SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
11-5
11: DATA CONVERSION INSTRUCTIONS
HTOA (Hex to ASCII)
Applicable SmartAXIS
Valid Devices
For valid device address ranges, see "Device Addresses" on page 3-1.
When T (timer) or C (counter) is used as S1 or S2, the timer/counter current value (TC or CC) is displayed.
The quantity of digits to convert can be 1 through 4. Make sure that the quantity of digits designated by S2 is within the valid range. If the S2 data 
exceeds the valid range, a user program execution error will result, turning on special internal relay M8004 and the ERR LED on the SmartAXIS.
When a user program execution error occurs, the execution of the instruction is canceled. The value of D1 is left unchanged and the next instruction 
is executed. For user program execution errors, see "User Program Execution Errors" on page 4-13.
Since the HTOA instruction is executed in each scan while input is on, a pulse input from a SOTU or SOTD instruction should be used.
Valid Data Types
S1 D1, D1+1, D1+2, D1+3
When input is on, the 16-bit binary data assigned by S1 is read from the lowest digit as 
many times as the quantity of digits assigned by S2, converted into ASCII data, and 
stored to the destination starting with the device assigned by D1.
The quantity of digits to convert can be 1 through 4.
HTOA(W)
S1
*****
S2
*****
D1
*****
FT1A-12
FT1A-24
FT1A-40
FT1A-48
FT1A-Touch
X
X
X
X
X
Device
Function
I
Q
M
R
T
C
D
Constant
Repeat
S1 (Source 1)
Binary data to convert
X
X
X
X
X
X
X
X
S2 (Source 2)
Quantity of digits to convert
X
X
X
X
X
X
X
1-4
D1 (Destination 1)
Destination to store conversion results
X
W (word)
X
When a bit device such as I (input), Q (output), M (internal relay), or R (shift register) is assigned as the source, 
16 points (word data) are used.
When a word device such as T (timer), C (counter), or D (data register) is assigned as the source or destination, 
1 point (word data) is used.
I (integer)
D (double word)
L (long)
F (float)
Add password to pdf preview - C# PDF Password Library: add, remove, edit PDF file password in C#.net, ASP.NET, MVC, WinForms, WPF
Help to Improve the Security of Your PDF Document by Setting Password
crystal report to pdf with password; convert protected pdf to word
Add password to pdf preview - VB.NET PDF Password Library: add, remove, edit PDF file password in vb.net, ASP.NET, MVC, WinForms, WPF
Help to Improve the Security of Your PDF Document by Setting Password
convert pdf password protected to word online; create password protected pdf online
11: DATA CONVERSION INSTRUCTIONS
11-6
SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
Examples: HTOA
 Quantity of Digits: 4
 Quantity of Digits: 3
 Quantity of Digits: 2
 Quantity of Digits: 1
D1
D20
S1
D10
I0
HTOA(W)
S2
4
SOTU
Binary
4660
D10
(1234h)
ASCII
49
D20
(0031h)
50
D21
(0032h)
51
D22
(0033h)
52
D23
(0034h)
D1
D20
S1
D10
I1
HTOA(W)
S2
3
SOTU
Binary
4660
D10
(1234h)
ASCII
50
D20
(0032h)
51
D21
(0033h)
52
D22
(0034h)
D1
D20
S1
D10
I2
HTOA(W)
S2
2
SOTU
Binary
4660
D10
(1234h)
ASCII
51
D20
(0033h)
52
D21
(0034h)
D1
D20
S1
D10
I3
HTOA(W)
S2
1
SOTU
Binary
4660
D10
(1234h)
ASCII
52
D20
(0034h)
C# WinForms Viewer: Load, View, Convert, Annotate and Edit PDF
PDF Annotation. • Add sticky notes to PDF document in preview. Add text to PDF document in preview. • Add text box to PDF file in preview.
convert password protected pdf to word; pdf protection remover
C# WPF Viewer: Load, View, Convert, Annotate and Edit PDF
PDF Annotation. • Add sticky notes to PDF document. • Highlight PDF text in preview. • Add text to PDF document. • Insert text box to PDF file.
add password to pdf; change password on pdf document
SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
11-7
11: DATA CONVERSION INSTRUCTIONS
ATOH (ASCII to Hex)
Applicable SmartAXIS
Valid Devices
For valid device address ranges, see "Device Addresses" on page 3-1.
Internal relays M0 through M1277 can be designated as D1. Special internal relays cannot be designated as D1.
When T (timer) or C (counter) is used as S2, the timer/counter current value (TC or CC) is displayed. When T (timer) or C (counter) is used as D1, 
the data is written in as a preset value (TP or CP) which can be 0 through 65535.
Valid values for source S1 data to convert are 30h to 39h and 41h to 46h. Make sure that the values for each source designated by S1 and the 
quantity of digits designated by S2 are within the valid range. If the S1 or S2 data exceeds the valid range, a user program execution error will 
result, turning on special internal relay M8004 and the ERR LED on the SmartAXIS.
When a user program execution error occurs, the execution of the instruction is canceled. The value of D1 is left unchanged and the next instruction 
is executed. For user program execution errors, see "User Program Execution Errors" on page 4-13.
Since the ATOH instruction is executed in each scan while input is on, a pulse input from a SOTU or SOTD instruction should be used.
Valid Data Types
S1, S1+1, S1+2, S1+3  D1
When input is on, the ASCII data, assigned by S1, is converted into 16-bit binary data. 
The number of times is determined by the quantity of digits assigned by S2. The data 
is then stored to the destination assigned by device D1.
Valid values for source data to convert are 30h to 39h and 41h to 46h.
The quantity of digits to convert can be 1 through 4.
ATOH(W)
S1
*****
S2
*****
D1
*****
FT1A-12
FT1A-24
FT1A-40
FT1A-48
FT1A-Touch
X
X
X
X
X
Device
Function
I
Q
M
R
T
C
D
Constant
Repeat
S1 (Source 1)
ASCII data to convert
X
S2 (Source 2)
Quantity of digits to convert
X
X
X
X
X
X
X
1-4
D1 (Destination 1)
Destination to store conversion results
X
X
X
X
X
W (word)
X
When a bit device such as I (input), Q (output), M (internal relay), or R (shift register) is assigned as the source 
or destination, 16 points (word data) are used.
When a word device such as T (timer), C (counter), or D (data register) is assigned as the source or destination, 
1 point (word data) is used.
I (integer)
D (double word)
L (long)
F (float)
How to C#: Preview Document Content Using XDoc.Word
With the SDK, you can preview the document content according to the preview thumbnail by the ways as following. C# DLLs for Word File Preview. Add references:
pdf password security; pdf password remover online
How to C#: Preview Document Content Using XDoc.PowerPoint
C# DLLs: Preview PowerPoint Document. Add necessary XDoc.PowerPoint DLL libraries into your created C# application as references. RasterEdge.Imaging.Basic.dll.
password protected pdf; acrobat password protect pdf
11: DATA CONVERSION INSTRUCTIONS
11-8
SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
Examples: ATOH
 Quantity of Digits: 4
 Quantity of Digits: 3
 Quantity of Digits: 2
 Quantity of Digits: 1
D1
D20
S1
D10
I0
ATOH(W)
S2
4
SOTU
Binary
4660
D20
(1234h)
ASCII
49
D10
(0031h)
50
D11
(0032h)
51
D12
(0033h)
52
D13
(0034h)
D1
D20
S1
D10
I1
ATOH(W)
S2
3
SOTU
Binary
291
D20
(0123h)
ASCII
49
D10
(0031h)
50
D11
(0032h)
51
D12
(0033h)
D1
D20
S1
D10
I2
ATOH(W)
S2
2
SOTU
Binary
18
D20
(0012h)
ASCII
49
D10
(0031h)
50
D11
(0032h)
D1
D20
S1
D10
I3
ATOH(W)
S2
1
SOTU
Binary
1
D20
(0001h)
ASCII
49
D10
(0031h)
VB.NET PDF File Compress Library: Compress reduce PDF size in vb.
Remove bookmarks, annotations, watermark, page labels and article threads from PDF while compressing. Also a preview component enables compressing and
convert password protected pdf to normal pdf online; change password on pdf file
C# PDF insert image Library: insert images into PDF in C#.net, ASP
viewer component supports inserting image to PDF in preview without adobe Insert images into PDF form field. How to insert and add image, picture, digital photo
copy text from protected pdf to word; password on pdf
SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
11-9
11: DATA CONVERSION INSTRUCTIONS
BTOA (BCD to ASCII)
Applicable SmartAXIS
Valid Devices
For valid device address ranges, see "Device Addresses" on page 3-1.
When T (timer) or C (counter) is used as S1 or S2, the timer/counter current value (TC or CC) is displayed.
The number of digits that can be converted is 1 through 5 for word data, and 1 through 10 for double-word data. Make sure that the quantity of 
digits designated by S2 is within the valid range. If the S2 data exceeds the valid range, a user program execution error will result, turning on special 
internal relay M8004 and the ERR LED on the SmartAXIS.
Make sure that the last destination data determined by D1+S2-1 is within the valid device range. If the derived destination device exceeds the valid 
device range, a user program execution error will result, turning on special internal relay M8004 and ERROR LED on the SmartAXIS.
When a user program execution error occurs, the execution of the instruction is canceled. The value of D1 is left unchanged and the next instruction 
is executed. For user program execution errors, see "User Program Execution Errors" on page 4-13.
Since the BTOA instruction is executed in each scan while input is on, a pulse input from a SOTU or SOTD instruction should be used.
Valid Data Types
Word data: 
S1  D1, D1+1, D1+2, D1+3, D1+4
Double-word data: 
S1·S1+1  D1, D1+1, D1+2, ... , D1+9
When input is on, the 16- or 32-bit binary data assigned by S1 is converted into BCD, 
and converted into ASCII data. The data is read from the lowest digit as many times 
as the quantity of digits assigned by S2. The result is stored to the destination starting 
with the device assigned by D1.
The number of digits that can be converted is 1 through 5 for word data, and 1 
through 10 for double-word data.
BTOA(*)
S1
*****
S2
*****
D1
*****
FT1A-12
FT1A-24
FT1A-40
FT1A-48
FT1A-Touch
X
X
X
X
X
Device
Function
I
Q
M
R
T
C
D
Constant
Repeat
S1 (Source 1)
Binary data to convert
X
X
X
X
X
X
X
X
S2 (Source 2)
Quantity of digits to convert
X
X
X
X
X
X
X
1-5, 1-10
D1 (Destination 1)
Destination to store conversion results
X
W (word)
X
When a bit device such as I (input), Q (output), M (internal relay), or R (shift register) is assigned as the source, 
16 points (word data) or 32 points (double-word data) are used.
When a word device such as T (timer), C (counter), or D (data register) is assigned as the source or destination, 
1 point (word data) or 2 points (double-word data) are used.
I (integer)
D (double word)
X
L (long)
F (float)
VB.NET PDF insert image library: insert images into PDF in vb.net
inserting image to PDF in preview without adobe provide users the most individualized PDF page image inserting function, allowing developers to add and insert
pdf security password; pdf password reset
How to C#: Preview Document Content Using XDoc.excel
following. C# DLLs: Preview Excel Document without Microsoft Office Installed. Add necessary references: RasterEdge.Imaging.Basic.dll.
protected pdf; add password to pdf without acrobat
11: DATA CONVERSION INSTRUCTIONS
11-10
SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
Examples: BTOA(W)
 Quantity of Digits: 5
 Quantity of Digits: 4
 Quantity of Digits: 3
 Quantity of Digits: 2
 Quantity of Digits: 1
D1
D20
S1
D10
I0
BTOA(W)
S2
5
SOTU
BCD
12345
D10
(3039h)
ASCII
49
D20
(0031h)
50
D21
(0032h)
51
D22
(0033h)
52
D23
(0034h)
Binary
53
D24
(0035h)
D1
D20
S1
D10
I1
BTOA(W)
S2
4
SOTU
12345
D10
(3039h)
ASCII
50
D20
(0032h)
51
D21
(0033h)
52
D22
(0034h)
53
D23
(0035h)
BCD
Binary
D1
D20
S1
D10
I2
BTOA(W)
S2
3
SOTU
12345
D10
(3039h)
ASCII
51
D20
(0033h)
52
D21
(0034h)
53
D22
(0035h)
BCD
Binary
D1
D20
S1
D10
I3
BTOA(W)
S2
2
SOTU
12345
D10
(3039h)
ASCII
52
D20
(0034h)
53
D21
(0035h)
BCD
Binary
D1
D20
S1
D10
I4
BTOA(W)
S2
1
SOTU
12345
D10
(3039h)
ASCII
53
D20
(0035h)
BCD
Binary
C# HTML5 Viewer: Load, View, Convert, Annotate and Edit Raster
zoom in or zoom out images while in preview. to Tiff (.tif, .tiff) online, create PDF document from Supported annotation features includes add text comments to
add password to pdf preview; add password to pdf online
C# PDF Page Insert Library: insert pages into PDF file in C#.net
Ability to add PDF page number in preview. Offer PDF page break inserting function. Free components and online source codes for .NET framework 2.0+.
add password to pdf file; add copy protection pdf
SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
11-11
11: DATA CONVERSION INSTRUCTIONS
Examples: BTOA(D)
 Quantity of Digits: 10
 Quantity of Digits: 6
 Quantity of Digits: 3
D1
D20
S1
D10
I0
BTOA(D)
S2
10
SOTU
BCD
1234567890
(499602D2h)
ASCII
49
D20
(0031h)
50
D21
(0032h)
51
D22
(0033h)
52
D23
(0034h)
Binary
53
D24
(0035h)
54
D25
(0036h)
55
D26
(0037h)
56
D27
(0038h)
57
D28
(0039h)
48
D29
(0030h)
D10·D11
D1
D20
S1
D10
I1
BTOA(D)
S2
6
SOTU
ASCII
53
D20
(0035h)
54
D21
(0036h)
55
D22
(0037h)
56
D23
(0038h)
57
D24
(0039h)
48
D25
(0030h)
BCD
Binary
D10·D11
1234567890
(499602D2h)
D1
D20
S1
D10
I2
BTOA(D)
S2
3
SOTU
ASCII
56
D20
(0038h)
57
D21
(0039h)
48
D22
(0030h)
D10·D11
1234567890
(499602D2h)
BCD
Binary
11: DATA CONVERSION INSTRUCTIONS
11-12
SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
ATOB (ASCII to BCD)
Applicable SmartAXIS
Valid Devices
For valid device address ranges, see "Device Addresses" on page 3-1.
Internal relays M0 through M1277 can be designated as D1.
When T (timer) or C (counter) is used as S2, the timer/counter current value (TC or CC) is displayed. When T (timer) or C (counter) is used as D1, 
the data is written in as a preset value (TP or CP).
Valid values for source S1 data to convert are 30h through 39h. The number of digits that can be converted is be 1 through 5 for word data, and 1 
through 10 for double-word data. Make sure that the values for each source designated by S1 and the quantity of digits designated by S2 are within 
the valid range. If the S1 or S2 data exceeds the valid range, a user program execution error will result, turning on special internal relay M8004 and 
the ERR LED on the SmartAXIS.
Make sure that the last source data determined by S1+S2-1 is within the valid device range. If the derived source device exceeds the valid device 
range, a user program execution error will result, turning on special internal relay M8004 and ERROR LED on the SmartAXIS.
When a user program execution error occurs, the execution of the instruction is canceled. The value of D1 is left unchanged and the next instruction 
is executed. For user program execution errors, see "User Program Execution Errors" on page 4-13.
Since the ATOB instruction is executed in each scan while input is on, a pulse input from a SOTU or SOTD instruction should be used.
Valid Data Types
Word data: 
S1, S1+1, S1+2, S1+3, S1+4  D1
Double-word data: 
S1, S1+1, S1+2, ... , S1+9  D1·D1+1
When input is on, the ASCII data assigned by S1 as many times as the quantity of 
digits assigned by S2 is converted into BCD, and converted into 16- or 32-bit binary 
data. The result is stored to the destination assigned by device D1.
Valid values for source data to convert are 30h through 39h.
The number of digits that can be converted is through 5 for word data, and 1 through 
10 for double-word data.
ATOB(*)
S1
*****
S2
*****
D1
*****
FT1A-12
FT1A-24
FT1A-40
FT1A-48
FT1A-Touch
X
X
X
X
X
Device
Function
I
Q
M
R
T
C
D
Constant
Repeat
S1 (Source 1)
ASCII data to convert
X
S2 (Source 2)
Quantity of digits to convert
X
X
X
X
X
X
X
1-5, 1-10
D1 (Destination 1)
Destination to store conversion results
X
X
X
X
X
W (word)
X
When a bit device such as I (input), Q (output), M (internal relay), or R (shift register) is assigned as the source 
or destination, 16 points (word data) or 32 points (double-word data) are used.
When a word device such as T (timer), C (counter), or D (data register) is assigned as the source or destination, 
1 point (word data) or 2 points (double-word data) are used.
I (integer)
D (double word)
X
L (long)
F (float)
SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
11-13
11: DATA CONVERSION INSTRUCTIONS
Examples: ATOB(W)
 Quantity of Digits: 5
 Quantity of Digits: 4
 Quantity of Digits: 3
 Quantity of Digits: 2
 Quantity of Digits: 1
D1
D20
S1
D10
I0
ATOB(W)
S2
5
SOTU
BCD
12345
D20
(3039h)
ASCII
49
D10
(0031h)
50
D11
(0032h)
51
D12
(0033h)
52
D13
(0034h)
Binary
53
D14
(0035h)
D1
D20
S1
D10
I1
ATOB(W)
S2
4
SOTU
BCD
1234
D20
(04D2h)
ASCII
49
D10
(0031h)
50
D11
(0032h)
51
D12
(0033h)
52
D13
(0034h)
Binary
D1
D20
S1
D10
I2
ATOB(W)
S2
3
SOTU
BCD
123
D20
(007Bh)
ASCII
49
D10
(0031h)
50
D11
(0032h)
51
D12
(0033h)
Binary
D1
D20
S1
D10
I3
ATOB(W)
S2
2
SOTU
BCD
12
D20
(0018h)
ASCII
49
D10
(0031h)
50
D11
(0032h)
Binary
D1
D20
S1
D10
I4
ATOB(W)
S2
1
SOTU
BCD
1
D20
(0001h)
ASCII
49
D10
(0031h)
Binary
11: DATA CONVERSION INSTRUCTIONS
11-14
SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
Examples: ATOB(D)
 Quantity of Digits: 10
 Quantity of Digits: 6
 Quantity of Digits: 3
D1
D20
S1
D10
I0
ATOB(D)
S2
10
SOTU
ASCII
49
D10
(0031h)
50
D11
(0032h)
51
D12
(0033h)
52
D13
(0034h)
53
D14
(0035h)
54
D15
(0036h)
55
D16
(0037h)
56
D17
(0038h)
57
D18
(0039h)
48
D19
(0030h)
BCD
1234567890
(499602D2h)
Binary
D20·D21
D1
D20
S1
D10
I1
ATOB(D)
S2
6
SOTU
123456
(0001E240h)
ASCII
49
D10
(0031h)
50
D11
(0032h)
51
D12
(0033h)
52
D13
(0034h)
53
D14
(0035h)
54
D15
(0036h)
D20·D21
BCD
Binary
D1
D20
S1
D10
I2
ATOB(D)
S2
3
SOTU
123
(0000007Bh)
ASCII
49
D10
(0031h)
50
D11
(0032h)
51
D12
(0033h)
D20·D21
BCD
Binary