SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
3-5
3: DEVICE ADDRESSES
M8000  Start Control
M8000 is used to control the operation of the CPU. The CPU stops operation when M8000 is turned off while the CPU is running. 
M8000 can be turned on or off using the WindLDR Online menu. When a stop or reset input is designated, M8000 must remain on 
to control the CPU operation using the stop or reset input.
M8000 maintains its status when the CPU is powered down. When the data to be maintained during power failure is broken after 
the CPU has been off for a period longer than the battery backup duration, the CPU restarts operation or not as selected in 
Configuration > Run/Stop Control > Run/Stop Selection at Memory Backup Error. For details on SmartAXIS Pro/Lite 
start control, see Chapter 4 “Operation Basics” – “Start/Stop Operation” in the SmartAXIS Pro/Lite User's Manual. 
M8001  1-sec Clock Reset
While M8001 is on, M8121 (1-sec clock) is turned off.
M8002  All Outputs OFF
When M8002 is turned on, all outputs and remote outputs go off until M8002 is turned off. Self-maintained circuits using outputs 
also go off and are not restored when M8002 is turned off.
M8003  Carry (Cy) and Borrow (Bw)
When a carry or borrow results from executing an addition or subtraction instruction, M8003 turns on. M8003 is also used for the 
bit shift and rotate instructions. For the causes of carry (CY) and borrow (BW), see "Carry and Borrow" on page 4-13.
M8004  User Program Execution Error
When an error occurs while executing a user program, M8004 turns on. The cause of the user program execution error can be 
checked using Online > Monitor > Monitor, then Online > Status > Error Status > Details.
For a list of Pro/Lite user program execution errors, see Chapter 13 “Troubleshooting” – “User Program Execution Errors” in the 
SmartAXIS Pro/Lite User's Manual. 
M8005  Remote I/O Slave 1 Communication Error
When an error occurs during communication with remote I/O slave 1, M8005 turns on. When the error is cleared, M8005 turns off.
M8006  Remote I/O Slave 2 Communication Error
When an error occurs during communication with remote I/O slave 2, M8006 turns on. When the error is cleared, M8006 turns off.
M8007  Remote I/O Slave 3 Communication Error
When an error occurs during communication with remote I/O slave 3, M8007 turns on. When the error is cleared, M8007 turns off.
M8010 In Daylight Saving Time Period
When the daylight saving time is enabled, M8010 is turned on while in the daylight saving time period. When the daylight saving 
tiem is disabled, M8010 is always off.
M8013  Calendar/Clock Data Write/Adjust Error Flag
When an error occurs while calendar/clock data is written or clock data is adjusted, M8013 turns on. If calendar/clock data is 
written or clock data is adjusted successfully, M8013 turns off.
M8014  Calendar/Clock Data Read Error Flag
When an error occurs while calendar/clock data is read from the internal clock to the special data registers (D8008 to D8014), 
M8014 turns on. If calendar/clock data is read successfully, M8014 turns off.
M8016  Calendar Data Write Flag
When M8016 is turned on, data in data registers D8015 through D8018 (calendar new data) are set to the internal clock. 
M8017  Clock Data Write Flag
When M8017 is turned on, data in data registers D8019 through D8021 (clock new data) are set to the internal clock. 
M8020  Calendar/Clock Data Write Flag
When M8020 is turned on, data in data registers D8015 through D8021 (calendar/clock new data) are set to the internal clock.
M8021  Clock Data Adjust Flag
When M8021 is turned on, the clock is adjusted with respect to seconds. If 
seconds
are between 0 and 29 for current time, 
adjustment for 
seconds
will be set to 0 and minutes remain the same. If 
seconds
are between 30 and 59 for current time, 
adjustment for 
seconds
will be set to 0 and 
minutes
are incremented by one. 
M8022  User Communication Receive Instruction Cancel Flag (Port 2)
When M8022 is turned on, all RXD2 instructions ready for receiving user communication through port 2 are disabled.
M8023  User Communication Receive Instruction Cancel Flag (Port 3)
When M8023 is turned on, all RXD3 instructions ready for receiving user communication through port 3 are disabled.
Convert pdf password protected to word online - C# PDF Password Library: add, remove, edit PDF file password in C#.net, ASP.NET, MVC, WinForms, WPF
Help to Improve the Security of Your PDF Document by Setting Password
add password to pdf file without acrobat; convert protected pdf to word document
Convert pdf password protected to word online - VB.NET PDF Password Library: add, remove, edit PDF file password in vb.net, ASP.NET, MVC, WinForms, WPF
Help to Improve the Security of Your PDF Document by Setting Password
pdf protection remover; crystal report to pdf with password
3: DEVICE ADDRESSES
3-6
SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
M8024  BMOV/WSFT Executing Flag
While the BMOV or WSFT is executed, M8024 turns on. When completed, M8024 turns off. If the CPU is powered down while 
executing BMOV or WSFT, M8024 remains on when the CPU is powered up again.
M8025  Maintain Outputs While CPU Stopped
Outputs are normally turned off when the CPU is stopped. M8025 is used to maintain the output statuses when the CPU is 
stopped. When the CPU is stopped with M8025 turned on, the output ON/OFF statuses are maintained. When the CPU restarts, 
M8025 is turned off automatically.
M8026  SD Memory Card Status
When an SD memory card is inserted into the SmartAXIS, M8026 turns on. When an SD memory card is not inserted, M8026 turns 
off.
M8027  SD Memory Card Writing Flag
While logging data is written to the SD memory card, M8027 turns on. When writing logging data is finished, M8027 turns off.
M8030-M8061  Special Internal Relays for High-speed Counter
Special internal relays used for the high-speed counter.
For details on the Pro/Lite high-speed counter, see Chapter 5 “Special Functions” – “High-Speed Counter” in the SmartAXIS Pro/
Lite User's Manual. For details on the Touch high-speed counter, see Chapter 3 “Project” – “4 Special Functions” – “High-Speed 
Counter” in the SmartAXIS Touch User's Manual.
M8070-M8075  Interrupt Input Status
Turns on when the corresponding user interrupt is allowed. When interrupt inputs are disabled, these internal relays are turned off.
M8070=Interrupt input I0 status, M8071=Interrupt input I2 status, M8072=Interrupt input I3 status
M8073=Interrupt input I5 status, M8074=Interrupt input I6 status, M8075=Interrupt input I7 status
M8076  SD Memory Card Access Stop Flag
Access to the SD memory card stops when M8076 is turned from
off to on.
M8080-M8085  Interrupt Input Edge (ON: Rising, OFF: Falling)
This flag indicates whether the interrupt input is triggered with a rising edge or falling edge.
M8090-M8095  Catch Input ON/OFF Status
When a rising or falling input edge is detected during a scan, the input statuses of catch inputs Group 1/I0 through Group 6/I7 at 
the moment are set to M8090 through M8095, respectively, without regard to the scan status. Only one edge is detected in one 
scan. For the catch input function, see Chapter 5 "Special Functions" - "Catch Input" in the SmartAXIS Pro/Lite User's Manual.
M8100-M8102  User Communication Receive Instruction Cancel Flag
When M8100, M8101, or M8102 is turned on, all ERXD instructions ready for receiving user communication through connection 1, 
connection 2, or connection 3 are disabled, respectively.
M8110-M8112  Connection Status
When SmartAXIS and a network device are connected via the maintenance communication server, user communication server/
client, or Modbus TCP server/client, the connection status turns on. When no network devices are connected, the connection 
status turns off.
These relays are always off for the 12-I/O type (SmartAXIS without Ethernet port).
VB.NET PDF Convert to Word SDK: Convert PDF to Word library in vb.
Convert PDF document to DOC and DOCX formats in Visual Basic control to export Word from multiple PDF files in VB. Supports transfer from password protected PDF.
convert password protected pdf to excel online; pdf open password
C# PDF Convert to Word SDK: Convert PDF to Word library in C#.net
Convert PDF to multiple MS Word formats such as .doc and .docx. Create editable Word file online without email. Password protected PDF file can be printed to
break password pdf; a pdf password online
SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
3-7
3: DEVICE ADDRESSES
M8124 Timer/Counter Preset Value Changed
When timer or counter preset values are changed in the CPU module RAM, M8124 turns on. When a user program is
downloaded to the CPU from WindLDR or when the changed timer/counter preset value is cleared, M8124 turns off.
When a timer or counter is designated as a destination of an advanced instruction, the timer/counter preset value is also changed.
M8125  In-operation Output
M8125 remains on while the CPU is running.
M8130-M8132  Disconnect User Communication Connection
When SmartAXIS is connected to a remote host with the user communication client and a special internal relay corresponding to 
the connection is turned from off to on, the connection is disconnected. Special internal relays M8130 through M8132 are allocated 
to connections 1 through 3, respectively.
These relays are enabled only when user communication client is used. These relays have no effect for the user communication 
server. Nothing happens for the 12-I/O type (SmartAXIS without Ethernet port) when these relays are turned on.
M8144  Timer Interrupt Status
When timer interrupt is enabled, M8144 is turned on. When disabled, M8144 is turned off.
M8150  Comparison Result 1
When the CMP= instruction is used, M8150 is turned on when the value of device designated by S1 is greater than that of device 
designated by S2 (S1 > S2). See "Special Internal Relays M8150, M8151, and M8152 in CMP=" on page 7-2.
When the ICMP>= instruction is used, M8150 is turned on when the value of device designated by S2 is greater than that of 
device designated by S1 (S2 < S1). See "Special Internal Relays M8150, M8151, and M8152 in ICMP>=" on page 7-6.
M8151  Comparison Result 2
When the CMP= instruction is used, M8151 is turned on when the value of device designated by S1 is equal to that of device 
designated by S2 (S1 = S2). See "Special Internal Relays M8150, M8151, and M8152 in CMP=" on page 7-2.
When the ICMP>= instruction is used, M8151 is turned on when the value of device designated by S3 is greater than that of 
device designated by S2 (S3 > S2). See "Special Internal Relays M8150, M8151, and M8152 in ICMP>=" on page 7-6.
M8152  Comparison Result 3
When the CMP= instruction is used, M8152 is turned on when the value of device designated by S1 is less than that of device 
designated by S2 (S1 < S2). See "Special Internal Relays M8150, M8151, and M8152 in CMP=" on page 7-2.
When the ICMP>= instruction is used, M8152 is turned on when the value of device designated by S2 is less than that of device 
designated by S1 and greater than that of device designated by S3 (S1 > S2 > S3). See "Special Internal Relays M8150, M8151, 
and M8152 in ICMP>=" on page 7-6.
M8160-M8163  Button Input Status
When the ESC and direction buttons on the SmartAXIS Pro are simultaneously pressed, the corresponding special internal relays 
M8160 through M8163 turn on. When no buttons are pressed, M8160 through M8163 turn off.
M8166-M8177  Special Internal Relays for High-speed Counter
Special internal relays used for the high-speed counter.
For details on the Pro/Lite high-speed counter, see Chapter 5 “Special Functions” – “High-Speed Counter” in the SmartAXIS Pro/
Lite User's Manual. For details on the Touch high-speed counter, see Chapter 3 “Project” – “4 Special Functions” – “High-Speed 
Counter” in the SmartAXIS Touch User's Manual.
M8120  Initialize Pulse
When the CPU starts operation, M8120 turns on for a period of one scan.
1 scan time
Start
M8120
M8121  1-sec Clock
While M8001 (1-sec clock reset) is off, M8121 generates clock 
pulses in 1-sec increments, with a duty ratio of 1:1 (500 ms on and 
500 ms off).
M8121
500 ms
1 sec
500 ms
M8122  100-ms Clock
M8122 always generates clock pulses in 100-ms increments, 
whether M8001 is on or off, with a duty ratio of 1:1 (50 ms on and 
50 ms off).
M8122
50 ms
100 ms
50 ms
M8123  10-ms Clock
M8123 always generates clock pulses in 10-ms increments, 
whether M8001 is on or off, with a duty ratio of 1:1 (5 ms on and 5 
ms off).
M8123
5 ms
10 ms
5 ms
C# PDF Convert to Jpeg SDK: Convert PDF to JPEG images in C#.net
NET library to batch convert PDF files to jpg image files. Thumbnails can be created from PDF pages. Password protected PDF document can be converted and changed.
pdf password; convert protected pdf to word online
VB.NET PDF Convert to Jpeg SDK: Convert PDF to JPEG images in vb.
VB.NET How-to, VB.NET PDF, VB.NET Word, VB.NET Excel Online VB.NET Tutorial for PDF to JPEG (JPG) Conversion in VB Able to convert password protected PDF document
add password to pdf document; copy protecting pdf files
3: DEVICE ADDRESSES
3-8
SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
Special Data Registers
Note: Do not change the data in any of the reserved special data registers, otherwise the SmartAXIS may not operate correctly.
Special Data Register Device Addresses
Device Address
Description
Updated
See Page
D8000
Quantity of Inputs
When I/O initialized
3-11
D8001
Quantity of Outputs
When I/O initialized
3-11
D8002
SmartAXIS Type Information
Power-up
3-11
D8003
Memory Cartridge Information
Power-up
3-11
D8004
— Reserved —
D8005
General Error Code
When error occurred
3-11
D8006
User Program Execution Error Code
When error occurred
3-11
D8007
— Reserved —
D8008
Calendar/Clock
Current Data
(Read only)
Year
Every 500 ms
3-11
D8009
Month
Every 500 ms
3-11
D8010
Day
Every 500 ms
3-11
D8011
Day of Week
Every 500 ms
3-11
D8012
Hour
Every 500 ms
3-11
D8013
Minute
Every 500 ms
3-11
D8014
Second
Every 500 ms
3-11
D8015
Calendar/Clock
New Data
(Write only)
Year
3-11
D8016
Month
3-11
D8017
Day
3-11
D8018
Day of Week
3-11
D8019
Hour
3-11
D8020
Minute
3-11
D8021
Second
3-11
D8022
Scan Time 
Data
Constant Scan Time Preset Value 
(1 to 1,000 ms) 
3-11
D8023
Scan Time Current Value (ms)
Every scan
3-11
D8024
Scan Time Maximum Value (ms)
At occurrence
3-11
D8025
Scan Time Minimum Value (ms)
At occurrence
3-11
D8026
Communication Mode Information (Port 2 and Port 3)
Every scan
3-11
D8027
Port 2 Slave Number
Every scan
3-12
D8028
Port 3 Slave Number
Every scan
3-12
D8029
System Software Version
Power-up
3-12
D8030
Communication Adapter Information
Power-up
3-12
D8031
Optional Cartridge Information
Power-up
3-12
D8032
Interrupt Input Jump Destination Label No. (I0)
3-12
D8033
Interrupt Input Jump Destination Label No. (I2)
3-12
D8034
Interrupt Input Jump Destination Label No. (I3)
3-12
D8035
Interrupt Input Jump Destination Label No. (I5)
3-12
D8036
Timer Interrupt Jump Destination Label No.
3-12
D8037
Interrupt Input Jump Destination Label No. (I6)
3-12
D8038
Interrupt Input Jump Destination Label No. (I7)
3-12
D8039
SD Memory Card Capacity (Megabytes)
Every 1 sec
3-12
D8040
Analog Input Value (AI0)
Every scan
3-13
D8041
Analog Input Value (AI1)
Every scan
3-13
D8042
Analog Input Value (AI2)
Every scan
3-13
D8043
Analog Input Value (AI3)
Every scan
3-13
D8044
Analog Input Value (AI4)
Every scan
3-13
D8045
Analog Input Value (AI5)
Every scan
3-13
D8046
Analog Input Value (AI6)
Every scan
3-13
D8047
Analog Input Value (AI7)
Every scan
3-13
D8048-D8049
— Reserved —
C# PDF: C#.NET PDF Document Merging & Splitting Control SDK
SDK > C# > Merge and Split Document(s). "This online guide content PDF document merging & splitting toolkit SDK to split password-protected PDF document using
password pdf files; break pdf password online
Online Convert PDF file to Word. Best free online PDF Conversion
Online PDF to Word Converter. Download Free Trial. Convert a PDF File to Word. Just upload your file by clicking on the blue button
password on pdf; convert password protected pdf to excel
SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
3-9
3: DEVICE ADDRESSES
D8050
High-speed 
Counter
(Group 1/I0)
High Word
Current Value / Frequency 
Measurement Value (I0)
Every scan
3-13
D8051
Low Word
D8052
High Word
Preset Value 
3-13
D8053
Low Word
D8054
High Word
Reset Value
3-13
D8055
Low Word
D8056
High-speed 
Counter
(Group 2/I2)
High Word
Current Value / Frequency 
Measurement Value  (I2)
Every scan
3-13
D8057
Low Word
D8058
High Word
Preset Value 
3-13
D8059
Low Word
D8060
High Word
Reset Value 
3-13
D8061
Low Word
D8062
High-speed 
Counter
(Group 3/I3)
High Word
Current Value / Frequency 
Measurement Value  (I3)
Every scan
3-13
D8063
Low Word
D8064
High Word
Preset Value 
3-13
D8065
Low Word
D8066
High Word
Reset Value
3-13
D8067
Low Word
D8068
High-speed 
Counter
(Group 4/I5)
High Word
Current Value / Frequency 
Measurement Value  (I5)
Every scan
3-13
D8069
Low Word
D8070
High Word
Preset Value 
3-13
D8071
Low Word
D8072
High Word
Reset Value
3-13
D8073
Low Word
D8074
Backlight ON Time
Every scan
3-13
D8075-D8076
— Reserved —
D8077
Out of Analog Input Range Status
3-13
D8078
MAC Address (Read only)
Every 1 sec
3-13
D8079
D8080
D8081
D8082
D8083
D8084
IP Address (Current Data) Read only
Every 1 sec
3-13
D8085
D8086
D8087
D8088
Subnet Mask (Current Data) Read only
Every 1 sec
3-13
D8089
D8090
D8091
D8092
Default Gateway (Current Data) Read only
Every 1 sec
3-13
D8093
D8094
D8095
D8096-D8103
— Reserved —
D8104
RS232C Control Signal Status (Ports 2 and 3)
Every scan
3-13
D8105
RS232C DSR Input Control Signal Option (Ports 2 and 3)
When sending/
receiving data
3-14
D8106
RS232C DTR Output Control Signal Option (Ports 2 and 3)
When sending/
receiving data
3-14
D8107-D8109
— Reserved —
D8110
Connection 1 Connected IP Address
Every 1 sec
3-14
D8111
D8112
D8113
Device Address
Description
Updated
See Page
Online Convert Word to PDF file. Best free online export docx, doc
Online Word to PDF Converter. Download Free Trial. Convert a Word File to PDF. Just upload your file by clicking on the blue button
add password to pdf preview; pdf file password
.NET PDF SDK - Description of All PDF Processing Control Feastures
Convert PDF to Word (.docx); Convert PDF to HTML; Convert PDF to text; Convert PDF to Jpeg images; More Able to Open password protected PDF; Allow users to add
pdf user password; acrobat password protect pdf
3: DEVICE ADDRESSES
3-10
SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
D8114
Connection 2 Connected IP Address
Every 1 sec
3-14
D8115
D8116
D8117
D8118
Connection 3 Connected IP Address
Every 1 sec
3-14
D8119
D8120
D8121
D8122-D8129
— Reserved —
D8130
Connection 1 Connected Port Number
Every 1 sec
3-14
D8131
Connection 2 Connected Port Number
Every 1 sec
3-14
D8132
Connection 3 Connected Port Number
Every 1 sec
3-14
D8133
— Reserved —
D8134
High-speed 
Counter 
(Group 5/I6) 
High Word
Current Value / Frequency 
Measurement Value (I6)  
Every scan
3-13
D8135
Low Word
D8136
High Word
Preset Value 
3-13
D8137
Low Word
D8138
High Word
Reset Value
3-13
D8139
Low Word
D8140
High-speed 
Counter 
(Group 6/I7) 
High Word
Current Value / Frequency 
Measurement Value (I7)  
Every scan
3-13
D8141
Low Word
D8142
High Word
Preset Value 
3-13
D8143
Low Word
D8144
High Word
Reset Value
3-13
D8145
Low Word
D8146
— Reserved —
——
D8147
D8148
Remote I/O 
Slave 1
Communication Error Status
When error occurred
3-14
D8149
Analog Input (AI10)
Every scan
3-14
D8150
Analog Input (AI11)
Every scan
3-14
D8151
Analog Input (AI12)
Every scan
3-14
D8152
Analog Input (AI13)
Every scan
3-14
D8153
Analog Input (AI14)
Every scan
3-14
D8154
Analog Input (AI15)
Every scan
3-14
D8155
Analog Input (AI16)
Every scan
3-14
D8156
Analog Input (AI17)
Every scan
3-14
D8157
Remote I/O 
Slave 2
Communication Error Status
When error occurred
3-14
D8158
Analog Input (AI20)
Every scan
3-14
D8159
Analog Input (AI21)
Every scan
3-14
D8160
Analog Input (AI22)
Every scan
3-14
D8161
Analog Input (AI23)
Every scan
3-14
D8162
Analog Input (AI24)
Every scan
3-14
D8163
Analog Input (AI25)
Every scan
3-14
D8164
Analog Input (AI26)
Every scan
3-14
D8165
Analog Input (AI27)
Every scan
3-14
D8166
Remote I/O 
Slave 3
Communication Error Status
When error occurred
3-14
D8167
Analog Input (AI30)
Every scan
3-14
D8168
Analog Input (AI31)
Every scan
3-14
D8169
Analog Input (AI32)
Every scan
3-14
D8170
Analog Input (AI33)
Every scan
3-14
D8171
Analog Input (AI34)
Every scan
3-14
D8172
Analog Input (AI35)
Every scan
3-14
D8173
Analog Input (AI36)
Every scan
3-14
D8174
Analog Input (AI37)
Every scan
3-14
D8175-D8199
— Reserved —
Device Address
Description
Updated
See Page
SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
3-11
3: DEVICE ADDRESSES
D8000  Quantity of Inputs
The total of input points provided on the SmartAXIS is stored to D8000. 
D8001  Quantity of Outputs
The total of output points provided on the SmartAXIS is stored to D8001.
D8002  SmartAXIS Type Information
Information about the SmartAXIS type is stored to D8002.
D8003  Memory Cartridge Information
When an optional memory cartridge is installed on the SmartAXIS cartridge connector, information about the user program stored 
on the memory cartridge is stored to D8003.
D8005  General Error Code
SmartAXIS general error information is stored to D8005. When a general error occurs, the bit corresponding to the error occurred 
turns on.
The general error and user program execution error can be cleared by writing “1” to the most significant bit of D8005 using a user 
program.
For details on Pro/Lite general error codes, see Chapter 13 “Troubleshooting” in the SmartAXIS Pro/Lite User's Manual. For details 
on Touch general error codes, see Chapter 30 “Troubleshooting” - “3 Troubleshooting” in the SmartAXIS Touch User's Manual.
D8006  User Program Execution Error Code
SmartAXIS user program execution error information is stored to D8006. When a user program execution error occurs, the error 
code corresponding to the error occurred is stored to D8006.
For details on Pro/Lite user program execution error codes, see Chapter 13 “Troubleshooting” in the SmartAXIS Pro/Lite User's 
Manual. For details on Touch user program execution error codes, see Chapter 30 “Troubleshooting” - “3 Troubleshooting” in the 
SmartAXIS Touch User's Manual.
D8008-D8021  Calendar/Clock Data
D8008 through D8021 are used for reading calendar/clock data from the internal clock and for writing calendar/clock data to the 
internal clock.
D8022-D8025  Scan Time Data
D8022 through D8025 are special data registers for checking the scan time and configuring the constant scan time.
For details on the SmartAXIS Pro/Lite scan time, see Chapter 5 “Special Functions” – “Constant Scan Time” in the SmartAXIS Pro/
Lite User's Manual. 
D8026  Communication Mode Information (Port 2 and Port 3)
Communication mode information of port 2 and port 3 is stored to D8026.
0:
1:
2:
3:
4:
SmartAXIS Pro/Lite 12-I/O type
SmartAXIS Pro/Lite 24-I/O type
SmartAXIS Pro/Lite 40-I/O type
SmartAXIS Pro/Lite 48-I/O type
SmartAXIS Touch
0:
1:
2:
3:
255:
SmartAXIS Pro/Lite 12-I/O type
SmartAXIS Pro/Lite 24-I/O type
SmartAXIS Pro/Lite 40-I/O type
SmartAXIS Pro/Lite 48-I/O type
The memory cartridge does not store any user program.
0:
1:
2:
3:
Maintenance Communication
User Communication
Modbus RTU Master
Modbus RTU Slave
Bit
0
0
0
0
Port 3
4
7
8
0
0
0
0
15
Bit
0
Port 2
D8026
Bit Bit
Bit
3: DEVICE ADDRESSES
3-12
SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
D8027-D8028  Slave Number
The slave number is stored to D8027 and D8028 when the communication mode for port 2 and 3 is maintenance communication 
or Modbus RTU slave.
The slave number can be specified with either a constant or a data register in the function area settings. When data register is 
specified, the slave number can be changed by storing the slave number in D8027 and D8028.
D8027: Port 2 Slave Number
D8028: Port 3 Slave Number
For SmartAXIS Pro/Lite maintenance communication, see Chapter 9 “Maintenance Communication” - “Maintenance 
Communication via Serial Communication” in the SmartAXIS Pro/Lite User's Manual. For Modbus RTU slaves, see Chapter 11 
“Modbus Communication” - “Modbus Communication via RS-232C/RS-485” in the SmartAXIS Pro/Lite User's Manual. For 
SmartAXIS Touch maintenance communication and Modbus RTU slaves, see Chapter 13 "Troubleshooting" - "Reading Error Data" 
in the SmartAXIS Pro/Lite User's Manual.
D8029  System Software Version
The PLC system software version number is stored to D8029. This value is indicated in the PLC status dialog box called from the 
WindLDR menu bar. Select Online > Monitor > Monitor, then select Online > Status. See Chapter 13 "Troubleshooting" - 
"Reading Error Data" in the SmartAXIS Pro/Lite User's Manual.
D8030  Communication Adapter Information
Information about the communication adapters installed on the port 2 and port 3 connectors is stored to D8030.
D8031  Optional Cartridge Information
Information about the optional cartridge installed on the SmartAXIS is stored to D8031.
D8032-D8035, D8037, D8038  Interrupt Input Jump Destination Label No.
Jump destination label numbers for interrupt inputs are stored in these special data registers. To use interrupt inputs, store the 
label number that corresponds to the special data register allocated to the interrupt input.
D8032=I0, D8033=I2, D8034=I3, D8035=I5, D8037=I6, D8038=I7
For details on SmartAXIS Pro/Lite interrupt inputs, see Chapter 5 “Special Functions” – “Interrupt Inputs” in the SmartAXIS Pro/
Lite User's Manual. For details on SmartAXIS Touch interrupt inputs, see Chapter 3 “Project” – “4 Special Functions” – “Interrupt 
Input” in the SmartAXIS Touch User's Manual.
D8036  Timer Interrupt Jump Destination Label No.
The jump destination label number when the timer interrupt occurs is stored in D8036. To use the timer interrupt, store the 
corresponding label number.
For details on the SmartAXIS Pro/Lite timer interrupt, see Chapter 5 “Special Functions” – “Timer Interrupt” in the SmartAXIS Pro/
Lite User's Manual. For details on the SmartAXIS Touch timer interrupt, see Chapter 3 “Project” – “4 Special Functions” – “Timer 
Interrupt” in the SmartAXIS Touch User's Manual.
D8039  SD Memory Card Capacity
The capacity of the inserted SD or SDHC (maximum size 32 GB) memory card in megabytes is stored to D8039.
0:
1:
RS232C communication adapter is installed
RS485 communication adapter is installed or no communication adapter is installed
Bit
0
0
Port 3
1
7
8
15
Bit
0
Port 2
D8030
Bit Bit
0:
1:
2:
3:
No optional cartridge is installed
Memory cartridge is installed
SD memory card is installed
Memory cartridge and SD memory card are installed
Bit
0
0
SD memory card
1
7
8
15
Bit
0
Memory cartridge
D8031
Bit Bit
SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
3-13
3: DEVICE ADDRESSES
D8040-D8047  Analog Input Value
The analog input values (0 to 10 VDC) to the analog input terminals are converted to digital values (0 to 1000) and stored to the 
corresponding special data registers.
D8040=AI0, D8041=AI1, D8042=AI2, D8043=AI3, D8044=AI4, D8045=AI5, D8046=AI6, D8047=AI7
D8050-D8073, D8134-D8145  High-speed Counter
These special data registers are used with the high-speed counter function and the frequency measurement function.
For details on the SmartAXIS Pro/Lite high-speed counter, see Chapter 5 “Special Functions” – “High-Speed Counter” in the 
SmartAXIS Pro/Lite User's Manual. For details on the SmartAXIS Touch high-speed counter, see Chapter 3 “Project” – “4 Special 
Functions” – “High-Speed Counter” in the SmartAXIS Touch User's Manual.
D8074 Backlight ON Time
The backlight ON time is stored. The backlight ON time can be configured by changing the value in D8074 between 1 to 65535 
seconds. When D8074 is 0, the backlight is always ON. The backlight ON time can also be changed with the HMI function. For 
details, see Chapter 5 "Special Functions" - "Changing Backlight ON Time" in the SmartAXIS Touch User's Manual.
D8077  Out of Analog Input Range Status
When an analog input value is 11V or higher, the corresponding D8077 bit turns on. When an analog input value is lower than 11V, 
the corresponding D8077 bit turns off.
The assignment of each analog input is as follows.
D8078-D8083  MAC Address (Read only)
MAC address of the SmartAXIS is stored to the special data registers in hexadecimal as shown below.
Example) MAC address: AA-BB-CC-DD-EE-FF
D8078=AAh, D8079=BBh, D8080=CCh, D8081=DDh, D8082=EEh, D8083=FFh
D8084-D8087  IP Address (Current Data) Read only
IP address of the SmartAXIS is stored to the special data registers as shown below.
Example) IP address: aaa.bbb.ccc.ddd
D8084=aaa, D8085=bbb, D8086=ccc, D8087=ddd
D8088-D8091  Subnet Mask (Current Data) Read only
Subnet mask of the SmartAXIS is stored to the special data registers as shown below.
Example) Subnet mask: aaa.bbb.ccc.ddd
D8088=aaa, D8089=bbb, D8090=ccc, D8091=ddd
D8092-D8095  Default Gateway (Current Data) Read only
Default gateway of the SmartAXIS is stored to the special data registers as shown below.
Example) Default gateway: aaa.bbb.ccc.ddd
D8092=aaa, D8093=bbb, D8094=ccc, D8095=ddd
D8104  RS232C Control Signal Status (Port 2 and Port 3)
RS232C control signal status of port 2 and port 3 is stored to D8104.
0
2
0
1
0
D8077
0
3
7
8
Bit
15
Bit
0
Bit Bit
4
5
6
0 0 0 0
Analog Input 0
Analog Input 1
Analog Input 2
Analog Input 3
Analog Input 4
Analog Input 5
Analog Input 6
Analog Input 7
00:
Both DSR and DTR are off
01:
DSR is off, DTR is on
10:
DSR is on, DTR is off
11:
Both DSR and DTR are on
0
2
0
1
0
D8104
0
3
Port 2
Port 3
7
8
Bit
15
Bit
0
Bit Bit
Bit
3: DEVICE ADDRESSES
3-14
SMARTAXIS LADDER PROGRAMMING MANUAL FT9Y-B1382
D8105  RS232C DSR Input Control Signal Option (Port 2 and Port 3)
Special data register D8105 is used to control data flow between the SmartAXIS RS232C port 2 and port 3 and the remote terminal 
depending on the DSR (data set ready) signal sent from the remote terminal.
D8106  RS232C DTR Output Control Signal Option (Port 2 and Port 3)
Special data register D8106 is used to control the DTR (data terminal ready) signal to indicate the SmartAXIS operating status or 
transmitting/receiving status.
D8110-D8121  Connection (1 through 3) Connected IP Address
The IP address of the remote host accessing the connection 1 through 3 is stored in special data registers.
Example) Connection 1 Connected IP Address: aaa.bbb.ccc.ddd
D8110=aaa, D8111=bbb, D8112=ccc, D8113=ddd
D8130-D8132  Connection Connected Port Number
When connections are established with other network devices, the port numbers of the connected network devices are stored in 
these special data registers.
D8130 : Connection 1 Connected Port Number
D8131 : Connection 2 Connected Port Number
D8132 : Connection 3 Connected Port Number
D8148, D8157, D8166  Remote I/O Communication Error Status
When a communication error occurs between the remote I/O communication slave and master, the details of the communication 
error are stored in these special data registers.
D8148 : Remote I/O Slave 1 Communication Error Status
D8157 : Remote I/O Slave 2 Communication Error Status
D8166 : Remote I/O Slave 3 Communication Error Status
D8149-D8156, D8158-D8165, D8167-D8174  Remote I/O Analog Input Values
The analog input values (0 to 10 VDC) to the remote I/O analog inputs are converted to digital values (0 to 1000) and stored in the 
special data registers allocated to each remote I/O slave.
 D8149=AI10, D8150=AI11, D8151=AI12, D8152=AI13, D8153=AI14, D8154=AI15, D8155=AI16, D8156=AI17
 D8158=AI20, D8159=AI21, D8160=AI22, D8161=AI23, D8162=AI24, D8163=AI25, D8164=AI26, D8165=AI27
 D8167=AI30, D8168=AI31, D8169=AI32, D8170=AI33, D8171=AI34, D8172=AI35, D8173=AI36, D8174=AI37
0
2
0
1
0
0
D8105
0
3
Port 2
0
5
0
4
7
8
Port 3
000:
DSR is not used for data flow control
001:
When DSR is on, SmartAXIS can transmit and receive data
010:
When DSR is off, SmartAXIS can transmit and receive data
011:
When DSR is on, SmartAXIS can transmit data (busy control)
100:
When DSR is off, SmartAXIS can transmit data
Others: Same as 000
Bit
15
Bit Bit
Bit
Bit
0
2
0
1
0
0
D8106
0
3
Port 2
Port 3
7
8
00:
DTR is on (off while SmartAXIS is stopped)
01:
DTR is off
10:
DTR is on while SmartAXIS can receive data (auto switching)
11:
Same as 00
Bit
15
Bit Bit
Bit
Bit
Documents you may be interested
Documents you may be interested