SKM Power*Tools for Windows
Compares device rating to total fault current at bus or maximum fault
current through branch. For this tutorial select Branch.
Specifies study type ANSI, IEC 61909, or Comprehensive Fault. For
this tutorial, select the Comprehensive Option.
Navigates through the report by jumping to the selected component
type, or reduces the number of components shown in the evaluation list.
Choose from All Non-protection components, buses, cables, 2-winding
transformers, 3-winding transformers, transmission lines, pi impedance,
generators, loads, induction motors, synchronous motors, schedules,
filters, or reduce the number of components reported by custom query.
3. Click on the Report button to generate the spreadsheet-style report shown below. The
report can be printed or saved as an Excel spreadsheet file.
The Report button generates a spreadsheet-style report and the Run Study
button allows you to re-run any combination of studies from the balanced
and unbalanced study options.
Options… button brings up the “Evaluation options”
window where the user
can setup the Pass-Fail Limits, Evaluation Criteria, and Input Data Criteria
The Input Eval… button generates a report listing c omponents with obvious
input data errors as shown in the following screen.