itextsharp datagridview to pdf c# : Add hyperlink to pdf online Library control component asp.net azure .net mvc viewse-um006_-en-e59-part751

Setting up data logging                  Chapter 22 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
591 
Set up the FactoryTalk View data log fields in the existing ODBC 
tables before setting up a data log model. 
Create new tables in the existing database automatically or manually, 
from within the Data Log Models editor. 
To use the tables in an existing ODBC data source: 
1.  Add fields for the data log data to the tables in the ODBC database. 
For information about modifying the ODBC database tables, see the 
documentation for the ODBC database you are using. 
2.  Set up a data log model, as described in Help. Specify the existing 
ODBC database as the ODBC Data Source, and then specify the tables 
you edited. 
Tip: When creating the tables for Float and String data 
logging to MS SQL Server 2008, ensure that Microsoft 
SQL Server 2008 Service Pack 1 has been installed first, 
or table creation will not be possible. 
To create new tables in an existing ODBC data source: 
1.  Specify the name of the existing ODBC data source in the ODBC Data 
Source field of the Data Log Models editor. 
2.  Click Create Tables. FactoryTalk View automatically creates new 
data log tables in the existing database. You can also create tables 
manually. 
3.  Set up the rest of the data log model, as described in Help. 
Creating a new ODBC data source 
To create a new ODBC data source, click the browse (...) button next to the 
ODBC Data Source text box, or use the ODBC Data Source Administrator 
in the Windows Control Panel. Click Help in the ODBC Data Source 
Administrator window for more details about creating a new ODBC data 
source. 
You can create the tables for a new data source using either of the methods 
described in Logging data to an existing ODBC data source on page 590
Add hyperlink to pdf online - insert, remove PDF links in C#.net, ASP.NET, MVC, Ajax, WinForms, WPF
Free C# example code is offered for users to edit PDF document hyperlink (url), like inserting and deleting
accessible links in pdf; add hyperlinks pdf file
Add hyperlink to pdf online - VB.NET PDF url edit library: insert, remove PDF links in vb.net, ASP.NET, MVC, Ajax, WinForms, WPF
Help to Insert a Hyperlink to Specified PDF Document Page
convert doc to pdf with hyperlinks; pdf hyperlinks
Chapter 22                  Setting up data logging 
592 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
Setting up security to log data to a remote 
computer 
If you are logging data to an ODBC database that is not located on the 
computer where the data is being generated, you must change certain DCOM 
security settings. For details, see the FactoryTalk View Site Edition Help. 
To create new file sets or ODBC backup files at run time, use the 
FactoryTalk View command DataLogNewFile
If a data log model uses the ODBC format, and if FactoryTalk View is 
logging to the backup path, running the DataLogNewFile command creates 
a new set of backup files. 
If FactoryTalk View is logging to the ODBC database, an End Snapshot and 
then a Begin Snapshot are logged when this command is run. 
If a data log model uses file sets, DataLogNewFile creates a new file set 
regardless of how the data log model is set up to start new files. The new file 
set is created in the same location that FactoryTalk View is currently logging 
to. 
DataLogNewFile records two snapshots of data: an End Record in the old 
file, and a Begin Record in the new file. It is not necessary to use the 
DataLogSnapshot command in this case. 
Using the DataLogNewFile command 
You can use the DataLogNewFile command with either of these parameters: 
DataLogNewFile <component> (where <component> is a data log 
model name) creates a new file set for the specified data log model. 
DataLogNewFile * creates a new file set for all data log models that 
are currently running. 
You can use the DataLogNewFile command anywhere you can type a 
FactoryTalk View command or macro. 
To provide operators with a way to create new files at run time, create a 
button object in a graphic display, or a display key or client key, that uses 
DataLogNewFile as the press action. 
FactoryTalk View lets you specify a secondary or backup path to be used in 
the event the primary path for file sets, or the ODBC database, becomes 
unavailable. This could happen due to a network failure, or lack of disk 
space on the computer where the data is being logged. 
Creating new files at 
run time 
Switching log paths 
at run time 
VB.NET Create PDF from Word Library to convert docx, doc to PDF in
Change Word hyperlink to PDF hyperlink and bookmark. VB.NET Demo Code for Converting Word to PDF. Add necessary references: RasterEdge.Imaging.Basic.dll.
change link in pdf; add hyperlinks to pdf online
VB.NET Create PDF from Excel Library to convert xlsx, xls to PDF
Change Excel hyperlink to PDF hyperlink and bookmark. VB.NET Demo Code for Converting Excel to PDF. Add necessary references: RasterEdge.Imaging.Basic.dll.
adding a link to a pdf in preview; add a link to a pdf in preview
Setting up data logging                  Chapter 22 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
593 
If the primary data log location becomes unavailable, FactoryTalk View 
begins to store the data in a buffer. 
The buffer can hold up to 64 Kb of data. If the primary location is still 
unavailable when the buffer fills, or when the maximum amount of time to 
buffer data has elapsed, FactoryTalk View switches to the secondary path. 
FactoryTalk View checks periodically to determine whether the primary file 
path has become available again. Once it is available, FactoryTalk View 
switches back automatically. 
If the secondary path becomes unavailable, FactoryTalk View also checks 
the status of the primary path, and will switch back if possible. If both paths 
are unavailable, FactoryTalk View buffers the data. 
If the buffer fills and both paths are still unavailable, FactoryTalk View 
empties the buffer (the data in the buffer is lost) and begins storing new data 
in the buffer. FactoryTalk View continues checking both paths until one 
becomes available. 
Tip: For data log models that use the file set format, 
FactoryTalk View creates a new file set each time the 
logging path changes. 
Setting up switching options 
In the Advance Configuration dialog box, you can specify the length of 
time data will be buffered before switching to the secondary path, and when 
data logging will switch back to the primary path. 
For example, if the data log file is locked, data is buffered for the maximum 
time (in minutes) you specify to buffer data before attempting a switchover. 
When the buffer time elapses, a new set of files is created on the primary 
path. 
If the model is logging to the secondary path and the file is locked, the 
behavior is the same: the data is buffered, and then a new file set is created 
when the specified time period has elapsed. 
To open the Advance Configuration dialog box, in the Data Log Models 
editor, select the Paths tab, and then click Advanced. For details about 
options in the Paths dialog box, click Help
.NET PDF Document Viewing, Annotation, Conversion & Processing
Extract bookmark & outlines. Extract hyperlink inside PDF. PDF Write. Insert images into PDF. Edit, remove images from PDF. Add, edit, delete links. Form Process
adding hyperlinks to pdf files; adding hyperlinks to pdf
VB.NET PDF: Basic SDK Concept of XDoc.PDF
You may add PDF document protection functionality into your VB.NET program. Hyperlink Edit. XDoc.PDF for .NET allows VB.NET developers to edit hyperlink of PDF
change link in pdf file; add hyperlink in pdf
Chapter 22                  Setting up data logging 
594 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
Tip: 
If a secondary path is not set up, the data is buffered for 
10 minutes (the default value for maximum time). If the 
maximum time is set to zero, a new file set is started 
immediately. 
Switching back manually to the primary path 
To switch back to the primary path or ODBC database manually, use the 
FactoryTalk View command DataLogSwitchBack. 
You can only use the command to switch back to the primary path or 
database. You cannot use it to switch from the primary path or ODBC 
database to the secondary or backup path. 
The switchback is performed only if the specified data log model is running, 
FactoryTalk View is logging data to the secondary or backup path, and the 
primary path or ODBC database is available. 
For data log models that use file sets, FactoryTalk View creates a new set of 
files when it switches back to the primary path. 
Tip: Data logged to the secondary path is not moved 
automatically, when a switchback to the primary occurs. 
To move the data manually, use the 
DataLogMergeToPrimary command. For details, see 
Moving data from the secondary path on page 595. 
Using the DataLogSwitchBack command 
You can use the DataLogSwitchBack command with either of these 
parameters: 
DataLogSwitchBack <component> (where <component> is a data log 
model name) switches logging for the specified data log model. 
DataLogSwitchBack * switches logging for all data log models that are 
currently running. 
You can use the DataLogSwitchBack command anywhere you can type a 
FactoryTalk View command or macro. 
To provide operators with a way to switch manually to the primary path or 
ODBC database at run time, create a button object in a graphic display, or a 
display key or client key, that uses DataLogSwitchBack as the press action. 
VB.NET Create PDF from PowerPoint Library to convert pptx, ppt to
Export PowerPoint hyperlink to PDF. VB.NET Demo Code for Converting PowerPoint to PDF. Add necessary references: RasterEdge.Imaging.Basic.dll.
pdf link to email; add links to pdf acrobat
How to C#: Basic SDK Concept of XDoc.PDF for .NET
You may add PDF document protection functionality into your C# program. Hyperlink Edit. XDoc.PDF for .NET allows C# developers to edit hyperlink of PDF document
add hyperlink to pdf in preview; add hyperlink pdf
Setting up data logging                  Chapter 22 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
595 
Moving data from the secondary path 
When you begin writing to or reading from a data log model, if there are files 
in the secondary (or backup) path, FactoryTalk View sends a message to the 
FactoryTalk Diagnostics log. 
You must move these files manually to the primary path or ODBC database. 
To do this, use the FactoryTalk View command DataLogMergeToPrimary
If a data log model is running when the command is run, FactoryTalk View 
performs a switchback to the primary path or ODBC database for the 
specified model, or all running models. 
If the model uses file sets, FactoryTalk View moves all files on the 
secondary path (including the current file set) to the primary path, begins a 
new file set on the primary path, and then continues logging to the new file 
set. 
If the model uses the ODBC format, FactoryTalk View merges the data in 
the ODBC backup files into the ODBC database, and then continues logging 
to the ODBC database. 
Using the DataLogMergeToPrimary command 
You can use the DataLogMergeToPrimary command with either of these 
parameters: 
DataLogMergeToPrimary <component> (where <component> is a data 
log model name) moves data for the specified data log model, whether 
or not the model is running. 
DataLogMergeToPrimary * moves data for all data log models 
whether or not they are running. 
You can use the DataLogMergetoPrimary command anywhere you can 
type a FactoryTalk View command or macro. 
To provide operators with a way to restore backup data to the primary path or 
ODBC database at run time, create a button object in a graphic display, or a 
display key or client key, that uses DataLogMergetoPrimary as the press 
action. 
To record the values of tags in a data log model on demand, use the 
FactoryTalk View command DataLogSnapshot. If you specified the On 
Demand trigger for the data log model, logging will occur only when the 
DataLogsnapshot command is run. 
Logging on demand 
C# Create PDF from Word Library to convert docx, doc to PDF in C#.
Change Word hyperlink to PDF hyperlink and bookmark. C#.NET Sample Code: Convert Word to PDF in C#.NET Project. Add necessary references:
add a link to a pdf file; add link to pdf acrobat
C# Create PDF from PowerPoint Library to convert pptx, ppt to PDF
Export PowerPoint hyperlink to PDF in .NET console application. C#.NET Demo Code: Convert PowerPoint to PDF in C#.NET Application. Add necessary references:
add url pdf; convert a word document to pdf with hyperlinks
Chapter 22                  Setting up data logging 
596 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
Using the DataLogSnapshot command 
You can use the DataLogSnapshot command with either of these 
parameters: 
DataLogSnapshot <component> (where <component> is a data log 
model name) records tag values for all tags in the specified model at 
the instant the command is run. 
DataLogSnapshot * records tag values for all tags in all running 
models at the instant the command is run. 
You can use the DataLogSnapshot command anywhere you can type a 
FactoryTalk View command or macro. For example, you can use the 
command as the action for an event (an example of how to do this follows). 
To provide operators with a way to log on demand at run time, create a 
button object in a graphic display, or a display key or client key, that uses 
DataLogSnapshot as the press action. 
Example: Creating an event for on-demand logging 
To create an event that will trigger logging when an alarm occurs: 
1.  In the Data Log Models editor, in the Log Triggers tab, select the 
option On Demand
2.  Open the Event editor. Create an expression such as: 
If alm_in_alarm(motor_fault) and new_batch_started 
then 1 else 0
3.  In the Event 
editor’s 
Action field, type 
DataLogSnapshot <component> where component is the name of the 
data log model. 
When the tag called motor_fault goes into alarm, and the tag called 
new_batch_started is 1, the DataLogSnapshot <component> command 
runs. All tags in the model will then be logged (not just the tag in alarm). 
Combining logging 
You can combine periodic or on-change logging with on-demand logging, to 
capture data at particular times and when a particular event occurs. 
To combine logging: 
1.  In the Data Log Models editor, in the Log Triggers tab, select the 
Periodic or On Change option. 
Setting up data logging                  Chapter 22 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
597 
2.  Type the DataLogSnapshot command with the <component> or * 
(asterisk) parameter, anywhere you can use a macro or command. 
You can modify a data log model during development or at run time, using 
either FactoryTalk View Studio or the FactoryTalk View SE Administration 
Console. 
If you change a model at run time, the changes will not take effect until you 
stop and then restart data logging. For information about starting and 
stopping data logging, see Starting and stopping data logging on page 598
Tip: 
If a tag that you delete from a data log model is used in a 
trend object, be sure to remove all references to the 
deleted tag from the trend. 
Changing log paths 
To change the log paths for a data log model after deploying a FactoryTalk 
View SE application, you can use FactoryTalk View Studio or the 
FactoryTalk View SE Administration Console. 
Tip: 
You can launch the FactoryTalk View SE Administration 
Console from the following location: 
(32-bit operating systems)  
C:\Program Files\Rockwell Software\RSView 
View 
Enterprise\Admin Console.exe 
(64-bit operating systems)  
C:\Program Files (x86)\Rockwell Software\RSView 
View 
Enterprise\Admin Console.exe 
You can change the primary and secondary paths for file sets, and the backup 
path for ODBC data log models. You cannot use the Administration Console 
to change the ODBC database. 
Making run-time changes without modifying the 
model 
At run time, you can also change the following data log parameters, without 
modifying the data log model: 
The log rate for periodic logging (use the DataLogChangeRate 
command) 
The log file identifier string (use the DataLogRenameFile command) 
Use these commands anywhere you can enter a FactoryTalk View command 
or macro. For example, in FactoryTalk View Studio, or the FactoryTalk 
Modifying existing 
data log models 
Chapter 22                  Setting up data logging 
598 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
View SE Administration Console, type the command directly at the 
command line. 
These changes take effect immediately, but only apply to the current logging 
session. When you stop and restart logging, FactoryTalk View uses the 
logging rate and log file identifier specified for the data log model. 
For details about the DataLogChangeRate and DataLogRenameFile 
commands, see the FactoryTalk View Site Edition Help. 
There are many ways to start and stop data logging. Choose the way that 
works best for the application. 
To provide operators with a way to start and stop data logging, use 
FactoryTalk View commands and macros in conjunction with graphic 
objects. For details about FactoryTalk View command syntax, see the 
FactoryTalk View Site Edition Help. 
In the following methods, <component> represents the name of a data log 
model. 
Ways to start data logging 
To start data logging, use one of these methods: 
In the HMI Server Properties dialog box, click the Components tab, 
select the Data Logging check box, and then specify a data log model. 
The data log model will run the next time the HMI server runs, or 
when the HMI server’s components are started manually.
In the Macros editor, create a macro that contains the command, 
DataLogOn <component>. In the HMI Server Properties dialog box, 
click the Components tab, select the Macro check box, and then 
specify the macro. 
The specified data log model will run when the HMI server runs. To 
start more than one data log model, specify multiple DataLogOn 
<componentcommands in the macro. 
In the Graphics editor, open the Display Settings dialog box, and then 
click the Behavior tab. In the Startup box, type DataLogOn 
<component>
In the Graphics editor, create a button object and then specify 
DataLogOn <component
as the button’s press action. When the 
button is pressed, the command runs. 
In the Graphics editor, create a graphic object and attach touch 
animation to it, using DataLogOn <component> in the Action box. 
When the object is touched, data logging starts for the specified model. 
Starting and 
stopping data 
logging 
Setting up data logging                  Chapter 22 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
599 
In the Events editor, type the DataLogOn <componentcommand in 
the Action box for an event. 
At the command line in FactoryTalk View Studio, or the FactoryTalk 
View SE Administration Console, type DataLogOn <component> and 
then press Enter. 
Ways to stop data logging 
To stop data logging only, use one of these methods: 
Use the DataLogOff <componentcommand (where <component> is 
the name of the data log model) to stop a single model. To stop all data 
log models, use the DataLogOff * command. 
In the Graphics editor, create a button object, and then specify 
DataLogOff <component> or DataLogOff * 
as the button’s press 
action. When the button is pressed, the command runs. 
In the Graphics editor, create a graphic object and attach touch 
animation to it, using DataLogOff <component> or DataLogOff * in 
the Action box. When the object is touched, data logging is stopped for 
the specified model. 
In the Events editor, specify DataLogOff <component> or 
DataLogOff * as the action for an event. 
At the command line in FactoryTalk View Studio, or the FactoryTalk 
View SE Administration Console, type DataLogOff <component> or 
type DataLogOff * and then press Enter
You can also stop data logging by stopping all HMI server components 
running on the computer. For details, see Starting and stopping HMI server 
components manually on page 160