ghostscript.net convert pdf to image c# : Convert word document to fillable pdf form application SDK cloud windows wpf winforms class viewse-um006_-en-e58-part1518

Creating embedded variables                  Chapter 21 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
581 
would show the short date followed the time, for example: 
9/28/2006 1:12:25 PM
A space is inserted between the time and date at run time. 
If there is no valid data available for an embedded variable, the caption, local 
message, tooltip, or title bar that contains it will show question marks ( ? ). 
This might occur when a display first opens and the data has not arrived yet, 
or when there is a problem that prevents communication with the data 
source. 
Numeric embedded variables 
For numeric embedded variables that use tag values, how the value is shown 
depends on whether the data type is integer or floating-point: integer values 
are shown as they are; floating-point values are rounded to fit the number of 
digits specified for the variable. 
For example, if 6 is the number or digits specified, the floating point value 
1234.56 is rounded to 1234.6, and the value 1234.44 is rounded to 1234.4
The decimal point counts as one of the digits. If the value is negative, the 
minus sign also counts as a digit. 
If the floating-point value, including a decimal point and a minus sign, 
contains more digits than specified for the variable, the numeric variable is 
replaced with asterisks ( * ). 
Number formats 
Numeric embedded variables use the number format you set up on the 
run-time computer. For example, if the run-time computer is set up to use a 
comma for the decimal symbol, the numeric variable will also use a comma 
for the decimal symbol. 
String embedded variables 
For string embedded variables that do not use a fixed number of characters, 
the entire tag value or literal string is shown, unless a null character (?) is 
read. Nothing after a null character is shown. 
For string embedded variables that do use a fixed number of characters, the 
entire tag value or literal string is shown up to the number of characters 
specified, unless a null character (?) is read. Nothing after a null character is 
shown. 
If necessary, spaces are used to make up the specified number of characters. 
How embedded 
variables are shown 
at run time 
Convert word document to fillable pdf form - C# PDF Form Data fill-in Library: auto fill-in PDF form data in C#.net, ASP.NET, MVC, WinForms, WPF
Online C# Tutorial to Automatically Fill in Field Data to PDF
convert pdf to fillable form online; create a fillable pdf form from a word document
Convert word document to fillable pdf form - VB.NET PDF Form Data fill-in library: auto fill-in PDF form data in vb.net, ASP.NET, MVC, WinForms, WPF
VB.NET PDF Form Data fill-in library: auto fill-in PDF form data in vb.net, ASP.NET, MVC, WinForms, WPF
asp.net fill pdf form; convert pdf file to fillable form
Chapter 21                  Creating embedded variables 
582 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
Tip: 
Null characters have a hex value of 0, and indicate the 
end of a string. A null character does not add to the 
actual length of the string. 
By default, string variables that use a fixed number of characters show the 
characters from left to right. To show characters from right to left, in the 
String Variable dialog box, select the check box, Right-most characters in 
string are shown
If the string is longer than the width of the field it is embedded in, you can 
also specify whether asterisks (*) are shown at run time. 
Time and date embedded variables 
For embedded variables that show both the time and the date, a space is 
placed between the time and date when the embedded variable is shown at 
run time. 
Time and date formats 
Time and date embedded variables use the time and date formats you set up 
on the run-time computer. For example, if the time and date variable shows 
the short date, at run time the variable will use the short date format set up 
for the run-time computer. 
How an embedded variable is updated at run time depends on the type of 
variable and where it is embedded: 
In caption text, title bar text, and local messages, numeric or string 
embedded variables that use tag values are updated whenever a new 
tag value is read from the data source. 
Embedded variables that use tags are also updated when the graphic 
display is loaded into the cache, using the Always Updating option. 
For information about setting up display caching, see Setting up 
displays to open more quickly on page 440
In tooltips on graphic objects, numeric or string embedded variables 
that use tag values are updated only when the graphic display 
containing the object is opened. 
Embedded variables that use tags in tooltips will not update 
dynamically, while the display is running. 
Time and date embedded variables are updated as the system time and 
date change. 
How embedded 
variables are 
updated at run time 
C# Create PDF from OpenOffice to convert odt, odp files to PDF in
Create PDF document from OpenOffice Presentation in both .NET WinForms and ASP.NET using RasterEdge.XDoc.Word; How to Use C#.NET Demo Code to Convert ODT to
convert pdf into fillable form; convert pdf fillable form to html
C# Create PDF Library SDK to convert PDF from other file formats
Best C#.NET component to create searchable PDF document from Microsoft Office Word, Excel and PowerPoint. Create fillable PDF document with fields.
pdf signature field; convert pdf to fill in form
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
583 
Chapter 22 
Setting up data logging 
This chapter describes: 
What data logging is. 
Data log storage formats. 
Creating a data log model. 
Working with ODBC data sources. 
Creating new files at run time. 
Switching log paths at run time. 
Logging on demand. 
Modifying existing data log models. 
Starting and stopping data logging. 
Data log is a FactoryTalk View component that collects and stores tag 
values. 
Logged data can be stored in an internal file set, or an ODBC-compliant 
database, and can be: 
Shown in trends. To show historical data in a trend, assign a tag from a 
data log model to a pen. For more information, see Setting up trends on 
page 601
Archived for future use. 
Analyzed using any ODBC-compatible reporting software, such as 
Microsoft Excel, or Business Objects Crystal Reports. 
Gathering tag data in data log models 
A data log model defines which tags to log data for, when to log the data, and 
where to log the data. 
In the Data Log Models editor, you also specify the format of the log files 
(file set, or ODBC), and when to create and delete the files (also called 
records). 
A single data log model can log data for up to 10,000 tags. 
About data logging 
C# PDF Field Edit Library: insert, delete, update pdf form field
A best C#.NET PDF document SDK library for PDF form field manipulation in Visual A professional PDF form creator supports to create fillable PDF form in C#.NET.
converting a word document to a fillable pdf form; convert pdf fillable form
VB.NET Create PDF from OpenOffice to convert odt, odp files to PDF
VB.NET How-to, VB.NET PDF, VB.NET Word, VB.NET Excel, VB.NET Convert OpenOffice Spreadsheet data to PDF. Export PDF document from OpenOffice Presentation.
convert html form to pdf fillable form; form pdf fillable
Chapter 22                  Setting up data logging 
584 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
Using multiple data log models 
At run time, up to 20 data log models can run simultaneously on each 
FactoryTalk View SE Server. 
Use multiple data log models to: 
Store related information in separate file sets. 
Log groups of tags at different rates. 
Log groups of tags based on events. 
Logged data is stored either in an internal file set or in an ODBC-compliant 
database. 
Each data log file set includes files for storing numeric values (either integers 
or floating point values), text, and tag names. 
Internal file sets store tag values in proprietary-format files. You cannot view 
the contents of the file sets, except in trends. 
If you log tag values to an ODBC database, you can view the data in trends, 
or use third-party, ODBC-compliant tools to analyze and create reports from 
the data. 
If the ODBC database becomes unavailable, FactoryTalk View logs the data 
to backup files in proprietary format. 
To use data in multiple formats, define multiple data log models for the same 
set of tags. 
How log file sets are named 
When you create a log file set, the set is given a name automatically. The 
name is based on the date the file was created, and the type of data it 
contains. The maximum length of a log file set’s name, including its path, is 
200 characters. 
File sets use the following file name format: 
YYYY MM DD NNNN <Log File Identifier String> <(type )>.dat
where 
YYYY is the year. 
MM is the month. 
DD is the day. 
NNNN is the sequential file identifier. 
Data log storage 
formats 
VB.NET Create PDF Library SDK to convert PDF from other file
SharePoint. Best VB.NET component to convert Microsoft Office Word, Excel and PowerPoint to searchable PDF document. Gratis
pdf fillable form creator; convert word to pdf fillable form online
VB.NET Create PDF from Word Library to convert docx, doc to PDF in
VB.NET Tutorial for Creating PDF document from MS Office Word. Convert multiple pages Word to fillable and editable PDF documents.
create a pdf form that can be filled out; change font size in fillable pdf form
Setting up data logging                  Chapter 22 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
585 
This number indicates the sequence files were created in. You can 
haveThe number can be up to 9999 file sets per day. At midnight, the 
sequence starts again at 0000. 
<Log File Identifier String> is a text string you can specify to help 
identify the log file. The maximum string length is 20 characters. 
<(type )> is the file type. 
The type is enclosed in parentheses. There are three file types: 
Tagname, Float (for analog and digital tag values), and String. 
Example: Parts of a data log long file name 
The data log file named 
2006 10 30 0004 Oven Temperatures (Float).dat
was created October 30 2006: 
0004 indicates that this is the fourth file set created that day. 
Oven Temperatures is the log file identifier string, which the user 
defined to help identify the data. 
(Float) indicates that this file contains analog or digital tag values. 
ODBC database storage format and schemas 
Use the ODBC database format to store data using an ODBC data source 
such as Oracle, Microsoft SQL Server, or Microsoft Access. 
Tip: 
When creating the tables for Float and String data 
logging to MS SQL Server 2008, ensure that Microsoft 
SQL Server 2008 Service Pack 1 has been installed first, 
or table creation will not be possible. 
The ODBC format stores data in up to three tables:   
Float table stores analog and digital tag values. 
String table (optional) stores string tag values. 
Tag table (optional) stores tag names in an index so that they can be 
referenced using a 2- or 4-byte numeric field (rather than a 40-byte 
character field) in the float and string tables. 
Tip: ODBC backup files are stored as binary files with the 
extension .obf. You cannot view the contents of .obf files. 
C# Create PDF from Word Library to convert docx, doc to PDF in C#.
C# Demo Code to Create PDF Document from Word in C# Program with .NET XDoc.PDF Component. Convert multiple pages Word to fillable and editable PDF
convert pdf to form fill; create fillable pdf form
VB.NET Create PDF from Excel Library to convert xlsx, xls to PDF
C#.NET convert PDF to text, C#.NET convert PDF to images DNN, C#.NET Winforms Document Viewer, C#.NET WPF Document Viewer. How-to, VB.NET PDF, VB.NET Word, VB.NET
pdf fill form; convert word form to fillable pdf
Chapter 22                  Setting up data logging 
586 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
How ODBC tables are named 
The ODBC tables are created with the default names TagTable, FloatTable
and StringTable. In the Data Log Models editor, you can modify these 
names before creating the tables, or you can specify the names of different 
tables. 
If you specify a backup path for an ODBC model, FactoryTalk View names 
the backup log files as described on How log file sets are named on page 
584
Format for ODBC float and string tables 
Floating-point and string data stored in ODBC format uses the following 
table: the float table contains analog and digital tag data; the string table 
contains string tag data. 
This column 
Contains 
SQL data type 
Length 
DateAndTime 
The date and time the tag values were logged. 
SQL_DATETIME 
Driver dependent 
Millitm 
The millisecond time the tag values were logged. 
SQL_SMALLINT, or 
SQL_INTEGER 
TagIndex, or 
TagName 
The index number for the tag. The tag name that 
corresponds to this number is listed in the tag name 
table. 
If the tag name table is not used, the tag name 
appears in this column 
SQL_SMALLINT, or 
SQL_INTEGER 
SQL_VARCHAR, or 
SQL_CHAR 
or 
255 
Val 
The analog or digital value of the tag. 
SQL_DOUBLE, or 
SQL_INTEGER, or 
SQL_SMALLINT 
8, or 
4, or 
The string value of the tag. 
SQL_VARCHAR, or 
SQL_CHAR 
82 
Status 
Blank if communications are working properly. 
E if a communication error occurred while 
FactoryTalk View was trying to acquire the tag 
value. 
S if the tag value is stale; that is, if the value has 
been acquired before, but has not been updated. 
U if the tag is uninitialized. 
SQL_VARCHAR, or 
SQL_CHAR 
Marker 
Internal tag marker. 
SQL_VARCHAR, or 
SQL_CHAR 
Format for ODBC tag table 
This column 
Contains 
SQL data type 
Length 
TagName 
The tag name. 
SQL_VARCHAR, or 
SQL_CHAR 
255 
TagIndex 
The index number assigned to the tag name. 
SQL_SMALLINT, or 
SQL_INTEGER 
or 
C# Create PDF from Excel Library to convert xlsx, xls to PDF in C#
C#.NET PDF SDK- Create PDF from Word in Visual C#. Description: Convert to PDF/TIFF and save it on the targetType, The target document type will be converted to.
create fill pdf form; convert fillable pdf to html form
C# Create PDF from PowerPoint Library to convert pptx, ppt to PDF
multiple pages PowerPoint to fillable and editable doc = new PPTXDocument(inputFilePath); // Convert it to PDF document can be converted from PowerPoint2003 by
create a fillable pdf form online; convert word form to pdf with fillable
Setting up data logging                  Chapter 22 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
587 
TagType 
The tag type: 
2 for Analog tag 
for Digital tag 
4 for String tag 
SQL_SMALLINT 
TagDataType 
The tag data type: 
-1 for Integer 
for Long 
1 for Float 
for String 
SQL_SMALLINT 
In the Data Log Models editor, you can create data log models that specify: 
Which log file format to use. 
Where to store data log file sets (primary or secondary paths). 
When to create and delete log files. 
Which actions will trigger logging. 
Which tag values will be logged. 
To open the Data Log Models editor: 
1.  In FactoryTalk View Studio, in the Explorer window, open the Data 
Log folder 
2.  Right-click the Data Log Models icon, and then select New
You can also open the Data Log Models editor by dragging its icon 
into the FactoryTalk View Studio workspace, or by double-clicking an 
existing Data Log Models component. 
For details about options in the Data Log Models editor, click Help
Creating data log 
models 
Chapter 22                  Setting up data logging 
588 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
Specifying the storage format 
In the Data Log Models editor, use the Setup tab to specify a log file 
identifier string, storage format, and description for the data log model. 
The log file identifier string becomes part of the file name. The description is 
for information only. 
If you select File Set as the storage format and you plan to log string tags, 
you can also specify the number of characters to be logged. 
For details about options in the Setup tab, click Help
Selecting the ODBC database format 
When you select ODBC database as the storage format, type the path and file 
name of the ODBC data source, and specify the ODBC tables that will be 
used, or create new tables. 
To create tables for a new data source, click Create Tables. If FactoryTalk 
View cannot create the tables automatically, you will have to open the 
database using its editing tool, and create the tables manually. 
To extend the length of the message to 1999 for a Microsoft SQL Server or 
Oracle database, click Extend table. The default length of the message is 
254. You can only extend the table when the length is between 254 and 1999. 
To log a longer diagnostic messages to the database, select the Use long 
message text check box. The message can be up to 1999 characters. If the 
check box is not selected, the message can be no more than 254 characters. 
Tip: Make sure the table is successfully extended before you 
choose to log long messages. Otherwise the message 
longer than 254 and all subsequent messages cannot be 
logged until the length is extended. 
To select an existing table from the specified database, click the Browse 
button, and then select a table in the Select ODBC Table dialog box. To 
view the order, type, length, and precision of the fields in the table, click the 
table to select it and then click Details
For more information, see Logging data to an existing ODBC data source on 
page 590
Setting up log paths 
In the Data Log Models editor, use the Paths tab to set up logging paths. 
Setting up data logging                  Chapter 22 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
589 
If the storage format is file sets, specify the primary path, and an optional 
secondary file path in case the primary path becomes unavailable. If the 
storage format is ODBC, you can specify a backup file path for the ODBC 
database. 
Setting up a secondary or backup logging path prevents loss of data. For 
example, if the disk space for the primary path becomes full, data logging 
will switch to the secondary path, if available, until space becomes available 
on the primary path. For more information, see Switching log paths at run 
time on page 592
If you do not set up a secondary path, when the primary path runs out of disk 
space, data logging stops and no more log files are created. 
For details about options in the Paths tab, click Help
Setting up and managing data log files 
In the Data Log Models editor, use the File Management tab to specify 
when to start new files and when to delete old files. 
Creating new file sets 
If the data log model uses file sets, you can set up data logging to create new 
file sets: 
Periodically. 
At specified times. 
When a particular event occurs. 
Never. This means that all data will be logged to one file set. 
Log files are saved in the folder you specify in the Paths tab. 
Tip: If the data log model uses the ODBC format, data is 
added continually to the same database, so this section 
does not apply. 
Deleting file sets and ODBC database records 
If a data log model uses file sets, you can set up file management to delete 
file sets after a specified period or once a specified number of file sets has 
been created. To never delete file sets, clear the check boxes under Delete 
Oldest Files
Chapter 22                  Setting up data logging 
590 
Rockwell Automation Publication VIEWSE-UM006K-EN-E 
Data log file sets are deleted only when a new file set is created. If the 
application creates a new file set each day and deletes the oldest file set every 
third day, there will be file sets for the three previous days’ d
ata, as well as a 
file set for the current day. 
If a data log model uses the ODBC database format, you can purge old 
records from the database using standard relational database tools or SQL 
queries. You can also set up FactoryTalk View to delete (purge) records in 
the ODBC database after a specified time. 
For details about options in the File Management tab, click Help
Specifying when to log data 
In the Data Log Models editor, use the Log Triggers tab to specify what 
will trigger the data to be logged, and when or how frequently this will occur. 
You can set up data logging to log tag values: 
Periodically. This is called periodic logging. 
Only when a tag’s value changes. This is called on
-change logging. 
When a particular event occurs and triggers the DataLogSnapshot 
command. This is called on-demand logging. For more information, 
see Using the DataLogSnapshot command on page 596
You can also combine types of logging. For more information, see 
Combining logging on page 596
For details about options in the Log Triggers tab, click Help
Choosing the data to be logged 
In the Data Log Models editor, use the Tags in Model tab to specify which 
tags will be scanned for data. A data log model can contain up to 10,000 tags. 
For details about options in the Tags in Model tab, click Help. 
You can store logged data in an existing ODBC data source, or you can 
create a new ODBC data source. 
Logging data to an existing ODBC data source 
You can log data to an existing ODBC data source, but its tables must 
contain fields that are formatted for the FactoryTalk View data log. 
There are two ways to prepare tables for data logging to an existing database: 
Logging data to 
ODBC data sources 