTalk View 
commands or macros. 
Events 
Create macros to run series of FactoryTalk View commands. 
Macros 
Re-map the FactoryTalk View SE Client keyboard to run 
FactoryTalk View commands. 
Client Keys 
Create data log models to specify where, when, and how selected 
tag values will be logged. 
Data Log Models 
Creating and modifying components 
The Explorer manages components that represent physical files located in 
folders under the application directory. 
To display components associated with a particular editor: 
Use one of these methods: 
Click the + sign beside the editor’s icon.
Double-
click the editor’s icon.
Click the editor’s icon, and then press 
Enter
Components created with the editor are shown under the editor’s icon in the 
tree. 
C#: How to Open a File from a URL (HTTP, FTP) in HTML5 Viewer
License and Price. File Formats. PDF. Word. Excel. PowerPoint. Tiff. DNN (Dotnetnuke). Quick to Start. Add a Viewer Control on Open a File from a URL (HTTP, FTP).
pdf hyperlinks; change link in pdf
C#: How to Add HTML5 Document Viewer Control to Your Web Page
addTab(_tabRedact); //add Tab "Sample new UserCommand("pdf"); _userCmdDemoPdf.addCSS( new customStyle({ background: "url('RasterEdge_Resource_Files/images
adding hyperlinks to a pdf; change link in pdf file
Exploring FactoryTalk View Studio                  Chapter 2 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
53 
To create a new component: 
Use one of these methods: 
Drag the editor’s icon into the workspace
Right-
click the editor’s icon, and then click 
New
To open a component: 
Use one of these methods: 
Double-click the component. 
Drag the component into the workspace. 
Right-click the component, and then click Open. 
Adding components to an application 
To add a component, using drag and drop: 
1.  In Windows Explorer, locate the file to add to the application. 
2.  Drag the file to the Explorer window in FactoryTalk View Studio. 
The component is added to the Explorer automatically, under the editor 
used to modify it. 
To add a component, using the Add Component option: 
1.  In FactoryTalk View Studio, in the Explorer window, right-click the 
editor used to create the component you want to add, and then click 
Add Component into Application
For example, to add a graphic display, right-click the Displays icon, 
and then click Add Component into Application
2.  Find and select the component you want to add, and then click Open
Selected components are added to the Explorer, under the editor’s icon.
Tip: To select several consecutive components, click the first 
component you want to select, press the Shift key, and 
then click the last component. To select several 
individual components, press the Ctrl key, and then click 
each component. 
When you use this option, you create a copy of the file in the application. 
C# PDF Library SDK to view, edit, convert, process PDF file for C#
editing PDF document hyperlink (url) and quick navigation link in PDF bookmark. C#.NET: Edit PDF Metadata. PDF SDK for .NET allows you to read, add, edit, update
adding an email link to a pdf; adding a link to a pdf
C# Image: How to Download Image from URL in C# Project with .NET
Add this imaging library to your C#.NET project jpeg / jpg, or bmp image from a URL to your provide powerful & profession imaging controls, PDF document, tiff
add a link to a pdf file; pdf reader link
Chapter 2                  Exploring FactoryTalk View Studio 
54 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
Naming components 
When you name a component in FactoryTalk View Studio, the file name is 
created on disk automatically. The component name shown in the Explorer 
window becomes part of the file name. 
FactoryTalk View supports long file names with a maximum limitation of 
260 characters including spaces. When considering a filename, you need to 
keep in mind four characters for the extension (.gfx) and all the characters 
necessary for the path leading to the file. The remainder would be the 
number of characters, including spaces, you can use for a file name. 
Different files will be dependent on the path where they reside. 
For example, including spaces, there are 115 characters in the following path 
and file name, as the limit is 260, leaving 145 additional characters, including 
spaces, allowable: 
C:\Documents and Settings\All Users\Documents\RSView 
Enterprise\SE\HMI Projects\InstantFizz_SE\Gfx\cip overview.gfx 
Another example path is shown below, it is based on saving a macro: 
C:\Documents and Settings\All Users\Documents\RSView 
Enterprise\SE\HMI Projects\InstantFizz_SE\Mcr 
That is 108 total characters just for the path, 260 - 108 = 142. The filename 
can be up to 142 characters including spaces and allowing 4 characters for 
the extension. 
Using component names that contain spaces 
Component names can contain spaces, like the graphic display name in the 
previous example. When using component names with spaces in commands, 
you might need to enclose the component names in double quotes ( " " ). 
For example, to load a parameter file with spaces in its name, you would type 
the following Display command: 
Display Screen1 /P"Bottling Line 1"
Tip: 
For information about the command syntax for specific 
FactoryTalk View commands, see the FactoryTalk View 
Site Edition Help. 
Avoiding names that conflict with commands or macros 
To avoid problems when issuing commands and macros, do not give macros 
the same names as commands. For example, instead of giving a macro the 
C# PDF insert image Library: insert images into PDF in C#.net, ASP
C#.NET PDF SDK - Add Image to PDF Page in C#.NET. How to Insert & Add Image, Picture or Logo on PDF Page Using C#.NET. Add Image to PDF Page Using C#.NET.
add hyperlink pdf; add links in pdf
C# HTML5 PDF Viewer SDK to view PDF document online in C#.NET
Insert Image to PDF. Image: Remove Image from PDF Page. Cut Image in Page. Link: Edit URL. Bookmark: Edit Images. Redact Pages. Annotation & Drawing. Add Sticky Note
add url link to pdf; add links to pdf online
Exploring FactoryTalk View Studio                  Chapter 2 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
55 
name Display, to avoid confusion with the Display command, name the 
macro DisplayScreen instead. 
Deleting, removing, and renaming components 
In FactoryTalk View Studio, when you: 
Delete a component, the component and the corresponding physical 
file are deleted. 
Remove a component, the component is removed from the Explorer 
window, but the physical file is not deleted. 
Rename a component, the component and the physical file are both 
renamed. 
To delete a component and file: 
In FactoryTalk View Studio, in the Explorer window, right-click the 
component you want to delete, and then select Delete
To remove a component: 
In FactoryTalk View Studio, in the Explorer window, right-click the 
component you want to remove, and then select Remove
To rename a component: 
1.  In FactoryTalk View Studio, in the Explorer window, right-click the 
component you want to rename, and then select Rename
2.  Type the new name, and then click OK
Restoring a component after renaming the physical file 
If you rename a physical file in Windows Explorer, you will no longer be 
able to open the corresponding component in FactoryTalk View Studio. You 
must remove the component, and then add the renamed file back into the 
application. 
To restore a component after changing the physical file name: 
1.  In FactoryTalk View Studio, in the Explorer window, right-click the 
component, and then select Remove
2.  Right-click the icon of the editor used to create the component you 
want to restore, and then select Add Component into Application
For example, to restore a graphic display, right-click the Displays icon. 
VB.NET PDF- View PDF Online with VB.NET HTML5 PDF Viewer
to PDF. Image: Remove Image from PDF Page. Image Link: Edit URL. Bookmark: Edit Bookmark. Metadata: Edit, Delete Redact Pages. Annotation & Drawing. Add Sticky Note
clickable links in pdf from word; add links to pdf document
VB.NET Image: VB Code to Download and Save Image from Web URL
Apart from image downloading from web URL, RasterEdge .NET Imaging SDK still dedicated to provide powerful & profession imaging controls, PDF document, image
add hyperlink to pdf in preview; convert excel to pdf with hyperlinks
Chapter 2                  Exploring FactoryTalk View Studio 
56 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
3.  Find and select the renamed physical file, and then click Open
Many of the editors you will use to develop a FactoryTalk View application 
have similar features, that require similar information. Knowing about these 
features saves time. 
Gaining quick access to common operations 
Shortcut menus provide quick access to actions you perform frequently, in 
different environments. 
In the Explorer, everything in the tree hierarchy has a shortcut menu, except 
the folders. In the Graphics editor, graphic displays and objects in the 
displays have shortcut menus. 
To open a shortcut menu, position the pointer over an icon, graphic display, 
or object, and then right-click. 
Browsing lists and components 
The Browse button is beside fields that require input. For example, instead of 
typing information in a text box, you can click the Browse button to open: 
A list containing valid entries for the text box. 
A dialog box or browser, such as the Tag Browser, in which you can 
search for and select a valid entry. 
An editor, in which you can create a valid entry. 
Supplying tag names 
Tags are stored in devices, data servers, and in the HMI tag database. 
Tag names are used, for example, to specify connections for input objects in 
FactoryTalk View graphic displays. To supply a tag name, use one of these 
methods: 
Type the name of the tag. You do not have to create the tag in order to 
use its name, but be sure to create the tag later, or errors will be 
reported at run time. 
Click the Browse or Tags button (whichever is available) to open the 
Tag Browser, where you can select or create a tag. 
For more information about tags, see Working with tags on page 189
Techniques for 
working in editors 
Exploring FactoryTalk View Studio                  Chapter 2 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
57 
Selecting and building commands 
You can use FactoryTalk View commands to interact with and control 
application components. Most commands accept parameters for added 
precision and control. 
You can set up keys and graphic objects to run commands at run time. You 
can also run commands from the HMI server’s command line, or create a list 
of commands in a macro, and run the macro in places where the commands 
are required. 
Use the Command Wizard for assistance with selecting and building 
commands. 
To open the Command Wizard, use one of these methods: 
Click the Browse button beside a text box where a command is 
expected, for example, in the Press action text box for a button object, 
or in the Command Line. 
Double-click in a box where a command is expected or in the Macros 
editor. 
From the Edit menu, select Commands. 
For information about specific FactoryTalk View commands, click Help
Building expressions 
Many editors use expressions to compute values based on tags and functions. 
Expressions can be complex logical expressions, or they can be tag names. 
Chapter 2                  Exploring FactoryTalk View Studio 
58 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
For more information, see Creating expressions on page 553
From each FactoryTalk View SE editor, you can print selected items or the 
editor’s entir
e contents. 
To print selections: 
1. 
Select the item you want to print, for example, a record in an editor’s 
spreadsheet. 
2.  From the File menu, select Print
3.  Under Print Range, select Selection
To print the entire contents of the window: 
1.  From the File menu, click Print. 
2.  Under Print Range, click All
Selecting a printer 
You must install a printer before you can select it. 
FactoryTalk View can print to a network printer. For information about 
installing and setting up printers, see your Windows documentation. 
To select a printer: 
1.  In any FactoryTalk View editor, from the File menu, choose Print 
Setup
2.  If you do not want to use the default printer, specify another printer. 
3.  Choose the appropriate orientation and paper options. 
Tip: Print Setup settings apply to the development computer 
only. If the application will run on a different computer, 
you must also set up a printer on that computer. 
Printing at run time 
To print graphic displays at run time, use the PrintDisplay command. 
Printing from 
FactoryTalk View 
SE 
Exploring FactoryTalk View Studio                  Chapter 2 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
59 
To let an operator print specific displays, provide a way to run the command 
for these displays. For example, create a button object, display key, or client 
key using PrintDisplay as the press action. 
When you use the PrintDisplay command, FactoryTalk View prints the entire 
display, even if parts are covered by other displays. If you want to print an 
image of whatever shows on the monitor, use the ScreenPrint command. 
For more information about the PrintDisplay command, see the FactoryTalk 
View Site Edition Help. 