SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
21-7
21: TRIGONOMETRIC FUNCTION INSTRUCTIONS
ACOS (Arc Cosine)
Applicable SmartAXIS
Valid Devices
For valid device address ranges, see "Device Addresses" on page 3-1.
When the data designated by source device S1 is not within the range between –1.0 and 1.0 or does not comply with the normal floating-point 
format, a user program execution error will result, turning on special internal relay M8004 and ERR LED on the SmartAXIS. For details about the user 
program execution errors, see "User Program Execution Errors" on page 4-13.
Since the ACOS instruction is executed in each scan while input is on, a pulse input from a SOTU or SOTD instruction should be used.
Valid Data Types
Example: ACOS
acos S1·S1+1  D1·D1+1 rad
When input is on, the arc cosine of the value assigned by source device S1 is stored in radians to 
the destination assigned by device D1.
The S1·S1+1 value must be within the following range:
-1.0  S1·S1+1  1.0
If the S1·S1+1 value is not within this range, 0 is stored to D1·D1+1.
ACOS(F)
S1
*****
D1
*****
FT1A-12
FT1A-24
FT1A-40
FT1A-48
FT1A-Touch
X
X
X
X
X
Device
Function
I
Q
M
R
T
C
D
Constant
Repeat
S1 (Source 1)
Arc cosine value to convert into radian
X
X
D1 (Destination 1)
Destination to store conversion results
X
W (word)
Since floating point data is used, the source and destination devices use two consecutive data registers.
I (integer)
D (double word)
L (long)
F (float)
X
When input I1 is turned on, the arc cosine of the value of data registers D10 and D11 
assigned by source device S1 is stored to data registers D20 and D21 assigned by 
destination device D1.
acos –0.7071068   2.356195 rad
2.356195 rad = 3
/4 rad
I1
S1
D10
ACOS(F)
D1
D20
SOTU
D1
S1
–0.7071068
D10·D11
2.356195
D20·D21
Create password protected pdf reader - C# PDF Password Library: add, remove, edit PDF file password in C#.net, ASP.NET, MVC, WinForms, WPF
Help to Improve the Security of Your PDF Document by Setting Password
change password on pdf; add password to pdf file
Create password protected pdf reader - VB.NET PDF Password Library: add, remove, edit PDF file password in vb.net, ASP.NET, MVC, WinForms, WPF
Help to Improve the Security of Your PDF Document by Setting Password
password protected pdf; pdf password security
21: TRIGONOMETRIC FUNCTION INSTRUCTIONS
21-8
SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
ATAN (Arc Tangent)
Applicable SmartAXIS
Valid Devices
For valid device address ranges, see "Device Addresses" on page 3-1.
When the data designated by source device S1 does not comply with the normal floating-point format, a user program execution error will result, 
turning on special internal relay M8004 and ERR LED on the SmartAXIS. For details about the user program execution errors, see "User Program 
Execution Errors" on page 4-13.
Since the ATAN instruction is executed in each scan while input is on, a pulse input from a SOTU or SOTD instruction should be used.
Valid Data Types
Example: ATAN
atan S1·S1+1   D1·D1+1 rad
When input is on, the arc tangent of the value assigned by source device S1 is stored in radians 
to the destination assigned by device D1.
ATAN(F)
S1
*****
D1
*****
FT1A-12
FT1A-24
FT1A-40
FT1A-48
FT1A-Touch
X
X
X
X
X
Device
Function
I
Q
M
R
T
C
D
Constant
Repeat
S1 (Source 1)
Arc tangent value to convert into radian
X
X
D1 (Destination 1)
Destination to store conversion results
X
W (word)
Since floating point data is used, the source and destination devices use two consecutive data registers.
I (integer)
D (double word)
L (long)
F (float)
X
When input I1 is turned on, the arc tangent of the value of data registers D10 and D11 
assigned by source device S1 is stored to data registers D20 and D21 assigned by 
destination device D1.
atan 0.4142136   0.3926992 rad
0.3926992 rad = 
/8 rad
I1
S1
D10
ATAN(F)
D1
D20
SOTU
D1
S1
0.4142136
D10·D11
0.3926992
D20·D21
VB.NET PDF Convert to Jpeg SDK: Convert PDF to JPEG images in vb.
XImage.Barcode Reader. XImage.Barcode Generator. Reading, C#.NET Annotate PDF in WPF, C#.NET PDF Create, C#.NET Able to convert password protected PDF document.
convert password protected pdf to word online; pdf password recovery
C# PDF Convert to Jpeg SDK: Convert PDF to JPEG images in C#.net
Support for customizing image size. Password protected PDF document can be converted and changed. Open source codes can be added to C# class.
create password protected pdf online; pdf password encryption
SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
22-1
22:LOGARITHM / POWER INSTRUCTIONS
Introduction
This chapter describes logarithm and power instructions which are used to calculate logarithm or powered values of source 
devices.
LOGE (Natural Logarithm)
Applicable SmartAXIS
Valid Devices
For valid device address ranges, see "Device Addresses" on page 3-1.
When the operation result is not within the range between –3.402823  1038 and –1.175495  10–38 or between 1.175495  10–38  and 3.402823  
1038, special internal relay M8003 (carry or borrow) is turned on except when the result is 0. For details, see "Carry and Borrow in Floating-Point 
Data Processing" on page 4-11.
When the value of S1 (source 1) is 0, a user program execution error occurs and an infinity is stored in D1.
When the value of S1 (source 1) is less than 0, a user program execution error occurs and a non-numeric value is stored in D1.
When the data designated by source device S1 does not comply with the normal floating-point format, a user program execution error occurs, and 
the execution of the instruction is canceled. The value of D1 is left unchanged and the next instruction is executed.
When a user program execution error occurs, special internal relay M8004 and ERR LED on the SmartAXIS are turned on. For details about the user 
program execution errors, see "User Program Execution Errors" on page 4-13.
Since the LOGE instruction is executed in each scan while input is on, a pulse input from a SOTU or SOTD instruction should be used.
Valid Data Types
Example: LOGE
log
e
S1·S1+1   D1·D1+1
When input is on, the natural logarithm of the binary data assigned by source device S1 is stored 
to the destination assigned by device D1.
LOGE(F)
S1
*****
D1
*****
FT1A-12
FT1A-24
FT1A-40
FT1A-48
FT1A-Touch
X
X
X
X
X
Device
Function
I
Q
M
R
T
C
D
Constant
Repeat
S1 (Source 1)
Binary data to convert into natural logarithm
X
X
D1 (Destination 1)
Destination to store conversion results
X
W (word)
Since floating point data is used, the source and destination devices use two consecutive data registers.
I (integer)
D (double word)
L (long)
F (float)
X
When input I1 is on, the natural logarithm of the binary data of data registers D10 and 
D11 assigned by source device S1 is stored to data registers D20 and D21 assigned by 
destination device D1.
log
e
86.0   4.454347
I1
S1
D10
LOGE(F)
D1
D20
SOTU
D1
S1
86.0
D10·D11
4.454347
D20·D21
VB.NET PDF Convert to Word SDK: Convert PDF to Word library in vb.
Create editable Word file online without email. Supports transfer from password protected PDF. VB.NET class source code for .NET framework.
pdf passwords; creating password protected pdf
C# PDF Convert to Word SDK: Convert PDF to Word library in C#.net
and .docx. Create editable Word file online without email. Password protected PDF file can be printed to Word for mail merge. C# source
annotate protected pdf; pdf document password
22: LOGARITHM / POWER INSTRUCTIONS
22-2
SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
LOG10 (Common Logarithm)
Applicable SmartAXIS
Valid Devices
For valid device address ranges, see "Device Addresses" on page 3-1.
When the operation result is not within the range between –3.402823  1038 and –1.175495  10–38 or between 1.175495  10–38  and 3.402823  
1038, special internal relay M8003 (carry or borrow) is turned on except when the result is 0. For details, see "Carry and Borrow in Floating-Point 
Data Processing" on page 4-11
When the value of S1 (source 1) is 0, a user program execution error occurs and an infinity is stored in D1.
When the value of S1 (source 1) is less than 0, a user program execution error occurs and a non-numeric value is stored in D1.
When the data designated by source device S1 does not comply with the normal floating-point format, a user program execution error occurs, and 
the execution of the instruction is canceled. The value of D1 is left unchanged and the next instruction is executed.
When a user program execution error occurs, special internal relay M8004 and ERR LED on the SmartAXIS are turned on. For details about the user 
program execution errors, see "User Program Execution Errors" on page 4-13.
Since the LOG10 instruction is executed in each scan while input is on, a pulse input from a SOTU or SOTD instruction should be used.
Valid Data Types
Example: LOG10
log
10
S1·S1+1   D1·D1+1
When input is on, the common logarithm of the binary data assigned by source device S1 is 
stored to the destination assigned by device D1.
LOG10(F)
S1
*****
D1
*****
FT1A-12
FT1A-24
FT1A-40
FT1A-48
FT1A-Touch
X
X
X
X
X
Device
Function
I
Q
M
R
T
C
D
Constant
Repeat
S1 (Source 1)
Binary data to convert into common logarithm
X
X
D1 (Destination 1)
Destination to store conversion results
X
W (word)
Since floating point data is used, the source and destination devices use two consecutive data registers.
I (integer)
D (double word)
L (long)
F (float)
X
When input I1 is on, the common logarithm of the binary data of data registers D10 and 
D11 assigned by source device S1 is stored to data registers D20 and D21 assigned by 
destination device D1.
log
10
0.0000278   –4.555955
I1
S1
D10
LOG10(F)
D1
D20
SOTU
D1
S1
0.0000278
D10·D11
–4.555955
D20·D21
C# PDF: C#.NET PDF Document Merging & Splitting Control SDK
easily merge two or more independent PDF files to create a larger PDF document merging & splitting toolkit SDK to split password-protected PDF document using
adding a password to a pdf; copy protection pdf
.NET PDF SDK - Description of All PDF Processing Control Feastures
Able to Open password protected PDF; Allow users to add Easy to change PDF original password; Options for Create signatures in existing PDF signature fields;
pdf password remover; change password on pdf file
SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
22-3
22: LOGARITHM / POWER INSTRUCTIONS
EXP (Exponent)
Applicable SmartAXIS
Valid Devices
For valid device address ranges, see "Device Addresses" on page 3-1.
When the operation result is not within the range between –3.402823  1038 and –1.175495  10–38 or between 1.175495  10–38  and 3.402823  
1038, special internal relay M8003 (carry or borrow) is turned on except when the result is 0. For details, see "Carry and Borrow in Floating-Point 
Data Processing" on page 4-11.
When the operation result is between –1.175495  10–38 and 1.175495  10–38, the destination device designated by D1 stores 0. When the 
operation result is less than –3.402823  1038 or larger than 3.402823  1038, causing an overflow, the destination device designated by D1 stores a 
value of minus or plus infinity.
When the data designated by source device S1 does not comply with the normal floating-point format, a user program execution error occurs, and 
the execution of the instruction is canceled. The value of D1 is left unchanged and the next instruction is executed.
When a user program execution error occurs, special internal relay M8004 and ERR LED on the SmartAXIS are turned on. For details about the user 
program execution errors, see "User Program Execution Errors" on page 4-13.
Since the EXP instruction is executed in each scan while input is on, a pulse input from a SOTU or SOTD instruction should be used.
Valid Data Types
Example: EXP
eS1·S1+1   D1·D1+1
When input is on, e is raised to the power S1·S1+1 assigned by source device S1 and is stored to 
the destination assigned by device D1.
e (base of natural logarithm) = 2.7182818
EXP(F)
S1
*****
D1
*****
FT1A-12
FT1A-24
FT1A-40
FT1A-48
FT1A-Touch
X
X
X
X
X
Device
Function
I
Q
M
R
T
C
D
Constant
Repeat
S1 (Source 1)
Binary data of exponent
X
X
D1 (Destination 1)
Destination to store results
X
W (word)
Since floating point data is used, the source and destination devices use two consecutive data registers.
I (integer)
D (double word)
L (long)
F (float)
X
When input I1 is on, e is raised to the data of data registers D10 and D11 assigned by 
source device S1 and the operation result is stored to data registers D20 and D21 
assigned by destination device D1.
e2 = 2.71828182   7.389056
I1
S1
D10
EXP(F)
D1
D20
SOTU
D1
S1
2.0
D10·D11
7.389056
D20·D21
C# PDF: C# Code to Create Mobile PDF Viewer; C#.NET Mobile PDF
detailed guidance on how to create a mobile public float DocWidth = 819; protected void Page_Load Demo_Docs/").Replace("\\" Sample.pdf"; this.SessionId
break pdf password; pdf password unlock
C# Word: How to Create Word Online Viewer in C# Application
viewer creating, you can go to PDF Web Viewer HTML into your document's body to create Word document string mode; public string fid; protected void Page_Load
break a pdf password; add password to pdf file
22: LOGARITHM / POWER INSTRUCTIONS
22-4
SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
POW (Power)
Applicable SmartAXIS
Valid Devices
For valid device address ranges, see "Device Addresses" on page 3-1.
When the operation result is not within the range between –3.402823  1038 and –1.175495  10–38 or between 1.175495  10–38 to 3.402823  
1038, special internal relay M8003 (carry or borrow) is turned on, except when the result is 0. For details, see "Carry and Borrow in Floating-Point 
Data Processing" on page 4-11.
When the operation result is between –1.175495  10–38 and 1.175495  10–38, the destination device designated by D1 stores 0. When the 
operation result is less than –3.402823  1038 or greater than 3.402823  1038, causing an overflow, the destination device designated by D1 stores 
a value of minus or plus infinity.
When one of the following conditions occurs, a user program execution error occurs and 0 is stored in D1.
 The data designated by source device S1 is less than 0 and the data designated by source device S2 is not an integer.
 The data designated by source device S1 is 0 and the data designated by source device S2 is less than or equal to 0.
When the data designated by source device S1 or S2 does not comply with the normal floating-point format, a user program execution error occurs, 
and the execution of the instruction is canceled. The value of D1 is left unchanged and the next instruction is executed.
When a user program execution error occurs, special internal relay M8004 and ERR LED on the SmartAXIS are turned on. For details about the user 
program execution errors, see "User Program Execution Errors" on page 4-13.
Since the POW instruction is executed in each scan while input is on, a pulse input from a SOTU or SOTD instruction should be used.
Valid Data Types
Example: POW
S1·S1+1S2·S2+1   D1·D1+1
When input is on, data assigned by source device S1 is raised to the power S2·S2+1 
assigned by source device S2 and the operation result is stored to the destination 
assigned by device D1.
POW(F)
S1
*****
D1
*****
S2
*****
FT1A-12
FT1A-24
FT1A-40
FT1A-48
FT1A-Touch
X
X
X
X
X
Device
Function
I
Q
M
R
T
C
D
Constant
Repeat
S1 (Source 1)
Binary data of base
X
X
S2 (Source 2)
Binary data of exponent
X
X
D1 (Destination 1)
Destination to store results
X
W (word)
Since floating point data is used, the source and destination devices use two consecutive data registers.
I (integer)
D (double word)
L (long)
F (float)
X
When input I1 is on, the data of data registers D10 and D11 assigned by 
source device S1 is raised to the power D20·D20+1 assigned by source device 
S2 and the operation result is stored to data registers D30 and D31 assigned 
by destination device D1.
41.25   5.656856
I1
S2
D20
POW(F)
D1
D30
SOTU
S1
D10
S2
S1
4.0
D10·D11
1.25
D20·D21
D1
5.656856
D30·D31
SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
23-1
23:FILE DATA PROCESSING INSTRUCTIONS
Introduction
File data processing instructions implement the first-in first-out (FIFO) data structure. FIFOF (FIFO Format) instructions initialize 
the FIFO data files storing the data. FIEX (First-In Execute) instructions store new data to the FIFO data files, and FOEX (First-Out 
Execute) instructions retrieve the stored data from the FIFO data files. The first data to be stored to the FIFO data files by FIEX 
instructions will be the first data to be retrieved by FOEX instructions.
NDSRC (N Data Search) instructions search a designated value through a specified range.
FIFOF (FIFO Format)
Applicable SmartAXIS
Valid Devices
For valid device address ranges, see "Device Addresses" on page 3-1.
Special internal relays cannot be designated as D2.
Since the FIFOF instruction is executed in each scan while input is on, a pulse input from a SOTU or SOTD instruction should be used.
Valid Data Types
When input is on, FIFOF instruction initializes an FIFO data file. Each data 
file has unique number 0 through 9. A maximum of 10 data files can be used 
in a user program.
FIFOF(W)
*
S1
***
S2
***
D1
*****
D2
*****
FT1A-12
FT1A-24
FT1A-40
FT1A-48
FT1A-Touch
X
X
X
X
X
Device
Function
I
Q
M
R
T
C
D
Constant
Repeat
N (File Number)
File Number
0-9
S1 (Source 1)
Quantity of data registers per record
1-255
S2 (Source 2)
Quantity of records
2-255
D1 (Destination 1)
First data register to store FIFO data file
X
D2 (Destination 2)
FIFO status output
W (word)
X
When an M (internal relay) is assigned as the D2, three internal relays starting with the device assigned by D2 
are used.
I (integer)
D (double word)
When a D (data register) is assigned as the D1, S1S2+2 data registers starting with the device assigned by D1 
are used.
L (long)
F (float)
23: FILE DATA PROCESSING INSTRUCTIONS
23-2
SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
Destination Device D1 (FIFO Data File)
FIFO data files are initialized when corresponding FIFOF instructions are executed. FIFO data file is placed in the area starting with 
the device designated by D1 and occupies as many as S1S2+2 data registers. The size of each record is equal to S1. S1-1 records 
of data can be stored in an FIFO data file using FIEX instructions. The stored data can be retrieved from the FIFO data file using 
FOEX instructions.
Destination Device D2 (FIFO Status Output)
When FIEX or FOEX instructions are executed, the following internal relays are turned on or off according to the execution status.
Note: The FIFOF instruction cannot be used in an interrupt program.
If used, a user program execution error will result, turning on special internal relay M8004 and the ERR LED on the SmartAXIS. For details about the 
user program execution errors, see "User Program Execution Errors" on page 4-13.
Device
Function
Description
D1+0
FI pointer
The FI pointer indicates the position to store new data into the FIFO data file. When an 
FIEX instruction is executed, the new data in data registers starting with the device 
designated by S1 of the FIEX instruction is stored at the position indicated by the FI 
pointer, and the FI pointer is incremented by 1 to indicate the position to store the next 
data.
When the FI pointer indicates the last record of the FIFO data file, and an FIEX 
instruction is executed, the FI pointer will return to 0.
D1+1
FO pointer
The FO pointer indicates the position to retrieve the stored data from the FIFO data 
file. When an FOEX instruction is executed, the data at the position indicated by the 
FIFO pointer is retrieved and stored to the data registers starting with the device 
designated by D1 of the FOEX instruction, and the FO pointer is incremented by 1 to 
indicate the position to retrieve the next data.
When the FO pointer indicates the last record of the FIFO data file, and an FOEX 
instruction is executed, the FO pointer will return to 0.
D1+2
Record 0
The first record to store the data.
...
D1+(S1+1)
D1+(S1+2)
Record 1
The second record to store the data.
...
D1+(S12+1)
D1+(S1(S2–1)+2)
Record S2–1
The last record to store the data.
...
D1+(S1S2+1)
Device
Function
Description
D2+0
Data file full output
When the value stored in the FI pointer (D1+0) is equal to the value stored in the FO 
pointer (D1+1) – 1, the FIFO data file is full, and no more data can be stored. If an FIEX 
instruction is executed when the FIFO data file is full, no operation is executed, and the 
data file full output (D2+0) will be turned on.
D2+1
Data file empty output
When the value stored in the FI pointer (D1+0) is equal to the value stored in the FO 
pointer (D1+1), the FIFO data file is empty. If an FOEX instruction is executed when the 
FIFO data file is empty, no operation is executed, and the data file empty output (D2+1) 
will be turned on.
D2+2
Pointer out of range 
output
The value stored in the FI or FO pointer can be 0 through S2–1. When an FIEX or FOEX 
instruction is executed while the FI or FO pointer value exceeds the valid range, no 
operation is executed, and the pointer out of range output (D2+2) will be turned on.
SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
23-3
23: FILE DATA PROCESSING INSTRUCTIONS
FIEX (First-In Execute)
Applicable SmartAXIS
Valid Devices
For valid device address ranges, see "Device Addresses" on page 3-1.
Make sure that FIEX instructions are executed after the corresponding FIFOF instruction has initialized the FIFO data file. If FIEX instructions are 
executed without executing the corresponding FIFOF instruction, a user program execution error will result, turning on special internal relay M8004 
and the ERR LED on the SmartAXIS.
When a user program execution error occurs, the execution of the instruction is canceled and the next instruction is executed. For details about the 
user program execution errors, see "User Program Execution Errors" on page 4-13.
Since the FIEX instruction is executed in each scan while input is on, a pulse input from a SOTU or SOTD instruction should be used.
Valid Data Types
FOEX (First-Out Execute)
Applicable SmartAXIS
Valid Devices
For valid device address ranges, see "Device Addresses" on page 3-1.
Make sure that FOEX instructions are executed after the corresponding FIFOF instruction has initialized the FIFO data file. If FOEX instructions are 
executed without executing the corresponding FIFOF instruction, a user program execution error will result, turning on special internal relay M8004 
and the ERR LED on the SmartAXIS.
When a user program execution error occurs, the execution of the instruction is canceled and the next instruction is executed. For details about the 
user program execution errors, see "User Program Execution Errors" on page 4-13.
Since the FOEX instruction is executed in each scan while input is on, a pulse input from a SOTU or SOTD instruction should be used.
When input is on, the data stored in data registers starting with the device assigned by S1 is stored to the 
corresponding FIFO data file.
FIEX(W)
*
S1
*****
FT1A-12
FT1A-24
FT1A-40
FT1A-48
FT1A-Touch
X
X
X
X
X
Device
Function
I
Q
M
R
T
C
D
Constant
Repeat
N (File Number)
File number
0-9
S1 (Source 1)
First data register to store data to FIFO data file
X
W (word)
X
When a D (data register) is assigned as the source, as many data registers as the value stored in device S1 of 
the corresponding FIFOF instruction are used.
I (integer)
D (double word)
L (long)
F (float)
When input is on, the data is retrieved from the corresponding FIFO data file and stored to the data 
registers starting with the device assigned by D1.
FOEX(W)
*
D1
*****
FT1A-12
FT1A-24
FT1A-40
FT1A-48
FT1A-Touch
X
X
X
X
X
Device
Function
I
Q
M
R
T
C
D
Constant
Repeat
N (File Number)
File number
0-9
D1 (Destination 1)
First data register number to store data
X
23: FILE DATA PROCESSING INSTRUCTIONS
23-4
SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
Valid Data Types
Example: FIFOF, FIEX, and FOEX
This program demonstrates a user program of the FIFOX, FIEX, and FOEX instructions to use an FIFO data file.
FIFO Data File
The table below shows the data stored in FIFO data file 2 when inputs I0, I1, and I2 are turned on in this order. Only valid data 
managed by the FIFOF, FIEX, and FOEX instructions are shown in the table.
W (word)
X
When a D (data register) is assigned as the destination, as many data registers as the value stored in device S1 
of the corresponding FIFOF instruction are used.
I (integer)
D (double word)
L (long)
F (float)
File number:
2
Quantity of data registers per record:
3
Quantity of records:
4
FIFO Data file:
D100 through D113 (34+2 data registers)
FIFO status outputs:
M100 through M102
M8120 is the initialize pulse special internal relay.
When the CPU starts, MOV sets 0 to FI and FO pointers, and FIFOF initializes 
FIFO data file 2.
When input I0 is turned on, the data in D10 through D12 are stored to the 
FIFO data file 2.
When input I1 is turned on, the data in D20 through D22 are stored to the 
FIFO data file 2.
When input I2 is turned on, the first data is retrieved from the FIFO data file 2 
and stored to D50 through D52.
I0
S1
D10
FIEX(W)
2
M8120
SOTU
Ladder Diagram
REP
2
S1 –
0
D1 R
D100
MOV(W)
D2
M100
S1
3
D1
D100
FIFOF(W)
2
S2
4
I1
S1
D20
FIEX(W)
2
I2
D1
D50
FOEX(W)
2
SOTU
SOTU
Function
Device Address
Input I0
Input I1
Input I2
FI Pointer
D100
1
2
2
FO Pointer
D101
0
0
1
Record 0
D102 through D104
D10, D11, D12
D10, D11, D12
Record 1
D105 through D107
D20, D21, D22
D20, D21, D22
Record 2
D108 through D110
Record 3
D111 through D113
Documents you may be interested
Documents you may be interested