19: PULSE OUTPUT INSTRUCTIONS
19-18
SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
6. Steady pulse frequency
This setting specifies the steady pulse frequency after the pulse frequency increases.
For operation mode 0, set the frequency in the range of 1 to 10,000 (increments of 1 Hz).
For operation mode 1, set the frequency in the range of 20 to 10,000 (increments of 10 Hz).
7. Initial pulse frequency
This setting specifies the frequency when pulse output starts.
For operation mode 0, set the frequency in the range of 1 to 10,000 (increments of 1 Hz).
For operation mode 1, set the frequency in the range of 20 to 10,000 (increments of 10 Hz).
8. Frequency change time
This setting specifies the time to increase and decrease the pulse frequency.
Set the time between 10 and 10,000 ms in increments of 10 ms. The first digit of the setting is ignored.
9. Reversible control enable
This setting enables or disables reversible control and selects the reversible control method from the following reversible control
modes.
There are two modes for the pulse output mode: single-pulse and dual-pulse. They can be combined with reversible control as
follows.
The ports used on the SmartAXIS vary based on the instruction used, the combination of the pulse output mode and reversible
control, and the model used.
Note: When using single-pulse mode on the 40-I/O type, Q16 or Q17 are used. Therefore, PULS3, PWM3, or PULS4, PWM4 cannot be used.
10. Control direction
When reversible control is enabled, store 0 in this data register for forward operation and store 1 in this data register for reverse
operation.
11. Preset value
This setting configures the total number of output pulses from 1 to 100,000,000.
Reversible control enable
0: Reversible control disabled
1: Reversible control (single-pulse output)
2: Reversible control (dual-pulse output)
Reversible control
disabled
Select this option when using pulse output
in a single direction. Pulse A and pulse B
can be used independently.
Reversible control
Single-pulse
output mode
Pulse A is used as pulse output. Pulse B on/
off is used as reversible control.
Reversible control
Dual-pulse output
mode
Pulse A is used as forward pulse (CW)
output.
Pulse B is used as reverse pulse (CCW)
output.
Instruction
Operating condition
Port used
40-I/O type
48-I/O type
Pulse output
port
Reversible
control port
Pulse output
port
Reversible
control port
RAMP1
Reversible control disabled
Q14
—
Q14
—
Reversible control (single-pulse output)
Q14
Q16 (Note)
Q14
Q12
Reversible control (dual-pulse output)
Q14
Q15
Q14
Q15
RAMP2
Reversible control disabled
Q15
—
Q15
—
Reversible control (single-pulse output)
Q15
Q17 (Note)
Q15
Q13
Dual-pulse output mode cannot be used.
—
—
—
—
A
B
A
B
A
B